Complete Guide On Plans & Calculations
Complete Guide On Plans & Calculations
Complete Guide On Plans & Calculations
NFPA 13
(Standard for Installation of Sprinkler System/2013)
(Chapter 23)
COMPLETE GUIDE ON
PLANS
&
CALCULATIONS
Basics of Hydraulics
Hydraulic Calculation- PRILIMINARY CONCEPTS
Hydraulic Calculation –EXAMPLE CALCULATION (MANUAL+
SOFTWARE)
Hydraulic Calculation Considerations for Storage Sprinklers
– CMDA/CMSA/ESFR Sprinklers
– In Rack Sprinklers
Plan Review Checklists
CONTENT
BASICS OF HYDRAULICS
PRESSURE FLOW
2
62.4 lbs/ft 2
0.433 lbs/in
1 ft 1 ft
A cubic foot of water results in a static pressure at its base of 62.4 lbs/ft2
Converted to square inches a column of water 1-foot high exerts a
pressure of 0.433 lbs/in2
15 ft
5 ft
Example : 02
What is the pressure at the hydrant?
Pressure (psi) = 0.433 x Elevation (ft)
P 0.433 x 200 ft
P 90.93psi
P 91 psi
0.001123Q2
Pv 4
di
• When velocities are high in a closed system the pressure needs to
be accounted for in the calculations.
• It can reduce the flows and pressures needed in a system 5-10
percent.
• In most sprinkler systems velocities are low and their pressures
create a minor effect, therefore velocity pressures can be ignored.
• It should be used at points where large flows take a 90-degree turn
in the piping.
FLOW :
Q=AxV
Q = Flow in ft3/sec
A = Cross sectional area of pipe in ft2
V = Water velocity in ft/sec
Q is a constant for any given closed system.
Q = A1 x V 1 = A2 x V 2
A 1 x V 1 = A2 x V 2
If water is flowing at 5.7 ft/sec in 6-inch pipe, how fast is it flowing when
the pipe size is reduced to 3-inch?
Solution :
𝐴1 X 𝑉1
V2 =
𝐴2
2 2 2
A = r = (3 in) = 28.3 in
1
2 2 2
A = r = (1.5 in) = 7.1 in
2
(28.3in2 )(5.7ft/sec)
V2 22.7ft/sec
7.1in2
V2 = 22.7 ft/sec
Q 29.83 di Pv CD
2
Note : This is used when testing water supplies to determine the amount
of flow
Q k P
Where:
Q is flow (gpm)
k is k-factor determined in the sprinkler listing (gpm/psi½)
P is the pressure (psi)
• The diameter of the opening and discharge coefficient are
incorporated into the empirical determination of k-factor.
Solution :
Q k P
Q 5.6 20 psi
Q 25.0 gpm
Example : 05
What is the pressure for a sprinkler that has a k-factor of 17.6 and the
expected flow is 83 gpm?
Solution :
2
Q
P
k
2
83 gpm
P
17.6
Solution :
Q
k
P
65 gpm
k
30 psi
65
k 11.86
5.48
Hydraulic Calculation
(PRILIMINARY CONCEPTS)
Hazen-Williams formula
– Fire sprinkler systems
– Water-spray systems
Darcy-Weisbach formula
(The Darcy-Weisbach equation more accurately accounts for the
effects of turbulence, temperature, and viscosity )
– Anti-freeze systems
– Water mist systems
– Foam-water systems
Fanning formula
4.52Q1.85
PL 1.85 4.87
C di
Where:
PL = friction loss (psi/ft)
Q = flow (gpm)
C = roughness coefficient (based on pipe material)
di = interior pipe diameter (inches)
40 ?
Solution :
4.52Q1.85 4.52(110gpm)1.85
PL 1.85 4.87
C di (120)1.85(2.067in)4.87
PL = 0.112 psi/ft
Friction Loss = 0.112 psi/ft x 32 ft = 3.6 psi
4.87
Actual inside diameter
Factor
Schedule 40 Steel Pipe inside diameter
What is the equivalent pipe length of Type K copper tube which used for
a 3-inch standard turn 90-degree elbow?
Solution:
– Type K Copper
– Interior diameter
4.87
4.87
Actual i.d. 2.907
Factor 0.77
Schedule 40 Steel Pipe i.d. 3.068
Hydraulic Calculation
STEP BY STEP PROCEDURE
MANUAL + ELITE SOFTWARE
9. Hydraulic Calculations
9.1 Identify hazard category
9.2 Determine sprinkler spacing
9.3 Determine piping arrangement
9.4 Calculate amount of water needed per sprinkler
9.5 Calculate number and location of open sprinklers in
the hydraulically most demanding area
9.6 Start at most remote sprinkler and work towards the
water supply calculating flows and pressures
9.7 Compare demand with supply
10. Notes and Details for Plans
11. As-Built Drawings
Plan view
200 FT.
Elevation view
18 FT.
200 FT.
info@mitionline.com Design|Inspection|Training Mehboob Shaikh | +919146861270
MECHSOFT ENGINEERING DESIGN AND CONSULTANCY
z
100 FT.
200 FT.
Mains and branches are Sch 40
pipes
15 FT.
Isometric View
1
2
5 Area of operation have
3 1-inch been reduced in
1 ½-inch accordance with cl.
1 ¼-inch 6 11.2.3.2.3
4
1 ¼-inch 7
1 ½-inch 8
BL1
3-inch
Riser
- 3x
y 55
2
3(18)
y 55
2
54
y 55 28%
2
Area of Coverage = S x L
Area of Coverage = 10 x 12.5
Area of Coverage = 125 Sq. ft.
