Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

305M and 255J

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Submersible Sewage Pump Type ABS XFP-PE4 to PE6

Submersible Mixed Flow Column Pump Type ABS AFLX-PE4 to PE6


Submersible Propeller Pump Type ABS VUPX-PE4 to PE6

2500-0001
1 597 2500 GB 11.2015

en Installation and Operating Instructions


translation of original instruction

www.sulzer.com
GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

Installation and Operating Instructions

For submersible sewage pumps


XFP CB - Hydraulics
XFP 105J XFP 150M XFP 200J XFP 250J XFP 300J XFP 356M XFP 405M
XFP 155J XFP 201J XFP 255J XFP 305J
XFP 205J XFP 305M
XFP 206J XFP 306M


XFP CH; SK - Hydraulics
XFP 100J XFP 150J XFP 200J XFP 250M XFP 300J XFP 350M XFP 400M XFP 500U XFP 600V
XFP 200M XFP 300M XFP 351M XFP 400R XFP 501U XFP 600X
XFP 301M



AFLX-Hydraulics
AFLX 0601 AFLX 0701 AFLX 0801
AFLX 0802 AFLX 1202
AFLX 0803 AFLX 1203
AFLX 1207
VUPX-Hydraulics
VUPX 0501 VUPX 0601 VUPX 0801 VUPX 1001 VUPX 1201
VUPX 0402 VUPX 0502 VUPX 0602 VUPX 0802 VUPX 1002 VUPX 1202
VUPX 0403 VUPX 0503

Sulzer reserves the right to alter specifications due to technical developments !

32 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

Table of contents
1 General.................................................................................................................................................. 35
1.1 Correct usage of the products ............................................................................................................... 35
1.2 Application areas for the series XFP...................................................................................................... 36
1.3 Application areas for the series AFLX.................................................................................................... 36
1.4 Application areas for the series VUPX................................................................................................... 37
1.5 Technical data........................................................................................................................................ 37
1.6 Nameplate.............................................................................................................................................. 38
2 Safety.................................................................................................................................................... 38
3 Transport and storage......................................................................................................................... 39
3.1 Transport securing devices.................................................................................................................... 39
3.2 Storage of the units................................................................................................................................ 39
4 Monitoring system............................................................................................................................... 40
4.1 Motor monitoring system........................................................................................................................ 40
4.2 DI-Electrode........................................................................................................................................... 40
4.3 Temperature monitoring of the stator..................................................................................................... 40
4.4 Temperature monitoring of the bearings (Option).................................................................................. 40
4.5 Temperature densor indication............................................................................................................... 40
4.5.1 Temperature sensor bimetall.................................................................................................................. 41
4.5.2 Temperature sensor PTC....................................................................................................................... 41
4.5.3 Temperature sensor PT 100................................................................................................................... 41
4.6 Operation with frequency inverters........................................................................................................ 42
5 Installation............................................................................................................................................ 42
5.1 Installation of the XFP submersible sewage pumps.............................................................................. 42
5.1.1 Installation options for the XFP submersible sewage pumps................................................................. 42
5.1.2 HD- pedestal fitting of O-ring and guide piece....................................................................................... 44
5.1.3 Tightening torque................................................................................................................................... 44
5.1.4 Fitting position of the Nord-Lock® securing washers.............................................................................. 44
5.2 Installation of the AFLX and VUPX submersible pumps........................................................................ 45
5.2.1 Installations examples with AFLX and VUPX submersible pumps......................................................... 45
5.3 Electrical connection.............................................................................................................................. 47
5.3.1 Lead designations ................................................................................................................................. 48
5.4 Checking direction of rotation................................................................................................................. 48
5.5 Connection of the control circuit leads................................................................................................... 48
5.6 Connection of the seal monitoring unit to the control panel................................................................... 49
6 Commissioning.................................................................................................................................... 49

GB 2500-J
33
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

7 Maintenance......................................................................................................................................... 50
7.1 Coolant filling.......................................................................................................................................... 51
7.1.1 Coolant filling / Oil filling XFP................................................................................................................. 51
7.1.2 Coolant filling / Oil filling VUPX / AFLX.................................................................................................. 52
7.1.3 Reference values for antifreeze behaviour............................................................................................ 54
7.1.4 Coolant filling quantities......................................................................................................................... 54
7.2 Removal of the submersible sewage pump .......................................................................................... 56
7.2.1 Removal of the XFP submersible sewage pump from a wet sump........................................................ 56
7.2.2 Removal of the XFP submersible sewage pump when dry installed..................................................... 57
7.2.3 Removal of the AFLX and VUPX submersible pump ............................................................................ 57

34 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

1 General
These Installation and Operating Instructions and the separate booklet Safety Hints contain basic instruc-
tions and safety hints which must be observed during transport, installation and commissioning. For this reason
it is essential that they are read by the installing technician as well as by relevant skilled operators or users.
They should also be always available where the unit is installed.

m
Safety Instructions which might cause danger to life in case of non-observance have been specifically
highlighted with the general danger symbol.

c
The presence of a dangerous voltage is identified with this safety symbol.

g
This symbol indicates the danger of an explosion occurring.

ATTENTION Appears at safety hints, the non-observance of which could damage the unit or affect
its functioning.

NOTE Used for important pieces of information.

1.1 Correct usage of the products


In the case of any faults arising, the Sulzer units should immediately be taken out of use and secured. The fault
should be immediately rectified or, if necessary, contact your Sulzer Pump Solutions Germany ( in the follow-
ing called Sulzer ). service centre.
The submersible pumps with PE motor can be supplied both as standard versions and in explosion-proof
execution with (ATEX II 2Gk Ex d IIB T4) for 50 Hz or FM execution (NEC 500, Class I, Division 1, Group C&D,
T3C) for 60 Hz in isolation class H (140).
Temperatur limiter in the winding = 140 °C/284 °F (bimetallic or thermistor (PTC) as an option).
Special version Class H

A special version with temperature limiter in the winding = 160 °C/320 °F (bimetallic, temperature sensor (PTC)
as an option or PT100) is also available. This version is only available without explosion-proof or NEC 500 ap-
proval with isolation class H (160) components.
For both versions an EMV-execution is available as an option.

ATTENTION Repair work on explosion-proof motors may only be carried out in authorized work-
shops by qualified personnel using original parts supplied by the manufacturer.
Otherwise the ex-approvals are no longer valid. All Ex-relevant components and
dimensions can be found in the modular workshop manual and the spare parts list.

