3 M Fire Barrier Duct Wrap 15 A

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

3

Fire Barrier Duct Wrap 15A


Commerical Kitchen Grease Duct Fire Protection System

Product Data and Installation Instructions

Complies with Complies with


Compliance International Standard
1998 Edition Mechanical Code Mechanical Code

Compliance
Report 2132
1. Product Description 5. Performance
3MTM Fire Barrier Duct Wrap 15A is a fire resistant 3M Fire Barrier Duct Wrap 15A has been tested in
wrap consisting of a patented inorganic blanket accordance with the following:
encapsulated with a scrim-reinforced foil. It is used to ASTM C 411
fire rate commercial kitchen grease ducts and is a ASTM C 51
proven alternative to 1 or 2 hour fire resistant rated ASTM E 84
shaft enclosures. This non-asbestos wrap contains a ASTM E 119
safer fiber construction* and installs easily because of ASTM E 136
its high flexibility and strength. 3M Fire Barrier Duct ASTM E 814
Wrap 15A is the thinnest standard, single layer fire UL 1978 (Sections 12 & 13)
resistant wrap that has passed the UL1978 test which
simulates a grease duct fire. With its excellent Surface Burning Characteristics (ASTM E 84)
insulating capabilities, it is an ideal choice for tight Foil Encapsulated Blanket:
spaces because it protects combustible constructions Flame Spread: 0
at zero clearance to the overlap or collar. 3M Fire Smoke Developed: 0
Barrier 1000 N/S, 1003 S/L and 2000+ Silicone Blanket:
Sealants used in combination 3M Fire Barrier Duct Flame Spread: 0
Wrap 15A provide an effective firestop when the duct Smoke Developed: 0
penetrates fire rated walls and floors.
Thermal Conductivity
Temperature OF (OC) btu•in./(hr.•ft2•F)
Features 500 (260) 0.417
• Thinnest, standard one layer wrap for grease ducts 1000 (537) 0.922
rated as a shaft alternative per UL 1978 1500 (815) 1.69
1800 (982) 2.27
• Zero clearance to the overlap or collar for
congested spaces
For technical data and properties of 3M Fire Barrier
• High flexibility for installation ease 1000 N/S, 1003 S/L and 2000+ Silicone Sealants see
• Foil encapsulated with unique center overlap seam separate product data sheets available from your 3M
for blanket protection, less dust, and high wrap representative
strength
• Safer fiber construction* Grease Duct Listings
Fire Enclosure System Omega Point Lab. Design Nos.
Resistive Duct System Through-
*Has been demonstrated to be soluble in the lungs according to Rating Penetration
EU guidelines 67/548/EWG, Note Q for bio persistence. System
1 or 2 hours 1 layer of 3M Fire Barrier GD 532 F FS 557 W
2. Applications Duct Wrap 15A , 3 in. FS 558 F
(76 mm) perimeter and FS 559 W
3M Fire Barrier Duct Wrap 15A is an ideal fire FS 560 F
longitudinal overlaps
resistive enclosure for commercial kitchen grease FS 561 F
ducts. It is a proven performance alternative to a FS 562 W
1 or 2 hour fire resistant rated shaft enclosures and FS 563 W
provides zero clearance to combustible construction
at overlap or collar. 3M Fire Barrier 1000 N/S, 1003 Code Compliance
S/L or 2000+ Silicone Sealant is used in combination 3M Fire Barrier Duct Wrap 15A complies with
with 3M Fire Barrier Duct Wrap 15A to firestop the requirements of the following codes:
duct when the duct penetrates fire rated floors and NFPA 96, 1998 Edition
walls. Standard Mechanical Code
International Mechanical Code
3. Availability Standard Building Code
Product Unit Size Units/ Wt./ SBCCI Compliance Report 2132
ctn. ctn.
3M Fire Barrier Roll 1.5 in.x 24 in. x 20 ft. 1 53 lbs.
Duct Wrap 15A (38mm x 60,9cm x 609 cm) 24 kg This is only a partial list of code compliance. For the
3M Fire Barrier Roll 1.5 in. x 48 in. x 20 ft. 1 106 lbs. latest code and approval information go to
Duct Wrap 15A (38mm x 121 cm x 609 cm) 48 kg www.3m.com/firestop or speak to your authorized 3M
distributor or sales representative at (800) 328-1687.
4. Typical Physical Properties
Blanket Color: gray/green 6. Installation Techniques
Weight: 1.38 lbs./sq. ft. (6.73 kg/sq. m) 3M Fire Barrier Duct Wrap 15A system should be
installed in accordance with the following installation
instructions.

