Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

A5E46496083 2 76 - MANUAL - SITOP SEL1200 1400 - en US

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

Overview

Safety instructions 1
Description, device design,
dimension drawing 2
SITOP power supply
Mounting/removal 3
SITOP SEL1200-1400 Mounting position, mounting
4
clearances

Installation 5
Equipment Manual

Technical data 6

Safety, approvals, EMC 7

Ambient conditions 8

Environment 9

Service & Support 10

SITOP SEL1200 8 x 5 A
6EP4437-7FB00-3DX0
SITOP SEL1200 4 x 10 A
6EP4437-7FB00-3CX0
SITOP SEL1200 8 x 10 A
6EP4438-7FB00-3DX0

SITOP SEL1400 8 x 5 A
6EP4437-7EB00-3DX0
SITOP SEL1400 4 x 10 A
6EP4437-7EB00-3CX0
SITOP SEL1400 8 x 10 A
6EP4438-7EB00-3DX0

06.2020
A5E46496083-2-76
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG A5E46496083-2-76 Copyright © Siemens AG 2020.


Digital Industries Ⓟ 06/2020 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Overview

Description

In conjunction with a 24 V power supply, the selectivity module is used to distribute the load
current across several branches and to monitor the individual currents in these branches.
Faults in the individual branches caused by overload or short-circuit are detected and
selectively switched off, so that the fault does not impact the other load circuits. This means
fast troubleshooting and minimized downtimes.
SEL1200 assumes loads that correspond to the PLC standard and can therefore
automatically buffer a voltage-free period of 10 ms. At the time of shutdown, the current
cannot be briefly limited, and as a consequence brief voltage dips below 20 V are possible.
SEL1400 is designed for demanding applications, and does not permit voltage dips below
20 V for any period of time. This is also suitable for loads/consumers that do not comply with
the PLC standard.
The key benefits of the product include:
● A maximum of 8 load branches are monitored for each module
● The response threshold can be continually set for each output using a potentiometer
● Overcurrents are reliably switched off, independent of the cable length and cable cross-
section
● The 24 V supply for the other loads is maintained
● 2 adjacent outputs can be connected in parallel to increase the power rating (for max.
15 A)

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 3
Overview

● Fast fault diagnostics using:


– Multi-colored LEDs for each output for faster troubleshooting on-site
– You can toggle between group message and single-channel diagnostics
● Floating group signal contact for remote diagnostics
● Single-channel signal using the diagnostics interface to serially signal the state of the
individual outputs
● Evaluation using free of charge SIMATIC S7 function blocks (S7-1200/1500)
● It can be selected that the load branches are sequentially switched on to reduce the total
inrush current
● Narrow design
● Push-in terminals

SITOP SEL1200-1400
4 Equipment Manual, 06.2020, A5E46496083-2-76
Overview

Ordering data
The following device options are available:

Selectivity modules
Type Order number
SITOP SEL1200 8 × 5 A 6EP4437-7FB00-3DX0
24 V DC input
Number of outputs: 8
Setting range of the response threshold: 1 - 5 A
with group signaling contact
SITOP SEL1200 4 × 10 A 6EP4437-7FB00-3CX0
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 2 - 10 A
with group signaling contact
SITOP SEL1200 8 × 10 A 6EP4438-7FB00-3DX0
24 V DC input
Number of outputs: 8
Setting range of the response threshold: 2 - 10 A
with group signaling contact
SITOP SEL1400 8 × 5 A 6EP4437-7EB00-3DX0
24 V DC input
Number of outputs: 8
Setting range of the response threshold: 1 - 5 A
with group signaling contact
SITOP SEL1400 4 × 10 A 6EP4437-7EB00-3CX0
24 V DC input
Number of outputs: 4
Setting range of the response threshold: 2 - 10 A
with group signaling contact
SITOP SEL1400 8 × 10 A 6EP4438-7EB00-3DX0
24 V DC input
Number of outputs: 8
Setting range of the response threshold: 2 - 10 A
with group signaling contact

Accessories
Type Order number
Reference labeling plate (160 plates) 6ES7193-6LF30-0AW0

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 5
Overview

Validity
This manual provides information on the following products:
● Selectivity module SITOP SEL1200 8 × 5 A
Article number: 6EP4437-7FB00-3DX0
Product state: 1
● Selectivity module SITOP SEL1200 4 × 10 A
Article number: 6EP4437-7FB00-3CX0
Product state: 1
● Selectivity module SITOP SEL1200 8 × 10 A
Article number: 6EP4438-7FB00-3DX0
Product state: 1
● Selectivity module SITOP SEL1400 8 × 5 A
Article number: 6EP4437-7EB00-3DX0
Product state: 1
● Selectivity module SITOP SEL1400 4 × 10 A
Article number: 6EP4437-7EB00-3CX0
Product state: 1
● Selectivity module SITOP SEL1400 8 × 10 A
Article number: 6EP4438-7EB00-3DX0
Product state: 1

SITOP SEL1200-1400
6 Equipment Manual, 06.2020, A5E46496083-2-76
Table of contents