ATTENTION After repair work in not authorized workshops by not qualified personnel the ex-ap-
provals are no longer valid. After such repair the unit must not be operated in hazar-
dous areas. The ex-nameplate (see figure 2, 3) has to be removed.

ATTENTION All regulations and guidelines, which may vary from country to country must be fol-
lowed without exception.
Limitations: Fluid temperature maximum 40 °C (104 °F)
Immersion depth maximum 20 m (65 ft)

GB 2500-J
35
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

For the operation of units as explosion-proof execution the following applies:

In hazardous areas care must be taken that during switching on and operation of the pumps the pump section
is filled with water (dry installation) or alternatively is submerged or under water (wet installation with cooling
jacket. Other types of operation e.g. snore operation or dry running are not allowed!
For the operation of explosion-proof submersible pumps in wet-well installation without cooling jacket
applies:

It must be ensured that the motor of the ex-submersible pump is always fully submerged during start-up and
operation!
For the operation of explosion-proof submersible pumps applies:

The temperature monitoring of the explosion-proof submersible pumps has to be carried out by bimetallic
temperature limiters or thermistors according to DIN 44 081-150 connected to a suitable release device which
is certified in accordance with EC directive 94/9/EC.
For the operation of explosion-proof submersible pumps with frequency inverter in hazardous areas
(ATEX Zone 1 and 2) applies:

Motors must have direct thermal protection devices fitted. These consist of temperature sensors (PTC DIN
44081 -150) embedded in the windings. These must be connected to a suitable release device which is certified
in accordance with EC directive 94/9/EC.
Machines designated as Ex machines may never, without exception, be operated using a mains frequency that
is greater than the maximum of 50 or 60 Hz as indicated on the nameplate.
Operation with frequency inverters

See chapter 4.6

1.2 Application areas for the series XFP


The submersible sewage pumps type ABS XFP series have been designed for the economical and reliable
pumping of commercial, industrial and municipal sewage and can be installed dry or wet.
They are suitable for pumping of the following liquids:

• Clear and wastewater, for sewage containing solids and fibrous material
• Faecal matter
• Sludge
• Fresh and process water pumping
• Raw water for drinking water supply
• Surface and rain water
• Sewage
1.3 Application areas for the series AFLX
The mixed flow column pump type ABS AFLX series have been developed for environmental protection, water
supply, municipal sewage treatment and dewatering of polders.
They are suitable for the following liquids:

• Raw water with solid or fibrous material.


• Sewage
• Surface water, rain water, drainage water
• Sludge
The AFLX pumps are installed in a concrete sump or in a steel pressure pipe using a suitable coupling ring

36 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

1.4 Application areas for the series VUPX


The submersible propeller pumps type ABS VUPX series are designed for those applications where large wa-
ter volumes must be pumped at low heads (up to 10 m/33 ft).
They are suitable for the following liquids

• Fresh and process water pumping


• Raw water for drinking water supply
• Surface and rain water
The VUPX pumps are installed in a concrete sump or in a steel pressure pipe using a suitable coupling ring.

1.5 Technical data


Please take the technical data and the weight from the nameplate. Please take the dimensions of the units from
the resp. dimension drawing.
The maximum noise level of the units of this series is ≤ 70 dB(A).

HINT The resp. dimension drawings can be found in downloads „dimension drawing“ by
the following link: www.sulzer.com.
The maximum noise level of the units of this series is ≤ 70 dB(A).
The weights in the dimension sheets refer to a cable length of 10 m. In the case of cable lengths exceeding
10 m, the additional weight must be determined using the following table and added.
Cable type Weight Kabelart Weight kg/m Weight kg/m Cable type Weight Weight
kg/m TECWATER OZOFLEX (PLUS) kg/m lb/1000ft
S1BN8-F H07RN8-F

3x6/6KON 0,4 4G6 0,4 0,5 AWG 8-3 0,9 597


3x10/10KON 0,7 4 G 10 0,5 0,8 AWG 6-3 1,2 764
3x16/16KON 1 4 G 16 1 1,25 AWG 4-3 1,6 1070
4 G 25 1,5 1,8 AWG 2-3 2,3 1533
G-GC

3x6/6KON +3x1,5ST 0,6 4 G 35 1,9 2,3 AWG 1-3 2,8 1865


TECWATER S1BN8-F / OZOFLEX (PLUS) H07RN8-F

4 G 50 2,6 3,0 AWG 1/0-3 3,5 2315


3x25 +3G16/3 1,5 4 G 70 3,7 4,2 AWG 2/0-3 4,1 2750
3x35 +3G16/3 1,9 4 G 95 4,7 5,5 AWG 3/0-3 5 3330
TECWATER EMV-FC S1BC4N8-F

3x50 +3G25/3 2,6 4 G 120 5,9 6,7 AWG 4/0-3 6,1 4095
3x70 +3G35/3 3,6
3x95 +3G50/3 4,7 4 G 1,5 0,2 0,17 AWG 1/0 0,7 480
3x120 + 3G70/3 6 8 G 1,5 0,3 0,45 AWG 2/0 0,8 558
3x150 + 3G70/3 7,1 10 G 1,5 0,4 0,47 AWG 3/0 1,1 742
3x185 +3G95/3 8,8 12 G 1,5 0,5 0,48 AWG 4/0 1,3 872
3x240 +3G120/3 11
DLO

3x300 +3G150/3 13,5 1x150 1,6 1,8 262 MCM 1,6 1068
1x185 2 2,2 313 MCM 1,9 1258
1x185 2,2 1x300 3,2 3,4 373 MCM 2,2 1462
1x240 2,7 1x400 4,1 444 MCM 2,6 1726
1x300 3,4 535 MCM 3,1 2047
646 MCM 3,6 2416

AWG 16/4 0,3 144


SOOW

AWG 16/8 0,4 222


AWG 16/10 0,5 278
AWG 16/12 0,5 305

GB 2500-J
37
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

1.6 Nameplate
We recommend that you record the data from the original nameplate Figure 1 so that you can refer to the data
at any time.

