1 General Notes and Instructions
1 General Notes and Instructions
1 General Notes and Instructions
2 Drawings
Dimension drawing alternator 12124.5
Rotor drawing 86571.1
3 Circuit Diagram
Circuit diagram K811.1.231
Legend to circuit diagram K811.1.231
4 Operating Instructions
Three-phase synchronous electrical machines series DSG 29...144
Enclosure to operating instructions
5 Regulator Descriptions
Voltage regulator Cosimat N+
6 Bearings
RENK Slide Bearings Type EF with self lubrication
RENK recommendation for lubrication
7 Spare Parts
Drawings 1.2.2, 2.2.2, 3.0NS, 4.0.0oRT, 6.0obi, 0.2.0
8 Technical Data
Technical Data
Test report 8127281C002
H. Cegielski-FSA 12/2005
Your order: 8702088
Your project: Szczecin Sipyard B178-I/15,16,17, Poland
AvK Order no. 8127281C002
General Notes and Instructions
General Notes
Safety Precautions
Read this advice as well as additional parts can be found in the
the operating instructions documentation.
supplied prior to
commissioning or storage of The documentation, including the
the generator. operating instructions, are part of the
Any works on the generator have to be machine and have to be passed on to the
performed by qualified and trained next user in case the generator is sold or
personnel only. moved.
Any person, working on the generator
has to read and understand these 1.2 Liability and guarantee
operating instructions.
All statements and advice in the operating
instructions are made under consideration
1. General Notes of our present knowledge and experience.
Any works on the generator has to be We particularly point out, that spare parts
performed by qualified and trained and additional parts not supplied by AvK,
personnel only. The necessary have to be accepted by AvK. AvK will
qualification can be obtained by training or exclude any liability for damages that
courses through the manufacturer. result from the use of spare and additional
Technicians can obtain a special parts that have not been accepted by AvK.
generator training at AvK Germany. The installation or use of foreign products
may possibly change the constructively
The installation should preferably be given design of the electric machine in a
performed by an AvK service technician or negative way, and may restrict the safety
by a specially trained qualified technician. of persons, machine or other values.
General Notes
AH/e-04-2003/A page 2
Besides these safety notes all local valid
Manufacturer's Address instructions for safety and accident
prevention have to be followed.
AvK Deutschland GmbH & Co. KG
Bunsenstraße 17 Follow all warnings and
D-85053 Ingolstadt advice and act very carefully
in these cases. Inform all
Phone (+49) (0)841 / 792-0 persons working on the
FAX (+49) (0)841 / 792-250 generator about all work-safety
regulations.
All rights reserved. Reprints
or copies - even extracts -
need the permission of AvK. 2.2 Signs on the generator
General Notes
AH/e-04-2003/A page 3
case the installation manual for the Unprotected machine parts
transformers is in the terminal box and in may cause severe injuries.
the enclosed documents.
General Notes
AH/e-04-2003/A page 4
After completion of the maintenance work, They are only used as mounting device
it must be ensured that all protection and for these add-ons.
safety devices are back in place properly.
• The ring bolts can only be used for the
2.5 Special Dangers transport of the separate machine,
they are not designed to lift the
The operator of the machine complete unit (generator and prime
has to take care, that the mover)
rules for fire protection are
kept and the equivalent • For transporting the machine, the
agents for fire extinction are available following devices are permitted:
near the machine and ready for use.
- Cable and chains,
3. Shipping, Handling, Storage
that comply with the local regulations,
3.1 Safety precautions for transport that have a sufficient carrying capacity,
that are in an excellent working condition
Please comply with the local
valid regulations for It is not permitted to use
shipments. cables that are torn or worn.
Cables and chains may not be
knotted. Cables and chains
Warning! must not touch any sharp edges.
Never move loads over
persons! - Lifting devices: cranes
overhead cranes
• The shipment and the unloading of the
generator must only be performed by • Moving the machine over rough
personnel, who are familiar with the ground e.g. rails, by using a haulage
lifting cranes and corresponding car is not permitted. This may cause
devices. damage to the bearings and the
windings. This is especially important
• The lifting devices have to be designed for the moving of the machine within
for the weight of the generator the factory.
(Chapter 3.4).
3.2 Packaging
• Follow the shipping instructions
(pictographs) on the cover of the The material used for the packing of the
generator. generator is made of ozone-friendly
material – like wood. The packaging
• The generator must only be supported depends on the mode of transport used –
on its feet. The support on any other surface, water or air freight.
part is not permitted. That is why the When the transport time is for a longer
generator is delivered with a period, then the generator will be packed
transportation construction. in a protective covering against dust or
humidity.
• For the lifting of the generator, ring
bolts are mounted on the generator 3.3 Checking for Shipping Damage
housing.
We recommend checking the
Ring bolts, that are mounted generator for shipping
on add-on pieces like e.g. the damages and complete
cooler top, must not be used delivery by the time of
to lift the whole machine! delivery.
General Notes
AH/e-04-2003/A page 5
If there are damages on the goods (open
damages) report these to the haulage
contractor at take-over. In this case, the
receipt should only be given under
reservation with a written statement
regarding the estimated amount of the
damage.
General Notes
AH/e-04-2003/A page 6
AvK Deutschland GmbH & Co. KG
Bunsenstraße 17
85053 Ingolstadt, Germany
Phone: +49(0)841-792-0
Fax: +49(0)841-792-250
e-mail: infoavkin@newage-avkseg.com
www.newage-avkseg.com
Customer: .............................................................
Sleeve bearing o
YES NO
Replacement of oil: o o
YES NO
Bearing inspection performed: o o
I. Electrical Inspection
Environmental Conditions:
Operating Conditions:
Generator Conditions:
I. Electrical Inspection
performed Complaints
see page 11
performed Complaints
see page 11
............. V ............. A
performed Complaints
see page 11
YES NO
Oil lubrication system installed: o o
.................... mbar
.................... mbar
o 2.9 Check for any corrosion on drive side and non-drive side bearing o
performed Complaints
see page 11
o 2.17 Check of inlet and outlet airducts for dust and dirt o
performed Complaints
see page 11
Output: ............. kW
performed Complaints
see page 11
I1-I1': ............. A
I1-I1': ............. A
UH1-WH2: ............. V
WH1-WH2: ............. V
XE2 o
TO 109/110.1 o
performed Complaints
see page 11
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
Complaints:
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
________________________
(AvK-Service-Technician)
Dokumentenname:
Revisionsstand:
Customer contact.doc AvK Deutschland GmbH & Co. KG
B vom 30.03.05
Stand: B vom 07.04.05
Customer Contact List DA 7.5-1
Service and Warranty Claim Handling for AvK Alternators 2 von 2
Issued Approved
am: 30.03.03 30.03.03
Dokumentenname:
Revisionsstand:
Customer contact.doc AvK Deutschland GmbH & Co. KG
B vom 30.03.05
Stand: B vom 07.04.05
Customer Complaint Report FM 7.5-14
Defect Part
Defektes Bauteil
Dokumentenname: Revisionsstand:
7_5f14a.doc AvK Deutschland GmbH & Co. KG A vom 09.10.03
Drawings
Circuit Diagram
Seite 1 Legende zum Schaltbild Nr. Legend to Circuit Diagram No.