𝐷𝑒𝑠𝑖𝑔𝑛 𝐴𝑟𝑒𝑎
No. of Sprinklers in the design area =
𝐴𝑟𝑒𝑎 𝑜𝑓 𝐶𝑜𝑣𝑒𝑟𝑎𝑔𝑒
1080
No. of Sprinklers in the design area =
125
No. of Sprinklers in the design are = 9 Sprinklers
Data Summary :
Main Path :
1 2 3 4 BL1 BL2
BL3 TOR
Auxillary Paths-1 :
5 6 7 8 BL2
Auxillary Paths-2 :
6 BL3
18.8 gpm @
11.3 psi
19.95 gpm
@ 12.69 psi
84..36 gpm
@ 27.28 psi
28.33 gpm
21.3 gpm @
@ 27.71psi
14.4 psi
84.36 gpm
@ 24.38 psi
N 197.07 gpm
@ 41.41 psi
System Demand
197 gpm @ 41.40 psi
Flow (gpm)
ELITE SOFTWARE
CALCULATION
Print Report
Therefore,
Design area = Allowable area per sprinkler x no. of sprinkler in the design
area
Design Area = 100 x 15
Design Area = 1500 SF
Depends on,
In accordance, 17.1.5.6
In accordance, 18.5.3
Depends on,
– Type of sprinklers at the ceiling ( CMSA/ESFR)
Min. Q = 30 GPM
Hence for k = 5.6 , P = 28.7 psi
for k = 8.0 , P = 14.1 psi
for k = 11.2 , P = 7.2 psi
• 18.5.4
– 30 psi
– 30.7 gpm for k‐5.6 sprinkler
– 43.8 gpm for k‐8.0 sprinkler
– 61.3 gpm for k‐11.2 sprinkler
Example- 11 :
1
2
B 3
4
5
6
7
8
9
10
A
10
Ceiling
– 665 GPM @ 84 PSI
In Rack
– 247 at 75 PSI
– Calculate the two demands separately from the most remote point
to the node where they connect
– Apply the k‐factor to the higher pressure to get the new flow:
Step 01 :
– Calculate the two demands separately from the most remote point
to the node where they connect
Step 02 :
– Get the k‐factor for the lower pressure situation
𝑄
K=
𝑆𝑞.𝑟𝑡 𝑃
247
K=
𝑆𝑞.𝑟𝑡 75
K = 28.52
Step 03 :
Apply the K‐factor to the higher pressure,
Q = K X Sq. rt (P)
Q = 261.4 GPM
Step 04:
Add the flows together
– In‐Racks: 262 gpm at 84 psi
– Ceiling: 665 gpm at 84 psi To In Ceiling Level Sprinklers
To In Rack Sprinklers
Project address:
______________________________________________________________________
Owner’s name:
______________________________________________________________________
Contractor address:
______________________________________________________________________
______________________________________________________________________
• Type of system being installed: Wet___ Dry ___ Preaction ___ Deluge_____________
•Building description:
Square footage of the project: ________________________
Use of building: __________________________ Building height: __________________
Total area of building: _____________________ Area per floor: ___________________
Total number for floors above grade: __________ below grade: ___________________
– Class I
– Class II
– Class III
– Class IV
– Group A
– Group B
– Group C
YES NO
– __ Name of owner or occupant
– __ Location, including street address
– __ Point of compass
– __ Full height cross section
– __ Ceiling/roof heights and slopes not shown in the full height cross section
– __ Location of partitions
– __ Location of fire walls
– __ Occupancy class of each area or room
– __ Location and size of concealed spaces, closets, attics, and bathrooms
– __ Small enclosures in which no sprinklers are to be installed
– __ Scale the plans were drawn to
_____Capacity is verified at _______ gpm (L/min) for a duration of ______ hours for a
total capacity of ______ gal (L)
YES NO
_ _ Location and elevation of static and residual hydrants in relationship to the riser
location
_ _ Date and time of flow test (must be within one year of design)
_ _ Static, residual, and flow from test
_ _ Name of person who conducted or source of water supply information
Fire Pump
– Electric
– Diesel
– Steam
– N/A
Rated Capacity: ____________________
Water Tank
– Steel
– Wood
– Concrete
– Wet
– Dry
– Preaction
– Deluge
• Classification of occupancy:
– Light hazard
– Ordinary: Group 1 _ Group 2 _
– Extra hazard: Group 1 _ Group 2 _
– Class I
– Group A plastic
– Class II
– Group B plastic
– Class III
– Group C plastic
– Class IV
– Mixed commodity
Reinforced _
Unreinforced _
STEP 6: DESIGN
The following information has been clearly indicated on plans / specifications / hydraulic
calculations:
– Type of system:
– Hydraulically calculated
– Pipe schedule
– Density/area method
– Area of operation and density noted?
– Area of operation reduced for:
– Quick-response sprinklers
– High-temperature sprinklers
– Area of operation increased for: Sloped ceilings
– Dry pipe/double-interlock preaction systems _
– Multiple adjustments needed?
STEP 8: ALARMS
f. Date.
g. Time.
h. Test conducted by or information supplied by.
INDIVIDUAL PLANS
Plot or Site Plan
Description Yes No NA
Mains
Description Yes No NA
Size of FDC indicated and per code, both inlets and outlets.
END OF DOCUMENT