2500-0001
1

Type 2 5

PN 3 SN 4 6

UN 7 V 3~ max. 8 IN 9 A 10 Hz
P 1N 11 P 2N 12 n 13 Ø 14
TA max. 15 °C Nema Code 16 Hmin. 17

DN 18 Q 19 H 20 Hmax . 21
Weight 22 IP68
Motor Eff. Cl . 23 24

Figure 1 Nameplate 42242501

Legend
1 Address 13 Rotation speed [flexible unit]
2 Type designation 14 Impeller/Propeller ø [flexible unit]
3 Art. no. 15 Max. ambient temperature [flexible unit]
4 Serial number 16 Nema Code Letter (only at 60 Hz, e.g., H)
5 Order number 17 Min. pumping height [flexible unit]
6 Year of manufacture [month/year] 18 Nominal width [flexible unit]
7 Nominal voltage 19 Pumping quantity [flexible unit]
8 Max. immersion depth [flexible unit] 20 Pumping height [flexible unit]
9 Nominal current 21 Max. pumping height [flexible height]
10 Frequency 22 Weight (without attached parts) [flexible unit]
11 Power (consumption) [flexible unit] 23 Motor efficiency class
12 Power (output) [flexible unit] 24 Motor shaft direction of rotation
4224 0249

Figure 2 Nameplate ATEX Figure 3 Nameplate FM / CSA

2 Safety
The general and specific health and safety hints are described in detail in the separate booklet Safety Hints. If
anything is not clear or you have any questions as to safety make certain to contact the manufacturer Sulzer.

38 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

3 Transport and storage


Depending on model and mode of installation, the units are prepared at the factory for vertical or horizontal
transportation.
The units are equipped with a safety shackles (series for vertical setup) or swivel ring bolt (horizontal setup),
which allow fixing chains for transporting or for installing or removing. We recommend using chains from the
Sulzer list of accessories.

ATTENTION In the case of pumps set up vertically, sealing plugs are mounted for protecting
the thread holes instead of swivel ring bolt. These seals may only be replaced by a
swivel ring bolt for maintenance work but must be screwed on again before startup!

0838-0005

0838-0004
Figure 4 Transport in a horizontal manner XFP Figure 5 Transport in a horizontal manner AFLX/VUPX

ATTENTION α max. ≤ 45°. The angle α between the centre line of the unit and the lifting tools
should not exceed 45°.

3.1 Transport securing devices


The motor connection cables are protected against the ingress of moisture along the cable by having the ends
sealed at the works with protective covers.
These protective covers should only be removed immediately prior to connecting the pumps electrically.

ATTENTION These protective covers only provide protection against water spray or similar and
are not a water tight seal. The ends of the cables should not be immersed in water,
otherwise moisture could enter the connection chamber of the motor.

NOTE If there is a possibility of water ingress then the cables should be secured so that the
ends are above the maximum possible flood level.

ATTENTION Take care not to damage the cable or its insulation when doing this!
In order to avoid damage to the pump shaft or the bearings during horizontal transport, the shaft is clamped in
an axial direction when leaving the works.

ATTENTION The motor shaft transport lock must be removed before startup!

3.2 Storage of the units

ATTENTION The Sulzer products must be protected from weather influences such as UV from
direct sunlight, high humidity, aggressive dust emissions, mechanical damage,
frost etc. The Sulzer original packaging with the relevant transport securing devices
GB 2500-J
39
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

(where used) ensures optimum protection of the unit. If the units are exposed to
temperatures under 0 °C/32 °F check that there is no water in the hydraulics, coo-
ling system, or other spaces. In the case of heavy frosts, the units and cable should
not be moved if possible. When storing under extreme conditions, e.g. in tropical or
desert conditions suitable additional protective steps should be taken. We would be
glad to advise you further

NOTE The Sulzer units normally require no maintenance during storage. During longer
storage times, (after approx. one year) the transport locks on the motor shaft (not all
versions) must be dismantled. Coolant is applied to the sealing surfaces by manually
turning the shaft several times (also for the purpose of cooling or lubricating so that
trouble-free function of the sliding ring seal is ensured. No maintenance is required
when storing the motor shaft.

4 Monitoring system

4.1 Motor monitoring system


Motor equipment:

Motors PE4/PE5 PE6 PE4/PE5 PE6


Monitoring non Ex / Ex non Ex / Ex non FM / FM non FM / FM
Seal monitor Separation chamber ● ● ● ●
Motor chamber ○ ● ○ ●
Connection chamber ○ ○ ○ ●
Stator temperature Bimetallic ● ● ● ●
Thermistors (PTC) ○ ○ ○ ○
PT 100 ○ ○ ○ ○
Bearing temperature Bimetallic ○ ● ○ ●
Upper/lower Thermistors (PTC) ○ ○ ○ ○
PT 100 ○ ○ ○ ○
● = Standard ○ = Option

4.2 DI-Electrode
The DI-electrodes carry out the seal monitoring function and signal the ingress of moisture into the motor by
means of a special electronic device. Connection see chapter 5.6

4.3 Temperature monitoring of the stator


Thermal limiters protect the stator from overheating in the case of asymmetric phase loading or voltage, conti-
nuous dry running or excessive temperatures in the medium itself. The stator is equipped with three bimetallic
thermal limiters (optional PTC, PT100) which are connected in series.

4.4 Temperature monitoring of the bearings (Option)


In the case of existing bearing monitoring, a bimetal temperature limiter is built into the bearing flanges of the
standard version. This enables premature switching off of the submersible motor (e.g., due to wear-related
increase in storage temperature).
Switching temperature: Upper bearing = 140 °C/284 °F Lower bearing = 130 °C/269 °F

4.5 Temperature densor indication


A continuous indication of the temperature in the stator and the bearings is not possible using bimetallic thermal
limiters or thermistors. For this application it is necessary to fit thermal sensors of the type PT 100 with linear
characteristics into the stator and bearing blocks. This type of resistor has a linear characteristic, i.e. the resi-
stance rise is proportional to the temperature rise.
40 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

4.5.1 Temperature sensor bimetall

0562-0017
Resistance Application Option
Function Temperature switch using the bime-
tallic principle, which opens at a rated
temperature
Switching Taking care not to exceed the allowa-
ble switching current, these can be
Temperature fitted directly into the control circuit

Figure 6 Curve showing principle of operation of bimetallic temperature limiter

Operating voltage ...AC 100 V to 500 V ~


Rated voltage AC 250 V
Rated current AC cos φ = 1,0 2.5 A
Rated current AC cos φ = 0,6 1.6 A
max. switching current at IN 5.0 A

ATTENTION The maximum switching ability of the thermal sensors is 5 A, the rated voltage 250 V.
Explosion-proof motors which are connected to static frequency inverters must be
fitted with thermistors. Activation must be by means of a thermistor protective relay
device with PTB-Approval number.