Page 2
Material and Equipment 1. Telescoping 3 in. (76 mm) Overlap Wrap
• 3M Fire Barrier Duct Wrap 15A blanket, 1-1/2 in. With the telescoping overlap wrap method, each
(38 mm) thick, 24 in. (60 cm) or 48 in. (121 cm) blanket overlaps one adjacent blanket, and each
wide, 20 ft. (609 cm) standard length. The 48 in. blanket has one edge exposed and one edge covered
(121 cm) wide blanket helps to minimize waste. by the next blanket as shown in Figure 1A and 1B.
The visible edges of the perimeter overlaps all point in
• Aluminum foil tape.
the same direction.
• Minimum 3/4 in. (19 mm) wide filament tape.
• Carbon steel or stainless steel banding material, 2. Checkerboard 3 in. (76 mm) Overlap Wrap
minimum 1/2 in. (12,7 mm) wide, minimum 0.015 With the 3 in. (76 mm) checkerboard overlap wrap
in. (0,38 mm) thick, with steel banding clips. method, blankets with both edges exposed alternate
• Hand banding tensioner, crimping tool, and banding with blankets with covered edges, as shown in Figure
cutter. 1C. The visible edges of the perimeter overlaps
• Minimum 12 gauge copper-coated steel insulation alternate their directions and appear on every other
pins; galvanized steel speed clips, minimum blanket.
1-1/2 in. (38 mm) square or 1-1/2 in. (38 mm) dia.
round, or equivalent sized insulated cup-head pins; 3. Butt Joint With Collar
capacitor discharge stud gun. With the butt joint and collar method, adjacent
blankets are butted tightly together and 6 in. (152
• Access door hardware: four galvanized steel thread
rods, 1/4 in. (6 mm) diameter by 4-1/2 in. to 5 in. mm) wide collar of 3M Fire Barrier Duct Wrap is cen-
long (114 mm to 127 mm) with 1/4 in. (6 mm) wing tered over the joint, overlapping each blanket by
nuts and 1/4 in. (6 mm) washers: 4 in. (102 mm) 3 in. (76 mm) minimum as shown in Figure 1D.
long steel hollow tubing to fit threaded rods.
In all three overlap techniques the perimeter overlap
• Minimum 4.0 lb. (1,8 kg) density mineral wool or can occur at any location on the duct.
scrap pieces of 3M Fire Barrier Duct Wrap 15A
blanket The blanket is mechanically attached to the duct by
• 3M Fire Barrier 1000 N/S, 1003 S/L or 2000+ steel banding or by welded insulation pins and clips
Silicone Sealant. for all three installation methods listed above.

Storage For Banding Only (See Figures 1A to 1D)