Overview................................................................................................................................................. 3
1 Safety instructions ................................................................................................................................... 9
1.1 General safety instructions ....................................................................................................... 9
1.2 Safety instructions for hazardous zones .................................................................................10
2 Description, device design, dimension drawing...................................................................................... 11
2.1 Device description...................................................................................................................11
2.2 Connections and terminal designation....................................................................................13
2.3 Potentiometer ..........................................................................................................................15
2.4 Status displays and signaling .................................................................................................16
2.5 Buttons and selector switches ................................................................................................19
2.6 Electronic overload shutdown and reset .................................................................................21
2.7 Setting the switch-on delay time .............................................................................................24
2.8 Block diagram .........................................................................................................................25
2.9 Dimensions and weight ...........................................................................................................26
3 Mounting/removal ................................................................................................................................. 29
4 Mounting position, mounting clearances ................................................................................................ 31
4.1 Standard mounting position ....................................................................................................31
4.2 Other mounting positions ........................................................................................................34
4.2.1 SEL1200 8 x 5 A 6EP4437-7FB00-3DX0 ...............................................................................34
4.2.2 SEL1200 4 x 10 A 6EP4437-7FB00-3CX0 .............................................................................36
4.2.3 SEL1200 8 x 10 A 6EP4438-7FB00-3DX0 .............................................................................38
4.2.4 SEL1400 8 x 5 A 6EP4437-7EB00-3DX0 ...............................................................................40
4.2.5 SEL1400 4 x 10 A 6EP4437-7EB00-3CX0 .............................................................................42
4.2.6 SEL1400 8 x 10 A 6EP4438-7EB00-3DX0 .............................................................................44
5 Installation ............................................................................................................................................ 47
5.1 Connection at the input ...........................................................................................................47
5.2 Connection at the output .........................................................................................................49
6 Technical data ...................................................................................................................................... 51
6.1 Input ........................................................................................................................................51
6.2 Output .....................................................................................................................................52
6.3 Efficiency .................................................................................................................................54
6.4 Protection and monitoring .......................................................................................................54
6.5 MTBF ......................................................................................................................................54

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 7
Table of contents

6.6 Mechanical system ................................................................................................................ 55


6.7 Accessories ............................................................................................................................ 55
6.8 Dimension drawing ................................................................................................................ 56
7 Safety, approvals, EMC ........................................................................................................................ 57
7.1 Safety ..................................................................................................................................... 57
7.2 Approvals ............................................................................................................................... 57
7.3 EMC ....................................................................................................................................... 58
8 Ambient conditions................................................................................................................................ 59
9 Environment ......................................................................................................................................... 61
10 Service & Support ................................................................................................................................. 63

SITOP SEL1200-1400
8 Equipment Manual, 06.2020, A5E46496083-2-76
Safety instructions 1
1.1 General safety instructions

WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 9
Safety instructions
1.2 Safety instructions for hazardous zones

1.2 Safety instructions for hazardous zones


The devices comply with ATEX directive 2014/34/EU; EN 60079-0; EN 60079-7.

WARNING

OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY!

SITOP SEL1200-1400
10 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing 2
2.1 Device description
Using the selectivity module, a 24 V DC output voltage from a regulated power supply can
be distributed across four or eight load circuits. The response threshold of the output current
can be individually set for each output using a potentiometer. When the set response
threshold is exceeded, the output is automatically switched off according to a defined switch
off characteristic, and can be switched on again after a wait time using a pushbutton
(ON/OFF/RST) or remote reset (RST). The status of the output is displayed using a multi-
color LED for each output. The status of the outputs can be processed via a group signaling
contact (13, 14) or via a serial single-channel signal.

NOTICE

In addition to the energy demand for continuous operation of the application, an adequate
energy reserve must be taken into consideration for tripping according to the l²t
characteristic if a fault occurs.

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 11
Description, device design, dimension drawing
2.1 Device description

① +24 V DC input
② 0 V connection for the internal supply
③ +24 V DC outputs
④ Group signaling contact (13, 14); not assigned (NF); remote reset (RST)
⑤ Potentiometer for each output
⑥ (ON/OFF/RST) pushbutton and indicator light for each output
⑦ Selector switch for diagnostic interface (COM)
⑧ Selector switch for switch-in delay (time definition) (TD1, TD2)
⑨ Mounting rail slider
⑩ Natural convection
⑪ Clearance above/below

Figure 2-1 Design

SITOP SEL1200-1400
12 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.2 Connections and terminal designation

2.2 Connections and terminal designation


The input terminals ① can be used to establish the connection to the supply voltage. The
"0 V" connection ② is used to supply the internal electronics. The output terminals ③ are
used to connect to the loads to be supplied (see also Chapter Installation (Page 47)).
The operating state of the device can be processed using the group signal contact ④ (for
the function and content rating, see Figure 2-4 Status displays and signaling (Page 16)).
The remote reset (RST) input ④ is used to reset outputs that have automatically been shut
down (function, see Chapter Status displays and signaling (Page 16)).