4.5.2 Temperature sensor PTC


0562-0018

Resistance Application Option


Function Temperature dependent resistance (no
switch) curve with stepwise behaviour
Switching Cannot be installed direct into the
control circuit. Evaluation of the signal
must be carried out by suitable electro-
Temperature nic equipment

Figure 7 Curve showing principle of operation of thermistor

4.5.3 Temperature sensor PT 100

Application Option (not for Ex)


0562-0019

Resistance
Function Function temperature dependent
resistance (no switch). The linear curve
allows continuous measurement and
indication of the temperature
Switching Cannot be installed direct into the
Temperature control circuit. Evaluation of the signal
must be carried out by suitable electro-
nic equipment
Figure 8 Curve showing principle of operation of PT 100

ATTENTION Thermistors or PT 100 devices must never be directly connected into the control or
power system. They must always be connected to a suitable evaluation device.
The thermal monitoring circuit must be wired into the motor contactors in such a manner that a manual reset is
required.
GB 2500-J
41
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

4.6 Operation with frequency inverters


The stator design and the insulation grade of the motors from Sulzer means that they suitable for usage with
fre-quency inverters. It is however essential that the following conditions are met when the motors are used with
frequency inverters:
• The guidelines for EMC (electromagnetic compatibility) are complied with.
• Explosion-proof motors must be equipped with thermistors (PTC temperature sensors) if operated in ha-
zardous areas (ATEX Zone 1 and 2).
• Machines designated as Ex machines may never, without exception, be operated using a mains frequency
that is greater than the maximum of 50 or 60 Hz as indicated on the type plate.
• Machines that are not designated as Ex machines may only be operated using the mains frequency indicated
on the type plate. Greater frequencies can be used but only after consulting with and receiving permission
from the Sulzer manufacturing plant.
• For operation of ex-motors on frequency inverters special requirements in relation to the tripping times of the
thermo control elements, must be observed.
• The lowest frequency must be set so that the minimum fluid velocity of 1 m/s is present in the volute.
• The maximum frequency must be set so the rated power of the motor is not exceeded.
Modern frequency inverters are using higher wave frequencies and a steeper rise on the flanks of the voltage
wave. This means that motors losses and motor noise is reduced. Unfortunately these inverter output signals
cause higher voltage spikes in the stator. Experience has shown that, depending on rated voltage and the
length of the cable between the inverter and the motor, these voltage spikes can adversely affect the life of the
motor. In order to avoid this, inverters of this type must equipped with sinus filters when used in the critical zone
(see fig 9). The sinus filter chosen must be suitable for the inverter with regard to rated voltage, inverter wave
frequency, rated current of the inverter and maximum inverter output frequency.

0562-0012
UN[V]

660

600 critical area

460
400
380

230 non critical area

10 50 100 150 L[m]


L = total length (from frequency inverter to motor)

Figure 9 Critical / non critical area


5 Installation

5.1 Installation of the XFP submersible sewage pumps

5.1.1 Installation options for the XFP submersible sewage pumps


There are three main installation options for the submersible pumps.
1. Wet installation vertical with ABS automatic coupling system
2. Dry installation with ground support ring (with closed cooling system)
3. Dry installation horizontal (with closed cooling system)
42 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

Wet installation:

NOTE The dimensional sheets and foundation plans for each type of installation are sup-
plied either with the planning documents or your order confirmation.

4 2 3 5 6 1 7 10 9 8

0562-0020
13

11
12

14 15

18
17

16 16

Figure 10 Wet installation vertical with ABS automatic coupling system

Legend
1 Venting 10 Guide tube
2 Valve chamber 11 Discharge line
3 Shut-off valve 12 Inflow chamber with impact wall
4 Outflow line 13 Inflow line
5 Non-return valve 14 Sulzer submersible sewage pump
6 Fitting for valve removal 15 Automatic level control
7 Cable duct 16 Concrete benching
8 Bracket for float switches 17 Pedestal
9 Collection sump 18 Bracket

ATTENTION The power cables should be handled carefully during installation and removal of
the pumps in order to avoid damage to the insulation. When raising the submersible
pump out of the concrete sump or the steel discharge pipe with the hoist ensure that
the connection cables are lifted out simultaneously as the pump itself is being raised.
• Fit a hoist to the submersible sewage pump.
• The Sulzer submersible sewage pump is suspended on the guide tube by means of the pedestal bracket on
the pressure connection and carefully lowered vertically, or at a slight inclination (max. 3°). It couples automa-
tically at the pedestal and seals the pressure connection at the pedestal leak-tight by means of its own weight
and a seal.
Dry sump installation:
• Fit a hoist to the submersible pump.
GB 2500-J
43
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

• With the aid of the hoist place the submersible pump carefully into the prepared mounting frame and fasten.
• Mount suction and pressure nozzles on the pump housing.
• If required, fit the vent line to the volute.
• Open the gate valves on the suction and discharge side.
5.1.2 HD- pedestal fitting of O-ring and guide piece

m
Care, ensure that adhesive does not come into contact with skin or eyes! Wear goggle and gloves!

The groove of the guide piece and O-ring must be clean and free of grease. The instant adhesive LOCTITE
type 454 (supplied with the unit) is spread evenly on the base of the groove in the bracket (11/1) and the O-ring
inserted immediately.

NOTE The hardening time of the adhesive is only about 10 seconds!


The guide piece (11/3) must be screwed on as shown in the drawing! Fasten the guide piece (11/3) with the two
M12 screws (11/2). Tighten the screws with a torque of 56 Nm.

0562-0027
Legend
1
1 Bracket (is fitted to the pump)
2 2 Screws (2 off)
3 Guide piece
3 4 O-ring
5 Pedestal
4 LOCTITE 454

Figure 11 HD-Pedestal DN 100 - 800

5.1.3 Tightening torque

Tightening torque for ABS stainless steel screws A4-70:


Thread M8 M10 M12 M16 M20 M24 M27 M30
Tightening torque 17 Nm 33 Nm 56 Nm 136 Nm 267 Nm 460 Nm 500 Nm 600 Nm

5.1.4 Fitting position of the Nord-Lock® securing washers


0562-0009

Outer side of the 2 securing washers

Inner side of the 2 securing washers

Figure 12 Correct fitting position of the Nord-Lock ® securing washers

44 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

5.2 Installation of the AFLX and VUPX submersible pumps


A rake must be attached to the inlet of the AFLX submersible mixed flow column pump. The maximum bar
spacing depends on the type of hydraulics fitted to the pump and can be obtained from the table below.

