Fuente DC 440/24vdc
Fuente DC 440/24vdc
Fuente DC 440/24vdc
■ Features :
Single and two phase wide input range 180 ~ 550VAC
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
Built-in DC OK relay contact
3 years warranty
SPECIFICATION
MODEL WDR-120-12 WDR-120-24 WDR-120-48
DC VOLTAGE 12V 24V 48V
RATED CURRENT 10A 5A 2.5A
CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~2.5A
RATED POWER 120W 120W 120W
RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p 150mVp-p
OUTPUT
VOLTAGE ADJ. RANGE 12 ~ 15V 24 ~ 29V 48 ~ 58V
VOLTAGE TOLERANCE Note.3 ±1.5% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±0.5% ±0.5% ±0.5%
SETUP, RISE, HOLD UP TIME 2000ms, 70ms, 50ms/400VAC 2000ms, 70ms, 10ms/230VAC at full load
VOLTAGE RANGE 180 ~ 550VAC 254 ~ 780VDC
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 89.5% / 400V 91% / 400V 92% / 400V
INPUT
AC CURRENT 0.7A/400VAC 1.2A/230VAC
INRUSH CURRENT (max.) COLD START 50A
LEAKAGE CURRENT <3.5mA / 530VAC
105 ~ 130% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
PROTECTION 16 ~ 18V 31 ~ 37V 60 ~ 67V
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK SIGNAL Relay contact rating(max.) : 30V / 1A resistive
WORKING TEMP. -25 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
SAFETY STANDARDS UL508, EAC TP TC 004 approved, IEC60950-1 CB approved by SIQ, design refer to GL;(meet EN60204-1)
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 4) EMC EMISSION Compliance to EN55011 (CISPR11), EN55032 (CISPR32), EN61204-3 Class B, EAC TP TC 020
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
MTBF 268K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 40*125.2*113.5mm (W*H*D)
PACKING 0.65Kg; 20pcs/14Kg/1.16CUFT
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
NOTE
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quick may lead to increase of the set up time.
6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
113.5
125.2
DC OK
1
1
+V ADJ.
DC OK
2
40
2 3
3 4
TB1 TB2
+
Terminal Pin No. Assignment (TB1)
Pin No. Assignment
1 FG
2 AC/L2
3 AC/L1
35
Block Diagram
DC OK
DETECTION
CIRCUIT
FG
CURRENT
LIMIT
PWM
O.L.P. O.T.P.
CONTROL
O.V.P.
DC OK Relay Contact
Others 100
100
90
80
80
60 12V 70
LOAD (%)
LOAD (%)
60
40
50
20
40
-25 0 10 20 30 40 50 60 70 (VERTICAL) 180 190 200 250 290 310 360 400 450 490 500 520 550