Connections and terminal designations


① 24 V DC input 2 spring-loaded terminals

② 0 V connection for the internal supply 2 spring-loaded terminals

③ 24 V DC output: 1 - 4 (1 - 8) one spring-loaded terminal each

④ Group signaling contact (13, 14); not as- one spring-loaded terminal each
signed (NF); remote reset (RST)

*1) Do not subject the end stop to higher loads


*2) 8 mm of insulation has to be stripped when using conductor end sleeves

Figure 2-2 Terminal data

The terminal location must first be opened for smaller conductor cross-sections and for
flexible conductors without conductor end sleeves. To do this, an appropriate slotted
screwdriver must be inserted into the square slot at the appropriate connection.
We recommend the CRIMPFOX 6 - 1212034 crimping tool to crimp conductor end sleeves. If
the conductor end sleeve is longer than the permissible length of the crimping tool, then the
end sleeve must be crimped in several steps.
Applying pulling and lateral forces to the terminal should be avoided.

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 13
Description, device design, dimension drawing
2.2 Connections and terminal designation

NOTICE
Overload of the wiring
The "0 V" connection is only used to supply the internal electronics of the selectivity
module. The 0 V of the connected loads must be routed directly to the power supply using
separate cables!

SITOP SEL1200-1400
14 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.3 Potentiometer

2.3 Potentiometer
The potentiometer ⑤ on the front of the device is used to set the response threshold of the
output current. When delivered, the maximum possible response threshold is set.

Figure 2-3 Potentiometer

Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.

For information on actuating the potentiometer (screwdriver, torque), see Figure 2-2
Terminal data (Page 13).

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 15
Description, device design, dimension drawing
2.4 Status displays and signaling

2.4 Status displays and signaling

6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Group signal contact (13, 14) ④ floating relay contact (NO contact),
contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A
NOTICE: It is not permissible that the signaling contact is connected to the line
voltage!
Remote reset (RST) ④ non-isolated 24 V DC input
Signal level "High" for > 15 V
Indicator light and pushbutton Three-color LED: rot, green and orange
(ON/OFF/RST) for each output ⑥
Selector switch for diagnostic interface Switchover between signaling the status of the output channels and communi-
(COM) ⑦ cation at the signaling contact.

Figure 2-4 Status displays and signaling

The operating state of the outputs is displayed using multi-color LEDs at the front of the
device. Symbols indicate the significance of each LED, which are listed in the following table.

LED off
LED is continuously lit
LED flashes

SITOP SEL1200-1400
16 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.4 Status displays and signaling

Indicator light (LED 1 - 4 (1 - 8)) ⑥, signaling contact (13, 14) ④ and selector switch for
diagnostics interface (COM) ⑦

Signaling 6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Off All LEDs:
• No supply voltage
• Device powering up: After the device has powered up, the out-
puts are switched on, taking into consideration the switch-on de-
lay that has been set.
LED, individual output:
Output defective (internal fuse has ruptured)
Lights up green Normal operation, output is switched on
Flashes green The output current is in the overload range according to the shut-
down characteristic (see Chapter Electronic overload shutdown and
reset (Page 21))
Overload at the output: Output current 100 - 150 % of the response
threshold (permissible for 5 s)
Flashes orange Output manually switched off using pushbutton (ON/OFF/RST) ⑥:
The state is saved when the device is switched off, and can only be
reset again by pressing the up button again.
Lights up red Output is automatically shut down due to overload or external over-
voltage > typ. 30 V/100 ms. The output can be switched on again
after a typical wait time of 20 s. The wait time still to elapse is saved
when switching off the device – and is reactivated after the device
has been switched on again.
Flashes red Output ready to be reset after an automatic switch off by actuating
the (ON/OFF/RST) ⑥ or remote reset (RST) ④ (effective for all
outputs that have been automatically switched off)
... all LEDs indi- Overload - total max. output current exceeded, after max. 30 s out-
vidually flash puts are successively switched off (4 → 3 → 2 → … (8 → 7 → 6 → …))
red until there is no longer an overload condition.
Red running Device overtemperature: The outputs can be switched-on again once
light the temperature is in the normal range.
Contact (13, 14) (NO con- Contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A
tact): NOTICE: It is not permissible that the signaling contact is connected
to the line voltage!
closed:
for COM = '0': all outputs active
for COM = '1': Data transfer
Selector switch for diagnostic Switchover between signaling the status of the output channels and
interface (COM) communication at the signaling contact.
'0': Displays the status of the output channels
'1': Internal device parameters are transferred via the signaling con-
tact
Signaling contact '1' = 24 V DC / '0' = 0 V (pull down)

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 17
Description, device design, dimension drawing
2.4 Status displays and signaling

If the selector switch for the diagnostics interface (COM) is at 0, then signal contact ④ is
only closed if all channels are in the LED state "green", "green flashing" or "orange flashing".
Additional information about the data transfer (COM = 1) is provided in the documents:
● Diagnostics interface (https://support.industry.siemens.com/cs/ww/en/view/109767425)
● Faceplates and communication blocks
(https://support.industry.siemens.com/cs/ww/en/view/109763709)

SITOP SEL1200-1400
18 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.5 Buttons and selector switches

2.5 Buttons and selector switches

Figure 2-5 Buttons and selector switches

Buttons (ON/OFF/RST) ⑥ for the selectivity module SITOP SEL1200-1400 fulfill the
following two functions:
1. manually switching an output off and on (see the following).
2. resetting an output automatically switched off due to an overload condition (see Chapter
Electronic overload shutdown and reset (Page 21)).
Using selector switch COM ⑦, at the message contact (13, 14) ④ you can toggle between
signaling the state of the output channels and the communication at the signaling contact.
COM = 0: Displays the status of the output channels
COM = 1: Internal device parameters are transferred via the signaling contact (diagnostics
interface)
Selector switches (TD1, TD2) ⑧ can be used to select the delay time when switching on the
individual outputs (see Chapter Setting the switch-on delay time (Page 24)).