Type of hydraulics Clean water Runoff water, river water, used water, rain water,
pre-screened liquid, recirculation
Bar spacing in mm Bar spacing in mm
AFLX 0600/0700 ≤ 40 ≤ 20
AFLX 0800 ≤ 60 ≤ 30
AFLX 1200 ≤ 100 ≤ 50
If larger bar spacings are required, please contact Sulzer

A rake must be attached to the inlet of the VUPX submersible propeller pump. The maximum bar spacing
depends on the type of hydraulics fitted to the pump and can be obtained from the table below.

Type of hydraulics Clean water Runoff water, river water, pre-screened liquid,
used water, rain water recirculation
Bar spacing in mm Bar spacing in mm Bar spacing in mm
VUPX 0400 ≤ 30 ≤ 25 ≤6
VUPX 0500 ≤ 40
VUPX 0600 ≤ 50
VUPX 0800 ≤ 60
VUPX 1000 ≤ 80
VUPX 1200 ≤ 80
If larger bar spacings are required, please contact Sulzer

ATTENTION When setting the switching off level the minimum cover as given in the installation
documents must be adhered to.

5.2.1 Installations examples with AFLX and VUPX submersible pumps


7 1 8 7 8 1
0562-0028

0562-0029

3
2

4
4

6 6

Figure 13a AFLX/VUPX in a steel discharge pipe Figure 13b AFLX/VUPX in a concrete sump
GB 2500-J
45
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

Legend
1 Tank cover 5 Coupling ring
2 Discharge pipe (riser pipe) 6 Minimum water level (see installation drawings)
3 Concrete sump 7 Connection cable
4 AFLX/VUPX submersible pump 8 Cable support (for fixing the power cable)

ATTENTION The power cables should be handled carefully during installation and removal of the
pumps in order to avoid damage to the insulation.
• Fit a hoist to the submersible pump.
The coupling ring required for installation of the AFLX/VUPX submersible pump must already be installed as
shown in Figure 12 and 13. Before installation of the pump a suitable support (hook) for the chain, as well as an
opening and suspension (cable sock) for the cable must be provided in the sump or riser pipe.
Before or during the installation the motor connection cables should be fitted on site with suitable strain relief
(e.g. cable socks). Particular care should be taken that the cable insulation is not crushed or damaged by the
weight of the hanging cable especially in the area of the cable inlet.

ATTENTION When raising the submersible pump out of the concrete sump or the steel discharge
pipe with the hoist ensure that the connection cables are lifted out simultaneously as
the pump itself is being raised.
Lowering of the AFLX and VUPX submersible pump into the coupling ring

ATTENTION Before lowering the pump a direction of rotation check should be carried out.
• Draw the cable hose over the end of the connection cable.
2500-0009

2500-0010

Figure 14 adjustment Bellmouth AFLX Figure 15 adjustment Bellmouth VUPX

ATTENTION The steel riser pipe, or concrete sump must be cleaned thoroughly (builder‘s rubble,
etc.). To optimise the inflow and to reduce the noise level it is important that one pair
of fins of the suction pipe are in line with the main flow direction of the inflow cham-
ber. This must be observed when fitting the pump into a sump or into a steel dischar-
ge pipe.
• Use lifting equipment to slowly lower the submersible mixed flow column/propeller pump into the shaft up to
the coupling ring; feed in the motor connecting cable at the same time. The submersible mixed flow column/
propeller pump centres itself automatically and leakage free in the coupling ring.
• Attach the lifting chain to the hook provided so that it cannot strike either the pump cable or the sump wall.

46 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

• Tension the pump cable and fasten to the hook provided with the aid of the cable sock. Where a steel pressu-
re pipe is used the connection cable should be brought through the connection cable inlet and sealed off in a
watertight manner.

c
The connection cable should only be tightened sufficiently so that no tension acts at the cable inlet in
the head of the pump. The connection cable should not strike the chain or the sump wall.

• If necessary, the steel riser pipe is sealed off in a watertight manner.


5.3 Electrical connection

0838-0006

0838-0007
Cable 1
PE
Cable 1
U1
PE PE = G
U2 U1
V1 GC = ground check
GC Cable 2
V2 V1
W1
W2 W1 Cable 3 U1 10
M3 ~ U2 U1
PE
PE V1 11
V2 V1
10
W2
W1 22
11 W2 W1
U2
M3 ~
22
V2

Cable 2

Figure 16 Two power cables and one control cable Figure 17 60 Hz version: One power cable and one con-
trol cable

2500-0002
Cable 1 Cable 3

Ex-Di Ölraum/ Oil chamber


PE
10K - 22/ 1

U1 10K - 22/ 2
Motorüberwachung / Motor monitoring
U2 U1 V1
Betriebsanleitung und Sicherheitshinweise
beachten!
Observe installation and operating
V2 V1 PE instructions and safety instructions! Bei Überwachung je Phase
W1 For monitoring each phase
10 (F0) ( 30/ 1 - 30/ 2 - 30/ 3 )
PTC PT100
W2 W1 ( 31/ 1 - 31/ 2 - 31/ 3 )
Abschalten/ Switch off
Abschalten / Switch off

40 30
Temperaturmessung/

M3 11 Wicklung/
Temp. measurement

(F1) Winding 41 31
42 34
PE 12
Lager oben/
43 35
~3
Upper bearing
44 36
W2 13
Lager unter/
45 37 ~3
Lower bearing

U2 20 Di Anschlussraum/ Connection chamber


Vibration Sensor
21 Di Motorraum/ Motor chamber
22 Di Öl-/ Überwachungsraum 50 (+ )
V2 (DI) Oil-/ Separation chamber 51 (- )

Cable 2

Figure 18 Special versions: two power cables and one control cable - for optional motor monitoring features
2500-0008

Cable 1 Cable 2

Ex-D i Öl raum/ Oilchamber


PE=G (Schutzleiter) 10K - 22/ 1
GC= ground check
(Prüfleiter für PE) Motorüberwachung / Motor monitoring
10K - 22/ 2
PE Betriebsanleitung und Sicherheitshinweise
beachten!
GC PE
Observe installation and operating
Bei Überwachung je Phase
instructions and safety instructions!
For monitoring each phase
10 (F0) ( 30/ 1 - 30/2 - 30/3 )
PTC PT100 ( 31/ 1 - 31/2 - 31/3 )
Abschalten/ Switch off
Abschalten / Switch off

40 30
Temperaturmessung/
Temp. measurement

11 Wicklung/
U1 (F1) Wind ing 41 31
U2 U1
12
Lager oben/
42
43
34
35
~3
Upper bearing
V1
V2 V1 13
Lager unten/
44 36
~3
Lower bearing 45 37
W1 20 Di Anschlussraum/ Connection chamber
W2 W1 21 Di Motorraum/ Motor chamber
Vibration Sensor

M3~ 22 Di Öl -/ Überwachungsraum 50 (+ )
51 (- )
(D I) O il-/ Separation chamber

Figure 19 60 Hz version: one power cable and one control cable - for optional motor monitoring features

GB 2500-J
47
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

ATTENTION The cable leads are routed out of the motor. No switching takes place in the motor! (Exception
US-version). Any switching required (use of bridges) must be carried out in the control panel.