Page 1 K 8**.*.** K 8**.*.**
ZUBEHÖR ACCESSORIES
Widerstandsthermometer PT100 Resistance Thermometer PT100
A1-12 Statorwicklung Stator winding
Phase U: 1, 4, 7, 10 Phase U: 1, 4, 7, 10
Phase V: 2, 5, 8,11 Phase V: 2, 5, 8, 11
Phase W: 3, 6, 9, 12 Phase W: 3, 6, 9, 12
A13, 14 Lager, B-Seite Bearing, NDE
A15, 16 Lager, A-Seite Bearing, DE
A20, 21 Generator Zuluft Alternator air inlet
A22, 23 Generator Abluft Alternator air outlet
A24, 26 Statorblechpaket Stator core
A27/28 Sekundär Kühlmittel EIN/AUS Secondary Cooling agent inlet / outlet
AR1-24 Überspannungsableiter Overvoltage arrester
Thermometer Thermometer
TF20, 21 Lager, B-Seite Bearing, NDE
TF22, 23 Lager, A-Seite Bearing, DE
TF24, 25 Generator Zuluft Alternator air inlet
TF26, 27 Generator Abluft Alternator air outlet
WW1-4 Wasserdurchflußwächter Water flow indicator
Z1 Entstörfilter (Funkstörgrad “K“) Interference filter (R.I.S. degree “K“)
Before installing and starting up this machine, please read these instructions carefully.
Machine No._____________________________
2. Faults, causes and remedies for DSG machines with "COSIMAT C" and "COSIMAT
N" voltage regulators
2
1. Operating and maintenance instructions
1.1 Checking for damage incurred during • cooling air can enter and exit freely
transit
• exhaust gas and heated cooling air cannot
Immediately after receiving the machine, inspect it be drawn in by the machine.
for damage incurred during transit. The transport or
delivering company must be notified of possible
complaints immediately, or at the latest within seven
1.4 Cooling the machine
days of delivery (covered by warranty).
1.4.1 Coolant temperature
Machines with plain or taper roller bearings and 1.4.2 Direction of cooling air
machines in a stored condition are supplied with
The machine is cooled by an integral fan de-
additional transit protection.
pendent on the direction of rotation,
On dual-bearing versions with deep-groove ball mounted on the shaft. It draws cooling air from
bearings, the bearings are pre-loaded and are the non-drive end and expels it at the drive end.
supplied without an additional transit keeper.
If it is intended to use forced cooling on special
This transit keeper should never be removed until versions, either alone or to support the integral
the machine has been set up in its future operating fan, the direction of airflow and rotation must
position on site. be correct here too (see dimensions sheet for
data).
Install the transit protection again if the machine is,
for instance, to be shipped on or stored as a sepa-
rate unit after trials. Important:
For transport as a complete machine set, take the The distance between the fan inlet
necessary safety precautions, for instance support the or outlet on the machine and any
machine set on anti-vibration elements or attach tran- nearby wall must not be less than
sit keepers. the minimum dimension, otherwise
ventilation will be obstructed.
1.3 Setting up the machine Minimum distance (guide value):
1 x diameter of machine
When setting up the machine, make sure that: To extend the service life of the machine, and in
particular its windings and bearings, it is ex-
• the relevant operation and maintenance safety
regulations are observed
3
tremely important that neither contaminated nor replaced by new ones (since they will have be-
aggressive cooling air be allowed to enter it. come too hard for re-use).
4
When aligning a machine of single bearing design • Local electricity supplier’s guidelines re-
which is not flanged onto the drive motor, it is im- garding protective measures
portant to comply with the reference dimen-
5
When measuring the insulation resistance, all con- 1.10 Interference suppression
nections (main connection, measuring connection
and protection or suppression circuit) must be dis- The machines comply with radio interference
connected from the winding. The suppression ele- requirement "N" as stated in German VDE
ments and measuring leads must be disconnected 0875.
during high-voltage insulation tests and tests with
Note that the standard of interference suppres-
insulation measuring appliances.
sion is related to the quality of earthing.
Do not drop below the following specific
insulation resistance values (at 25°C) on
windings that have been in operation for 1.11 Operation
lengthy periods:
With nominal voltage < 1000 V During operation, current-conducting and rotat-
Insulation resistance ≥ 0.5 MΩ/kV ing parts must be sealed with the covers pro-
vided for this purpose.
Measurement must be carried out using 500 V
direct voltage or a crank indicator with a direct Increased vibration may result from insufficiently
voltage output. Due to the capacitive charge in the accurate alignment, poorly fitted foundations or
winding, the measuring unit indicates the correct frame, or weak mountings.
insulation resistance value only after several se-
conds have elapsed.
6
1.13.2 Permanently lubricated bearings Initial greasing quantity and regreasing quantity
at each lubrication point in grams (guide values
Size 29, 36 and 43 machines are normally fitted only:)
with deep-groove ball bearings acc. to DIN 625,
version 2 Z, on both sides. The bearings are filled
with high grade bearing grease by the bearing Type Lubrication Re-Lubrication intervals in hours
manufacturer and sealed on each side with two points for machine running speed of:
cover plates. Quantity in g
1000-1200
1500-1800
Single bea-
erating hours at a machine speed of 1500 rpm.
500-600
750-900
bearing
Double
The bearings are lubricated for life. On machines
min-1
min-1
min-1
min-1
DSG
ring
of a single-bearing design, bearing operating life
must be expected to be 30% shorter.
52 30 3100 2500 2000 1300
1.13.3 Regreasable bearings 62 40 2800 2200 1800 1100
74 70 2600 2000 1600 1000
Size 52, 62, 74, 86, 99, 114, 125 and 144 ma- 86 70 40 2500 2000 1500 1000
chines with relubricating devices normally bear a 99 80 60 2500 1500 1200 800
plate on which the following information is stated: 114 100 60 2000 1500 800 600
125 100 60 2000 1000 800 600
• Relubricating interval in hours of operation 144 100 60 1800 900 700 500
* In the case of double bearing the amount of grease
• Type or specification of anti-friction bearing stated in the “double bearing” column is to be injected into
grease each of the grease nipples.
7
must be kept free of impurities, otherwise they will 1.14 Dust filters and monitoring of
wear out faster and possibly even fail. The bearing thermal behaviour
components must be arranged as shown in the
illustration (see spare part drawing). The grease To prevent the windings from overheating when
regulating disk should be rigidly attached to the the filters are dirty, three temperature sensors
shaft. are installed in the stator winding. Their trip
mechanism must be installed in the switch cabi-
When changing bearings, install type-approved net.
bearings only, and maintain the correct amount of
bearing play (usually "C3"). Do not remove new In addition, probes can be installed to allow the
bearings from their packs until just before they are degree of contamination at the filters to be
installed. Do not wash the bearings, as the anti-cor- measured directly. Their trip mechanism must be
rosion agent applied to them is intended to mix with installed in the switch cabinet. Cleaning must be
the similar agent in the anti-friction bearing grease. performed at regular intervals even if the ma-
Clean the old grease off the parts of the bearing chine is protected against excessive tempera-
that are to be re-installed. tures by integral coil temperature monitoring
devices.
When fitting the bearing, heat it to about 80 -
100°C in an oil bath, oven or by an inductive On machines with integral dust filters, please
method. Make absolutely sure that it is lo- note the following:
cated centrally and remains in positive
1.14.1 Synthetic filter elements
contact with the shaft shoulder.
