ANSULITE 1x1 AR-AFFF CONCENTRATE

Data/Specifications

FEATURES

n 1% proportioning for both hydrocarbon and polar solvent fuels


n UL-162 listed, EN 1568 approved, EPA 2015 compliant, and
LASTFIRE tested
n Use with aspirating and non-aspirating discharge devices
n Low “water-like” viscosity
n Suitable for use with fresh, salt, or hard water
n Freeze protected down to 0 °F (–18 °C)

APPLICATION

ANSULITE 1x1 Alcohol-Resistant Aqueous Film-Forming Foam


(AR-AFFF) Concentrate is formulated for use in a 1% foam solution 008649

on all Class B fuels, hydrocarbon or polar solvent, wherever life safety


and asset protection is essential. When diluted with fresh, salt, or hard
water; ANSULITE 1x1 AR-AFFF can be discharged through aspirat- Typical Physiochemical Properties at 77 °F (25 °C)
ing or non-aspirating branch pipes and nozzles, fixed foam making Appearance Amber Liquid
devices, and sprinklers to suppress Class A and B fuel fires. Typical Density 1.09 ± 0.01 g/ml
applications include oil and gas facilities, chemical plants, refineries
and tank farms, alternative fuel facilities, warehouses, municipal fire pH 7.0 – 8.0
service, and many others. Refractive Index 1.3980 ± 0.0015
Viscosity 50 cSt
Spreading Coefficient 4.0 – 6.0

DESCRIPTION

ANSULITE 1x1 AR-AFFF Concentrate is manufactured using C-6


fluoro-chemistry in compliance with the U.S. Environmental Protection PERFORMANCE
Agency 2015 Stewardship Program. This proprietary formulation is
Fire Performance
the first AR-AFFF that does not rely on biopolymer precipitation to
suppress polar solvent fires. Therefore, the concentrate does not The fire performance of ANSULITE 1x1 AR-AFFF is measured against
possess a thixotropic property, but rather has the appearance and Underwriters Laboratories Standard 162 (Latest Revision) fire tests.
viscosity of an AFFF. The UL testing focuses on fuels such as heptane and isopropyl
alcohol.
Unlike conventional AR-AFFF products, the physical properties of
ANSULITE 1x1 concentrate are similar to traditional AFFF products. Foaming Properties
Benefits to the end user include a reduction in the required storage When used with fresh, salt or hard water at the correct dilution with
space for the foam concentrate because of its ability to work as a most conventional foam making equipment, the expansion will vary
1% solution on both hydrocarbon and polar solvent fuels. ANSULITE depending on the performance characteristics of the equipment.
1X1 AR-AFFF is approved for use in salt, fresh, or hard water. Aspirating discharge devices produce expansion ratios from 5:1 to 10:1
Proportioning properties are very similar to AFFF and its water-like depending primarily on the type of aspirating device and the flow rate.
viscosity enhances performance in all types of foam proportioning Non-aspirating devices, such as hand-line water fog/stream nozzles or
equipment. standard sprinkler heads, give expansion ratios of 2:1 to 4:1. Medium-
expansion discharge devices produce typical expansion ratios between
There are three fire extinguishing mechanisms in effect when using
20:1 and 60:1 depending primarily on the type of device and operating
ANSULITE 1x1 foam solution on either a conventional Class B hydro-
conditions.
carbon fuel such as gasoline, diesel fuel, etc.; or a Class B polar
solvent (water miscible fuel) such as methyl alcohol, acetone, etc. Proportioning
1. An aqueous film is formed in the case of a conventional ANSULITE 1x1 AR-AFFF can be easily proportioned (at the correct
hydrocarbon fuel, or a polymeric membrane in the case of a polar dilution) using most conventional proportioning equipment such as:
solvent fuel. This film or membrane forms a barrier to help prevent
the release of fuel vapor. n Balanced pressure and in-line balanced pressure pump
proportioning equipment
2. Regardless of the fuel type, a foam blanket is formed which
excludes oxygen. The liquids that form the film or the polymeric n Balanced pressure bladder tank proportioners
membrane are drained from the foam blanket. n Around-the-pump and through-the-pump proportioners
3. The water content of the foam produces a cooling effect. n Fixed or portable (in-line) Venturi-type proportioners
n Hand-line nozzles with fixed induction/pickup tubes
The minimum and maximum usable temperature for ANSULITE 1x1
AR-AFFF in this equipment is 0 °F (–18 °C) to 120 °F (49 °C).
PERFORMANCE (Continued) ORDERING INFORMATION