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 19
Description, device design, dimension drawing
2.5 Buttons and selector switches

Manually switching an output on and off


An individual output can be switched on and switched off using the button
(ON/OFF/RST) ⑥. When the device is delivered, the outputs are manually switched off.
Switching off an output:
For outputs that are switched on, LED ⑥ of the particular output is lit green. You can switch
off the output by pressing the assigned button (ON/OFF/RST) ⑥. The LED then flashes
orange (output has been manually switched off).
Switching on an output:
For outputs that have been manually switched off, LED ⑥ of the particular output is lit
orange. You can switch on the output by pressing the assigned button (ON/OFF/RST) ⑥.
The LED is then lit green (output is switched on).

Note
An output that has been manually switched-off can only be manually switched-on again by
manually pressing the button again. It is not possible to switch on an output that has been
manually switched off using the remote reset signal (RST) ④.
An output that has been manually switched off remains saved (latch) even when the supply
voltage is no longer available, and is a manually switched off when the supply voltage
returns.

SITOP SEL1200-1400
20 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset

2.6 Electronic overload shutdown and reset


An overload is permitted for a defined period of time for each selectivity module output. The
output is electronically shut down according to the "Shutdown characteristic" diagram after
the limit value has been exceeded.

Figure 2-6 Shutdown characteristic

The following applies for the SEL1200: In the range > 150 %, a higher current is briefly
permitted; afterwards it is shut down corresponding to the "Shutdown characteristic"
diagram.
The following applies for the SEL1400: In the range > 150 % of the selected current
response threshold, the current is limited to 150 %, typically after 10 ms to 100 ms, the
output is electronically shut down (LED of the output is lit red).
● An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
● In the range 100 - 150 % of the selected current response threshold, an overload current
is permissible for 5 seconds (LED of the output flashes green), then the output is
electronically shut down (LED of the output is lit red).

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 21
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset

Reset of an electronic overload shutdown via button (ON/OFF/RST) ⑥ and remote reset
(RST) ④
An output that has been shut down due to overload can be reset by pressing the associated
button (ON/OFF/RST) ⑥ (reset).

Figure 2-7 Button and remote reset terminal

The initial situation is an electronic shutdown of individual outputs as a result of an overload


condition. This is signaled using the LED 1-8 ⑥ of the particular output.

LED Meaning/handling
Lit red Electronic shutdown as a result of an overload; wait time until a reset is possible:
approx. 20 seconds.
Flashes red Output ready for a reset; press the button to switch-on the output again.
Lit green The reset was carried out, the output was switched-on again.

Procedure to reset an electronic shutdown:


1. After an electronic shutdown (LED of the output is lit red), allow a wait time of 20 seconds
to elapse (LED of the output flashes red).
2. Press the reset button ⑥ of the particular output:
Electronic shutdown was reset, and the output is switched-on again (LED of the output is
lit green).

SITOP SEL1200-1400
22 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset

Remote reset (RST) ④:


Alternatively, the reset can be performed using a remote reset signal (RST) ④. The non-
isolated 24 V input (referred to the "0 V" terminal of the module) can be used at terminal
"RST". A reset is executed for an input level of > 15 V.

Note
The rising edge of the remote reset signal is evaluated, i.e. for an additional remote reset
signal, initially a voltage level of 13 V must be fallen below.

Using a remote reset signal at terminal "RST" all outputs that were shut down electronically
due to an overload are again reset. Prerequisite: The output is ready to be reset, i.e. the
electronic overload shutdown occurred longer than 20 s ago (LED of the output flashes red).

Note
If, after a reset, the cause of the overload is still present, then the output is again
automatically shut down. Before carrying out a reset, remove the cause of the overload to
prevent a new shutdown.

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 23
Description, device design, dimension drawing
2.7 Setting the switch-on delay time

2.7 Setting the switch-on delay time


For specific loads, it can make sense to sequentially switch-on the outputs in order to reduce
the peak inrush currents, and therefore the load on the power supply. To achieve this, the
individual outputs of the selectivity module can be switched-in with a time delay between one
another in a fixed sequence (output 1 ⇒ 2 ⇒ 3 ⇒ 4 (1 ⇒ 2 ⇒ 3 ⇒ 4 ⇒ 5 ⇒ 6 ⇒ 7 ⇒ 8)). The
delay time set between the individual outputs is the same for all of the outputs. The delivery
condition is load-dependent switch on.

Setting the sequential switch-on delay

Figure 2-8 Selector switch

The switch-on delay time is set at selector switches TD1 and TD2 ⑧. When delivered, DIP
switches "TD1" and "TD2" are in the "0" position (load-dependent switch on delay).

Procedure when setting the delay time:


With the selectivity module in a no-voltage condition, set DIP switches "TD1" and "TD2" to
the required delay time.

Outputs switched on depending on the load: The next output is switched on as soon as the
previous output has run-up (at the earliest, after 5 ms).
25 ms delay between the outputs being switched on

200 ms delay between the outputs being switched on

500 ms delay between the outputs being switched on

The next time that the selectivity module powers up, the outputs are sequentially switched on
corresponding to the selected delay time.

