Af-650 Quick Guide (En, Es, De, FR, It)
Af-650 Quick Guide (En, Es, De, FR, It)
Af-650 Quick Guide (En, Es, De, FR, It)
AF-650 GPTM
General Purpose Drive
Quick Guide
Guia rapida
Kurzanleitung
Guide rapide
Guida rapida
The instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be
desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the GE company.
GE
41 Woodford Avenue
Plainville, CT 06062
www.geelectrical.com/drives
DET-758/S/D/F/I
130R0287
*MG34V16S*
Safety AF-650 GP Quick Guide
1 Safety 1 1
WARNING WARNING
UNINTENDED START! Indicates a potentially hazardous situation which, if not
When the adjustable frequency drive is connected to AC avoided, could result in death or serious injury.
line power, the motor may start at any time. The
adjustable frequency drive, motor, and any driven
equipment must be in operational readiness. Failure to be CAUTION
in operational readiness when the adjustable frequency Indicates a potentially hazardous situation which, if not
drive is connected to AC line power could result in death, avoided, may result in minor or moderate injury. It may
serious injury, equipment, or property damage. also be used to alert against unsafe practices.
Unintended Start
When the adjustable frequency drive is connected to the
CAUTION
Indicates a situation that may result in equipment or
AC line power, the motor may be started by means of an
property damage-only accidents.
external switch, a serial bus command, an input reference
signal, or a cleared fault condition. Use appropriate
precautions to guard against an unintended start. NOTE
Indicates highlighted information that should be observed
WARNING in order to avoid mistakes or operate equipment at less
DISCHARGE TIME! than optimal performance.
Adjustable frequency drives contain DC link capacitors that
can remain charged even when AC line power is discon- Approvals
nected. To avoid electrical hazards, remove AC line power
from the adjustable frequency drive before doing any
service or repair and wait the amount of time specified in
Table 1.1. Failure to wait the specified time after power has
been removed prior to doing service or repair on the unit
could result in death or serious injury.
DET-759A 1
Introduction AF-650 GP Quick Guide
2 Introduction
2 2
NOTE
Please consult the AF-650 GP Instruction Manual for other unit sizes.
2 DET-759A
Installation AF-650 GP Quick Guide
3 Installation
• Keep the drive interior free from dust and dirt. • Top and bottom clearance for air cooling must be
Ensure that the components stay as clean as provided. Generally, 4–10 in [100–225 mm] is
possible. In construction areas, provide a required. See Illustration 3.1 for clearance
protective covering. Optional IP54 (NEMA 12) requirements
enclosures may be necessary. • Improper mounting can result in overheating and
• Keep the manual, drawings, and diagrams reduced performance.
accessible for detailed installation and operation • Derating for temperatures starting between 104°F
instructions. It is important that the manual is [40°C]) and 122°F [50°C] and elevation 3,300 ft
available for equipment operators. [1,000 m] above sea level must be considered.
• Locate equipment as near to the motor as See the equipment Design Guide for detailed
possible. Keep motor cables as short as possible. information.
Check the motor characteristics for actual
tolerances. Do not exceed
DET-759A 3
Installation AF-650 GP Quick Guide
3.3.2 Lifting
Item A is a backplate properly installed for required airflow
• Check the weight of the unit to determine a safe
lifting method to cool the unit.
3.3.3 Mounting
4 DET-759A
Installation AF-650 GP Quick Guide
• After power has been applied, checking input and motor power; programming control terminals for their intended
functions
A=Analog, D=Digital
Terminal 37 is used for Safe Stop. For Safe Stop installation instructions, refer to the Design Guide.
*The brake chopper factory option must be ordered to use dynamic braking resistors.
**This is available when ordering the brake chopper option on unit size 23 and above drives.
DET-759A 5
Installation AF-650 GP Quick Guide
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous.
3 3 All electrical work must conform to national and local
electrical codes. It is strongly recommended that instal-
lation, start-up, and maintenance be performed only by
trained and qualified personnel. Failure to follow these
guidelines could result in death or serious injury.
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in three
separate metallic conduits or use separated shielded cable Illustration 3.5 Fuses
for high frequency noise isolation. Failure to isolate power,
motor and control wiring could result in less than
optimum adjustable frequency drive and associated Wire Type and Ratings
equipment performance.
• All wiring must comply with local and national
regulations regarding cross-section and ambient
For your safety, comply with the following requirements. temperature requirements.
• All adjustable frequency drives must be provided • A dedicatedground wire is required for input
with short-circuit and overcurrent protection. power, motor power and control wiring
Input fusing is required to provide this
protection, see Illustration 3.5. Fuses must be
• Use the clamps provided with on the equipment
for proper ground connections
6 DET-759A
Installation AF-650 GP Quick Guide
DET-759A 7
Installation AF-650 GP Quick Guide
Actual configurations vary with unit types and optional 3.4.5 Control Wiring
equipment.
• Isolate control wiring from high power
components in the adjustable frequency drive.
8 DET-759A
Installation AF-650 GP Quick Guide
DET-759A 9
Installation AF-650 GP Quick Guide
Correct shielding
• It is important to confirm that the control
terminal is programmed for the correct function.
The preferred method in most cases is to secure control
See 5 User Interface for details on accessing
and serial communication cables with shielding clamps
parameters and for details on programming.
provided at both ends to ensure best possible high
frequency cable contact.
10 DET-759A
Installation AF-650 GP Quick Guide
130BT310.10
The information and instructions of the instruction manual
are not sufficient for a proper and safe use of the safe stop
Illustration 3.13 Location of Terminals 53 and 54 Switches and functionality. The related information and instructions of
Bus Termination Switch the relevant Design Guide must be followed.
DET-759A 11
Installation AF-650 GP Quick Guide
12 DET-759A
Installation AF-650 GP Quick Guide
3 3
Illustration 3.15 Installation to Achieve a Stopping Category 0 (EN 60204-1) with Safety Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1).
DET-759A 13
Installation AF-650 GP Quick Guide
14 DET-759A
Start Up and Functional Tes... AF-650 GP Quick Guide
4.1 Pre-start
4.1.1 Safety Inspection
WARNING 4 4
HIGH VOLTAGE!
If input and output connections have been connected
improperly, there is potential for high voltage on these
terminals. If power leads for multiple motors are
improperly run through the same conduit, there is a
potential for leakage current to charge capacitors within
the drive, even when disconnected from line power input.
For initial start-up, make no assumptions about power
components. Follow pre-start procedures. Failure to follow
pre-start procedures could result in personal injury or
damage to equipment.
DET-759A 15
Start Up and Functional Tes... AF-650 GP Quick Guide
CAUTION
Before applying power to the unit, inspect the entire installation as detailed in Table 4.1. Check mark those items when
completed.