NOTE Information on the type of starting can be obtained from the nameplate of the pump.

ATTENTION The unit should only be operated with the overload relay and thermal sensors/limiters
connected.

5.3.1 Lead designations

Direct starting in star 1 U1

0562-0033
L1 L2 L3 Join
North America 1 2 3 4&5&6 4 U2
6 5
W2 V2
3 2
Sulzer/Germany U1 V1 W1 U2 & V2 & W2 W1 V1

Direct starting in delta

0562-0034
6 1
W2 U1
L1 L2 L3 -
North America 1; 6 2; 4 3; 5 -
W1 U2
3 4
Sulzer/Germany U1; W2 V1; U2 W1; V2 - 5 V2 V1 2

5.4 Checking direction of rotation


0562-0035

ATTENTION ATTENTION
RO
N
T R E A C TI O

The direction of rotation is correct The start reaction is


T O R R E A C TI

if the imeller/propeller rotates in a anti clockwise


clockwise manner when viewing
down from the top of the placed unit
AR
ST

ON

Figure 20 Rotor rotation

NOTE If a number of pumps are connected to a single control panel then each unit must be
individually checked.

ATTENTION The mains supply to the control panel should have a clockwise rotation. If the leads
are connected in accordance with the circuit diagram and lead designations, the
direction of rotation will be correct.

5.5 Connection of the control circuit leads


Control circuit leads for submersible pumps
2500-0003

Ex-Di Ölraum/ Oil chamber

10 = Common lead
10K - 22/ 1

10K - 22/ 2
Motorüberwachung / Motor monitoring
Betriebsanleitung und Sicherheitshinweise
beachten !
11 = Stator upper
PE
Observe installation and operating
instructions and safety instructions ! Bei Überwachung je Phase 12 = Bearing upper
For monitoring each phase
10 (F0)
PTC PT100
( 30/1 - 30/2 - 30/3 ) 13 = Bearing lower
Ab schalten/ Switch off

( 31/1 - 31/2 - 31/3 )


Ab schalten / Switch off

Temperaturmessung /

40 30
20 = DI-connection chamber
Temp. measurement

11 Wicklung /
(F1) Winding 41 31
42 34
~3
12
Lager oben /
Upper bearing 43 35 21 = DI-Motor chamber
22 = DI-Oil chamber
44 36
Lager unten/
13
Lower bearing 45 37 ~3
20 Di Anschlussraum/ Connection chamber
Vibration Sensor
21 Di Motorraum/ Motor chamber

= PE (green/yellow)
22 Di Öl-/ Überwachungsraum 50 (+ )
(DI) Oil-/ Separation chamber 51 (- )

Figure 21 Designation of control circuit leads

48 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

5.6 Connection of the seal monitoring unit to the control panel


The submersible pumps, depending on execution, are supplied as standard with one or more DI-probes for seal
monitoring. In order to integrate this seal monitoring function into the control panel of the pump it is necessary
to fit an Sulzer DI-module and connect this in accordance with the circuit diagrams below.

ATTENTION If the DI-seal monitoring is activated the unit must be immediately taken out of ser-
vice. Please contact your Sulzer service centre.

Power Supply

Connect terminal 3
to ground or housing
of the pump.

CA 461

3 4 5 6

Output
Input
Leakage

Figure 22 Sulzer leakage relay CA 461

Electronic amplifier for 50/60 Hz


110 - 230 V AC (CSA) (Part No.: 1 690 7010)
18 - 36 V DC (CSA) (Part No.: 1 690 7011)

ATTENTION Maximum relay contact loading: 2 Ampere

6 Commissioning
Before commissioning the pump/pump station should be checked and a functional test carried out. Particular
attention should be paid to the following:

g
In explosive zones care must be taken that during switching on and operation of the pumps the pump
section is filled with water (dry running) or alternatively is submerged or under water (wet installation).
Ensure in this case that the minimum submergence given in the data sheet is observed, Other types
of operation e.g. snore operation or dry running are not allowed.

• Have the electrical connections been carried out in accordance with regulations?
• Have the thermal sensors been connected?
• Is the seal monitoring device (where fitted) correctly installed?
• Is the motor overload switch correctly set?
• Have the power and control circuit cables been correctly fitted?
• Was the sump cleaned out?
• Have the inflow and outflows of the pump station been cleaned and checked?
GB 2500-J
49
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

• Is the direction of rotation of the pump correct - even if run via an emergency generator?
• Are the level controls functioning correctly?
• Are the required gates valves (where fitted) open?
XFP
• Do the non-return valves (where fitted) function easily?
• Have the hydraulics been vented in the case of dry installed pumps?
AFLX/VUPX

• Have the steel riser pipe, or concrete sump be cleaned thoroughly (builder’s rubble, etc.)?
7 Maintenance
General maintenance hints

NOTE The maintenance hints given here are not designed for “do-it-yourself” repairs as
special technical knowledge is required.
Sulzer submersible pumps are reliable quality products each being subjected to careful final inspection. Lubri-
cated-for-life ball bearings together with monitoring devices ensure optimum pump reliability provided that the
pump has been connected and operated in accordance with the operating instructions.
Should, nevertheless, a malfunction occur, do not improvise but ask your Sulzer customer service department
for assistance.
This applies particularly if the pump is continually switched off by the current overload in the control panel, by
the thermal sensors/limiters of the thermo-control system or by the seal monitoring system (DI).