These are dry filters and must be cleaned at
Once they have cooled down, pack the bearings
regular intervals. These intervals vary depending
with grease.
on the rate at which dirt accumulates. Cleaning
The inner and outer bearing covers must each be may be performed using compressed air, water
filled with grease to 2/3 of their full capacity. at temperatures up to 50°C, or cleaning fluid.
Comply with the relevant environmental and
1.13.5 Dismantling the bearings safety regulations. However, it is often more
economical to change the filter mat.
During shaft production, the bearing seat and the
bearing stop shoulder on the shaft are subject to 1.14.2 Wire mesh filter elements
particularly stringent quality control. This is essential
to maintain the accuracy of shape needed to keep These are wet filters and are supplied dry. Be-
the bearings fully operational. fore starting up, apply a thin film of oil or "Visci-
nol" to the filter plates. Dirty wire mesh filters
When dismantling the bearings and bearing rings, it should be cleaned using compressed air or
is therefore important to handle the bearings and suitable washing agents (soda or "Purinol") and
bearing rings with particular care, otherwise the wetted again when dry.
bearing seats on the shaft could become damaged.
Use a puller to remove. Heat the parts evenly to a
temperature of app. 80°C all round.
1.15 Drying out the machine
1.13.6 Monitoring the bearings
If the insulation value between the winding and
The first indication of damaged bearings is usually the core or between windings is less than that
a notice-able change in running behaviour, or stated in Item 1.9.1, the machine needs drying.
noise, vibration or temperature if bearing damage
1.15.1 Drying out with integral ventilation sys-
has reached an advanced stage.
tem
8
1.15.2 Drying out by short-circuiting on the "COSIMAT C" or at terminals I1 and
K1 on the "COSIMAT N".
a) Short the main terminals U, V and W via a
current transformer and current meter (for app. Important: connect the positive pole
1.2 x nominal current) while the machine is at to I1 and the negative pole to K1.
a standstill.
d) Run the alternator at its nominal speed
b) Pull off plugs at terminals I1 and K1 as well and adjust the short circuit current at the
as UH1 and WH1 on the "COSIMAT C". rheostat to app. 1.2 x nominal current (see
performance data plate).
Open bridges I1-I1’ and K1-K1’ as well as
UH1-UH1’ and WH1-WH1’ at the "COSIMAT Continue to dry the machine until its insulation
N" voltage regulator. resistance has risen to a sufficient level. We
recommend measuring at approx. 2-hour inter-
c) Use a 12 V or 24 V battery and rheostat to vals.
feed in exciter current at terminals I1 and K1
9
2. Faults, causes and remedies for DSG alternators with "COSIMAT C" or "COSIMAT N"
voltage regulator
1. Voltage too low. 1.1 Input speed too low. Check whether LED H2 on regulator
lights up. If it does so, then the under-
speed protection has tripped; increase
the speed until the LED goes out.
2. Nominal voltage does not re- 2.1 Setpoint potentiometer is defec- Check voltage setpoint potentiometer
spond to adjustment at R1. tive. at terminal s/t for signs of interruption.
Rectify the interruption.
3. Alternator voltage too high, can- 3.1 Setpoint potentiometer is defec- Examine the voltage setpoint potenti-
not be brought down by adjust- tive. ometer for a short circuit. Renew the
ment at R1. setpoint potentiometer. Check the
potentiometer leads for a short circuit.
Rectify the short circuit.
4. Severe voltage collapse when 4.1 Input speed drops under load. Check the regulator of the drive ma-
under load. chine.
4.2 One of the fuses on the cooling Check the fuse on the inside of the
body is defective on the "COSI- cooling body; renew if necessary (10 A
MAT N". super quick acting).
4.3 Rotating diodes are defective. Check rotating diodes V1 and over-
voltage conductor V3; renew if neces-
sary.
5. Alternator does not respond to 5.1 Input speed too low. Less than Check the speed regulator of the drive
excitation. 50 % of nominal speed. motor. Check the power transmission
to the alternator.
10
Fault at alternator Cause Remedy
5.6 Regulator fuse has blown on Check the regulator fuse on the inside
"COSIMAT N". of the cooling body and renew if nec-
essary (10 A super quick-acting).
5.7 Power stage transistor is defec- On the "COSIMAT N", replace the
tive. regulator’s power stage. On the "CO-
SIMAT C", replace the entire regulator.
6. Oscillating voltage in separate 6.1 I-share too low. Set switch S1 to a higher number, and
operation. move R1 slightly in a clockwise direc-
tion if necessary.
7. Alternator voltage fluctuates at 7.1 Loose contact in one regulator Check the leads that connect the regu-
irregular intervals. input lead. lator. Check the connections on the
machine’s terminal board. Re-tighten
nuts.
7.2 Blockage at mechanical regula- Check the speed regulator on the drive
tor on drive machine. motor. Rectify the fault.
8. Oscillating reactive output in 8.1 Droop setting is too low. Move R7 slightly in a clockwise direc-
parallel operation. tion.
9. Excessively high reactive current 8.2 I-share too low. Set switch S1 to a higher number.
output in parallel operation.
9.3 Are the secondary connections at Swap over the k/l connections, "k"
terminals k/l correct or not? must be the white lead.
9.4 Droop transformer not installed Install droop transformer in phase "V",
in phase "V". check direction of rotation.
9.5 If "COSIMAT C" is installed sepa- Check the sensing lead. There must be
rately, sensing leads U/W may a right-handed field on "COSIMAT
be wrongly positioned (U/V/W N".
on "COSIMAT N").
10. Excessively low reactive current 10.1 Droop setting is too high. Move R7 slightly in an anti-clockwise
output in parallel operation. direction.
11. Active load not equally distrib- 11.1 This is affected by the drive ma- Check the drive motor (regulator, fuel
uted. chine only, i.e. determined by supply etc.).
the drive machine regulator. The
alternator’s regulator affects
only the reactive output and
therefore the distribution of the
reactive load (see 8., 9. and
10).
11
Please contact our Service Department if you have any problems. Our experienced spe-
cialists will be glad to help you. If possible, inform us of your findings by telefax or tele-
phone.
12
3. Circuit diagrams
Circuit diagram for DSG 29 and 36 with "COSIMAT C" voltage regulator (No. Z 2811.001)
3.2 Circuit diagram for DSG 43 with "COSIMAT C" voltage regulator (No. Z 2811.003)
13
3.3 Circuit diagram for DSG 43...74 with "COSIMAT N" voltage regulator (No. Z 2817.001)
3.4 Circuit diagram for DSG 86...144 with "COSIMAT N" voltage regulator (No. )
14
F1 Schutzschalter für G3 Protection switch for G3
NUR IM STILLSTAND BETÄTIGEN ONLY SWITCH ON AT STANDSTILL
G1 Hauptmaschine Main machine
G2 Erregermaschine Exciter machine
G3 Hilfserregerwicklungen Auxiliary exciter windings
Zubehör Accessories
Widerstandsthermometer PT100 Resistance Thermometer PT100
A1-12 Statorwicklung Stator winding
Phase U: 1, 4, 7, 10 Phase U: 1, 4, 7, 10
Phase V: 2, 5, 8,11 Phase V: 2, 5, 8, 11
Phase W: 3, 6, 9, 12 Phase W: 3, 6, 9, 12
A13, 14 Lager, B-Seite Bearing, NDE
15
AvK Deutschland GmbH & Co. KG
Bunsenstraße 17
85053 Ingolstadt, Germany
Phone: +49(0)841-792-0
Fax: +49(0)841-792-250
e-mail: infoavkin@newage-avkseg.com
OI_DSG29_144/en-06-2004/A
www.newage-avkseg.com
16
Enclosure to Operating Instructions
Advise for Commissioning
Generator with vibration
absorbers on foundation
By connection of the cables it must be ensured that In order to ensure that the movements do not have
no forces have an effect on the machine connection a negative influence on the connection terminals,
terminals. The same counts for the time during the cable must be fixed with max. 300 mm distance
assembly. from the terminal box screw fitting. This cable fixing
has to be connected rigidly to the gen-set in order
If shock load or vibrations are to be expected, the to avoid relative movements between the cable
cables should be fixed over the cable clips and the fixing and the terminal box.
cable platform.