• Check function and installation of any sensors used for feedback to the drive.
Cable routing • Ensure that input power, motor wiring, and control wiring are separated or in
three separate metallic conduits for high frequency noise isolation.
Control wiring • Check for broken or damaged wires and loose connections.
• Check that control wiring is isolated from power and motor wiring for noise
immunity.
• The use of shielded cable or twisted pair is recommended. Ensure that the
shield is terminated correctly.
Cooling clearance • Measure to make sure that the top and bottom clearance is adequate to
ensure proper airflow for cooling.
Environmental considerations • See equipment label for the maximum ambient operating temperature limits.
Fusing and circuit breakers • Check for proper fusing or circuit breakers.
• Check that all fuses are inserted firmly and in operational condition and that all
circuit breakers are in the open position.
Grounding • The unit requires a ground wire from its chassis to the building ground.
• Check for good ground connections that are tight and free of oxidation.
• Check that motor and line power are in separate conduits or separated
shielded cables.
Panel interior • Inspect to ensure that the unit interior is free of dirt, metal chips, moisture, and
corrosion.
Switches • Ensure that all switch and disconnect settings are in the proper positions.
Vibration • Check that the unit is mounted solidly or that shock mounts are used, as
necessary.
16 DET-759A
Start Up and Functional Tes... AF-650 GP Quick Guide
Adjustable frequency drives require basic operational This concludes the quick set-up procedure. Press [Status]
programming prior to running for best performance. Basic to return to the operational display.
operational programming requires entering motor
nameplate data for the motor being operated and the
4.4 Auto Tune
minimum and maximum motor speeds. Enter data in
accordance with the following procedure. Parameter Auto tune is a test procedure that measures the electrical
settings recommended are intended for start-up and characteristics of the motor to optimize compatibility
checkout purposes. Application settings may vary. See between the drive and the motor.
5 User Interface for detailed instructions on entering data
through the Keypad. • The drive builds a mathematical model of the
motor for regulating output motor current. The
procedure also tests the input phase balance of
Enter data with power ON, but prior to operating the electrical power. It compares the motor character-
adjustable frequency drive. istics with the data entered in parameters P-0#.
1. Press [Quick Menu] on the Keypad. • It does not cause the motor to run or harm to
the motor
2. Use the navigation keys to scroll to Quick Start
and press [OK].
DET-759A 17
Start Up and Functional Tes... AF-650 GP Quick Guide
• Some motors may be unable to run the complete 3. Note any acceleration problems.
version of the test. In that case, select Reduced 4. Press [OFF].
Auto Tune
5. Note any deceleration problems.
• If an output filter is connected to the motor,
select Reduced Auto Tune. If acceleration problems were encountered
1. Press [Hand].
2. Accelerate the drive by pressing [▲] to full speed.
Moving the cursor left of the decimal point
provides quicker input changes.
18 DET-759A
Start Up and Functional Tes... AF-650 GP Quick Guide
1. Press [Auto].
2. Ensure that external control functions are
properly wired to the drive and all programming
completed.
3. Apply an external run command.
4. Adjust the speed reference throughout the speed
range.
5. Remove the external run command.
6. Note any problems.
4 4
If warnings or alarms occur, see 7 Warnings and Alarm.
DET-759A 19
User Interface AF-650 GP Quick Guide
5 User Interface
NOTE
The display contrast can be adjusted by pressing [STATUS]
and the up/down key.
a. Display area.
b. Display menu keys for changing the display to
show status options, programming, or error
message history.
c. Navigation keys for programming functions,
moving the display cursor, and speed control in
local operation. Also included are the status
indicator lights.
d. Operational mode keys and reset.
20 DET-759A
User Interface AF-650 GP Quick Guide
DET-759A 21
User Interface AF-650 GP Quick Guide
Key Function
Hand Press to start the drive in local control.
• Use the navigation keys to control drive
speed
22 DET-759A
User Interface AF-650 GP Quick Guide
DET-759A 23
User Interface AF-650 GP Quick Guide
5 5
24 DET-759A
6.1.1 Main Menu F-11 Motor External Fan E-24 Function Relay C-23 Quick Stop Decel Time H-52 Min Speed Normal Magnetizing [Hz]
Structure F-12 Motor Thermistor Input E-26 On Delay, Relay C-24 Quick Stop Ramp Type H-53 Model Shift Frequency
F-18 Motor Speed Low Limit [RPM] E-27 Off Delay, Relay C-25 Quick Stop S-ramp Ratio at Decel. Start H-54 Voltage reduction in fieldweakening
F-16 Motor Speed Low Limit [Hz] E-3# X46 Digital Inputs C-26 Quick Stop S-ramp Ratio at Decel. End H-55 U/f Characteristic - U
Keypad Set-up F-17 Motor Speed High Limit [RPM] E-30 Terminal X46/1 Digital Input C-3# Frequ. Set. 2 and 3 H-56 U/f Characteristic - F
K-0# Keypad Basic Set. F-15 Motor Speed High Limit [Hz] E-31 Terminal X46/3 Digital Input C-30 Frequency Command 2 H-58 Flystart Test Pulses Current
K-01 Language F-2# Fundamental 2 E-32 Terminal X46/5 Digital Input C-34 Frequency Command 3 H-59 Flystart Test Pulses Frequency
