Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

HCI444E (For 300)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

SH STF-330 - Technical Data Sheet

SH STF-330
SPECIFICATIONS & OPTIONS

STANDARDS MX321 AVR


Newage Stamford industrial generators meet the The most sophisticated of all our AVRs combines all the
requirements of BS EN 60034 and the relevant section features of the MX341 with, additionally, three-phase
of other international standards such as BS5000, VDE rms sensing, for improved regulation and performance.
0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. Over voltage protection is built-in and short circuit
Other standards and certifications can be considered on current level adjustments is an optional facility.
request.
WINDINGS & ELECTRICAL PERFORMANCE
VOLTAGE REGULATORS All generator stators are wound to 2/3 pitch. This
eliminates triplen (3rd, 9th, 15th …) harmonics on the
SX440 AVR - STANDARD voltage waveform and is found to be the optimum
With this self-excited system the main stator provides design for trouble-free supply of non-linear loads. The
power via the Automatic Voltage Regulator (AVR) to the 2/3 pitch design avoids excessive neutral currents
exciter stator. The high efficiency semi-conductors of sometimes seen with higher winding pitches, when in
the AVR ensure positive build-up from initial low levels parallel with the mains. A fully connected damper
of residual voltage. winding reduces oscillations during paralleling. This
The exciter rotor output is fed to the main rotor through winding, with the 2/3 pitch and carefully selected pole
a three-phase full-wave bridge rectifier. The rectifier is and tooth designs, ensures very low waveform
protected by a surge suppressor against surges distortion.
caused, for example, by short circuit or out-of-phase
paralleling. TERMINALS & TERMINAL BOX
The SX440 will support a range of electronic Standard generators are 3-phase reconnectable with 12
accessories, including a 'droop' Current Transformer ends brought out to the terminals, which are mounted
(CT) to permit parallel operation with other ac on a cover at the non-drive end of the generator. A
generators. sheet steel terminal box contains the AVR and provides
If 3-phase sensing is required with the self-excited ample space for the customers' wiring and gland
system, the SX421 AVR must be used. arrangements. It has removable panels for easy
access.
SX421 AVR
This AVR also operates in a self-excited system. It SHAFT & KEYS
combines all the features of the SX440 with, All generator rotors are dynamically balanced to better
additionally, three-phase rms sensing for improved than BS6861:Part 1 Grade 2.5 for minimum vibration in
regulation and performance. Over voltage protection is operation. Two bearing generators are balanced with a
provided via a separate circuit breaker. An engine relief half key.
load acceptance feature is built in as standard.
INSULATION/IMPREGNATION
MX341 AVR The insulation system is class 'H'.
This sophisticated AVR is incorporated into the All wound components are impregnated with materials
Stamford Permanent Magnet Generator (PMG) control and processes designed specifically to provide the high
system. build required for static windings and the high
The PMG provides power via the AVR to the main mechanical strength required for rotating components.
exciter, giving a source of constant excitation power
independent of generator output. The main exciter QUALITY ASSURANCE
output is then fed to the main rotor, through a full wave Generators are manufactured using production
bridge, protected by a surge suppressor. The AVR has procedures having a quality assurance level to BS EN
in-built protection against sustained over-excitation, ISO 9001.
caused by internal or external faults. This de-excites
the machine after a minimum of 5 seconds. The stated voltage regulation may not be maintained in
An engine relief load acceptance feature can enable full the presence of certain radio transmitted signals. Any
load to be applied to the generator in a single step. change in performance will fall within the limits of
If three-phase sensing is required with the PMG system Criteria 'B' of EN 61000-6-2:2001. At no time will the
the MX321 AVR must be used. steady-state voltage regulation exceed 2%.
We recommend three-phase sensing for applications
with greatly unbalanced or highly non-linear loads.

NB Continuous development of our products entitles us


to change specification details without notice, therefore
they must not be regarded as binding.

Front cover drawing typical of product range.

2
SH STF-330
WINDING 311

CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.