The relative movements between the gen-set and
By elastic mounted gen-sets (see picture above) the foundation have to be compensated for by a
sufficient 'free cable length' should be ensured to sufficiently long free cable length between the cable
compensate the movements of the diesel/gas motor. fixing on the gen-set and the foundation.
Open the bridges UH1-24 and WH1-14 on the No tests are to be performed with open star point!
terminal strip X2. De-excitation with extern switch The correct connection of the power cables can be
takes place on these terminals, too. checked with appropriate equipment.
Description
Insulation material:
pure magnesium oxide, highly compacted
Connection:
threaded bolt M4 with silicon insulated cable
Tolerances
screws screws
property class property class
8.8 4.6
M4 3,0 1,1
M5 3,5 2,2
M6 9,0 3,7
M8 18 9,0
M10 45 18
M12 50 31
M16 110 75
M20 250 150
M24 440 255
M30 980 510
M36 1730 890
M42 2700 1450
starting torque in Nm
Description
Type of filter
Maintenance
Caution:
2. Brief summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1 General diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Adjusting elements and their effects . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Optimising the regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Monitoring alternator voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Desired value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Droop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6 Control amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.7 Additional functions of the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . 10
3.7.1 Underspeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.7.2 Protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.8 Power stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8. Diagrams of connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.1 Assembly for DSG alternators 52 – 74 . . . . . . . . . . . . . . . . . . . . . . . 21
8.2 Assembly for DSG alternators 86 – 125 . . . . . . . . . . . . . . . . . . . . . . . 22
8.3 Assembly for DIG medium-voltage alternators with UN ≤ 11.5 kV . . . . . . . . . . . . 23
8.4 Assembly for DIG medium-voltage alternators with UN > 11.5 kV . . . . . . . . . . . . 24
8.5 De-excitation circuit on the ”COSIMAT N+” . . . . . . . . . . . . . . . . . . . . . 25
8.6 Monitoring field current and voltage on the ”COSIMAT N+” . . . . . . . . . . . . . . 25
2
2. Brief summary
2.1 General-arrangement diagram
3
2.2 Adjusting elements and their effects
4
2.3 Start-up
Figure 3 - Start-up
5
2.4 Optimisation of the regulator It is not necessary to adjust the D parameter in order to
optimise the control properties. It is generally determined just
To optimise regulation, it is necessary to connect loads to the once, in accordance with the size of the alternator. In the case
alternator. of alternators > 1 MVA, switch S2.4 is switched to the ON
position.
To allow the trend of the control property following a change
in the P or I parameter to be evaluated, the load connected To decide whether the D parameter should be increased
must be reproducible. beyond this, it is necessary to take specific measurements of
the alternator voltage and at the output of the regulator.
The factor with the greatest general significance in achieving
an optimum regulating system is an overshoot amplitude xm Satisfactory optimisation of the regulator will normally be
which is as small as possible. The essential criterion in the achieved by the free adjustment of the P and I parameters.
evaluation of the regulating process with respect to time is the
settling time taus.
6
3. Functional description
3.1 Block diagram
7
3.2 Power supply 3.3 Monitoring alternator voltage
Power is supplied to the "COSIMAT N+" by means of The "COSIMAT N+" measures alternator voltages from 90 to
so-called auxiliary excitation voltages, which are produced 500 V AC (external conductor voltage) within two selectable
in the alternators. The excitation energy and the supply ranges by means of an internal three-phase measuring trans-
voltage for the "COSIMAT N+" are derived from the auxiliary former.
excitation voltages.
To measure higher voltages, corresponding voltage transfor-
In the case of AvK alternators in Series DSG and DIG with mers must be connected in series.
UN ≤ 11.5 kV, the "COSIMAT N+" is supplied with power
via two single-phase auxiliary windings, which are inserted Signal input N allows intervention into the internal formation
into the main stator. The windings are designated UH1/UH2 of the actual value.
and WH1/WH2.
The secondary AC measurement voltage of the measuring
The voltages UH1 and UH2 are offset by 90° with respect transformer is converted into a DC voltage, smoothed, condi-
to WH1 and WH2 and are 80 V AC ± 20 % at the nominal tioned and output as an actual value to the regulator circuit.
voltage of the alternator.
The measured value which is produced corresponds to the
In the case of AvK alternators belonging to Series DIG with arithmetic mean of the rectified three-phase AC measurement
UN > 11.5 kV, the "COSIMAT N+" is supplied with power voltage.
via a two-phase auxiliary exciter machine. The windings are
designated UH1, UH2, UH3 and WH1, WH2. Three-phase measurement allows for asymmetric loads.
The voltages UH1 and UH2 are offset by 90° with respect Note:
to WH1 and WH2 and are 80 V AC ± 20 % at the nominal For non-linear loads (static thyristor converter or rectifier),
speed of the machine. additional module TF (RC – low-pass filter) is recommended
as a measuring adapter. High non-linear loads may
The above-mentioned auxiliary exciter windings UH1 and require overdimensioning of the alternator.
UH2 and WH1 and WH2 are plugged into the correspon-
dingly designated terminals of the "COSIMAT N+":
3.4 Desired value
Special application
Three-phase auxiliary exciter machine The desired value for the "COSIMAT N+" is taken from a
If a three-phase auxiliary exciter machine is used, the winding temperature-compensated reference source.
terminals are designated UH1-VH1-WH1. The external con-
ductor voltage is 3 x 75 V AC ± 20 % at the nominal speed The signal input ”n” allows intervention in the internal formation
of the machine. of the desired value.
If the auxiliary excitation voltage is taken This potentiometer is used for fine adjustment of the alternator
from a constant "external" power source (e.g. voltage (= ”exact” desired value).
the mains), the supply must be switched on
only after the alternator has been started. The adjustment range is limited to ± 5 % to ± 10 % around
When switching off the alternator, the the nominal value, depending on the potentiometer used.
supply should be switched off before the
machine comes to a halt (see 11.10 External The ES additional module allows the adjustment range of the
power supply). external set-point potentiometer to be extended from remanence
to the nominal voltage.
8
If the ES module is used on AvK alternators, the regulator If, when the alternator is connected in parallel, the fixed mains
system must be provided with an external power supply. This forces it down to a figure which is 6 % lower, the reactive
must be decided on a case by case basis, depending on the current is inductive and equivalent to 100 % of the nominal
application and the excitation system used (auxiliary excitati- alternator current.
on windings or auxiliary excitation machine?)
