Principles of Circuit Breakers: Difference Between An Isolator and Circuit Breaker
Principles of Circuit Breakers: Difference Between An Isolator and Circuit Breaker
Principles of Circuit Breakers: Difference Between An Isolator and Circuit Breaker
MODULE 4
Difference between an isolator and circuit breaker
basic principle of operation of a circuit breaker, phenomena of arc, properties of arc,
initiation and maintenance of arc,
arc interruption theories - slepian’s theory and energy balance theory,
Re striking voltage, recovery voltage, Rate of rise of Re striking voltage,
DC circuit breaking, AC circuit breaking, current chopping, capacitance switching,
resistance switching
Rating of Circuit breakers.
Introduction
Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in
combination to detect and isolate faults. Circuit breakers are the main making and breaking
devices in an electrical circuit to allow or disallow flow of power from source to the load. These
carry the load currents continuously and are expected to be switched ON with loads (making
capacity). These should also be capable of breaking a live circuit under normal switching OFF
conditions as well as under fault conditions carrying the expected fault current until completely
isolating the fault side (rupturing/breaking capacity). Under fault conditions, the breakers should
be able to open by instructions from monitoring devices like relays. The relay contacts are used
in the making and breaking control circuits of a circuit breaker, to prevent breakers getting
closed or to trip breaker under fault conditions as well as for some other interlocks.
• Carry fault current without blowing itself open (or up!) i.e. no distortion due to magnetic forces
under fault conditions.
• The speed with which the main current is opened after a tripping impulse is received
• The capacity of the circuit that the main contacts are capable of interrupting.
The first characteristic is referred to as the ‘tripping time’ and is expressed in cycles. Modern
high-speed circuit breakers have tripping times between three and eight cycles. The tripping or
total clearing or break time is made up as follows:
• Opening time: The time between instant of application of tripping power to the instant of
separation of the main contacts.
• Arcing time: The time between the instant of separation of the main circuit breaker contacts to
the instant of arc extinction of short-circuit current.
The second characteristic is referred to as ‘rupturing capacity’ and is expressed in MVA. The
selection of the breaking capacity depends on the actual fault conditions expected in the system
and the possible future increase in the fault level of the main source of supply. In the earlier
chapters we have studied simple examples of calculating the fault currents expected in a system.
These simple calculations are applied with standard ratings of transformers, etc., to select the
approximate rupturing capacity duty for the circuit breakers.
Introduction
As already seen in the last chapter, whenever any fault occurs in the power system then that part
of the system must be isolated from the remaining healthy part of the system. This function is
accomplished by circuit breakers. Thus a circuit breaker will make or break a circuit either
manually or automatically under different conditions such as no load, full load or short circuit.
Thus it proves to be an effective device for switching and protection of different parts of a power
system. In earlier days fuse was included in. the protective system. But due to some limitations
they are not used in practice now a day. The main difference between a fuse and circuit breaker
is that under fault condition the fuse melts and it is to be replaced whereas the circuit breaker :an
close or break the circuit without replacement.
Requirements of Circuit Breaker: The power associated with the circuit breakers is large and it
forms the link between the consumers and suppliers. The necessary requirements of circuit
breakers are as follows, 1. The normal working current and the short circuit current must be
safely interrupted by the circuit breaker. 2. The faulty section of the system must be isolated by
circuit breaker as quickly as possible keeping minimum delay. 3 It should not operate with flow
of overcurrent during healthy conditions. 4. The faulty circuit only must be isolated without
affecting the healthy one.
The Fig. Shows the elementary diagram of a circuit breaker. It consists of two contacts a fixed
contact and a moving contact. A handle is attached at the end of the moving contact. It can be
operated manually or automatically. The automatic operation needs a separate mechanism which
consists of a trip coil. The trip coil is energized by secondary of current transformer. The
terminals of the circuit breaker are bought to the supply.
Under normal working conditions the e.m.f produced in the secondary winding of the
transformer is insufficient to energize the trip coil completely for its operation. Thus the contacts
remain in closed position carrying the normal working current. The contacts can be opened
manually also by the handle. Under abnormal or faulty conditions high current in the primary
winding of the current transformer induces sufficiently high e.m.f in the secondary winding so
that the trip coil is energized. This will start opening motion of the contacts. This action will not
be instantaneous as there is always a time lag between the energization of the trip circuit and the
actual opening of the contacts. The contacts are moved towards right away from fixed contact.
