ASTMB286
ASTMB286
ASTMB286
This standard has been approved for use by agencies of the Department of Defense.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
B 286 – 02
addition to the 5 allowed in 4.3.1), but in no case shall the shall be performed on Type I conductors before insulating and
elongation of any individual wire be less than 5 %. on the individual wires of Type II conductors before stranding.
4.4 D-C Resistance— The d-c resistance in ohms per 1000 8.2 Tests to determine conformance to the elongation re-
ft of annealed solid and stranded conductor shall not exceed, quirements prescribed in 4.3 shall be made before insulating
before insulating, the appropriate values prescribed in Table 1 and, in the case of stranded conductors, on component wires
(Explanatory Note 1). removed from the conductors.
8.3 Tests to determine conformance to the electrical resis-
5. Conductor Construction tance requirements prescribed in Table 1 shall be made on the
5.1 Solid conductors shall conform to the requirements for uninsulated conductor in accordance with Test Method B 193
Type I conductors prescribed in Table 1. (Explanatory Note 1).
5.2 Stranded conductors shall conform to the requirements 8.4 Examination for workmanship of finished uninsulated
for Type II conductors prescribed in Table 1. The method of stranded conductor—A visual inspection with the unaided eye
stranding for conductor size designations 32-7 through 10-104 shall be performed on the outer layer of the conductor on the
inclusive shall be at the option of the manufacturer unless supplied package. Use a white card (as a background) to
otherwise specified. Stranded conductors size designation 10- ascertain if any base metal is exposed through a break in the
105 and larger shall normally be furnished in a rope-lay- coating. Detection of any base metal constitutes rejection.
stranded construction consisting of either 7 or 19 bunch- 8.5 Examination for workmanship of finished uninsulated
stranded members. stranded conductor—AB visual inspection with 10X magnifi-
cation and with a white background shall be performed on a
6. Lay of Stranded Conductors conductor sample taken from the top of the supplied spool. The
6.1 The direction of lay of the outside layer of stranded sample shall be a minimum of 12 in. (30 cm) in length. The
conductors shall be left-hand. The direction of lay of the outer surface of all stranded constructions shall be examined.
bunch-stranded members composing rope-lay-stranded con- Detection of excessive exposed base metal due to the
ductors shall be at the option of the manufacturer unless stranding process, such as indications along one side of the
otherwise specified. sample due to excessive localized abrasion during stranding,
6.2 The direction of lay of the outer layer of rope-lay- constitutes rejection. Continuous lines or patterns of exposed
stranded conductors shall be lefthand. The direction of lay of base metals constitute rejection. Small random point failures
the other layers shall be reversed in successive layers, unless shall not be cause for rejection.
otherwise specified.
6.3 The length of lay of the outside layer of stranded 9. Density
conductors in size designation 32-7 through 10-104, inclusive, 9.1 For the purpose of calculating mass, cross-sectional
shall conform to the values in Table 1 (Explanatory Note 2). area, etc., the density of the coated copper shall be taken as
For strand constructions containing more than one distinct 8.89 g/cm 3(0.32117 lb/in.3) at 20°C (Explanatory Note 4).
layer the length of lay of the inner layer shall not exceed the
maximum value shown in Table 1 for the conductor in 10. Inspection
question. For rope-lay-stranded conductors size designation
10.1 All tests and inspection shall be made at the place of
10-105 and larger, and size 49/0.0142, the length of lay of the
manufacture unless otherwise especially agreed upon by the
wires composing the bunch-stranded members shall be not
manufacturer and the purchaser at the time of purchase. The
more than 30 times the diameter of the member, and the length
manufacturer shall afford the inspector representing the pur-
of lay of the outer layer of rope-lay-stranded conductors shall
chaser all reasonable facilities, without charge, to satisfy him
be not less than 8 nor more than 16 times the outside diameter
that the material is being furnished in accordance with this
of the completed conductor.
specification.
7. Joints
11. Product Marking
7.1 Necessary joints in the individual wires of conductors
size designation 32-7 through size designation 10-104, inclu- 11.1 The net mass, length (or lengths, and number of
sive, may be silver soldered, brazed, or butt welded. (Explana- lengths, if more than one length is included in the package),
tory Note 3). Bunch-stranded members composing ropelay- size designation, type of conductor, purchase order number,
stranded conductors may be joined as a unit by brazing and and any other marks required by the purchase order shall be
these joints shall be at least two lay lengths apart and be marked on a tag attached to the end of the conductor inside of
finished off so that the conductor diameter is not increased at the package. The same information, together with the manu-
the joint. Disposition of joints throughout the conductor shall facturer’s serial number (if any) and all shipping marks
be such that the diameter, configuration, conductor resistance, required by the purchaser, shall appear on the outside of each
flexibility, and mechanical strength are not substantially af- package.
fected.
12. Packing and Package Marking
8. Physical and Electrical Tests 12.1 Package sizes for conductors shall be agreed upon by
8.1 Tests to determine conformance of the coating to the the manufacturer and the purchaser in the placing of individual
requirements of Specifications B 33, B 189, B 298, or B 355 orders.
2
B 286 – 02
12.2 The conductors shall be protected against damage in
ordinary handling and shipping.