ANSULITE 1x1 AR-AFFF is available in pails, drums, totes or bulk


Storage/Shelf Life shipment.
When stored in the packaging supplied (polyethylene totes, drums, Part No. Description Shipping Weight Cube
_______ _________ _____________ _____
or pails) or in equipment recommended by the manufacturer and
within the temperature limits specified, the shelf life of ANSULITE 1x1 437681 5 gal 46 lb 1.25 ft3
AR-AFFF is about 20-25 years. The factors affecting shelf life and (19 L) Pail (20.9 kg) (0.0353 m3)
stability for AFFF agents are discussed in detail in ANSUL Technical 437682 55 gal 495 lb 11.83 ft3
Bulletin No. 54 (Form No. F-83114). Freezing of the product should (208 L) Drum (224.5 kg) (0.3350 m3)
be avoided. If the product is frozen during transport or storage, it must
437683 265 gal 2463 lb 50.05 ft3
be thawed and inspected for signs of separation. If separation has
(1000 L) Tote (1117 kg) (1.42 m3)
occurred, the product must be mechanically mixed until homogeneous.
437680 Bulk Order Contact ANSUL Technical Services
When the concentrate is to be stored in an atmospheric storage tank,
a 1/8 to 1/4 in. (3–6 mm) layer of mineral oil should be added to seal
the concentrate and minimize the effects of evaporation.

Compatibility
Since it is a unique blend of surfactants, high molecular weight poly-
mers, and solvents; it is recommended that ANSULITE 1x1 AR-AFFF
not be mixed with any other foam concentrates. Consult Technical
Services with any questions of compatibility.

Materials of Construction Compatibility


Tests have been performed with ANSULITE 1x1 AR-AFFF verifying its
compatibility with standard carbon steel ‘‘black’’ pipe and pipe manu-
factured from various stainless steel or brass compounds. Alternative
pipe, plastic fittings, and valves may be used in some cases if accept-
able to the customer and/or the authority having jurisdiction. Refer
to ANSUL Technical Bulletin No. 59 (Form No. F-90109) addressing
acceptable materials of construction for use with ANSUL foam concen-
trates.
To help prevent corrosion, galvanized pipe and fittings must not be
used in areas where they will contact the undiluted concentrate.
Please consult Technical Services for specific guidelines concerning
materials of construction.

Inspection
As with any fire extinguishing agent, ANSULITE 1x1 AR-AFFF,
whether in the concentrate or pre-mixed form, should be inspected
periodically. NFPA 11 ‘‘Standard for Low Expansion Foam and
Combined Agent Systems’’ requires that foam concentrate samples
be submitted to the manufacturer or other qualified laboratory for
quality condition testing at least annually. Please refer to the Field
Inspection Manual (Part No. 31274) for the detailed procedures neces-
sary to perform this inspection. An annual inspection is recommended
unless unusual conditions of exposure occur, as described in ANSUL
Technical Bulletin No. 54. In such cases, contact Technical Services.

APPROVALS AND LISTINGS

Underwriters Laboratories successfully tested ANSULITE 1x1


AR-AFFF to the requirements contained in UL 162 “Standard for
Air-Foam Equipment and Liquid Concentrates.” To receive a UL listing,
the following tests must be performed successfully:
n Foam Quality Tests
n Class B Hydrocarbon Fuel Fire Tests
n Class B Polar Solvent Fuel Fire Tests
n Foam Identification Tests
n Tests of Shipping Containers
In addition to determining agent characteristics, Underwriters
Laboratories lists ANSULITE 1x1 AR-AFFF for use with specific hard-
ware components that also carry the UL listing.
ANSULITE 1x1 AR-AFFF is approved to EN 1568 Parts 3 and 4. It has
also been successfully tested to LASTFIRE test protocol by Resource
Protection International.