As we have seen already the separation of contacts will not lead to breaking or interruption of
circuit as an arc is struck between the contacts. The production of arc delays the current
interruption and in addition to this it produces large amount of heat which may damage the
system or the breaker. Thus it becomes necessary to extinguish the arc as early as possible in
minimum time, so that heat produced will lie within the allowable limit. This will also ensure
that the mechanical stresses produced on the parts of circuit breaker are less the time interval
which is passed in between the enervation of the trip coil to the instant of contact separation is
called the opening time. It is dependent on fault current level. The time interval from the contact
separation to the extinction of arc is called arcing time It depends not only on fault current but
also on availability of voltage for maintenance of arc and mechanism used for extinction of arc.
Formation of an Arc: Under faulty conditions heavy current flows through the contacts of the
circuit breaker before they are opened. As soon as the contacts start separating, the area of
contact decreases which will increase the current density and consequently rise in the
temperature. The medium between the contacts of circuit breaker may be air or oil. The heat
which is produced in the medium is sufficient enough to ionize air or oil which will act as
conductor. Thus an arc is struck between the contacts. The p.d. between the contacts is sufficient
to maintain the arc. So long as the arc is remaining between the contacts the circuit is said to be
uninterrupted. The current flowing between the contacts depends on the arc resistance. With
increase in arc resistance the current flowing will be smaller. The arc resistance depends on
following factors,
a) Degree of ionization: If there is less number of ionized particles between the contacts then the
arc resistance increases.
b) Length of arc: The arc resistance is a function of length of arc which is nothing but separation
between the contacts. More the length more is the arc resistance.
c) Cross-section of arc: If the area of cross-section of the arc is less then arc resistance is large.
Initiation of Arc There must be some electrons for initiation of an arc when fault occurs circuit
breaker contacts start separating from each other and the electrons are emitted which are
produced by following methods. By high voltage gradient at the cathode, resulting in field
emission by increase of temperature resulting in thermionic emission. By High Voltage Gradient
As the moving contacts start separating from each other, the area of contact and pressure
between the separating contacts decreases. A high fault current causes potential drop (of the
order )between the contacts which will remove the electrons from cathode surface. This process
is called field emission.
By Increase of Temperature With the separation of contacts there is decrease in contact area
which will increase the current density and consequently the temperature of the surface as seen
before which will cause emission of electrons which is called thermal electron emission. In most
of the circuit breakers the contacts are made up of copper which is having less thermionic
emission.
Maintenance of an Arc In the previous section we have seen the initiation of the arc by field
emission emission. The electrons while travelling towards anode collide with another electron to
dislodge them and thus the arc is maintained. The ionizing is lactated by,
i) High temperature of the medium around the contacts due to high current densities. Thus the
kinetic energy gained by moving electrons is increased.
ii) ii) The increase in kinetic energy of moving electrons due to the voltage gradient which dislodge
more electrons from neutral molecules. iii) The separation of contacts of circuit breaker increases
the length of path which will increase number of neutral molecules. This will decrease the
density of gas which will increase free path movement of the electrons.
Arc Extinction It is essential that arc should be extinguished as early as possible. There are two
methods of extinguishing the arc in circuit breakers which are namely,
High Resistance Method In high resistance method the arc resistance is increased with time.
This will reduce the current to such a value which will be insufficient to maintain the arc thus the
current is interrupted and the arc is extinguished. This method is employed in only d.c circuit.
The resistance of the arc may he increased by lengthening the arc, cooling the arc, reducing the
cross-section of the arc and splitting the arc. These methods will be discussed in detail later in
this chapter.
Low Resistance Method The low resistance or current zero method is employed for arc
extinction in ac. circuits. In this method arc resistance is kept low until current zero where
extinction of arc takes place naturally and is prevented from restriking. This method is employed
in many of the modern a.c. circuit breakers.
This method is used in ac. arc interruption. -I he current becomes zero two tires in a cycle. So at
each current zero point the arc vanishes for small instant and again it appears. But in auxillary
circuit breakers the arc is interrupted at a current zero point. The space between the contacts is
ionized quickly if there is fresh unionized medium such as oil or fresh air or SF, gas between the
contacts at current zero point. This will make dielectric strength of the contact space to increase
such that arc will be interrupted and discontinued after current zero. This action produces high
voltage across the contacts which are sufficient to reestablish the arc. Thus the dielectric strength
must be building more than the restricting voltage for faithful interruption of arc. Then the arc is
extinguished at next current zero. While designing the circuit breakers the care is taken so as to
remove the hot gases from the contact space immediately after the arc. So that it can be filled by
fresh dielectric medium having high dielectric strength. In summary we can say that the arc
extinction process is divided in thee parts, a) Arcing phase b) Current zero phase c) Post arc
phase In arcing phase, the temperature of the contact space is increased due to the arc. The heat
produced must be removed quickly by providing radial and axial flow to gases. The arc can not
be broken abruptly but its diameter can be reduced by the passage of gas over the arc. When ax.