ATTENTION The lifting tools like chains and shackles should be visually checked in regular inter-
vals (approx. every 3-month) for wear and corrosion. These parts should be replaced
if required!
The Sulzer service organisation would be pleased to advise you on any applications you may have and to assist you
in solving your pumping problems.

NOTE The Sulzer warranty conditions are only valid provided that any repair work has been
carried out in Sulzer approved workshops and where original ABS spare parts have
been used.
Maintenance hints if the submersible pump is out of use for a considerable period

NOTE If the pumps have remained idle for more than 12 months then we recommend that
you ask Sulzer or an approved distributor for advice.
Before installation:

The covers giving moisture protection of the cables should be only removed immediately before actual installa-
tion of the pump. After the removal of the transport securing devices and before connecting up the pump electri-
cally the motor shaft should be rotated a number of times by turning the impeller or propeller by hand.
After installation:

If, after installation of the submersible pump, it remains out of use for prolonged periods (for example in storm
water holding tanks) then we recommend that the pump be run for a maximum of 1 minute every 3 months in
order to check both its functioning and availability.

50 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

7.1 Coolant filling

ATTENTION Only use products that are approved by the manufacturer!

7.1.1 Coolant filling / Oil filling XFP

2500-0016
4 5

2/3
2/3
Figure 23 Cooling liquid / Oil filling and emptying XFP PE4 - PE5 without cooling jacket

2500-0017

4 5

2
2
Figure 24 Cooling liquid / Oil filling and emptying XFP PE4 - PE5 with cooling jacket

GB 2500-J
51
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

2500-0018
1

4 5

2
2
Figure 25 Cooling liquid / Oil filling and emptying XFP PE6 with cooling jacket

Legend (Figure 23 - 25) XFP


1 Cooling liquid filling (with cooling jacket)
2 Cooling liquid emptying
3 Cooling liquid filling (without cooling jacket) pump should be in horizontal position!
4 Inspection hole dry chamber
5 Inspection hole engine bay

7.1.2 Coolant filling / Oil filling VUPX / AFLX

2500-0021

2
4 5
2 3
Figure 26 Cooling liquid / Oil filling and emptying VUPX / AFLX PE4 - PE5

52 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

4 5
2 3

Figure 27 Cooling liquid / Oil filling and emptying VUPX / AFLX PE6

Legend (Figure 26 / 27) VUPX / AFLX


2 Cooling liquid emptying (to exhaust)
3 Drill hole venting (Cooling liquid filling), pump should be in horizontal position!
4 Inspection hole dry chamber
5 Inspection hole engine bay
Initial filling ex works:
Fill or drain collant at position 1/2/3
Glycol Frostox WS (Partnr.: 11030083) (TYFOROP Chemie GmbH)
Alternative coolant released by Sulzer:
Propylenglykol Code 27
(Houghton Deutschland GmbH)
DOWCAL 20-G HEAT TRANSFER FLUID
(Dow Deutschland GmbH & Co. OHG)
DOWCAL brand of - The Dow Chemical Companyy

Data is only valid for coolant used ex works. (Additional product information and safety data sheet are available
on request).

Coolant filling quantities see chapter 7.1.4

m
When dealing with Frostox WS the general protective measures for chemicals must be observed. The
information and hints in the safety data sheets covering this must be observed!

Fill or drain the lubricant at position 4

ATTENTION Only starting with mechanical seal MG1


PE4 0,6 *
PE5 1,5 *
PE6 2,0 *
* Filling volumes in Litres.

HYDRAULIKÖL HLP-D (Art.nr.: 11030021)


GB 2500-J
53
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

7.1.3 Reference values for antifreeze behaviour

Concentration (vol.%) Antifreeze in C°


Frostox WS Water
10 90 bis -3
20 80 bis -8
30 70 bis -13
40 60 bis -23
50 50 bis -35
60 40 bis -52
33* 67* bis -16*

* default

7.1.4 Coolant filling quantities


XFP 105J, 155J, 200J, 201J, XFP 100J, 150J, 200J, VUPX 0400, 0500, 0600,
206J, 250J, 255J, 300J, 300J, 350M AFLX 0600, 0700
Motor PE4 305J

CB-hydraulics CH-Hydraulik Axial hydraulics


50 Hz 60 Hz A* B* A* B*
PE 75/8 6,9
PE 90/6 6,9
PE 90/8 6,9
PE 110/6 6,9
PE 110/8 6,9
PE 150/6 6,9
PE 150/8 PE 170/8 19.9 8.5 23.3 11.9 6.9
PE 185/6 PE 210/6 19.9 8.5 23.3 11.9 6.9
PE 185/8 PE 210/8 21.2 8.5 24.6 11.9 6.9
PE 220/4 PE 250/4 19.9 8.5 23.3 11.9 6.9
PE 220/6 PE 250/6 19.9 8.5 23.3 11.9 6.9
PE 220/8 PE 250/8 21.2 8.5 24.6 11.9 6.9
PE 300/4 PE 350/4 19.9 8.5 23.3 11.9 6.9
PE 300/6 PE 350/6 21.2 8.5 24.6 11.9 6.9
PE 300/8 PE 350/8 21.2 8.5 24.6 11.9 6.9
PE 370/4 PE 430/4 21.2 8.5 24.6 11.9 6.9
PE 370/6 PE 430/6 21.2 8.5 24.6 11.9 6.9
PE 450/4 PE 520/4 21.2 8.5 24.6 11.9 6.9
* A = Version with cooling jacket * B = Version without cooling jacket. Filling volumes in Litres. only version B

54 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

XFP 100J, 105J, XFP 150M, 200M, XFP XFP 501U VUPX 0500 VUPX
150J, 155J, 200J, 250M, 300M, 301M, Special 0600, AFLX 0800
Motor PE5 201J, 205J, 250J, 305M, 306M, 351M, version 0700, 0800
255J, 300J, 305J 356M, 400M, 405M