In parallel operation, regulation of the synchronous alternator
is made possible by the droop sensing signal.
3.5 Droop For stand-alone operation, adjustment is performed on the test
rig using a reactive load. The droop effect is set to 3 %.
Once an alternator has been connected in parallel, voltage
regulation is no longer possible because the system voltage The droop sensing signal in the "COSIMAT N+" influences
is fixed. The slightest fluctuation in the system voltage would the desired value and is produced by means of a geometrical
lead to the alternator producing reactive current > IN. addition of the external conductor voltage U-W and a
current-dependent voltage signal from the V phase.
To stabilise the alternator reactive current it is therefore
necessary to have a measured variable which is dependent In AvK synchronous machines, the corresponding current
on the reactive current and incorporates the magnitude of the transformer is located in phase V. The K side of the transfor-
current and the reactive power (inductive or capacitive). This mers points towards the alternator’s main winding (see Figure
measured variable is introduced at the addition point (com- 6 – Block diagram).
parison point of the desired value and the actual value) of the
control amplifier circuit. Internally load-relieved bushing-type transformers are used.
This produces a static droop control characteristic, which The outlet end of the secondary connections ( = potted end
represents the relationship between: of the transformer) is the primary-side K point (= current input).
the change in the alternator voltage in relation to the nominal The wire marked in white is the secondary-side k point.
voltage and
the change in the alternator reactive current in relation to the The secondary connections k and I of the droop current
nominal current. transformer should be plugged into the correspondingly mar-
ked terminals of the "COSIMAT N+".
The droop is represented by the slope of the characteristic
curve produced i.e. is the quotient of the above ratio. In the case of alternators for parallel and stand-alone opera-
tion, the measuring input k – I can be short-circuited by means
In the "COSIMAT N+" a linear droop characteristic is gene- of a switch for stand-alone operation. This gives better voltage
rated. The droop effect can be adjusted from 0 to 6 % using stability (see 8. Diagrams of connections, 11.5 Droop
the potentiometer R 7. switch).
Caution:
9
kink point” is set to 0.95 x fN. Above the kink point, voltage
Caution: regulation is constant.
Switch position 0 is not allowed; never pass The voltage reduction is delayed by about 2 seconds to
through 0. eliminate the effect of transient drops in the speed of the drive
machine.
The parameter of the P section can be varied by means of In exceptional circumstances, the underspeed protection fun-
potentiometer R 1. During this process, the adjustment range ction can be deactivated by means of code switch S2.2 (see
shown in Figure 8 should not be exceeded. 9.2 Adjusting elements).
Caution:
10
Time limitation of the maximum excitation cur- 3.8 Power stage
rent
The power stage of the "COSIMAT N+" provides an excita-
When the actuator is fully on, the excitation current tion current that corresponds to the output signal of the control
reaches a maximum. amplifier.
If this state is allowed to continue, the exciter system will A MOSFET transistor is used as the actuator, with pulse width
be damaged. modulation, i.e. the turn-on time varies but the switching
frequency remains constant.
However, the fully-on state only occurs in the case of
compensating processes or short circuits at the main The excitation energy is taken from the rectified supply
terminals of the alternator. voltage, the rectifier circuit being located in the power stage.
It allows the rectification of two single-phase or three-phase
The monitoring system of the "COSIMAT N+" limits supply voltages (see 3.2 Power supply).
maximum excitation to 8 to 10 seconds.
There is a short-circuit thyristor in the DC circuit. The protective
After this, the protection circuit isolates the exciter field circuit of the "COSIMAT N+" switches this thyristor on if faults
from the source of excitation energy by tripping the occur in the control circuit. The resulting short-circuit current
protection fuses. trips the two protection fuses on the front plate of the "COSI-
MAT N+" and the exciter field is isolated from the source of
Checking the direction of action of the control excitation energy.
amplifier and the actuator
Fuse:
This feature monitors the positioning transistor for short 10 A super quick-acting
circuits. 32 mm x 6.3 mm ø
IEC G 144.400
Short-circuiting of the positioning transistor leads to maxi-
mum excitation. The control amplifier tries to counteract
this but has no effect on the faulty actuator. The actuator
and the control amplifier act in opposite directions and Caution:
the fuses trip immediately.
Replacement fuses must be of the above type.
The following circumstances also lead to maximum excitation The power stage may suffer permanent dama-
and can trip the fuses: ge if the wrong type of fuse is used.
● Short circuit in the I1 / K1 exciter lead To ensure adequate cooling for the power semi-conductors in
the power stage, you must follow the instructions in Chapter
● Faulty exciter rectifier in the "COSIMAT N+" 11.2 Mounting the regulator.
Note:
Additional module ER1 can be used to limit the excitation
current when the alternator is operated in parallel.
11
4. Transfer function of the "COSIMAT N+"
There are three ways of influencing the control parameters in The time constant of the input low-pass filter is:
the "COSIMAT N+”:
TP1 = 3.62 ms
Potentiometer R1 (500 kΩ) for changing the P parameter. At
the right-hand stop, R1 is 0Ω. The time constant of the output low-pass filter is:
Switch S1 for changing the I parameter in 15 steps (from 0.22 TP2 = 0.268 x T2
to 3.85 µF) each of 0.22 µF (C1).
T1 = R1 x C1
T2 = 6,8 kΩ x C2
T3 = 22 kΩ x C1
TI = T1 + T2
TD = T1 x T2
T1 + T2
K1 =2,56 T1 + T2
T3
K2 = 716,1 ms x K1
Tl
K3 = 1 = 0,066
15
12
5. Special functions and additional
equipment
5.1 Stand-by and emergency manual switchover
13
5.2 Additional modules
COS
cos phi regulator
QPF
Reactive power regulator with single-phase
measurement
QPF
cos phi trimmer
QPF
Reactive power trimmer with single-phase
measurement
14
SB2
Automatic stand-by switchover
(see 5.1 Stand-by and emergency manual switchover)
TF/TF1
RC – low-pass filter
(Type TF1-50 for 50/60 Hz)
ES
Extended adjustment range
(incl. 10 x potentiometer)
UF
U/f characteristic module
15
UF3
U/f characteristic module with extension
SR2
Current limitation
UDC2
Detection of DC voltage actual value
16
KP
Cable compensation
ER1
Controlling exciter current limiter
17
6. Technical data
GENERAL DATA Type : fully potted aluminium housing incl. power stage
Maintenance : maintenance-free
Rated switch-on time : continuous operation
Installation position : mount with longitudinal axis vertical at
convectional cooling or longitudinal axis
in air flow direction at fan cooling
Installation clearance : 3 cm all round
(see 11.2 Mounting the regulator)
HOUSING, DIMENSIONS,
WEIGHT AND INSTALLATION Height x width x depth : 121 x 115 x 162.5 mm
Fixing : 4 M6 bolts, washers and circlips
Weight : 2 kg
18
7. Dimensions
Figure 25 – Dimensions
19
8. Diagrams of connections
Legend for diagrams of connections
G1 Main machine
G2 Exciter/excitation windings
V1 Rotating rectifier
X1 Main terminals
X2 – 6 Terminal strip
R3 Underspeed protection
R1 P component
S1 I component
R7 Droop adjustment
T6 Droop transformer
20
8.1 Assembly for DSG alternators 52 - 74
21
8.2 Assembly for DSG alternators 86 – 125
22
8.3 Assembly for DIG medium-voltage alternators with UN ≤ 11.5 kV
23
8.4 Assembly for DIG medium-voltage alternators with UN >11.5 kV
24
8.5 De-excitation circuit on the "COSIMAT N+" 8.6 Monitoring field current and voltage on the
"COSIMAT N+"
If a de-excitation circuit is fitted, the bridges on the double
terminals UH1/UH1’ and WH1/WH1’ should be removed. The "COSIMAT N+" is provided with double terminals I1/I1’
Switch contacts should be connected to the double terminals and K1/K1’ to allow the exciter field to be connected. Bridge
to de-excite the alternator when they open (see Figure 34 – I1/I1’ must be removed to allow the field current and voltage
De-excitation circuit). These de-excitation contacts must meet to be monitored (see Figure 35 – Field current/field voltage
the following specification: monitoring).