SITOP SEL1200-1400
24 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.8 Block diagram

2.8 Block diagram

Figure 2-9 Block diagram

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 25
Description, device design, dimension drawing
2.9 Dimensions and weight

2.9 Dimensions and weight

Figure 2-10 Dimension drawings 6EP4437-7FB00-3CX0 and 6EP4437-7EB00-3CX0

SITOP SEL1200-1400
26 Equipment Manual, 06.2020, A5E46496083-2-76
Description, device design, dimension drawing
2.9 Dimensions and weight

Figure 2-11 Dimension drawings 6EP4437-7FB00-3DX0, 6EP4437-7EB00-3DX0, 6EP4438-7FB00-


3DX0 and 6EP4438-7EB00-3DX0

6EP4437-7FB00-3CX0 6EP4437-7EB00-3CX0
Dimensions (W × H × D) in mm 45 × 135 × 125 45 × 135 × 125
Weight Approx. 0.3 kg Approx. 0.4 kg

6EP4437-7FB00-3DX0 6EP4437-7EB00-3DX0
Dimensions (W × H × D) in mm 45 × 135 × 125 45 × 135 × 125
Weight Approx. 0.3 kg Approx. 0.4 kg

6EP4438-7FB00-3DX0 6EP4438-7EB00-3DX0
Dimensions (W × H × D) in mm 45 × 135 × 125 45 × 135 × 125
Weight Approx. 0.3 kg Approx. 0.5 kg

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 27
Description, device design, dimension drawing
2.9 Dimensions and weight

SITOP SEL1200-1400
28 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting/removal 3
WARNING
Installing the device in a housing or a control cabinet
The SITOP SEL1200-1400 selectivity modules are built-in units. They must be installed in a
housing or control cabinet where only qualified personnel have access.

The device can be mounted in a control cabinet on standard mounting rails (see Chapter
Mechanical system (Page 55))

Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If this is too difficult,
simultaneously press the slider ⑨ as described under "Removal".

Removal
To remove, pull up the slider ⑨ using a screwdriver (see Figure 3-1 Mounting-removal
(Page 29)) and disengage the device at the bottom edge of the standard mounting rail. Then
you can remove the device from the upper edge of the standard mounting rail.

Figure 3-1 Mounting-removal

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 29
Mounting/removal

SITOP SEL1200-1400
30 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances 4
4.1 Standard mounting position
The device is mounted on standard mounting rails TH 35-15/7,5 (EN 60715). The device
must be mounted vertically in such a way that the input terminals are at the bottom.
A clearance of at least 45 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.

Individual output current as a function of the ambient temperature and installation altitude
Applicable for 8 × 10 A devices (6EP4438-7FB00-3DX0, 6EP4438-7EB00-3DX0)

NOTICE

In total, the maximum device load must not exceed 60 A. The derating of 2 %/K must also
be complied with here. At 70 °C, this corresponds to a total maximum device load of 48 A.

Figure 4-1 6EP4437-7FB00-3DX0 standard mounting position

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 31
Mounting position, mounting clearances
4.1 Standard mounting position

Figure 4-2 6EP4437-7FB00-3CX0 standard mounting position

Figure 4-3 6EP4438-7FB00-3DX0 standard mounting position

Figure 4-4 6EP4437-7EB00-3DX0 standard mounting position

SITOP SEL1200-1400
32 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.1 Standard mounting position

Figure 4-5 6EP4437-7EB00-3CX0 standard mounting position

Figure 4-6 6EP4438-7EB00-3DX0 standard mounting position

Figure 4-7 Mounting height derating

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 33
Mounting position, mounting clearances
4.2 Other mounting positions

4.2 Other mounting positions


For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.

Note
In the case of mounting positions that deviate from the standard mounting position, reduced
mechanical resistance of the devices against vibration and shock must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required, e.g. to prevent the device from slipping on the standard
mounting rail.

4.2.1 SEL1200 8 x 5 A 6EP4437-7FB00-3DX0

Figure 4-8 Mounting position 1

Figure 4-9 Mounting position 2

SITOP SEL1200-1400
34 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.2 Other mounting positions

Figure 4-10 Mounting position 3

Figure 4-11 Mounting position 4

Figure 4-12 Mounting position 5

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 35
Mounting position, mounting clearances
4.2 Other mounting positions

4.2.2 SEL1200 4 x 10 A 6EP4437-7FB00-3CX0

Figure 4-13 Mounting position 1

Figure 4-14 Mounting position 2

Figure 4-15 Mounting position 3

SITOP SEL1200-1400
36 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.2 Other mounting positions

Figure 4-16 Mounting position 4

Figure 4-17 Mounting position 5

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 37
Mounting position, mounting clearances
4.2 Other mounting positions

4.2.3 SEL1200 8 x 10 A 6EP4438-7FB00-3DX0

NOTICE

In total, the maximum device load must not exceed 60 A. The derating of 2 %/K must also
be complied with here. At 70 °C, this corresponds to a total maximum device load of 48 A.