Current wave is near its zero, the diameter of the arc is very less and consequently arc is
extinguished. This is nothing but current 7ero phase. Now in order to avoid the reestablishment
of arc, the contact space must be filled with dielectric medium having high dielectric strength.
This is post arc phase in which hot gases are removed and fresh dielectric medium is introduced.
Arc Interruption Theories There are two main theories explaining current zero interruption of arc
Slepian's Theory Slepian described the process as a race between the dielectric strength and
restriking voltage. After every current zero, there is a column of residual ionized gas. This may
cause arc to strike again by developing necessary restriking voltage and this voltage stress is
sufficient to detach electrons out of their atomic orbits which releases great heat. Si in this theory
rate at which positive ions and electrons recombine to form neutral molecules is compared with
rate of rise of restriking voltage. Due to recombination dielectric strength of gap gets recovered.
So rate of recovery of dielectric strength is compared with rate of rise of restriking voltage. If the
restriking voltage rises more rapidly than the dielectric strength, gap space breaks down and arc
strikes again and persists. In the Fig. a) Rate of dielectric strength is more than restriking voltage.
b) Rate of dielectric strength is less ------ -0 than rate of rise of restriking voltage. The
assumption made while developing this theory is that the restriking voltage and rise of dielectric
strength are comparable quantities which is not quite correct the second drawback is that the
theory does not consider the energy relations in the arc extinction. The arcing phase is not
covered by this theory so it is incomplete.
Cassie's Theory Alternative explanation of above process s afforded by Cassie's theory or also
called Energy balance theory. Cassie suggested that the reestablishment of arc or interruptions of
an arc both are energy balance process. If the energy input to an arc continues to increase, the arc
restrikes and if not, arc gets interrupted. Theory makes the following assumptions
a) Arc consists of a cylindrical column having uniform temperature at its cross section. The
energy distributed in the column is uniform
c) The cross section of the arc adjusts itself to accommodate the arc current.
d) Power dissipation is proportional to cross sectional area of arc column interruption theories -
slepian’s theory and energy balance theory.
Breakdown occurs if power fed to the arc s more than power loss. The theory is true for high
currents. Immediately after current zero, contact space contains ionized gas and therefore has a
finite post zero resistance. Now there is rising restriking voltage. This rising res. triking voltage
causes a current to flow between the contacts. Due to this current flow, power gets dissipated as
heat in the contact space of circuit breaker. Initially when restriking voltage is zero,
automatically current and hence power is zero. It is again zero when the space has become fully
deionize and resistance between the contacts is infinitely high. In between these two extreme
limits, power dissipated rises to a maximum. If the heat so generated exceeds the rate at which
heat can be removed from contact space, ionization will persist and breakdown will occur, giving
an arc for another half cycle.
Transient Recovery Voltage The transient recovery while has effect on the behavior of circuit
breaker. This voltage appears between the contacts immediately after final arc interruption. This
causes high dielectric stress between the contacts. If this dielectric strength of the medium
between the contacts does not build up faster than the rate of rise of the transient recovery
voltage then the breakdown takes place which will cause restriking of arc Thus it is very
important that the dielectric strength of the contact space must build very rapidly that rate of rise
of transient recovery voltage so that the Interruption of current by the circuit breaker takes place
successfully. The rate of rise of this transient voltage depends on the circuit parameters and the
type of the switching duty invoked. The rate of building up of the dielectric strength depends on
the effective design of the interrupter and the circuit breaker. If it is desired to break the
capacitive currents while opening the capacitor banks, there may appear a high voltage across the
contacts which can cause re ignition of the arc after initial arc extinction. Thus if contact space
breaks down within a period of one fourth of a cycle from initial arc extinction the phenomenon
is called Reigniting. Moving contacts of circuit breakers move a very small distance from the
fixed contacts then reigniting may occur without overvoltage. But the arc gets extinguished in
the next current zero by which time moving contacts should be moved by sufficient distance
from fixed contacts. Thus the re ignition is in a way not harmful as it will not lead to any
overvoltage beyond permissible limits. If the breakdown occurs after one fourth of a cycle, the
phenomenon is called Restrike. In restriking, high voltage appear across the circuit breaker
contacts during capacitive current breaking. In restrikes, voltage will go on increasing which
may lead to damage of circuit breaker. Thus the circuit breakers used for capacitors should be
free from Restrike I.e. they' should have adequate rating.