The 3M Fire Barrier Duct Wrap 15A and 3M Fire Filament tape can be used to temporarily hold the
Barrier 1000 N/S, 1003 S/L and 2000+ Silicone blanket in place until the banding is applied. The
Sealants must be stored in a dry warehouse steel banding is applied around the duct 1-1/2 in. (38
environment. Pallets should not be stacked. mm) from each edge of the blanket, and maximum
10-1/2 in. (26,7 cm) centers. The banding is placed
Preparatory Work: 3M Fire Barrier Duct Wrap 15A is around the material and tightened so as to sufficiently
installed with common tools, such as knives, banders hold the 3M Fire Barrier Duct Wrap 15A in place
and capacitor discharge guns for applying insulation against the duct, compressing the foil but not cutting
pins. In order to install the duct firestop system, the the foil.
surfaces of all the openings and penetrating items
need to be clean, dry, frost free and free of dust. Additional Pinning to Prevent Sagging of the Wrap:
For Ducts 24 in. (60 cm) and larger in width,
Method: To minimize waste, 3M Fire Barrier Duct additional pins are needed to support the blanket on
Wrap 15A material should be rolled out tautly before the bottom horizontal surface and on the outside face
measuring. General instructions for installing the 3M of a vertical duct run. Space pins a maximum of
Fire Barrier Duct Wrap 15A include a one-layer wrap 10-1/2 in. (26,7 cm) apart in the direction of the
construction applied directly to the duct. The 3M Fire blanket width, and a maximum of 12 in. (30 cm) apart
Barrier Duct Wrap 15A blanket is wrapped around the in the direction of the blanket length. Refer to
perimeter of the duct and is cut to a length to overlap paragraph below for more information on Mechanical
itself not less than 3 in. (76 mm). The overlap made Fastening with Pins.
by adjacent blankets forms the “longitudinal” overlap.
Aluminum foil tape is used to seal all cut edges of the For Mechanical Fastening with Pins Only
blanket and any tears in the foil scrim. (See Figure 2A to 2D)
Insulation pins are welded to the duct in the centers
There are three (3) approved installation of the overlaps a minimum of 1-1/2 in. (38 mm) from
techniques for installing the 3M Fire Barrier Duct each edge of the blanket, and spaced a maximum of
Wrap 15A (See Figures 1A-1D and Figures 2A-2D): 10-1/2 in. (26,7 cm) on center along perimeter
overlap, and a maximum of 10-1/2 in. (26,7 mm) on
center along longitudinal overlaps. The blanket is
Page 3
impaled over the pins and held in place by galvanized
speed clips. Insulation pins that extend beyond the To firestop the wrapped duct, follow the installation
blanket wrap shall be turned down to eliminate sharp parameters detailed in the following Omega Point
points. Insulated cup-head pins can be used at the Laboratories, Inc. systems:
same spacing requirements of the insulation pins. FS 557 W, FS 558 F, FS 559 W, FS 560 F, FS 561 F,
FS 562 W, FS 563 W.
NOTE: Support hangar systems do not need to be
wrapped provided the hangar rods are at least a Other Applications
minimum of 3/8 in. (9,53 mm) diameter and spaced a Refer to Figures 5, 6, 7, 8 and 9 for additional typical
maximum of 60 in. (152 cm) on center along the conditions.
length of the duct. Use a minimum 2 in. x 2 in. x
1/4 in. (50 mm x 50 mm x 6,35 mm) steel angle steel 7. Maintenance
support channel or SMACNA equivalent support No maintenance is required when installed in accor-
system. dance with the 3M Installation Instructions. Once
installed, if any section of the 3M Fire Barrier Duct
Access Door Installation (See Figure 3) Wrap 15A is damaged so that the blanket is dam-
Four galvanized steel threaded rods, 1/4 in. diameter aged, the following procedures will apply:
(6,35 mm) by 4-1/2 in. to 5 in. long (114 mm to
127 mm) are welded to the duct at the corners of the • The damaged section should be removed by cutting
door opening. Four steel tubes, each 3 in. (76 mm) the steel banding or removing the clips holding it in
long, are placed over the rods to act as protection for place.
the 3M Fire Barrier Duct Wrap 15A when fastening A new section of the same dimension should be cut

the door. Four insulation pins are welded to the door from a roll of 3M Fire Barrier Duct Wrap 15A, either
panel for installation of the blanket. One layer of 3M 24 in. (60,9 cm) or 48 in. (121 cm) wide.
Fire Barrier Duct Wrap 15A is cut approximately the
• The new section should be placed and fitted
same size as the access panel and impaled over the
insulation pins on the panel. It is essential that this ensuring the same overlap that existed previously.
layer fit tightly against the wrap surrounding the • The steel banding should be placed around the
access door opening with no through openings. A material and tensioned so as to sufficiently hold the
second layer of 3M Fire Barrier Duct Wrap 15A is cut 3M Fire Barrier Duct Wrap 15A in place.
so as to overlap the first layer by a minimum of 1 in. • If the blanket has not been damaged but the foil
(25,4 mm). The second layer is impaled over the pins has ripped, seal the rips with aluminum foil tape.
and both layers are locked in place with galvanized
speed clips. Pins that extend beyond the outer layer 8. Purchase Information
of 3M Fire Barrier Duct Wrap 15A shall be turned 3M Fire Barrier products are available through a
down to avoid sharp points on the door. network of nationwide distributors. For information on
where to buy, go to www.3m.com/firestop.
The insulated door panel is placed over the threaded
rods and held in place with washers and wing nuts. 9. Safe Handling Information
The details are shown in Figure 3. Consult Material Safety Data Sheet prior to
handling and disposing of 3M Fire Barrier Duct
Penetrations (See Figures 4A to 4D) Wrap 15A.
When the duct penetrates a fire rated wall, ceiling or
floor, an approved firestop system must be employed.
Figures 4A to 4D illustrate typical conditions.