Figure 4-18 Mounting position 1

Figure 4-19 Mounting position 2

Figure 4-20 Mounting position 3

SITOP SEL1200-1400
38 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.2 Other mounting positions

Figure 4-21 Mounting position 4

Figure 4-22 Mounting position 5

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 39
Mounting position, mounting clearances
4.2 Other mounting positions

4.2.4 SEL1400 8 x 5 A 6EP4437-7EB00-3DX0

Figure 4-23 Mounting position 1

Figure 4-24 Mounting position 2

Figure 4-25 Mounting position 3

SITOP SEL1200-1400
40 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.2 Other mounting positions

Figure 4-26 Mounting position 4

Figure 4-27 Mounting position 5

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 41
Mounting position, mounting clearances
4.2 Other mounting positions

4.2.5 SEL1400 4 x 10 A 6EP4437-7EB00-3CX0

Figure 4-28 Mounting position 1

Figure 4-29 Mounting position 2

Figure 4-30 Mounting position 3

SITOP SEL1200-1400
42 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.2 Other mounting positions

Figure 4-31 Mounting position 4

Figure 4-32 Mounting position 5

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 43
Mounting position, mounting clearances
4.2 Other mounting positions

4.2.6 SEL1400 8 x 10 A 6EP4438-7EB00-3DX0

NOTICE

In total, the maximum device load must not exceed 60 A. The derating of 2 %/K must also
be complied with here. At 70 °C, this corresponds to a total maximum device load of 48 A.

Figure 4-33 Mounting position 1

Figure 4-34 Mounting position 2

Figure 4-35 Mounting position 3

SITOP SEL1200-1400
44 Equipment Manual, 06.2020, A5E46496083-2-76
Mounting position, mounting clearances
4.2 Other mounting positions

Figure 4-36 Mounting position 4

Figure 4-37 Mounting position 5

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 45
Mounting position, mounting clearances
4.2 Other mounting positions

SITOP SEL1200-1400
46 Equipment Manual, 06.2020, A5E46496083-2-76
Installation 5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.

5.1 Connection at the input

WARNING

The device is only suitable for operation with 24 V DC voltages (safety extra low voltage). If
this device is connected to line supplies with higher voltage levels this can result in death or
serious injury as well as extensive material damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.

Figure 5-1 Input connection

The supply is connected via input terminal ①, designated "24 V" and the 0 V terminal ②,
designated "0 V"; the "0 V" connection is not used for the load supply, but only to supply the
internal electronics of the selectivity module (terminal cross-sections, see Figure 2-2
Terminal data (Page 13)).

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 47
Installation
5.1 Connection at the input

NOTICE
Overload of the wiring
The "0 V" connection is only used to supply the internal electronics of the selectivity
module. The 0 V of the connected loads must be routed directly to the power supply using
separate cables!
The input terminals of the selectivity module are designed for a maximum input current of
40 A or 60 A. This must be taken into account when connecting several selectivity modules
in parallel by "looping through". If the total current demand of all selectivity modules
connected in parallel is more than 40 A or 60 A, then the maximum current should be
reduced to 40 A or 60 A per branch by using additional feeder cables directly from the
power supply to the selectivity modules connected in parallel.

SITOP SEL1200-1400
48 Equipment Manual, 06.2020, A5E46496083-2-76
Installation
5.2 Connection at the output

5.2 Connection at the output


(see Chapter Technical data (Page 51))

Figure 5-2 Output connection

The loads to be supplied are connected at output terminals ③ labeled OUTPUT 1, 2, 3, 4


(1, …, 8). (terminal cross-sections, see Figure Terminal data (Page 13)).

Note
The 0 V of the loads must be routed directly to the power supply using separate cables!

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 49
Installation
5.2 Connection at the output

SITOP SEL1200-1400
50 Equipment Manual, 06.2020, A5E46496083-2-76
Technical data 6
Note
Technical data apply for a rated input voltage, rated load and 25 °C ambient temperature if
nothing else is specified.

6.1 Input

6EP4437-7FB00-3DX0 6EP4438-7FB00-3DX0
6EP4437-7FB00-3CX0 6EP4438-7EB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
Input Regulated DC voltage
Rated voltage Uin rated 24 V
Voltage range 20.4 - 30 V
Overvoltage strength 35 V
Input current at Uin rated Max. 40 A Max. 60 A

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 51
Technical data
6.2 Output

6.2 Output

6EP4437-7FB00- 6EP4437-7EB00- 6EP4437-7FB00- 6EP4438-7FB00-


3DX0 3DX0 3CX0 3DX0
6EP4437-7EB00- 6EP4438-7EB00-
3CX0 3DX0
Output Regulated DC voltage
Output voltage Uout = Uin - approx. 0.2 V
Total tolerance Corresponding to the supplying input voltage
Number of outputs 8 8 4 8
Output current up to 60 °C for 5A 5A 10 A 10 A (in total, not
each output (rated value) more than 60 A)
• Remark 60 ... 70 °C derating: 60 ... 70 °C derating: 60 ... 70 °C derating: 60 ... 70 °C derating:
3.25 % Iout/K 2.5 % Iout/K 2 % Iout/K 2 % Iout/K
Adjustable response threshold 1 - 5 A 1-5A 2 - 10 A 2 - 10 A
Connecting outputs in parallel Yes, max. 4 × 2 outputs each that must lie next to one another.
Switching on outputs All outputs are switched-on after the supply voltage ramps up > 20 V, delay time of 25 ms,
200 ms, 500 ms – or "load optimized", selectable using DIP switch.