K-02 Motor Speed Unit F-24 Holding Time E-33 Terminal X46/7 Digital Input P-## Motor Data H-6# Load Depend. Settings
K-03 Regional Settings F-25 Start Function E-34 Terminal X46/9 Digital Input P-0# Motor Data H-61 High Speed Load Compensation
K-04 Operating State at Power-up F-22 Start Speed [RPM] E-35 Terminal X46/11 Digital Input P-07 Motor Power [kW] H-64 Resonance Dampening
K-09 Performance Monitor F-23 Start Speed [Hz] E-36 Terminal X46/13 Digital Input P-02 Motor Power [HP] H-65 Resonance Dampening Time Constant
K-1# Keypad Set-up Ops F-29 Start Current E-5# I/O Mode / Add On I/O P-03 Motor Current H-66 Min. Current at Low Speed
Parameter Menu Structure
K-10 Active Set-up F-26 Motor Noise (Carrier Freq) E-51 Terminal 27 Mode P-06 Base Speed H-7# Adj. Warnings
K-11 Edit Set-up F-27 Motor Tone Random E-52 Terminal 29 Mode P-05 Motor Cont. Rated Torque H-70 Warning Current Low
K-12 This Set-up Linked to F-28 Dead Time Compensation E-53 Terminal X30/2 Digital Input P-04 Auto Tune H-71 Warning Current High
K-13 Readout: Linked Set-ups F-3# Fundamental 3 E-54 Terminal X30/3 Digital Input P-01 Motor Poles H-72 Warning Speed Low
K-14 Readout: Edit Set-ups / Channel F-37 Adv. Switching Pattern E-55 Terminal X30/4 Digital Input P-09 Slip Compensation H-73 Warning Speed High
K-2# Keypad Display F-38 Overmodulation E-56 Term X30/6 Digi Out (OPCGPIO) P-10 Slip Compensation Time Constant H-74 Warning Reference Low
K-20 Display Line 1.1 Small F-4# Fundamental 4 E-57 Term X30/7 Digi Out (OPCGPIO) P-2# Motor Selection H-75 Warning Reference High
K-21 Display Line 1.2 Small F-40 Torque Limiter (Driving) E-6# Pulse Input P-20 Motor Construction H-76 Warning Feedback Low
K-22 Display Line 1.3 Small F-41 Torque Limiter (Braking) E-60 Term. 29 Low Frequency P-3# Adv. Motor Data H-77 Warning Feedback High
K-23 Display Line 2 Large F-43 Current Limit E-61 Term. 29 High Frequency P-30 Stator Resistance (Rs) H-78 Missing Motor Phase Function
K-24 Display Line 3 Large F-5# Extended References E-62 Term. 29 Low Ref./Feedb. Value P-31 Rotor Resistance (Rr) H-8# Stop Adjustments
K-25 Quick Start F-50 Reference Range E-63 Term. 29 High Ref./Feedb. Value P-33 Stator Leakage Reactance (X1) H-87 Load Type
K-3# Keypad Custom Readout F-51 Reference/Feedback Unit E-64 Pulse Filter Time Constant #29 P-34 Rotor Leakage Reactance (X2) H-88 Minimum Inertia
K-30 Unit for Custom Readout F-52 Minimum Reference E-65 Term. 33 Low Frequency P-35 Main Reactance (Xh) H-89 Maximum Inertia
K-31 Min Value of Custom Readout F-53 Maximum Reference E-66 Term. 33 High Frequency P-36 Iron Loss Resistance (Rfe) H-80 Function at Stop
K-32 Max Value of Custom Readout F-54 Reference Function E-67 Term. 33 Low Ref./Feedb. Value P-37 d-axis Inductance (Ld) H-81 Min Speed for Function at Stop [RPM]
K-37 Display Text 1 F-6# References E-68 Term. 33 High Ref./Feedb. Value H-## High Perf Parameters H-82 Min Speed for Function at Stop [Hz]
K-38 Display Text 2 F-62 Catch up/slow-down value E-69 Pulse Filter Time Constant #33 H-0# High Perf Operations H-83 Precise Stop Function
K-39 Display Text 3 F-64 Preset Relative Reference E-7# Pulse Output H-09 Start Mode H-84 Precise Stop Counter Value
DET-759A
K-4# Keypad Buttons F-68 Relative Scaling Reference Resource E-70 Terminal 27 Pulse Output Variable H-07 Accel/Decel Time 1 Type H-85 Precise Stop Speed Compensation
AF-650 GP Quick Guide
K-40 [Hand] Button on Keypad F-9# Digital Potentiometer E-72 Pulse Output Max Freq #27 H-08 Reverse Lock Delay
K-41 [Off] Button on Keypad F-90 Step Size E-73 Terminal 29 Pulse Output Variable H-04 Auto-Reset (Times) H-9# Motor Temperature
K-42 [Auto] Button on Keypad F-91 Accel/Decel Time E-75 Pulse Output Max Freq #29 H-05 Auto-Reset (Reset Interval) H-95 KTY Sensor Type
K-43 [Reset] Button on Keypad F-92 Power Restore E-76 Terminal X30/6 Pulse Output Variable H-03 Restore Factory Settings H-96 KTY Thermistor Input
K-44 [Off/Reset] Key on Keypad F-93 Maximum Limit E-78 Pulse Output Max Freq #X30/6 H-2# Motor Feedback Monitoring H-97 KTY Threshold level
K-5# Copy/Save F-94 Minimum Limit E-8# 24V Encoder Input H-20 Motor Feedback Loss Function AN-## Analog In / Out
K-50 Keypad Copy F-95 Accel/Decel Ramp Delay E-80 Term 32/33 Pulses Per Revolution H-21 Motor Feedback Speed Error AN-0# Analog I/O Mode
K-51 Set-up Copy E-## Digital In/Out E-81 Term 32/33 Encoder Direction H-22 Motor Feedback Loss Timeout AN-00 Live Zero Timeout Time
K-6# Password Protect. E-0# Digital Inputs E-9# Bus Controlled H-24 Tracking Error Function AN-01 Live Zero Timeout Function
K-60 Main Menu Password E-00 Digital I/O Mode E-90 Digital & Relay Bus Control H-25 Tracking Error AN-1# Analog Input 53
K-61 Access to Main Menu w/o Password E-01 Terminal 18 Digital Input E-93 Pulse Out #27 Bus Control H-26 Tracking Error Timeout AN-10 Terminal 53 Low Voltage
K-65 Quick Menu Password E-02 Terminal 19 Digital Input E-94 Pulse Out #27 Timeout Preset H-27 Tracking Error Ramping AN-11 Terminal 53 High Voltage
K-66 Access to Quick Menu w/o Password E-03 Terminal 27 Digital Input E-95 Pulse Out #29 Bus Control H-28 Tracking Error Ramping Timeout AN-12 Terminal 53 Low Current
K-67 Bus Password Access E-04 Terminal 29 Digital Input E-96 Pulse Out #29 Timeout Preset H-29 Tracking Error After Ramping Timeout AN-13 Terminal 53 High Current