Effect of Different Parameters on Transient Recovery Voltage (TRV) As seen from the
previous section, after the final current, zero high frequency transient voltage appears across the
circuit breaker poles which is superimposed on power frequency system voltage and tries to
restrike the arc. This voltage may last for a few tens or hundreds of microseconds. If the shape of
this TRV is seen on the oscilloscope then it can be seen that it may be oscillatory, non-oscillatory
or a combination of two depending upon the characteristics of the circuit and the circuit breaker.
The waveform is as shown in the Fig.
Transient voltage Shape of transient recovery voltage This voltage has a power frequency
component and an oscillatory transient component. The oscillatory component is due to
inductance and capacitance in the circuit. The power frequency component is due to the system
voltage. This is shown in the Fig.
Zero power factor If we consider zero power factor currents, the peak voltage E is impressed on
the circuit breaker contacts at the current zero instant This instantaneous voltage gives more
transient and provides high rate of rise of TRV. Hence if the p.f. is low then interrupting of such
current is difficult.
Recovery Voltage As seen previously it is the voltage having normal power frequency which
appears after the transient voltage.
Effect of Reactance Drop on Recovery Voltage Home fault is taking place let us consider that
the voltage appearing across circuit breaker is V. As the fault current increases, the voltage drop
in reactance also increases. After fault clearing the voltage appearing say V2 is slightly less than
V,. The system takes some time to regain the original value.
Affect of Armature Reaction on Recovery Voltage Me short circuit currents are at lagging power
factor. These lagging p.f. currents have a demagnetizing armature reaction in alternators.Thus the
induced end of alternators decreases To regain the original value this emf takes some time. Thus
the frequency component of recovery voltage is less than the normal value of system voltage.
D.C. Circuit Breaking The breaking in case of d.c. can be explained as follows. For this, we will
consider a circuit which will consist of generator with voltage E, resistance R. inductor L and the
circuit breaker as shown in the Fig.
The voltage-current relationship can be represented as shown in the graph it could be seen that
curve AB represents the voltage E - iR, i is nothing but current at any instant. The curve XY
represents the voltage-current characteristics of the arc for decreasing currents.
Voltage-current relationship
When the circuit breaker starts opening it carries the load current I. In the graph shown the
current is shown to be reduced respectively. Section represents voltage drop i3R whereas qs
represent arc voltage which is greater than available voltage. The arc becomes unstable and the
difference in voltage is supplied by inductance L across which the voltage is L. For decreasing
values of t currents this voltage is negative and according to Lenz's law it tries to maintain the
arc.
The voltage across inductance L is seen to be positive in the region of currents i, mid i2 since the
arc characteristics lies below the curve AB. The arc current in this region tries to increase so
interruption of current is not possible in this region. Afterwards the arc is lengthened with
Increase in contact separation which will raise the arc voltage above the curve AB. The operation
in case of d.c. circuit breakers is said to be ideal if the characteristics of the arc voltage are above
the curve AB even in the region of currents i1 and i2. This is shown in the fig..
It can be seen that arc voltage is greater than E - lit and the balance between the voltages is
supplied by the voltage across the inductance el, which is proportional to d i rate of change of
current dI.
Thus the function of the circuit breaker is to raise the arc characteristics without affecting its
stability. This is done by reducing the arcing time which is the time from contact separation to
final extinction of arc. But it will increase extinction voltage. Hence compromise between arcing
time and arc extinction voltage is made.
A.C. Circuit Breaking There is a difference between breaking in case of d c. and ac. circuits. In
ac. circuits the current passes through zero twice in one complete cycle. When the currents are
reduced to zero the beakers are operated to cut-off the current. This will avoid the striking of the
arc. But this conditions is difficult to achieve and very much expensive. The restriking of arc
when current is interrupted is dependent on the voltage between the contact gap at that instant
which will in turn depend on power factor. Higher the power factor, lesser is the voltage
appearing across the gap than its peak value.