Shutdown characteristics:

Figure 6-1 Shutdown characteristic

The following applies for the SEL1200: In the range > 150 %, a higher current is briefly
permitted; afterwards it is shut down corresponding to the "Shutdown characteristic"
diagram.

SITOP SEL1200-1400
52 Equipment Manual, 06.2020, A5E46496083-2-76
Technical data
6.2 Output

The following applies for the SEL1400: In the range > 150 % of the selected current
response threshold, the current is limited to 150 %, typically after 10 ms to 100 ms, the
output is electronically shut down (LED of the output is lit red).
● An output current is continuously permissible up to the selected current response
threshold (LED of the output is lit green).
● In the range 100 - 150 % of the selected current response threshold, an overload current
is permissible for 5 seconds (LED of the output flashes green), then the output is
electronically shut down (LED of the output is lit red).

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 53
Technical data
6.3 Efficiency

6.3 Efficiency

6EP4437-7FB00- 6EP4437-7EB00- 6EP4437-7FB00- 6EP4437-7EB00- 6EP4438-7FB00-


3DX0 3DX0 3CX0 3CX0 3DX0
6EP4438-7EB00-
3DX0
Efficiency at 98 % 98 % 99 % 99 % 99 %
Uout rated, Iout rated,
approx.
Power loss at 12 W 15 W 12 W 15 W 15 W
Uout rated, Iout rated,
approx.

6.4 Protection and monitoring

6EP4437-7FB00-3DX0 6EP4437-7FB00-3CX0 6EP4437-7EB00-3DX0 6EP4437-7EB00-3CX0


6EP4438-7FB00-3DX0 6EP4438-7EB00-3DX0
Device pro- Internal fuse 10 A for Internal fuse 20 A for Internal fuse 8 A for each Internal fuse 15 A for
tection each output (not acces- each output (not acces- output (not accessible) each output (not acces-
sible) sible) sible)
Operating One LED per output: LED green for "Output switched on", LED orange flashing for "Output manually
display switched off", LED red for "Output switched off due to overload or overvoltage", all LEDs flashing red for
"Device overload (total max. output current exceeded)", red running light for "Device overtemperature".
More detailed information is provided in Chapter Status displays and signaling (Page 16).
Signaling Group signaling contact (NO contact),
contact rating: 24 V AC/0.1 A; 30 V DC/0.1 A

6.5 MTBF

6EP4437-7FB00-3DX0 6EP4438-7EB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
Mean Time Between Failures > 500,000 hours at 40 °C, rated load, > 300,000 hours at 40 °C, rated load,
24 hour operation 24 hour operation

SITOP SEL1200-1400
54 Equipment Manual, 06.2020, A5E46496083-2-76
Technical data
6.6 Mechanical system

6.6 Mechanical system

6EP4437- 6EP4437- 6EP4438- 6EP4437- 6EP4437- 6EP4438-


7FB00-3DX0 7FB00-3CX0 7FB00-3DX0 7EB00-3DX0 7EB00-3CX0 7EB00-3DX0
Connection system Spring-loaded terminals
+24 V input 2 spring-loaded terminals for 0.75 - 16 mm² (0.75 - 25 mm²) solid/finely stranded
0 V connection 2 spring-loaded terminals for 0.2 - 4 mm² (0.2 - 2.5 mm²) solid/finely stranded
Output 1 - 4 / 1 - 8 one spring-loaded terminal per output for 0.2 - 4 mm² (0.2 - 2.5 mm²) solid/finely stranded
Group signaling contact 2 spring-loaded terminals for 0.2 - 1.5 mm² (0.2 - 1.5 mm²) solid/finely stranded
(13, 14)
Not assigned (NF) one spring-loaded terminal for 0.2 - 1.5 mm² (0.2 - 1.5 mm²) solid/finely stranded
Remote reset (RST) one spring-loaded terminal for 0.2 - 1.5 mm² (0.2 - 1.5 mm²) solid/finely stranded
Width of the housing 45 mm
Height of the housing 135 mm
Depth of the housing 125 mm
Installation width 45 mm
Mounting height 225 mm
Weight, approx. Approx. Approx. Approx. Approx. Approx. Approx.
0.3 kg 0.3 kg 0.3 kg 0.4 kg 0.4 kg 0.5 kg
Mounting Can be snapped onto standard TH 35-15/7,5 mounting rails (EN 60715)

6.7 Accessories

6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Mechanical accessories Reference labeling plate (160 plates) 6ES7193-6LF30-0AW0

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 55
Technical data
6.8 Dimension drawing

6.8 Dimension drawing


See Chapter Dimensions and weight (Page 26).
CAD data that can be downloaded from the Internet:
6EP4437-7FB00-3DX0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01648)
6EP4437-7FB00-3CX0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01645)
6EP4438-7FB00-3DX0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01575)
6EP4437-7EB00-3DX0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01654)
6EP4437-7EB00-3CX0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01651)
6EP4438-7EB00-3DX0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01578)

SITOP SEL1200-1400
56 Equipment Manual, 06.2020, A5E46496083-2-76
Safety, approvals, EMC 7
7.1 Safety