Current carrying capacity:10 AAC The measuring range for field voltage monitoring is 150 VDC;
Voltage carrying capacity:160 V AC for field current monitoring it is 10 ADC. Rotary coil or
moving-iron instruments are recommended. Under certain
The switch elements used must have dust-protected contact conditions, digital instruments may give false readings.
chambers. Ensure that contact resistance is low – the contacts
must be sensitive to low-level signals. Note:
In the case of AvK alternators (DSG 86 – 125, DIG),
Note:
there are connecting terminals for monitoring the field
One of the factors which determines the build-up of
current and voltage on terminal strip X2.
excitation is the quality of these contacts.
On AvK alternators (DSG 86 – 125, DIG), connecting
terminals for de-excitation are provided in the auxiliary
terminal box (see legend of the order-specific circuit
diagram).
25
9. Connections, adjusting elements and Monitoring droop current:
displays
k–I
9.1 Connections
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø screw
terminals
Voltage supply:
UH1 Caution:
UH2 (VH1)
WH1 Measuring input k – I is not a current input;
WH2 standard transformers should be load-relieved
accordingly.
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4mm Ø screw
terminals
Supply can be 2 x single-phase (80 V AC ± 20 %) or The droop current transformer must be installed in the "V"
phase of the alternator.
three-phase (75 V AC ± 20 % external conductor voltage).
Internally load-relieved droop current transformers are
2 x single-phase = UH1-UH2, WH1-WH2
used in AvK alternators.
three-phase = UH1-VH1-WH1
At the nominal current of the alternator, a voltage of 3 to
For de-excitation circuits, the bridges on the double
7 V AC is required at the terminals k – I (see 3.5 Droop
terminals must be removed (see 8.5 De-excitation circuit
and 6. Technical Data).
or order-specific circuit diagram).
Connecting leads to the transformer must be shielded if
Caution:
the regulator is installed externally. Connecting leads to
the short-circuit droop switch (see 11.5 Droop switch)
If there is an external power supply (e.g.
should be shielded in all cases. The shield should be
from the mains), it must not be switched on
earthed at one end on the "COSIMAT N+" (see 8.
until after the alternator has run up. It
Diagrams of connections).
should be switched off before the machine
has come to a halt (see 11.10 External
power supply).
Exciter field:
I1 – K1
Measuring alternator voltage:
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø screw
U-V-W 250 to 500 V AC terminals as double terminal.
U-V-W 90 to 250 V AC
If the regulator is mounted externally, the I1/K1 field leads to
6.3 x 0.8 mm flat plugs the alternator must be run through a separately shielded cable
(LSYCY or LIYCY).
Caution:
The shield should be earthed at one end on the "COSIMAT N+"
(see 8. Diagrams of connections).
A clockwise rotary field is required. If the
alternator rotates anticlockwise, U and W
should be interchanged (see 3.5 Droop).
External set-point potentiometer
26
The rated power of the potentiometer must be at least 1 This potential is not connected when the "COSIMAT N+"
W. A multiple-turn potentiometer must be used (see 3.4 is used for standalone operation.
Desired value).
Function:
Control inputs: Adjustment of the frequency-dependent lowering of alter-
nator voltage (see 3.7.1 Underspeed protection).
N
M/m Direction of action:
n Left-hand stop = beginning of reduction at >50/60 Hz.
Right-hand stop = beginning of reduction only after
4.8 x 0.8 mm flat plugs and/or 2.5 mm2/4 mm Ø about > 30 Hz.
screw terminals.
In special cases, the underspeed protection can be
A number of additional modules from the "COSIMAT N+" deactivated by means of switch S2.2 (see 9.2 Adjusting
equipment range can be connected to these control elements).
inputs (see 5.2 Additional modules).
This is necessary when regulating a DC voltage by way
of additional module UDC or in some cases when using
Caution: external UF modules.
Direction of action:
Circuit earth: Left-hand stop = minimum alternator voltage
Right-hand stop = maximum alternator voltage
-
Z
P component:
The load earth is used for connecting the internal interme-
diate circuit capacitors.
R1
Additional external capacitors can be connected between
the second Z connection tab (MINUS) and terminal I1 1-gang trim potentiometer
(PLUS).
27
Function: Direction of action:
Varying the proportional component of the control cha- Left-hand stop = maximum compensation value
racteristic. Right-hand stop = minimum compensation value
Function:
Caution:
Droop:
Required basic setting:
R7
AvK DSG alternators up to size 62:
1-gang trim potentiometer
S2.1 = no function
S2.2 = ON (underspeed protection)
Function:
S2.3 = ON (actual value smoothing)
Adjustment of the droop effect.
S2.4 = OFF (D parameter)
Direction of action:
AvK DIG, DSG 74 – 125 alternators
Left-hand stop = no droop effect (0 %)
parallel operation not possible.
S2.1 = no function
Right-hand stop = droop effect 6 %
S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
If the direction of rotation is reversed, sensing voltage
S2.4 = ON (D parameter)
connections U and W must be interchanged.
9.3 Displays
Droop matching:
Underspeed protection:
R6
H1
25-gang trim potentiometer
yellow 5 mm Ø LED
Function:
Matching the various alternator nominal currents and
current transformer ratios to the droop monitoring system.
28
H 1 lights up when the desired value or lowering of alternator g) Is the field connected with the correct polarity?
voltage in the case of underfrequency is active (3.7.1 Under-
speed protection)
10.2 Desired value setting range
Caution:
Once all the basic settings and visual checks have been
carried out, the alternator can be started up.
The regulator is set during the testing of the
alternator at the factory. See test protocol a) Run up alternator to nominal speed.
and order-specific circuit diagram.
b) Set external set-point potentiometer to the central position.
R3 right-hand stop position a) If the basic settings of R1 and S1 (see 10.1 Basic setting
R4 left-hand stop position and visual check) lead to continuous periodic fluctuations
R1 central position (stability limit), adjust R1 slowly to the left.
(in the case of DIG, DSG alternators, 1/4
rotation anticlockwise from the central position) b) If there is temporarily a tendency towards weakly
damped hunting in the event of load surges, adjust S1 one
S1 Pos. 4 or two positions to the right.
(in the case of DIG, DSG alternators Pos. 6,
at 600/750 rpm Pos. 9)
S2 S2.1 = no function 10.4 Underspeed protection
S2.2 = ON
S2.3 = ON a) 50/60 Hz alternators to 0.95 x fN.