13. Keywords
13.1 copper hookup wire; electronic equipment hookup
wire; electronic hookup wire; hookup wire
0000–2109 2109F 0.0100 210 900 0.635 ... 0.0576 0.0537 0.0559(2) 0.0610 0.0756
000–1672 1672F 0.0100 167 200 0.545 ... 0.0727 0.0677 0.0705(2) 0.0770 0.0954
00–1330 1330F 0.0100 133 000 0.486 ... 0.0914 0.0851 0.0887(2) 0.0967 0.120
0–1064 1064F 0.0100 106 400 0.435 ... 0.114 0.106 0.111(2) 0.121 0.150
0–1045 1045F 0.0100 104 500 0.431 ... 0.116 0.108 0.113(2) 0.123 0.153
1–836 836F 0.0100 83 600 0.386 ... 0.145 0.135 0.141(2) 0.154 0.191
1–817E 817F 0.0100 81 700E 0.382 ... 0.149 0.139 0.144(2) 0.158 0.195
2–665 665F 0.0100 66 500 0.342 ... 0.183 0.170 0.177(2) 0.194 0.240
4–133E 133F 0.0179 42 615E 0.274 ... 0.280 0.263 0.274(2) 0.299 0.371
4–420 420G 0.0100 42 000 0.275 ... 0.289 0.270 0.281(2) 0.306 0.380
6–133E 133F 0.0142 26 818E 0.217 ... 0.444 0.418 0.436(2) 0.475 0.589
6–266 266G 0.0100 26 600 0.220 ... 0.457 0.426 0.443(2) 0.484 0.600
8–133E 133F 0.0113 16 983E 0.173 ... 0.701 0.661 0.688(2) 0.751 0.930
8–168 168G 0.0100 16 800 0.177 ... 0.724 0.674 0.702(2) 0.766 0.949
10–105 105G 1.0100 10 500 0.130 1.2 to 1.8 1.15 1.07 1.11(2) 1.21 1.50
10–104 104H 0.0100 10 400 0.130 1.7 to 2.1 1.16 1.08 1.12(2) 1.23 1.52
10–49E 49G 0.0142 9 880G 0.132 ... 1.21 1.14 1.18(2) 1.29 1.60
10–37E 37E 0.0159 9 354E 0.115 1.10 to 1.75 1.26 1.19 1.24(2) 1.35 1.67
12–65 65H 0.0100 6 500 0.099 1.3 to 1.7 1.85 1.73 1.80(2) 1.96 2.43
3
B 286 – 02
TABLE 1 Continued
Type II (Stranded Conductors)
Conductor Construction D-C Resistance at 20°C, V/1000 ft, max (Explanatory Note 2)
Calculated Length of Lay, Annealed
Nominal Maximum Annealed
Size Number Cross- in. Tin or 50 to 100 µin. Class 10 Class 27
Diameter of Allowable Silver
DesignationB of WiresC Sectional (Explanatory Lead-Alloy of NickelI Nickel Nickel
Each Wire, in. Diameter, in.D Coated
Area, cmils Note 2) Coated
22–7E 7J 0.0100 700E 0.031 0.25 to 0.43 16.7 15.6 16.2(2) 17.7 21.9
24–19E 19J 0.0050 475E 0.027 0.25 to 0.35 25.4 23.6 25.2(4) 26.9 33.3
24–7E 7J 0.0080 448E 0.025 0.25 to 0.35 26.2 24.5 26.0(4) 27.8 34.4
26–19E 19J 0.0040 304E 0.022 0.25 to 0.30 40.1 37.3 41.0(7) 42.4 52.6
26–7E 7J 0.0063 278E 0.020 0.25 to 0.30 42.6 39.7 42.2(4) 45.1 55.9
28–19E 19J 0.0031 183E 0.017 0.25 to 0.30 67.7 63.1 69.3(7) 71.7 88.8
28–7E 7J 0.0050 175E 0.016 0.25 to 0.30 68.2 63.6 67.6(4) 72.2 89.5
30–7E 7J 0.0040 112E 0.013 0.25 to 0.30 108.0 100.0 110.0(7) 114.0 141.0
32–7E 7J 0.0031 67g 0.011 0.10 to 0.30 182.0 170.0 186.0(7) 193.0 239.0
A
Provides minimum of 50 µin. of nickel.
B
These size designations are solely for purposes of identification. They should not be confused with AWG sizes.
C
The stranded conductor constructions shown in this table provide for finished noninsulated conductors having the indicated cross-sectional area. The number of
component wires may vary slightly provided the specified resistances are not exceeded.
D
The maximum allowable diameters of these conductors are given here for guidance in making calculations regarded insulating material, etc. These diameters do not
include allowance for distortion of the conductor during stranding and are not intended to be used as limiting values.
E
The cross-sectional areas of these conductor-size designations deviate by more than 2 per cent from the nominal areas of the standard AWG sizes as defined in
Specification B 258.
F
Nineteen member ropes.
G
Seven member ropes.
H
Bunch-stranded.
I
The numbers in parentheses indicate the class of nickel coating required to meet resistance values tabulated. These classes appear in Specification B 355.
J
Concentric-stranded.
EXPLANATORY NOTES
4
B 286 – 02
economical insulating operations. When by mutual agreement between the (32°F) is 8.90 g/cm3(0.32150 lb/in.3). In calculations involving density it
manufacturer and the purchaser such joints are used, they shall be must be borne in mind that the apparent density of coated wire is not a
conspicuously marked, and removed from the conductor at the final constant but a variable function of wire diameter. The smaller the diameter
insulating operation. the greater the percentage of coating present and hence the greater
NOTE 5—The value of density of copper is in accordance with the departure from the density of copper.
International Annealed Copper Standard. The corresponding value at 0°C
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).