A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM SELF EXCITED


A.V.R. SX440 SX421
VOLTAGE REGULATION ± 1.0 % ± 0.5 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT WILL NOT SUSTAIN A SHORT CIRCUIT

INSULATION SYSTEM CLASS H


PROTECTION IP23
RATED POWER FACTOR 0.8
STATOR WINDING DOUBLE LAYER LAP
WINDING PITCH TWO THIRDS
WINDING LEADS 12
STATOR WDG. RESISTANCE 0.009 Ohms PER PHASE AT 22°C SERIES STAR CONNECTED
ROTOR WDG. RESISTANCE 1.19 Ohms at 22°C
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6317 (ISO)
BEARING NON-DRIVE END BALL. 6314 (ISO)
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 1024 kg 1030 kg
WEIGHT WOUND STATOR 470 kg 470 kg
WEIGHT WOUND ROTOR 400 kg 377 kg
2
WR² INERTIA 4.6331 kgm 4.4343 kgm2
SHIPPING WEIGHTS in a crate 1095 kg 1090 kg
PACKING CRATE SIZE 155 x 87 x 107(cm) 156 x 87 x 107(cm)
50 Hz 60 Hz
TELEPHONE INTERFERENCE THF<2% TIF<50
COOLING AIR 0.486 m³/sec 1030 cfm 0.580 m³/sec 1240 cfm
VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138
VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138
kVA BASE RATING FOR REACTANCE
325 325 325 325 381 394 406 419
VALUES
Xd DIR. AXIS SYNCHRONOUS 2.79 2.52 2.34 2.08 3.33 3.08 2.90 2.75
X'd DIR. AXIS TRANSIENT 0.19 0.17 0.16 0.14 0.20 0.18 0.17 0.17
X''d DIR. AXIS SUBTRANSIENT 0.13 0.12 0.11 0.10 0.14 0.13 0.12 0.12
Xq QUAD. AXIS REACTANCE 2.40 2.16 2.01 1.79 2.80 2.59 2.44 2.31
X''q QUAD. AXIS SUBTRANSIENT 0.33 0.30 0.28 0.25 0.39 0.36 0.34 0.32
XL LEAKAGE REACTANCE 0.07 0.06 0.06 0.05 0.08 0.07 0.07 0.07
X2 NEGATIVE SEQUENCE 0.23 0.20 0.19 0.17 0.27 0.25 0.24 0.22
X0 ZERO SEQUENCE 0.08 0.08 0.07 0.06 0.10 0.09 0.09 0.08
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.019s
T'do O.C. FIELD TIME CONST. 1.7s
Ta ARMATURE TIME CONST. 0.018s
SHORT CIRCUIT RATIO 1/Xd

3
50 SH STF-330
Winding 311
Hz THREE PHASE EFFICIENCY CURVES

330 KVA

330 KVA

330 KVA

330 KVA

4
SH STF-330
Winding 311
60
THREE PHASE EFFICIENCY CURVES
Hz

5
SH STF-330
Winding 311

Locked Rotor Motor Starting Curve

50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30

25 25

20 20

P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA

60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30

25 25

20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA

6
SH STF-330
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
50
Hz 100000

SYMMETRICAL

ASYMMETRICAL

10000
CURRENT (Amps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,500 Amps

60 10000

Hz SYMMETRICAL

ASYMMETRICAL
CURRENT (Amps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,600 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20
400v X 1.05 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50
415v X 1.10 460v X 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v X 1.16 480v X 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2
Series Delta = Curve current value X 1.732 7
SH STF-330
Winding 311 / 0.8 Power Factor

RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254

kVA 300 300 300 300 325 325 325 325 345 345 345 345 358 358 358 358

kW 240 240 240 240 260 260 260 260 276 276 276 276 286 286 286 286

Efficiency (%) 93.9 94.1 94.2 94.3 93.6 93.8 93.9 94.1 93.3 93.5 93.7 93.9 93.1 93.4 93.5 93.7

kW Input 256 255 255 255 278 277 277 276 296 295 295 294 308 307 306 306

60 Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480

Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277

kVA 350 363 375 381 381 394 406 419 406 419 431 444 419 431 444 456

kW 280 290 300 305 305 315 325 335 325 335 345 355 335 345 355 365

Efficiency (%) 93.9 94.0 94.1 94.2 93.6 93.7 93.8 93.9 93.3 93.5 93.6 93.6 93.1 93.3 93.4 93.5

kW Input 298 309 319 324 326 336 346 357 348 359 368 379 360 370 380 390

DIMENSIONS

PO Box 17 • Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100
Website: www.newage-avkseg.com
© 2002 Newage International Limited.
Reprinted with permission of N.I. only.
Printed in England. TD_HCI4E.GB_08.02_01_GB

You might also like