6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Standard for safety acc. to IEC61204-7 and EN 50178
Protection class Class III
Degree of protection IP20
(EN 60529)

7.2 Approvals

6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
CE marking Yes, (2014/35/EU, 2014/30/EU, 2011/65/EU, 2014/34/EU)
CB approval Yes
UL/cUL (CSA) approval UR (UL 2367) file E328600; cULus (UL 508, CSA C22.2 No. 107.1) file E197259
cCSAus approval cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection Yes
ATEX approval II 3G Ex ec IIC T4 Gc
IECEx approval Yes (IECEx EPS 14.0067X)
cULus HazLoc Available soon
Marine approvals Available soon
RCM approval Yes
EAC approval Yes
SONCAP certificate Yes

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 57
Safety, approvals, EMC
7.3 EMC

7.3 EMC

6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Electrostatic discharge EN 61000-4-2 8 kV contact, 8 kV air
Electromagnetic fields EN 61000-4-3 80 - 1000 MHz 10 V/m,
1000 - 6000 MHz 10 V/m,
900 MHz ± 5 MHz 10 V/m
Fast transient disturbance variables EN 61000-4-4 2 kV at the DC input
(burst) 2 kV at the DC output
Surge voltages EN 61000-4-5 0.5 kV symmetrical at the DC input
0.5 kV symmetrical at the DC output
High-frequency fields EN 61000-4-6 10 V/m; 0.15 - 80 MHz
Magnetic fields EN 61000-4-8 30 A/m; 50 Hz
Generic standards EN 61000-6-2 Noise immunity for industrial environments
EN 61000-6-3 Emission for residential areas

SITOP SEL1200-1400
58 Equipment Manual, 06.2020, A5E46496083-2-76
Ambient conditions 8
6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Ambient temperature -25 ... 70 °C for natural convection (self convection)
Tested according to:
• EN 60068-2-1 Cold, Ad test
• EN 60068-2-2 Dry heat, Bb test
• EN 60068-2-78 Humid heat, constant Cab test
• EN 60068-2-14 Temperature change, Nb test
Transport and storage temperature -40 … 85 °C
Tests (packed for shipping) according to:
• EN 60068-2-1 Cold, Ab test
• EN 60068-2-2 Dry heat, Bb test
• EN 60068-2-30 Humid heat, cyclic Db test
Humidity class Climatic class 3K3 according to EN 60721, 5 - 95 % no
condensation
Degree of pollution 2
Mechanical stressing in operation • Test according to EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz

• Test according to EN 60068-2-27 shock, test Ea:


acceleration 150 m/s2, test duration 11 ms

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 59
Ambient conditions

6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Damaging gases Sulfur dioxide: 10 cm3/m3, 4 days
Hydrogen sulfide: 1 cm3/m3, 4 days
Tested according to:
• EN 60068-2-42 sulfur dioxide
• EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
• 1080 - 795 hPa (0 - 2000 m)
• For operation at altitudes of 2000 - 6000 m above sea
level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by
5 K / 1000 m
(see Standard mounting position (Page 31))
Storage:
• 1080 - 660 hPa (0 - 3500 m)

SITOP SEL1200-1400
60 Equipment Manual, 06.2020, A5E46496083-2-76
Environment 9
The devices are in conformance with RoHS.
Only substances in conformance with PWIS are used (paint-wetting impairment substances)

Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 61
Environment

SITOP SEL1200-1400
62 Equipment Manual, 06.2020, A5E46496083-2-76
Service & Support 10
Technical support
You can access technical support through the following communication channels:
● Telephone: + 49 (0) 911 895 7222
● Internet:
Web form for support request (http://www.siemens.de/automation/support-request)

Technical documentation on the Internet


Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.com/sitop/manuals)

SITOP power supply homepage


Current information about our power supplies is available in the Internet at the SITOP home
page:
SITOP (http://www.siemens.com/sitop)

Texts for invitation to tender


You can find invitation to tender texts for SITOP power supplies here:
Link to the portal (http://www.siemens.de/ausschreibungstexte)

CAx data
You can find 2D-/3D data, devices circuit diagrams according to IEC and ANSI as well as
EPLAN macros as download in the Internet:
Siemens image database (http://www.siemens.com/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.com/cax)

TIA Selection Tool


Simply and quickly select the optimum power supply, add-on modules and DC-UPS:
TIA Selection Tool cloud (http://www.siemens.com/tst-powersupply)
In addition, the 24 V load view in the TIA Selection Tool allows you to simply select the
power supply for your particular project as the current demand of the automation products
being supplied is automatically calculated.
Download the TIA Selection Tool (http://www.siemens.de/tia-selection-tool-standalone)

Online catalog and ordering system


The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)

SITOP SEL1200-1400
Equipment Manual, 06.2020, A5E46496083-2-76 63
Service & Support

Contact persons
If you have any questions regarding the use of our products, then contact the Siemens
contact person in your regional Siemens sales office.
You can find these addresses as follows:
● On the Internet (http://www.automation.siemens.com/partner)
● Industry Mall (http://www.siemens.com/industrymall/de)

SITOP SEL1200-1400
64 Equipment Manual, 06.2020, A5E46496083-2-76

You might also like