Parameter Data Set E-05 Terminal 32 Digital Input E-97 Pulse Out #X30/6 Bus Control H-4# Advanced Settings AN-14 Terminal 53 Low Ref./Feedb. Value
F-## Fundamental Params E-06 Terminal 33 Digital Input E-98 Pulse Out #X30/6 Timeout Preset H-40 Configuration Mode AN-15 Terminal 53 High Ref./Feedb. Value
F-0# Fundamental 0 E-07 Terminal 37 Safe Stop C-## Freq Ctrl Functions H-41 Motor Control Principle AN-16 Terminal 53 Filter Time Constant
F-05 Motor Rated Voltage E-1# Additional Accel Decel Ramps C-0# Freq Ctrl Functions H-42 Flux Motor Feedback Source AN-2# Analog Input 54
F-04 Base Frequency E-10 Accel Time 2 C-05 Multi-step Frequency 1 - 8 H-43 Torque Characteristics AN-20 Terminal 54 Low Voltage
F-09 Torque Boost E-11 Decel Time 2 C-02 Jump Speed From [RPM] H-44 Constant or Variable Torque OL AN-21 Terminal 54 High Voltage
F-02 Operation Method E-12 Accel Time 3 C-01 Jump Frequency From [Hz] H-45 Local Mode Configuration AN-22 Terminal 54 Low Current
F-01 Frequency Setting 1 E-13 Decel Time 3 C-03 Jump Speed To [RPM] H-48 Clockwise Direction AN-23 Terminal 54 High Current
F-07 Accel Time 1 E-14 Accel Time 4 C-04 Jump Frequency To [Hz] H-46 Back EMF at 1000 RPM AN-24 Terminal 54 Low Ref./Feedb. Value
F-08 Decel Time 1 E-15 Decel Time 4 C-2# Jog Setup H-47 Motor Angle Offset AN-25 Terminal 54 High Ref./Feedb. Value
F-03 Max Output Frequency 1 E-2# Digital Output C-20 Jog Speed [Hz] H-5# Load Indep. Settings AN-26 Terminal 54 Filter Time Constant
F-1# Fundamental 1 E-20 Terminal 27 Digital Output C-21 Jog Speed [RPM] H-50 Motor Magnetization at Zero Speed AN-3# Analog Input X30/11
F-10 Electronic Overload E-21 Terminal 29 Digital Output C-22 Jog Accel/Decel Time H-51 Min Speed Normal Magnetizing [RPM] AN-30 Terminal X30/11 Low Voltage
25
6 6
6 6
AN-31 Terminal X30/11 High Voltage SP-43 Motor Cos Phi O-10 Control Word Profile DN-31 Store Data Values EN-20 Control Instance
26
AN-34 Term. X30/11 Low Ref./Feedb. Value SP-5# Environment O-13 Configurable Status Word STW DN-32 Devicenet Revision EN-21 Process Data Config Write
AN-35 Term. X30/11 High Ref./Feedb. Value SP-50 RFI Filter O-14 Configurable Control Word CTW DN-33 Store Always EN-22 Process Data Config Read
AN-36 Term. X30/11 Filter Time Constant SP-51 DC Link Compensation O-3# Drive Port Settings DN-34 DeviceNet Product Code EN-28 Store Data Values
AN-4# Analog Input X30/12 SP-52 Fan Operation O-30 Protocol DN-39 Devicenet F Parameters EN-29 Store Always
AN-40 Terminal X30/12 Low Voltage SP-53 Fan Monitor O-31 Address DN-5# DeviceNet Proc Data EN-3# EtherNet/IP
AN-41 Terminal X30/12 High Voltage SP-55 Output Filter O-32 Drive Port Baud Rate PB-## Profibus EN-30 Warning Parameter
AN-44 Term. X30/12 Low Ref./Feedb. Value SP-56 Capacitance Output Filter O-33 Drive port parity K-11 Edit Set-up EN-31 Net Reference
AN-45 Term. X30/12 High Ref./Feedb. Value SP-57 Inductance Output Filter O-34 Estimated cycle time PB-00 Setpoint EN-32 Net Control
AN-46 Term. X30/12 Filter Time Constant SP-59 Actual Number of Inverter Units O-35 Minimum Response Delay PB-07 Actual Value EN-33 CIP Revision
AN-5# Analog Output 42 SP-6# Automatic Derate O-36 Max Response Delay PB-15 PCD Write Configuration EN-34 CIP Product Code
AN-50 Terminal 42 Output SP-63 Option Supplied by External 24VDC O-37 Max Inter-Char Delay PB-16 PCD Read Configuration EN-35 EDS Parameter
Parameter Menu Structure
AN-51 Terminal 42 Output Min Scale SP-7# Add ACC/DEC settings O-4# Drive MC Port Set. PB-18 Node Address EN-37 COS Inhibit Timer
AN-52 Terminal 42 Output Max Scale SP-71 Accel Time 1 S-ramp Ratio at Accel. O-40 Telegram Selection PB-22 Telegram Selection EN-38 COS Filter
AN-53 Terminal 42 Output Bus Control Start O-41 Parameters for Signals PB-23 Parameters for Signals EN-4# Modbus TCP
AN-54 Terminal 42 Output Timeout Preset SP-72 Accel Time 1 S-ramp Ratio at Accel. O-42 PCD Write Configuration PB-27 Parameter Edit EN-40 Status Parameter
AN-55 Terminal 42 Output Filter End O-43 PCD Read Configuration PB-28 Process Control EN-41 Slave Message Count
AN-6# Analog Output X30/8 SP-73 Decel Time 1 S-ramp Ratio at Decel. O-5# Digital / Bus PB-44 Fault Message Counter EN-42 Slave Exception Message Count
AN-60 Terminal X30/8 Output Start O-50 Coasting Select PB-45 Fault Code EN-8# Other Ethernet Services
AN-61 Terminal X30/8 Min. Scale SP-74 Decel Time 1 S-ramp Ratio at Decel. O-51 Quick Stop Select PB-47 Fault Number EN-80 FTP Server
AN-62 Terminal X30/8 Max. Scale End O-52 DC Brake Select PB-52 Fault Situation Counter EN-81 HTTP Server
AN-63 Terminal X30/8 Bus Control SP-76 Accel/Decel Time 2 Type O-53 Start Select PB-53 Profibus Warning Word EN-82 SMTP Service
AN-64 Terminal X30/8 Output Timeout Preset SP-79 Accel Time 2 S-ramp Ratio at Accel. O-54 Reversing Select PB-63 Actual Baud Rate EN-89 Transparent Socket Channel Port
AN-7# Analog Output X45/1 Start O-55 Set-up Select PB-64 Device Identification EN-9# Advanced Ethernet Services
AN-70 Terminal X45/1 Output SP-80 Accel Time 2 S-ramp Ratio at Accel. O-56 Preset Reference Select PB-65 Profile Number EN-90 Cable Diagnostic
AN-71 Terminal X45/1 Min. Scale End O-57 Profidrive OFF2 Select PB-67 Control Word 1 EN-91 MDI-X
AN-72 Terminal X45/1 Max. Scale SP-81 Decel Time 2 S-ramp Ratio at Decel. O-58 Profidrive OFF3 Select PB-68 Status Word 1 EN-92 IGMP Snooping