S2.4 = OFF (ON in the case of DIG and DSG
alternators from size 74) b) In the case of 50/60 Hz alternators, turn R3 slowly in
the anticlockwise direction starting from the right-hand stop
R7 Central position position until H1 lights up. Then turn it slowly in the clock-
R6 Left-hand stop wise direction until H1 goes out.
After basic setting, the following visual checks must be carried c) Run the alternator up to nominal speed.
out:
29
Recommended droop settings: to flow freely through its power stage. Note the installation
position marking ”UNTEN” (= BOTTOM) (connecting
3% Parallel to the mains (If the mains supply is not leads towards the power stage). At fan cooling, the longitu-
stable, the setting may have to be increased). dinal axis of the "COSIMAT N+" has to be in air flow
direction. Deviating mounting is only suitable after checking
2% Parallel operation with identical alternators. by AvK.
6% Parallel operation with different alternators whose There must be a 3 cm clearance all the way round between
regulators do not have a linear droop. the "COSIMAT N+" and any structural elements that might
hinder flow (cable ducts, plates). This rule does not apply to
1% Parallel operation with different alternators which laterally mounted additional modules.
also have "COSIMAT N” or ”N+" regulators.
Protection concept: For standard applications of the "COSIMAT N+", the following
The exciter system should be protected from excessive exciter basic settings must be made before start-up at code switch S2
currents and voltages by a field discharge switch or relay. (see 9.2 Adjusting elements):
This switch or relay should be connected as shown in the
relevant order-specific circuit diagram. The tripping criteria AvK DSG alternators up to size 62
will be determined by the protection required by the alterna- S2.1 = no function
tor. S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
Where the alternator is operated in stand-alone mode, an S2.4 = OFF (D parameter)
overvoltage protection system must be installed in the swit-
ching station. In the case of operation in parallel with the AvK DIG and DSG 74 – 125 alternators:
mains or other alternators, an overcurrent protection system is S2.1 = no function
to be added. S2.2 = ON (underspeed protection)
S2.3 = ON (actual value smoothing)
DSG/DIG alternators with auxiliary windings: S2.4 = ON (D parameter)
DSG and DIG alternators with auxiliary windings are fitted
with an excess-current circuit breaker F1. This protects the Any differences from these settings must be agreed with the
auxiliary windings from excessively high thermal loading e.g. manufacturer beforehand and taken into account in the way
as the result of an external short circuit involving the auxiliary the alternator is operated.
exciter voltage UH1-UH2 or WH1-WH2.
30
operation if the k – I inputs of the "COSIMAT N+" are it is installed in the synchronous machine and the way the
short-circuited (see 8. Diagrams of connections). droop current transformer is connected to the "COSIMAT N+"
remains the same (see 8. Diagrams of connections).
The lead between the droop switch and the regulator must be
screened. For motor control, a cos phi controller (COS module) is
required additionally.
The screen must be earthed at one end on the "COSIMAT N+".
Caution:
Caution:
● Given a falling exciter current (underexcitation), the synchro- Two spare fuses are mounted on the underside of the "COSI-
nous machine becomes an acceptor of reactive power. MAT N+" (see 7. Dimensions).
When used as a generator, the synchronous machine is taken
as the reference point; where it is used as a motor, the mains 11.9 Drying out the alternator
are taken as the reference point.
If, because of inadequate insulation resistance, the alternator
When used as a generator, the synchronous machine supplies has to be dried out at nominal current by the short-circuit
”inductive” reactive power to the mains when overexcited. method, the "COSIMAT N+" should be disconnected from
the supply and exciter field connections.
When used as a motor, the synchronous machine draws
”inductive” reactive power from the mains when underexcited. The alternator is dried out by applying an external source of
excitation.
The droop system in the "COSIMAT N+" operates with the
correct direction of action whether the machine is being Further information on how to dry out the alternator can be
operated as a motor or a generator. The direction in which found in the alternator instructions.
31
11.10 External power supply must be connected to the correspondingly named connecting
terminal of the "COSIMAT N+".
If the auxiliary exciter voltage is taken from a different,
”external” source (e.g. the mains), the supply must not be
switched on until the alternator has started up.
When shutting down the alternator, the supply must be
switched off before the machine comes to a halt.
Caution:
Measuring voltage U, V, W
Supply UH1-UH2, WH1-WH2
Exciter field I1-K1
32
11.14 Malfunctions, causes and remedies
Alternator voltage is too low. Input speed too low. Check whether LED H1 on regulator
lights up. If so, underspeed protection
device has been activated, run up al-
ternator to nominal speed.
Alternator voltage is too low and can- Set-point potentiometer or its con- Check set-point potentiometer or its
not be adjusted with the set-point po- necting leads are disconnected/inter- connecting leads. Rectify fault.
tentiometer. rupted.
Alternator voltage is too high and can- Set-point potentiometer or its con- Check set-point potentiometer for short
not be adjusted with the set-point po- necting leads have a short circuit. circuit. Change potentiometer. Check
tentiometer. set-point leads for short circuits. Elimina-
te short circuit.
Severe voltage dip upon loading. Input speed falls upon loading. Check regulator of driving machine.
Alternator does not respond to excitati- Input speed too low. Less than 0,5 x nN. Check the speed regulator of the input
on. machine. Check the power transmissi-
on to the alternator.
Exciter protection switch has tripped. Switch on the protective switch again.
If it trips once more, search for the fault
and repair it.
33
Malfunction Cause Remedy
Alternator does not respond to excitati- Remanence too low. Alternator with auxiliary winding:
on. Briefly connect positive terminal of 4.5
or 6 V battery to I1 and negative
terminal to K1 (at nominal speed).
Alternator with two-phase auxiliary
exciter machine:
Briefly connect positive terminal of 4.5
or 6 V battery to I2 and negative
terminal to K2 (at nominal speed).
DIG alternators (UN > 11.5 kV): With alternator standing still!
Interruption in exciter windings I1/K1 Check windings I1/K1 and I2/K2 for
and/or I2/K2. interruptions using an ohmmeter. Elimi-
nate faults.
Periodic fluctuations in the alternator Incorrect regulator setting. Adjust R1 carefully in the anticlockwise
voltage when operated singly (stability direction and turn S1 one or two steps
limit)! to the right.
34
Malfunction Cause Remedy
Alternator voltage fluctuates at irregular Temporary interruption in one of the Check connecting leads to the regula-
intervals. regulator supply leads. tor. Check connections at the terminal
board of the alternator. Tighten all con-
tact screws and nuts.
Reactive power output too high in par- Droop set too low. Adjust R7 slightly in the clockwise di-
allel operation. rection on the "COSIMAT N+".
Phase angle connection (k/I) of the Check connecting leads from the alter-
droop current transformer has been nator to the regulator. Interchange k/I
wrongly positioned. if necessary. The white secondary con-
nection of the droop current transformer
is ”k”.
Droop switch is not in alternator phase Install droop transformer in phase ”V”.
”V”.
Reactive power output too low in par- Droop set too high. Adjust R7 slightly in the anticlockwise
allel operation. direction on the "COSIMAT N+".
Active load not equally distributed. This is affected by the driving machine Check the drive motor and its regulator.
only.
The "COSIMAT N+" affects only the
reactive power.