Page 4
Figure 1A
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Shaft Alternative Zero Clearance to Combustibles
Telescoping Wrap Technique With Banding For Ducts 24 inches (60,9 cm) or Less

1. One Layer 3M Fire Barrier Duct Wrap 15A


2. Steel Banding 1/2 in. (13 mm) Wide Min. Typical
3. 3 in. (76 mm) Min. Longitudinal Overlap
4. 3 in. (76 mm) Min. Perimeter Overlap
System integrity is limited by quality of installation.
Page 5
Figure 1B Telescoping Overlap Wrap Option
Cross Sectional View

Figure 1C Checkerboard Overlap Wrap Option


Cross Sectional View

Figure 1D Butt Joint With Collar Option


Cross Sectional View

1. One Layer 3M Fire Barrier Duct Wrap 15A


2. Steel Banding 1/2 in. (13 mm) Wide Min. Typical
3. 3 in. (76 mm) Min. Longitudinal Overlap
4. 3 in. (76 mm) Min. Perimeter Overlap
5. 6 in. (152 mm) Wide Collar Made From 3M Fire Barrier Duct Wrap 15A
Alternate Collar: Prefabricated 3M Fire Barrier 20A Collar
6. Firmly Butted Joint
System integrity is limited by quality of installation.
Page 6
Figure 2A
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Shaft Alternative Zero Clearance to Combustibles
Telescoping Wrap Technique With Weld Pins Only

1. One Layer 3M Fire Barrier Duct Wrap 15A


2. 1-1/2 in. Square (38 mm) or 1-1/2 Dia. (38 mm) Galvanized Speed Clips
3. 3 in. (76 mm) Min. Longitudinal Overlap
4. 3 in. (76 mm) Min. Perimeter Overlap
System integrity is limited by quality of installation.
Page 7
Figure 2B Telescoping Overlap Wrap Option
Cross Sectional View

Figure 2C Checkerboard Overlap Wrap Option


Cross Sectional View

Figure 2D Butt Joint With Collar Option


Cross Sectional View

1. One Layer 3M Fire Barrier Duct Wrap 15A


2. 1-1/2 in. Square (38 mm) or 1-1/2 Dia. (38 mm) Galvanized Speed Clips
3. 3 in. (76 mm) Min. Longitudinal Overlap
4. 3 in. (76 mm) Min. Perimeter Overlap
5. 6 in. (152 mm) Wide Collar Made From 3M Fire Barrier Duct Wrap 15A
Alternate Collar: Prefabricated 3M Fire Barrier 20A Collar
6. Firmly Butted Joint
System integrity is limited by quality of installation.
Page 8
Figure 3
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Access Door System

1. Access Hole
2. 1/4 in. (6 mm) Dia. All Threaded Rods
3. Access Cover – 16 Gauge
4. Insulation Pins – Welded
5. First Layer 3M Fire Barrier Duct Wrap 15A Cut Same Size As Cover
6. Second Layer 3M Fire Barrier Duct Wrap 15A with 1 in. (25mm) Overlap On All Sides
7. Speed Clips
8. Aluminum Tape Covering All Exposed Edges
9. Spool Pieces For Threaded Rods
10. 1/4 in. (6mm) Diameter Wing Nuts
System integrity is limited by quality of installation.
Page 9
Figure 4A
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Through Penetration Systems
4-1/2 inch (11,4 cm) Concrete Floor or Wall

1. Floor/Ceiling or Wall Assembly Omega Point Laboratories, Inc.


2. Duct Through Penetration Systems
3A. One Layer 3M Fire Barrier Duct Wrap 15A
3B Banding or Pinning FS 560 F
FS 562 W
3C. Packing Material
3D. 3M Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant
For Wall Assembly Apply Sealant To Both Sides of Wall
System integrity is limited by quality of installation.
Page 10
Figure 4B
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Through Penetration Systems
Fire-Rated Gypsum Wallboard

1A. Studs Omega Point Laboratories, Inc.