AN-73 Terminal X45/1 Bus Control Start O-8# Drive Port Diagns PB-71 Profibus Save Data Values EN-93 Cable Error Length
AN-74 Terminal X45/1 Output Timeout Preset SP-82 Decel Time 2 S-ramp Ratio at Decel. O-80 Bus Message Count PB-72 ProfibusDriveReset EN-94 Broadcast Storm Protection
AN-8# Analog Output X45/3 End O-81 Bus Error Count PB-80 Defined Parameters (1) EN-95 Broadcast Storm Filter
AN-80 Terminal X45/3 Output SP-84 Accel/Decel Ramp 3 Type O-82 Slave Messages Rcvd PB-81 Defined Parameters (2) EN-96 Port Mirroring
AN-81 Terminal X45/3 Min. Scale SP-87 Accel Time 3 S-ramp Ratio at Accel. O-83 Slave Error Count PB-82 Defined Parameters (3) EN-98 Interface Counters
AF-650 GP Quick Guide
DET-759A
AN-82 Terminal X45/3 Max. Scale Start O-9# Bus Jog / Feedback PB-83 Defined Parameters (4) EN-99 Media Counters
AN-83 Terminal X45/3 Bus Control SP-88 Accel Time 3 S-ramp Ratio at Accel. O-90 Bus Jog 1 Speed PB-84 Defined Parameters (5) EC-## Feedback Option
AN-84 Terminal X45/3 Output Timeout Preset End O-91 Bus Jog 2 Speed PB-90 Changed Parameters (1) EC-1# Inc. Enc. Interface
SP-## Special Functions SP-89 Decel Time 3 S-ramp Ratio at Decel. DN-## Devicenet serial communication bus PB-91 Changed Parameters (2) EC-10 Signal Type
SP-0# Fault Settings Start DN-0# Common Settings PB-92 Changed Parameters (3) EC-11 Resolution (PPR)
SP-00 Fault Level SP-90 Decel Time 3 S-ramp Ratio at Decel. DN-00 DeviceNet Protocol PB-93 Changed parameters (4) EC-2# Abs. Enc. Interface
SP-1# Line On/Off End DN-01 Baud Rate Select PB-94 Changed parameters (5) EC-20 Protocol Selection
SP-10 Line failure SP-92 Accel/Decel Ramp 4 Type DN-02 MAC ID PB-99 Profibus Revision Counter EC-21 Resolution (Positions/Rev)
SP-11 Line Voltage at Input Fault SP-95 Accel Time 4 S-ramp Ratio at Accel. DN-05 Readout Transmit Error Counter EN-## Ethernet IP EC-24 SSI Data Length
SP-12 Function at Line Imbalance Start DN-06 Readout Receive Error Counter EN-0# IP Settings EC-25 Clock Rate
SP-13 Line Failure Step Factor SP-96 Accel Time 4 S-ramp Ratio at Accel. DN-07 Readout Bus Off Counter EN-00 IP Address Assignment EC-26 SSI Data Format
SP-2# Reset Functions End DN-1# DeviceNet EN-01 IP Address EC-34 HIPERFACE Baud rate
SP-23 Typecode Setting SP-97 Decel Time 4 S-ramp Ratio at Decel. DN-10 Process Data Type Selection EN-02 Subnet Mask EC-6# Monitoring and App.
SP-24 Trip Delay at Current Limit Start DN-11 Process Data Config Write EN-03 Default Gateway EC-60 Feedback Direction
SP-25 Trip Delay at Torque Limit SP-98 Decel Time 4 S-ramp Ratio at Decel. DN-12 Process Data Config Read EN-04 DHCP Server EC-61 Feedback Signal Monitoring
SP-26 Trip Delay at Drive Fault End DN-13 Warning Parameter EN-05 Lease Expires RS-## Resolver Interface
SP-28 Production Settings O-## Options / Comms DN-14 Net Reference EN-06 Name Servers RS-50 Poles
SP-29 Service Code O-0# General Settings DN-15 Net Control EN-07 Domain Name RS-51 Input Voltage
SP-3# Current Limit Ctrl. O-01 Control Site DN-18 internal_process_data_config_write EN-08 Host Name RS-52 Input Frequency
SP-30 Current Limit Cntrl, Proportional Gain O-02 Control Word Source DN-19 internal_process_data_config_read EN-09 Physical Address RS-53 Transformation Ratio
SP-31 Current Limit Cntrl, Integration Time O-03 Control Word Timeout Time DN-2# COS Filters EN-1# Ethernet Link Parameters RS-59 Resolver Interface
SP-32 Current Lim Ctrl, Filter Time O-04 Control Word Timeout Function DN-20 COS Filter 1 EN-10 Link Status Parameter Data Check
SP-35 Stall Protection O-05 End-of-Timeout Function DN-21 COS Filter 2 EN-11 Link Duration Last 10 Changes
SP-4# Energy Savings O-06 Reset Control Word Timeout DN-22 COS Filter 3 EN-12 Auto Negotiation Since Factory Setting
SP-40 VT Level O-07 Diagnosis Trigger DN-23 COS Filter 4 EN-13 Link Speed Drive Information
SP-41 Energy Savings Min. Magnetization O-08 Readout Filtering DN-3# Parameter Access EN-14 Link Duplex ID-0# Operating Data
SP-42 Energy Savings Min. Frequency O-1# Control Settings DN-30 Array Index EN-2# Process Data ID-00 Operating Hours
ID-01 Running Hours DR-1# Motor Status DR-86 Drive Port REF 1 PI-## PID Controls SF-09 Wobble Random Function
ID-02 kWh Counter DR-10 Power [kW] 99-30 internal_ProfibusPCD_Config_Write PI-0# Speed PID Control SF-10 Wobble Ratio
ID-03 Power-ups DR-11 Power [hp] 99-31 internal_ProfibusPCD_Config_Read PI-00 Speed PID Feedback Source SF-11 Wobble Random Ratio Max.
ID-04 Over Temps DR-12 Motor Voltage DR-9# Diagnosis Readouts PI-03 Speed PID Integral Time SF-12 Wobble Random Ratio Min.
ID-05 Over Volts DR-13 Frequency DR-90 Alarm Word PI-04 Speed PID Differentiation Time SF-19 Wobble Delta Freq. Scaled
ID-06 Reset kWh Counter DR-14 Motor Current DR-91 Alarm Word 2 PI-05 Speed PID Diff. Gain Limit SF-2# Adv. Start Adjust
ID-07 Reset Running Hours Counter DR-15 Frequency [%] DR-92 Warning Word PI-06 Speed PID Low-pass Filter Time SF-20 High Starting Torque Time [s]
ID-1# Data Trending Settings DR-16 Torque [Nm] DR-93 Warning Word 2 PI-07 Speed PID Feedback Gear Ratio SF-21 High Starting Torque Current [%]
ID-10 Trending Source DR-17 Speed [RPM] DR-94 Ext. Status Word PI-08 Speed PID Feed Forward Factor SF-22 Locked Rotor Protection
ID-11 Trending Interval DR-18 Motor Thermal Adv Param Data Set PI-02 Speed PID Proportional Gain SF-23 Locked Rotor Detection Time [s]
ID-12 Trigger Event DR-19 KTY sensor temperature LC-## Logic Controller PI-1# Torque PI Ctrl.
