GENERAL DESCRIPTION
The universal isolated transmitter DAT4535 is able to measure and linearise voltage, current and resistance signals, potentiometers and the standard
thermocouples and RTDs with, if required, the cold junction compensation and the wires compensation.
In function of programming, the measured values are converted and transmitted on the 4÷20 mA current loop.
The device guarantees high accuracy and performances stability both versus time and temperature.
The programming is made by the dip-switch located in the window on the side of the enclosure. By means of dip-switches it is possible to select the input
type and range without recalibrate the device.
Moreover, by Personal Computer and the cable CVPROG the user can program all of the device's parameters for his own necessity.
The terminals of the current signal on input side must be only connected to active current loop.
The 1500 Vac galvanic isolation eliminates the effects of all ground loops eventually existing and allows the use of the transmitter in heavy environmental
conditions found in industrial applications.
It is housed in a plastic enclosure of 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.
USER INSTRUCTIONS
The transmitter DAT 4535 must be powered by a direct voltage between 7 to 32 V and applied to the terminals P(+V) and O (-V) or to the terminals N(+V)
and M (-V).
The 4÷20 mA output signal is measurable in the power loop as shown in the section “Output/Power supply connections”; Rload is the input impedance of
instruments on the current loop; to obtain a correct measure, the value of Rload will be calculated as function of the power supply value ( see section
“Technical specification – Load characteristic”).
The input connections must be made as shown in the section "Input connections".
To configure and install the transmitter refer to sections "Programming”, “Configuration by dip-switches”, “Dip-switches configuration tables” and
“Installation Instructions”.
TECHNICAL SPECIFICATIONS (Typical @ 25 °C and in nominal conditions)
INPUT Linearity (1) POWER SUPPLY
Input type Min Max Min. Span Tc, RTD, Pot ± 0.1 % f.s.
mV, V, mA ± 0.05 % f.s. Supply voltage 7 .. 32 Vdc
TC (CJC int./ext.) Reverse polarity protection 60 Vdc max
J -200°C 1200°C 100°C Input impedance
K -200°C 1300°C 100°C TC, mV >= 10 MW Load characteristic - Rload (maximum load
S 0°C 1750°C 400°C Volt >= 1 MW value on current loop per power supply value)
R 0°C 1750°C 400°C mA ~22 W Ohm
B 0°C 1820°C 400°C 1K
E -200°C 1000°C 100°C RTD excitation current
T -200°C 400°C 100°C RTD,Res 400 uA 750
N -200°C 1300°C 100°C Line resistance influence (1)
Voltage TC, mV <=0.8 uV/Ohm 500
CONFIGURATION BY DIP-SWITCHES
Input Tab. sel Opt Full Scale 1) Open the suitable door on the side of the device.
2) Set the input table selector by the dip-switch SW2 [1] (see TAB.1)
3) Set the input type by the dip-switches SW1 [1..4] (see TAB.2A and TAB.2B)
5) Set the minimum value of the input scale (Zero) by dip-switches SW1 [5..8] (see TAB.4)*
SW2
6) Set the full scale value by dip-switches SW2 [3..8] (see TAB.4)*
1
Ex of configuration Pt100 3 wires -50 ÷ 200 °C:
SW1
1
SW2 =
NOTE:
- It is also possible to set the dip-switches using the wizard of the configuration software following the procedure described in the section ”Configuration by
PC” until the step 6 and clicking on icon “Switch”.
TAB.1 – Input table selection TAB.2A – Input type selection TAB.2B – Input type selection TAB.3 - Option
SW2 TABLE SW1 SW1 SW1 SW1 SW2 CJC RTD/RES
1 123 4 12 34 1234 1234 2
TAB. 2A (mV, Volt, mA, TC) EPROM * Tc J Res. 2KW ------ External 3 wires
TAB. 2B (Res, RTD, Pot.) 90 mV Tc K Res. 500W ------ Internal 2/4 wires
200 mV Tc R Pt100 ------
800 mV Tc S Ni100 ------
10 V Tc T Pt 1K ------
20 mA Tc B Ni 1K ------
------- Tc E Pot. <500W ------
------- Tc N Pot. <50KW ------
NOTES:
* To set the input range refer to the TAB.4 (next pages) referred to the input type selected by TAB.1, TAB.2A and TAB 2B.
* If the dip-switches SW1 [1..4] and SW2 [1] are all set in the position 0 (“EPROM”), the device will follow the configuration programmed by PC ( input
type and range, output range and options).
* If the dip-switches SW1 [5..8] and SW2 [3..8] are all set in the position 0 (“Default”), the device will follow the input scale programmed by PC for the
input type selected by the dip-switches SW1[1..4] and SW2[1] .
* If the dip-switch SW2 [2] is set in the ON position and is in progress a measure by Resistance or RTD 2 wires sensor, it is necessary to
connect the terminal I to the terminal L and the terminal G to to the terminal H.
TAB.4a – mV, Tc Input scale settings
Zero Full Scale
SW1 SW2 SW2 SW2 SW2
5678 °C 345678 °C 345678 °C 345678 °C 345678 °C
Default Default 75 225 700
-200 0 80 250 750
-100 5 85 255 800
-80 10 90 275 850
-60 15 95 300 900
-50 20 100 325 950
-40 25 110 350 1000
-30 30 120 375 1100
-20 35 130 400 1200
-10 40 140 425 1300
0 45 150 450 1400
10 50 160 475 1500
20 55 170 500 1600
50 60 180 550 1750
100 65 190 600 1800
150 70 200 650 1850
CONNECTIONS
INPUT CONNECTION POWER SUPPLY / OUTPUT CONNECTION
mV TC RTD/RES 2W (*) RTD/RES 3W
P
L L G G +
+ +
7÷32 Vdc
H Iout
I I I O Rload
+
I
Terminal P = N; Terminal O = M
H + F ISOLATION STRUCTURE
H - I
Note: if the device is programmed by dip switches for RTD / RES with 2 wires
connection make a short circuit between the terminals I and L and the terminals
G and H.
HOW TO ORDER
The device is provided as requested on the Customer's order.
Refer to the section “Programming” to determine the input ranges.
In case of the configuration is not specified, the parameters must be set by the user.
Datexel reserves its rights to modify totally or in part the characteristics of its products without notice at any time . ED.04.13-R.06