Electro-Pneumatic Intersystem TRANSMITER Type A201: Technical Details
Electro-Pneumatic Intersystem TRANSMITER Type A201: Technical Details
Electro-Pneumatic Intersystem TRANSMITER Type A201: Technical Details
TECHNICAL DETAILS
- input standard signal 4...20 mA; 0...20 mA
- input inversion signal 20...4 mA; 20...0 mA
- output signal 20...100 kPa; 60...300 kPa
- pressure supply 140 ±14 kPa; 400 ±40 kPa
- input resistance ≤250W
- basis mistake 0,6%
- hysteresis 0,25%
- additional mistakes:
from changes of pressure supply by 10% max 0,5%
from change of ambient temperature max 0,8% on each 10OC
form vibrations in range:
10 ... 60 Hz, amplitude<0,35 mm
60 ... 500 Hz, acceleration 5g max 1%
form reaction the magnetic constant and commutative field
at intensity 100 A/m, 50 Hz (acc. to PN-EN 6100-4-8:1998) max 0,5 permissible basis mistake
form disturbances radiated magnetic field
at radio frequency 10 V/m., at frequency in range
80 MHz do 1 GHz (acc. to PN-EN 6100-4-3:2002) max 0,5 permissible basis mistake
from series of quick transient states made by voltage
at peak value 2 KV (acc. To PN-EN 6100-4-4:2002) max 0,5 permissible basis mistake
from surge at voltage 0,5 KV (acc. to PN-EN 6100-4-5:1998) max 0,5 permissible basis mistake
- working position optionally, subject to 0 correction in choosed position
- own air consumption max 0,35 kg/h at pz= 140 kPa
- max rate 7,5 kg/h at pz= 140 kPa
- spark-safety characteristic II 2 G EExia IICT6/T5/T4
- certificate KDB 04 ATEX 026X
- conditions of using in explosion-risk zone:
1. Electro-pneumatic system transmitter type A201-A2XX-XX-XX, ... may cooperate only with spark-safety circuit at parameters:
U1 = 28 V DC, I1 = 100 mA, P1 = 0,7 W
2. Transmitter connection with cooperating devices should be made by separate conductors pair or by cable, which OLNY spark-
safety circuits will be connected. L and C parameters of external circuit should be the same like for device cooperates with transmitter.
3. Acceptable ambient temperature - depending on temperature class
Temperature class of gases and steam T6 T5 T4
Acceptable ambient temperature(Ta) -400C ... +500C -400C ... +650C -400C ... +700C
- housing protection degree IP54 acc. to PN-EN 60529:2002
- mass 1,1 kg
- connectors:
Electric screw clamps for transmitter at diameter to 2,5 mm2
Pneumatic threaded holes St. B1/8” or connectors
WORKING CONDITIONS
Electro-pneumatic system transmitter type A201 is designed for working
in industry condition in little roof places, booths in the field, not heated and
closed rooms or in control room base in conditions: DIMENSION DRAWINGS
- ambient temperature -40 0C ... +70 0C 57 .s
otwle 70
- relative humidity 100% 22 oh
9,5 6,5 8-
- sinusoidal vibrations 10 ... 60 Hz, amplitude< 0,35 mm,
8
60 ... 500 Hz, acceleration 5g
(class VH6 acc. to PN-EN 60654:1996)
- working position optionally, subject to 0 correction 14
in chosed position
- working medium air without dust, oil and aggressive pollution,
125
146
at relative humidity when dew temperature
should be lesser than ambient temperature
at the value not lesser than 10OC (10OK)
(PN-EN 60654-2:1999)
21 6,5
35 28.5
55 30 33
104 84
ORDERING METHOD
A201- Electro-pneumatic intersystem transmitter
CODE1 VERSION
1 standard
2 spark-safety with certificate ATEX II 2 G EExia IICT6/T5/T4
REMARK: other versions of transmitter type A201 available aftr agreement with manufacturer
Example of ordering:
Electro-pneumatic intersystem transmitter type A201 in standard version with input signal 4...20 mA,
with connector for pipe f
6x1 mm with standard - metallic cable key and output signal from 20 ... 100 kP has denotation:
Electro-pneumatic system transmitter type A201-101 -D1-W1
The right of introducing design changes in the product, without deteriorating of its operation parameters, is reserved.