ID-13 Trending Mode DR-20 Motor Angle LC-0# LC Settings PI-12 Torque PI Proportional Gain
Parameter Menu Structure
ID-14 Samples Before Trigger DR-21 Torque [%] High Res. LC-00 Logic Controller Mode PI-13 Torque PI Integration Time
ID-2# Historic Log DR-22 Torque [%] LC-01 Start Event PI-2# Process PID Feedback
ID-20 Historic Log: Event DR-25 Torque [Nm] High LC-02 Stop Event PI-20 Process CL Feedback 1 Resource
ID-21 Historic Log: Value DR-3# Drive Status LC-03 Reset Logic Controller PI-22 Process CL Feedback 2 Resource
ID-22 Historic Log: Time DR-30 DC Link Voltage LC-1# Comparators PI-3# Process PID Control
ID-3# Alarm Log DR-32 Brake Energy /s LC-10 Comparator Operand PI-30 Process PID Normal/ Inverse Control
ID-30 Fault Log: Error Code DR-33 Brake Energy /2 min LC-11 Comparator Operator PI-31 Process PID Anti Windup
ID-31 Fault Log: Value DR-34 Heatsink Temp. LC-12 Comparator Value PI-32 Process PID Start Speed
ID-32 Fault Log: Time DR-35 Drive Thermal LC-2# Timers PI-33 Process PID Proportional Gain
ID-4# Drive Identification DR-36 Drive Nominal Current LC-20 Logic Controller Timer PI-34 Process PID Integral Time
ID-40 Drive Type DR-37 Drive Max. Current LC-4# Logic Rules PI-35 Process PID Differentiation Time
ID-41 Power Section DR-38 Logic Controller State LC-40 Logic Rule Boolean 1 PI-36 Process PID Diff. Gain Limit
ID-42 Voltage DR-39 Control Card Temp. LC-41 Logic Rule Operator 1 PI-38 Process PID Feed Forward Factor
ID-43 Software Version DR-40 Trending Buffer Full LC-42 Logic Rule Boolean 2 PI-39 On Reference Bandwidth
ID-46 GE Product No. DR-41 Keypad Bottom Statusline LC-43 Logic Rule Operator 2 PI-4# Adv. Process PID I
ID-47 Power Card Ordering No. DR-49 Current Fault Source LC-44 Logic Rule Boolean 3 PI-40 Process PID I-part Reset
ID-48 Keypad ID Number DR-5# Ref. & Feedb. LC-5# States PI-41 Process PID Output Neg. Clamp
ID-49 SW ID Control Card DR-50 External Reference LC-51 Logic Controller Event PI-42 Process PID Output Pos. Clamp
ID-50 SW ID Power Card DR-51 Pulse Reference LC-52 Logic Controller Action PI-43 Process PID Gain Scale at Min. Ref.
DET-759A
ID-51 Drive Serial Number DR-52 Feedback [Unit] B-## Braking Functions PI-44 Process PID Gain Scale at Max. Ref.
AF-650 GP Quick Guide
ID-53 Power Card Serial Number DR-53 Digi Pot Reference B-0# DC Brake PI-45 Process PID Feed Fwd Resource
ID-6# Option Ident DR-6# Inputs & Outputs B-00 DC Hold Current PI-46 Process PID Feed Fwd Normal/ Inv.
ID-60 Option Mounted DR-60 Digital Input B-01 DC Brake Current Ctrl.
ID-61 Option SW Version DR-61 Terminal 53 Switch Setting B-02 DC Braking Time PI-49 Process PID Output Normal/ Inv. Ctrl.
ID-62 Option Ordering No DR-62 Analog Input 53 B-03 DC Brake Cut-in Speed [RPM] PI-5# Adv. Process PID II
ID-63 Option Serial No DR-63 Terminal 54 Switch Setting B-04 DC Brake Cut-in Speed [Hz] PI-50 Process PID Extended PID
ID-70 Option in Slot A DR-64 Analog Input 54 B-05 Maximum Reference PI-51 Process PID Feed Fwd Gain
ID-71 Slot A Option SW Version DR-65 Analog Output 42 [mA] B-1# Brake Energy Funct. PI-52 Process PID Feed Fwd Ramp-up
ID-72 Option in Slot B DR-66 Digital Output [bin] B-10 Brake Function PI-53 Process PID Feed Fwd Ramp-down
ID-73 Slot B Option SW Version DR-67 Freq. Input #29 [Hz] B-12 Braking energy (kW) PI-56 Process PID Ref. Filter Time
ID-74 Option in Slot C1 DR-68 Freq. Input #33 [Hz] B-13 Braking Thermal Overload PI-57 Process PID Fb. Filter Time
ID-75 Slot C0 Option SW Version DR-69 Pulse Output #27 [Hz] B-15 Brake Check PI-6# PID Readouts
ID-76 Option in Slot C2 DR-70 Pulse Output #29 [Hz] B-16 AC brake Max. Current PI-60 Process PID Error
ID-77 Slot C1 Option SW Version DR-71 Relay Output [bin] B-17 Over-voltage Control PI-61 Process PID Output
ID-9# Parameter Info DR-72 Counter A B-18 Brake Check Condition PI-62 Process PID Clamped Output
ID-92 Defined Parameters DR-73 Counter B B-19 Over-voltage Gain PI-63 Process PID Gain Scaled Output
ID-93 Modified Parameters DR-74 Prec. Stop Counter B-11 Brake Resistor (ohm) SF-## Special Features
ID-98 Drive Identification DR-75 Analog In X30/11 B-2# Mechanical Brake SF-0# Wobbler
ID-99 Parameter Metadata DR-76 Analog In X30/12 B-20 Release Brake Current SF-00 Wobble Mode
Data Readouts DR-77 Analog Out X30/8 [mA] B-21 Activate Brake Speed [RPM] SF-01 Wobble Delta Frequency [Hz]
DR-0# General Status DR-78 Analog Out X45/1 [mA] B-22 Activate Brake Speed [Hz] SF-02 Wobble Delta Frequency [%]
DR-00 Control Word DR-79 Analog Out X45/3 [mA] B-23 Activate Brake Delay SF-03 Wobble Delta Freq. Scaling Resource
DR-01 Reference [Unit] DR-8# Serial communication bus & Drive Port B-24 Stop Delay SF-04 Wobble Jump Frequency [Hz]
DR-02 Reference % DR-80 Serial communication bus CTW 1 B-25 Brake Release Time SF-05 Wobble Jump Frequency [%]
DR-03 Status Word DR-82 Serial communication bus REF 1 B-26 Torque Ref SF-06 Wobble Jump Time
DR-05 Main Actual Value [%] DR-84 Comm. Option STW B-27 Torque Ramp Time SF-07 Wobble Sequence Time
DR-09 Custom Readout DR-85 Drive Port CTW 1 B-28 Gain Boost Factor SF-08 Wobble Up/Down Time
27
6 6
Parameter Menu Structure AF-650 GP Quick Guide
28 DET-759A
Warnings and Alarm AF-650 GP Quick Guide
• Auto reset
Trip lock
An alarm that causes the drive to trip-lock requires that
input power be cycled. The motor will coast to a stop. The
drive logic will continue to operate and monitor the drive
status. Remove input power to the drive and correct the
cause of the fault, then restore power. This action puts the
drive into a trip condition as described above and may be
reset in any of those four ways.