1B. Gypsum Wallboard Through Penetration Systems
2. Duct
3A. One Layer 3M Fire Barrier Duct Wrap 15A FS 557 W
FS 559 W
3B. Banding or Pinning
3C. Packing Material
3D. 3M Fire Barrier 1000 N/S or 2000+ Silicone Sealant
System integrity is limited by quality of installation.
Page 11
Figure 4C
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Through Penetration Systems
4-1/2 inch (11,4 cm) Concrete Floor or Wall

1. Floor/Ceiling or Wall Assembly Omega Point Laboratories, Inc.


2. Duct Through Penetration Systems
3A. One Layer 3M Fire Barrier Duct Wrap 15A – Terminated on Each
Side of Floor or Wall Penetration. FS 561 F
3B Banding or Pinning FS 563 W
3C. Packing Material
3D. 3M Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant
For Wall Assembly Apply Sealant To Both Sides of Wall
System integrity is limited by quality of installation.
Page 12
Figure 4D
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 Hour Through Penetration Systems
Fire-Rated Wood/Gypsum - Floor/Ceiling Assembly

1. Fire-rated Floor/Ceiling Assembly Omega Point Laboratories, Inc.


2. Duct Through Penetration Systems
3A. One Layer 3M Fire Barrier Duct Wrap 15A
3B Banding or Pinning FS 558 F
3C. Packing Material
3D. 3M Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant
System integrity is limited by quality of installation.
Page 13
Figure 5
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
Suggested 1 or 2 Hour Three Sided Wrap

1. Concrete Slab
2. One Layer 3M Fire Barrier Duct Wrap 15A
3. Concrete Fasteners - Minimum 1/4 in. (6 mm) Dia. Steel Concrete Anchors
4. 1/8 in. (3mm) Thick x 2 in.-3in. (50mm - 76mm) Wide Bar Stock Perforated 12 in. (30 cm)
O.C.
5. Duct
6. Banding
7. Banding Clips
Page 14
Figure 6
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
Suggested 1 or 2 Two Hour Two Sided Wrap

1. Concrete Slab
2. One Layer 3M Fire Barrier Duct Wrap 15A
3. Concrete Fasteners - Minimum 1/4 in. (6 mm) Dia. Steel Concrete Anchors
4. 1/8 in. (3 mm) Thick x 2 in.-3 in. (50 mm – 76 mm) Wide Bar Stock Perforated 12 in. (30 cm) O.C.
5. Duct
6. Banding
7. Banding Clips
System integrity is limited by quality of installation.
Page 15
Figure 7
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Shaft Alternative Zero Clearance to Combustibles
Suggested Exhaust Hood

1. Hood
2. One Layer 3M Fire Barrier Duct Wrap 15A
3. 6 in. (152 mm) Minimum Overlap
4. Banding

Page 16
Figure 8
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Shaft Alternative Zero Clearance to Combustibles
Suggested Roof Vent

1. Duct
2. Roof Assembly
3. Roof Flashing
4. Vent Flashing
5. One Layer 3M Fire Barrier Duct Wrap 15A
6. Firestopping System for Rated Roof Assemblies Only

Page 17
Figure 9
3M Fire Barrier Duct Wrap 15A
Commercial Kitchen Grease Duct Systems
1 or 2 Hour Shaft Alternative Zero Clearance to Combustibles
Suggested Vertical Support

1. One Layer 3M Fire Barrier Duct Wrap 15A


2. One Layer 3M Fire Barrier Duct Wrap 15A Overlapped At Base
3. Mechanical Fasteners and Washers
4. Duct
5. Rated Floor/Ceiling
6. Firestopping System
7. Banding
8. Support Channel

Page 18
Page 19
Warranty and Limited Remedy. This product will be free from defects in material and manufacture for a peri-
od of ninety (90) days from date of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT
LIMITED TO, ANY IMPLIED WARRANTY OR MERCHANTIBILITY OR FITNESS FOR A PARTICULAR
PURPOSE. User is responsible for determining whether the 3M product is fit for a particular purpose and
suitable for user’s method of application. If this 3M product is proved to be defective within the warranty period
stated above, your exclusive remedy and 3M’s sole obligation shall be, at 3M’s option, to replace or repair the
3M product or refund the purchase price of the product.

Limitation of Liability. Except where prohibited by law, 3M will not be liable for any loss or damages
arising from the use of this 3M product, whether direct, indirect, special, incidental or consequential,
regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.

3
Specified Construction Products Department
3M Center 223-2N-21 Printed in U.S.A.
St. Paul, MN 55144-1000
(800) 328-1687 © 3M 2001 98-0400-5054-8 (July 2001)