In power systems capacitor banks are used in the network which supplies reactive power at
leading power factors there are various aspects like long transmission where it is required
interrupt the capacitive current which is difficult. To understand this difficulty let us consider a
simple circuit shown in the Fig
The value of load capacitance CL is greater than C. The voltage across a capacitor cannot change
instantaneously. The currents supplied to the capacitor are generally small and interruption of
such currents take place at first current zero. Also at the beginning, the rate of rise of recovery
voltage is low and increases slowly. Whenever such circuit is opened a charge is trapped in the
capacitance Ct The voltage across the load capacitance will hold the same value when circuit
was opened. This voltage is making but peak of supply voltage as power factor angle is nearly
90° leading. After opening the circuit the voltage Vc across the capacitance C oscillates and
approaches a new steady value. But due to small value of capacitance C. the value attained is
close to the supply voltage. The recovery voltage Cr is nothing but difference between and CL.
Its initial value is zero as the circuit breaker will be closed and increases slowly in the beginning.
When Vc reverses after half cycle, the recovery voltage is about twice the normal peak value.
Therefore it is possible that at this instant arc may restrike as the electrical strength between the
circuit breaker contacts is not sufficient. The circuit will be reclosed and et oscillates at a high
frequency. The supply voltage at this instant will be at its negative peak; therefore a high
frequency oscillation takes place. At the instant of rest rucking the arc, the recovery voltage V, is
zero. The voltage across the load capacitance reaches - times the peak value of normal supply
voltage. The recovery voltage then starts increasing. If again restriking of arc takes place, a high
frequency of oscillation of CL takes place. Such several repetitions of the restriking cycle will
increase the voltage across load capacitance to a dangerously high value. In practice this voltage
is limited to 4 times the normal peak of the voltage.
Resistance switching
Resistance Switching It can be seen from previous sections that the interruption of low
inductivecurrents, interruption of capacitive currents gWe rise to severe voltage oscillations.
These excessive voltage surges during circuit interruption can be prevented by the use of shunt
resistance R across the circuit breaker contacts. This process is known as Resistance Switching.
When the rtsistance is connected across the arc, a part of the arc current flows through the
resistance. This will lead to decrease in arc current and increase in rate of deionization of the are
path and resistance of arc. This will increase current through shunt resistance . This process
continues until the current through the arc is diverted through the resistance either External 4.---
resistance completely or in major part. If C irt the small value of the current remains in the arc
then the path . A becomes so unstable that it is Fxed Moved switch easily extinguished. contact
contact . The resistance may be automatically switched in and arc current can be transferred. The
time required for this action is very small As shown in.. Fig the arc first appears across points A
and B which is then transferred across A and C. The shunt resistance also ensures the effective
damping of the high frequency re-striking Fig. voltage transients. This is shown in the Fig.
Before the instant of short-circuit, load current will be flowing through the switch and this can be
regarded as zero when compared to the level of fault current that would flow
1.Arc
The arc has three parts: 1. Cathode end (–ve): There is approximately 30–50 V drop due to
emission of electrons.
2. Arc column: Ionized gas, which has a diameter proportional to current. Temperature can be in
the range of 6000–25 000 °C.
When short-circuit occurs, fault current flows, corresponding to the network parameters. The
breaker trips and the current are interrupted at the next natural current zero. The network reacts
by transient oscillations, which gives rise to the transient recovery voltage (TRV) across the
circuit breaker main contacts.
All breaking principles involve the separation of contacts, which initially are bridged by a hot,
highly conductive arcing column. After interruption at current zero, the arcing zone has to be
cooled to such an extent that the TRV is overcome and it cannot cause a voltage breakdown
across the open gap. Three critical phases are distinguished during arc interruption, each
characterized by its own physical processes and interaction between system and breaker.
This consists of highly conductive plasma at a very high temperature corresponding to a low
mass density and an extremely high flow velocity. Proper contact design prevents the existence
of metal vapor in the critical arc region.
Thermal phase
Before current zero, the diameter of the plasma column decreases very rapidly with the decaying
current but remains existent as an extremely thin filament during the passage through current
zero. This thermal phase is characterized by a race between the cooling of the rest of the plasma
and the reheating caused by the rapidly rising voltage. Due to the temperature and velocity
difference between the cool, relatively slow axial flow of the surrounding gas and the rapid flow
in the hot plasma core, vigorous turbulence occurs downstream of the throat, resulting in
effective cooling of the arc. This turbulence is the dominant mechanism, which determines
thermal re-ignition or interruption.
Dielectric phase
After successful thermal interruption, the hot plasma is replaced by a residual column of hot, but
no longer electrically conducting medium. However, due to marginal ion-conductivity, local
distortion of the electrical field distribution is caused by the TRV appearing across the open
break. This effect strongly influences the dielectric strength of the break and has to be taken into
account when designing the geometry of the contact arrangement.