Warn. LED Alarm LED
Warning ON OFF
Alarm OFF ON (Flashing)
Trip Lock ON ON (Flashing)
DET-759A 29
Warnings and Alarm AF-650 GP Quick Guide
30 DET-759A
Warnings and Alarm AF-650 GP Quick Guide
DET-759A 31
Warnings and Alarm AF-650 GP Quick Guide
7 7
32 DET-759A
Specifications AF-650 GP Quick Guide
8 Specifications
DET-759A 33
Specifications AF-650 GP Quick Guide
2) See 3.4.5.7 Terminal 37 for further information about terminal 37 and Safe Stop.
8 8 Analog inputs:
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Switch S201 and switch S202
Voltage mode Switch S201/switch S202 = OFF (U)
Voltage level -10 to +10 V (scaleable)
Input resistance, Ri approx. 10 kΩ
Max. voltage ± 20V
Current mode Switch S201/switch S202 = ON (I)
Current level 0/4 to 20 mA (scaleable)
Input resistance, Ri approx. 200 Ω
Max. current 30 mA
Resolution for analog inputs 10 bit (+ sign)
Accuracy of analog inputs Max. error 0.5% of full scale
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Pulse/encoder inputs:
Programmable pulse/encoder inputs 2/1
Terminal number pulse/encoder 29, 331) / 322), 332)
Max. frequency at terminal 29, 32, 33 110 kHz (push-pull driven)
Max. frequency at terminal 29, 32, 33 5 kHz (open collector)
Min. frequency at terminal 29, 32, 33 4Hz
Voltage level see 8.1.1 Digital Inputs:
34 DET-759A
Specifications AF-650 GP Quick Guide
DET-759A 35
Specifications AF-650 GP Quick Guide
Relay outputs:
Programmable relay outputs 2 Form C
Relay 01 Terminal number 1-3 (break), 1-2 (make)
Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 (NO) (Resistive load) 240V AC, 2A
Max. terminal load (AC-15)1) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 (NC) (Resistive load) 60V DC, 1A
Max. terminal load (DC-13)1) (Inductive load) 24 V DC, 0.1A
Relay 02 Terminal number 4-6 (break), 4-5 (make)
Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load)2)3) Overvoltage cat. II 400V AC, 2A
Max. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load) 80V DC, 2A
Max. terminal load (DC-13)1) on 4-5 (NO) (Inductive load) 24 V DC, 0.1A
Max. terminal load (AC-1)1) on 4-6 (NC) (Resistive load) 240V AC, 2A
Max. terminal load (AC-15)1) on 4-6 (NC) (Inductive load @ cosφ 0.4) 240V AC, 0.2A
Max. terminal load (DC-1)1) on 4-6 (NC) (Resistive load) 50V DC, 2A
Max. terminal load (DC-13)1) on 4-6 (NC) (Inductive load) 24 V DC, 0.1A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24V DC 10mA, 24V AC 20mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
8 8 2) Overvoltage Category II
36 DET-759A
Specifications AF-650 GP Quick Guide
Environment:
Vibration test 1.0 g
Max. relative humidity 5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H2S test class Kd
Ambient temperature Max. 122°F [50°C]
1) Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation 32°F [0°C]
Minimum ambient temperature at reduced performance 14°F [-10°C]
Temperature during storage/transport -13°- +149°/158°F [-25°- +65°/70°C]
Maximum altitude above sea level without derating 3,280 ft [1,000 m]
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
EMC standards, Immunity EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions in the AF-650 GP Design Guide.
Protection and Features:
• Temperature monitoring of the heatsink ensures that the drive trips if the temperature reaches a predefined level.
An overload temperature cannot be reset until the temperature of the heatsink is below the values stated in the
tables on the following pages (guideline - these temperatures may vary for different power sizes, unit sizes,
8 8
enclosure ratings, etc.).
• If a line phase is missing, the drive trips or issues a warning (depending on the load).
• Monitoring of the intermediate circuit voltage ensures that the drive trips if the intermediate circuit voltage is too
low or too high.
• The drive constantly checks for critical levels of internal temperature, load current, high voltage on the
intermediate circuit and low motor speeds. As a response to a critical level, the drive can adjust the switching
frequency and/ or change the switching pattern in order to ensure the performance of the drive.
DET-759A 37
Installation AF-650 GP Quick Guide
9 Installation
9.1.1 Fuses
It is recommended to use fuses and/ or circuit breakers on the supply side as protection in case of component break-down
inside the drive (first fault).
NOTE
This is mandatory in order to ensure compliance with IEC 60364 for CE or NEC 2009 for UL.
WARNING
Personnel and property must be protected against the consequence of internal component break-down in the drive.
NOTE
The recommendations given do not cover branch circuit protection for UL.
Short-circuit protection:
9 9 GE recommends using the fuses/circuit breakers mentioned below to protect service personnel and property in case of
component break-down in the drive.
Overcurrent protection:
The drive provides overload protection to limit threats to human life, property damage and to avoid fire hazard due to
overheating of the cables in the installation. The drive is equipped with an internal overcurrent protection (4-18 Current
Limit) that can be used for upstream overload protection (UL applications excluded). Moreover, fuses or circuit breakers can
be used to provide the overcurrent protection in the installation. Overcurrent protection must always be provided in
accordance with national regulations.
WARNING
In case of malfunction, not following the recommendation may result in personnel risk and damage to the drive and other
equipment.
The following tables list the recommended rated current. Recommended fuses are of the type gG for small to medium
power sizes. For larger powers, aR fuses are recommended. Circuit breakers must be used provided they meet the national/
international regulations and they limit the energy into the drive to an equal or lower level than the compliant circuit
breakers.
If fuses/circuit breakers are chosen according to recommendations, possible damage to the drive will be limited to damage
mainly within the unit.
9.1.2 CE Compliance
Fuses or circuit breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the drive voltage rating. With the proper fusing, the drive short circuit current rating (SCCR) is
100,000 Arms.