50 Hz 60 Hz A* B* A* B* A* B* A* B*
PE 300/10 PE 350/10 - - - - - - 59.5 30.5 7.7 -
PE 370/8 PE 430/8 - - 48 24 46.5 22.5 54.5 30.5 7.7 -
PE 370/10 PE 430/10 - - - - - - 54.5 30.5 7.7 -
PE 450/6 PE 520/6 42.5 18.5 48 24 46.5 22.5 - - 7.7 -
PE 450/8 PE 520/8 - - 53 24 51,5 22.5 59.5 30.5 7.7 -
PE 450/10 PE 520/10 - - - - - - 54.5 30.5 7.7 9.4
PE 550/4 PE 630/4 42.5 18.5 48 24 46.5 22.5 - - - -
PE 550/6 PE 630/6 47.5 18.5 53 24 51.5 22.5 - - 7.7 -
PE 550/8 PE 630/8 - - 53 24 51.5 22.5 59.5 30.5 7.7 -
PE 550/10 PE 630/10 - - - - - - 59.5 30.5 7.7 9.4
PE 750/4 PE 860/4 42.5 18.5 48 24 46.5 22.5 - - - -
PE 750/6 PE 860/6 47.5 18.5 53 24 51.5 22.5 - - 7.7 -
PE 750/8 PE 860/8 - - 53 24 51.5 22.5 59.5 30.5 7.7 9.4
PE 900/4 PE 1040/4 47.5 18.5 53 24 51.5 22.5 - - - -
PE 900/6 PE 1040/6 47.5 18.5 53 24 51.5 22.5 - - 7.7 -
PE 1100/4 PE 1250/4 47.5 18.5 53 24 51.5 22.5 - - - -
* A = Version with cooling jacket * B = Version without cooling jacket. Filling volumes in Litres. only version B

Motor PE6 Radial hydraulics Axial hydraulics


VUPX 0800
XFP200M, 250M, 300M,
XFP400R VUPX 0500 VUPX 1000
50 Hz 60 Hz 301M, 305J, 306M, 356M,
XFP501U
XFP500 XFP600V XFP600X
VUPX 0600 AFLX 0800
400M, 405M
AFLX 1200

PE 750/12 PE 860/12 144 155 9,6


PE 750/10 PE 860/10 120 8,1 9,6
PE 900/12 PE 1040/12 144 155 9,6
PE 900/10 PE 1040/10 120 140 9,6
PE 900/8 PE 1040/8 114 120 8,1 9,6
PE 1100/12 PE 1250/12 153 164 9,6
PE 1100/10 PE 1250/10 155 9,6
PE 1100/8 PE 1250/8 114 120 8,1 9,6
PE 1100/6 PE 1250/6 114 120 8,1 9,6
PE 1320/12 PE 1500/12 153 164 9,6
PE 1320/10 PE 1500/10 155 9,6
PE 1320/8 PE 1500/8 114 120 135 140 8,1 9,6
PE 1320/6 PE 1500/6 114 120 8,1 9,6
PE 1320/4 PE 1500/4 114
PE 1600/10 PE 1700/10 153 164
PE 1850/10 153 164
PE 1600/8 PE 1700/8 135 150 155 9,6
PE 1850/8 135 150 155 9,6
PE 1600/6 PE 1850/6 130 135 8,1 9,6
PE 1600/4 PE 1850/4 114 9,6
PE 2000/10 PE 2000/10 153 164 9,6

GB 2500-J
55
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

Motor PE6 Radial hydraulics Axial hydraulics


VUPX 0800
XFP200M, 250M, 300M,
XFP400R VUPX 0500 VUPX 1000
50 Hz 60 Hz 301M, 305J, 306M, 356M,
XFP501U
XFP500 XFP600V XFP600X
VUPX 0600 AFLX 0800
400M, 405M
AFLX 1200
PE 2250/10 153 164 9,6
PE 2000/8 PE 2000/8 150 144 155
PE 2250/8 150 144 155
PE 2000/6 PE 2200/6 138 143 160 8,1 9,6
PE 2250/6 138 143 160 8,1 9,6
PE 2000/4 PE 2200/4 130
PE 2250/4 130
PE 2250/6 PE 2500/6 143
PE 2500/8 PE 2800/8 160 153 164 9,6
PE 2500/4 PE 2800/4 130
PE 3000/4 PE 3350/4 138
PE 3500/4 PE 4000/4 138
Filling volumes in Litres.

Motor PE6 Axial hydraulics with gear unit


Hydraulik Gear unit filling quantity Filling quantity
VUPX1000G
VUPX1200G 51 7
AFLX1200G
Filling volumes in Litres

Starting frequency of the motors

The allowable starting frequency per hour can be read from the table below (where not otherwise specified
from the works).

Motor power maximum starts per hour at interval in minutes


15 ≥ 160 kW 10 6

ATTENTION The allowable starting frequency for any starting devices should be obtained from
manufacturer of these devices.

7.2 Removal of the submersible sewage pump

m
The safety hints in the previous sections must be observed!

7.2.1 Removal of the XFP submersible sewage pump from a wet sump

c
Before removal of the unit the motor connection cables at the control panel should be completely dis-
connected by a qualified person from mains and care should be taken that it cannot be inadvertently
switched back on.

g
Before removal of units in hazardous areas the sump and surrounding area must be adequately ven-
ted to avoid the danger of a spark causing an explosion!

• Fit a hoist to the pump.


• Raise the submersible pump out of the sump with the hoist. While doing this the connection cables should be
simultaneously drawn out of the sump as the pump itself is being raised.

56 GB 2500-J
Installation and Operating Instructions
XFP-PE4-6 | AFLX-PE4-6 | VUPX-PE4-6

• Place the submersible sewage pump vertically onto a firm surface and secure against tipping.
7.2.2 Removal of the XFP submersible sewage pump when dry installed
• Close off the gate valves on the inlet and discharge sides.
• Empty the volute and, if necessary, the discharge line.
• If fitted, dismantle the venting line above the discharge.
• Install lifting gear on the submersible pump.
• Disconnect the suction inlet by opening the bolts on the bottom plate of the hydraulics (or at the pump hou-
sing).
• Dismantle the pressure hose by loosening the screws on the pressure flange of the pump housing.
• If necessary, remove the fastening bolts at the ground support ring and carefully lift off the pump with the
hoist.
• Place the pump on an even, firm, flat surface.
7.2.3 Removal of the AFLX and VUPX submersible pump
• If present, the discharge pipe cover should be removed and the water pressure-tight cable inlet opened.
• Raise the submersible pump out of the concrete sump or the steel discharge pipe with the hoist. While doing
this the connection cables should be drawn out as the pump itself is being raised.
• Place the submersible pump with propeller housing vertically on a solid surface, taking care that it cannot tip
over.

GB 2500-J
57
I Sulzer Pump Solutions Germany GmbH I Scheiderhöher Straße 30-38, D-53797 Lohmar, Germany I
I Tel. +49 22 46 900 0 I Fax +49 22 46 900 200 I www.sulzer.com I
GB 2500-J

You might also like