35
12. List of figures
36
AvK Deutschland GmbH & Co. KG
Bunsenstraße 17
85053 Ingolstadt, Germany
Phone: +49(0)841-792-0
Fax: +49(0)841-792-250
e-mail: infoavkin@newage-avkseg.com
www.newage-avkseg.com
AvK Deutschland GmbH & Co. KG AvK Deutschland GmbH & Co. KG
Bunsenstr. 17 Dreieich branch
85053 INGOLSTADT Benzstr. 47-49
GERMANY 63303 Dreieich
www.newage-avkseg.com Phone: +49(0)841-792-0 GERMANY
infoavkin@newage-avkseg.com Fax: +49(0)841-792-250 Phone: +49(0)6103-5039-0
Fax: +49(0)6103-5039-40
Ersatzteile: 2.2.2 Spare Parts: 2.2.2
1 Ventilator Fan
2 Ventilatorbuchse Fan hub
3 Passfeder für Wellenstummel Key for shaft end
4 Passfeder für Ventilatorbuchse Key for fan hub
5 Rotor komplett Rotor complete
6 Spulenhalter Coil holder
7 Passfeder für Erreger-Rotor Key for Exciter Rotor
8 Passfeder für Hilfserreger-Rotor-Buchse Key for Auxiliary-Exciter Rotor-Bushing
9 Erreger-Rotor Exciter Rotor
10 Wellensicherungsring für Erreger-Rotor Circlip for Exciter Rotor
11 Hilfserreger-Rotor Auxiliary Exciter Rotor
12 Wellensicherungsring für Hilfserreger-Rotor Circlip for Auxiliary Exciter Rotor
13 Passfeder für Hilfserreger-Rotor Key for Aux. Exciter Rotor
14 Buchse für Hilfserreger-Rotor Bushing for Aux. Exciter Rotor
15 Gleichrichterträger Rectifier Carrier
16 Rotierender Gleichrichter Rotating Rectifier
17 Überspannungs-Ableiter Overvoltage Arrestor
18 Wellensicherungsring für Hilfserreger-Rotor- Circlip for Aux. Exciter Rotor Bushing
Buchse
AvK Deutschland GmbH & Co. KG AvK Deutschland GmbH & Co. KG
Bunsenstr. 17 Dreieich branch
85053 INGOLSTADT Benzstr. 47-49
GERMANY 63303 Dreieich
www.newage-avkseg.com Phone: +49(0)841-792-0 GERMANY
infoav kin@newage-avkseg.com Fax: +49(0)841-792-250 Phone: +49(0)6103-5039-0
Fax: +49(0)6103-5039-40
Ersatzteile: 3.0NS Spare Parts: 3.0NS
AvK Deutschland GmbH & Co. KG AvK Deutschland GmbH & Co. KG
Bunsenstr. 17 Dreieich branch
85053 INGOLSTADT Benzstr. 47-49
GERMANY 63303 Dreieich
www.newage-avkseg.com Phone: +49(0)841-792-0 GERMANY
infoav kin@newage-avkseg.com Fax: +49(0)841-792-250 Phone: +49(0)6103-5039-0
Fax: +49(0)6103-5039-40
Ersatzteile: 4.0.0 oRT Spare Parts: 4.0.0 oRT
AvK Deutschland GmbH & Co. KG AvK Deutschland GmbH & Co. KG
Bunsenstr. 17 Dreieich branch
85053 INGOLSTADT Benzstr. 47-49
GERMANY 63303 Dreieich
www.newage-avkseg.com Phone: +49(0)841-792-0 GERMANY
infoavkin@newage-avkseg.com Fax: +49(0)841-792-250 Phone: +49(0)6103-5039-0
Fax: +49(0)6103-5039-40
Ersatzteile: 6.0 obi Spare Parts: 6.0 obi
AvK Deutschland GmbH & Co. KG AvK Deutschland GmbH & Co. KG
Bunsenstr. 17 Dreieich branch
85053 INGOLSTADT Benzstr. 47-49
GERMANY 63303 Dreieich
www.newage-avkseg.com Phone: +49(0)841-792-0 GERMANY
infoavkin@newage-avkseg.com Fax: +49(0)841-792-250 Phone: +49(0)6103-5039-0
Fax: +49(0)6103-5039-40
Ersatzteile: 0.2.0 Spare Parts: 0.2.0
AvK Deutschland GmbH & Co. KG AvK Deutschland GmbH & Co. KG
Bunsenstr. 17 Dreieich branch
85053 INGOLSTADT Benzstr. 47-49
GERMANY 63303 Dreieich
www.newage-avkseg.com Phone: +49(0)841-792-0 GERMANY
infoavkin@newage-avkseg.com Fax: +49(0)841-792-250 Phone: +49(0)6103-5039-0
Fax: +49(0)6103-5039-40
Technical Data
Technische Daten / technical data DSG 114 K1-10
Wirkungsgrad / efficiency
1/4*PN 2/4*PN 3/4*PN 4/4*PN
η [%] p.f.=0.8 93,20 95,70 96,20 96,20
η [%] p.f.=0.85 93,30 95,83 96,40 96,45
η [%] p.f.=0.9 93,40 95,95 96,60 96,70
η [%] p.f.=1.0 93,60 96,20 97,00 97,20
Bemerkungen / remarks
AvK NO. 81 27280-81-82 C002 *exact values see valid drawing
03.05.05 Ga
Alle Angaben sind gemäß VDE 0530, IEC 34 All data are in accordance to VDE 0530, IEC 34
Technische Daten selbstregelnden Drehstrom-Synchrongenerator 1.1
Rev. 0
technical data for self regulating three phase alternator
Type: DSG 99 L1-10 Projekt: Cegielski AvK-Order: 81 27280-81-82 A002
0,9
0,8
active power P (p.u.)
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
-0,80
-0,70
-0,60
-0,50
-0,40
-0,30
-0,20
-0,10
0,00
0,10
0,20
0,30
0,40
0,50
0,60
0,70
0,80
0,90
1,00
1,10
1,20
-0,1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
I2 (∞) = 0.08 p.u.
0,1
0 t [s]
100 101 102 103 104 105 106
Bemessungsdaten:
Type rating for this application and requirements:
SN/kVA 1499 Kriterien für Inversstrom:
IN/A 1923 Criterias for negative sequence current:
UN/V 450 Kurzzeitbetrieb
fN/Hz 60 Transient operation: (I2/IN)2*t <=20s
nN/rpm 720 Dauerbetrieb
power factor 0,80 Continuous operation: I2/IN <= 0,08 p.u.
Protection IP23
cooling air °C 45
temp.rise F
5
-. .-. -. --. ~~.
.~._.- ---
4,5 - -'~'-. . , -- ~ --. - .~.._._.
~
4
~~,-- --~
- - -.-
3,5 ----. "i .--c, , ~_.~-~ , ,
1- - -- ....- ~--
~
z
....
3
T
2,5
- , --- -,. --- ~.~. -.
2 ,
"-1'
, I
1 --I L .-J-1'
---'-" .- - .-- '-' ----.
1,5
'' ,- '. t-=r IT; .1., ---+ iTUJ'
1
10° 5s 101 30s Hf 103 60 min 104
t [s]
cooling air oe 45
temp.rise F
Short circuit decrement curve ( symmetrical short circuit current envelope Ik`` )
12
10
8
Ik``/IN [ p.u.]
0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
t [s]