38 DET-759A
Installation AF-650 GP Quick Guide
DET-759A 39
Installation AF-650 GP Quick Guide
40 DET-759A
Installation AF-650 GP Quick Guide
DET-759A 41
Installation AF-650 GP Quick Guide
9 9 15 / 20
18.5 / 25
gG-32 gG-63
22 / 30 gG-40
30 / 40 gG-80
gG-63
37 / 50 gG-100
45 / 60 gG-80 gG-125
55 / 75 gG-100
gG-160
75 / 100 gG-125
90 / 125 aR-250 aR-250
110 / 150 aR-315 aR-315
132 / 200
aR-350 aR-350
160 / 250
200 / 300 aR-400 aR-400
250 / 350 aR-500 aR-500
315 / 400 aR-550 aR-550
355 / 500
aR-700 aR-700
400 / 550
500 / 650
aR-900 aR-900
560 / 750
630 / 900
710 / 1000
aR-1600 aR-1600
800 / 1150
900 / 1250
1000 / 1350 aR-2000 aR-2000
Table 9.7 525–690V. IP21 / Nema 1 and IP55 / Nema 12 and IP66 / Nema 4
42 DET-759A
Installation AF-650 GP Quick Guide
Fuses or circuit breakers are mandatory to comply with NEC 2009. We recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 600V
depending on the drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
DET-759A 43
Installation AF-650 GP Quick Guide
1) KTS fuses from Bussmann may substitute KTN for 240 V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute FWX for 240 V adjustable frequency drives.
9 9 3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V adjustable frequency drives.
44 DET-759A
Installation AF-650 GP Quick Guide
AF-650 GP Bussmann
Recommended max. fuse
Ferraz-Shawmut Ferraz-Shawmut Littel fuse
9 9
[kW] / [HP] JFHR2 J JFHR21) JFHR2
0.37-0.75 / FWH-6 HSJ-6 - -
0.5-1
1.5-2.2 / FWH-10 HSJ-10 - -
2-3
3.7 / 5 FWH-20 HSJ-20 - -
5.5 / 7.5 FWH-25 HSJ-25 - -
7.5 / 10 FWH-30 HSJ-30 - -
11 / 15 FWH-40 HSJ-40 - -
15 / 20 FWH-50 HSJ-50 - -
18.5 / 25 FWH-60 HSJ-60 - -
22 / 30 FWH-80 HSJ-80 - -
30 / 40 FWH-100 HSJ-100 - -
37 / 50 FWH-125 HSJ-125 - -
45 / 60 FWH-150 HSJ-150 - -
55 / 75 FWH-200 HSJ-200 A50-P-225 L50-S-225
75 / 100 FWH-250 HSJ-250 A50-P-250 L50-S-250
DET-759A 45
Installation AF-650 GP Quick Guide
1)170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator
fuses of the same size and amperage may be substituted.
46 DET-759A
Installation AF-650 GP Quick Guide
9 9
DET-759A 47
Installation AF-650 GP Quick Guide
48 DET-759A
Installation AF-650 GP Quick Guide
**Any minimum 500V UL listed fuse with associated current rating may be used to meet UL requirements.
DET-759A 49
0 10
50
Power [kW / HP] Enclosur Line power Motor Load share Brake Ground *
e
Tightening Tightenin Tightening Tightening Tightening
Wire size Wire size Wire size Wire size
torque g torque torque torque torque
200–240V 380–480V 525–600V 525–690V [mm2 [mm2 [mm2 [mm2
[Nm / in- [Nm / in- [Nm / in- [Nm / in- [Nm / in-
(AWG)] (AWG)] (AWG)] (AWG)]
10.1 Cables
lbs] lbs] lbs] lbs] lbs]
0.25–2.2kW 0.37–4kW 0.75–4kW
IP20
0.33–3HP 0.5–5HP 1–5HP
5.5–7.5kW 5.5–7.5kW
3.7kW 5HP IP20 4 (10) 4 (10) 4 (10) 4 (10)
7.5–10HP 7.5–10HP
Terminal and Applicable Wir...
1.8 / 16 1.8 / 16
0.25–3.7kW 0.37–7.5kW 0.75–7.5kW IP55 or
1.8 / 16 1.8 / 16
0.33–5HP 0.5–10HP 1–10HP IP66
5.5–7.5kW 11–15kW 11–15kW
IP20
7.5–10HP 15–20HP 15–20HP
16 (6) 16 (6) 16 (6) 16 (6)
5.5–7.5kW 11–15kW 11–15kW IP55 or
1.5 / 14 1.5 / 14
7.5–10HP 15–20HP 15–20HP IP66
11–15kW 18.5–30kW 18.5–30kW
IP20 4.5 / 40 4.5 / 40 3 / 27
15–20HP 25–40HP 25–40HP
4.5 / 40 35 (2) 4.5 / 40 35 (2) 35 (2) 35 (2)
11kW 18.5–22kW 18.5–22kW 11–22kW 15– IP55 or
3.7 / 33 3.7 / 33
15HP 25–30HP 25–30HP 30HP IP66
18.5–22kW 37–45kW 37–45kW
IP20 50 (1) 50 (1) 50 (1) 50 (1)
10 Terminal and Applicable Wire
DET-759A
40–50HP 75–100HP 75–100HP mcm) mcm)
14 / 124 14 / 124 14 / 124 14 / 124
30–37kW 55–75kW 55–75kW 30–75kW 40– IP55 or
120 (4/0) 120 (4/0) 120 (4/0) 120 (4/0)
40–50HP 75–100HP 75–100HP 100HP IP66
90–110kW 90–132kW 2x70
all 2x70 (2x2/0) 2x70 (2x2/0) 2x70 (2x2/0)
125–150HP 125–200HP (2x2/0)
9.5 / 84 2x185
132–200kW 160–315kW 2x185 2x185
all (2x350mcm
200–350HP 250–400HP (2x350mcm) (2x350mcm)
) 2x185
4x240 (2x350mcm)
250–400kW 355–560kW 4x240 4x240
all 19 / 168 19 / 168 (4x500mcm 9.5 / 84 19 / 168
350–550HP 500–750HP (4x500mcm) (4x500mcm)
)
450–630kW 630–800kW 8x150 4x185
all 19 / 168
600–900HP 900–1150HP (8x300mcm) 4x120 (4x350mcm)
8x240
710–800kW 900–1000kW 12x150 (4x250mcm
(8x500mcm) 6x185
1000– 1250– all (12x300mcm )
(6x350mcm)
1200HP 1350HP )
* Maximum cable size according to national code
Seguridad Guía rápida del AF-650 GP
1 Seguridad 1 1
DET-758A/S 1
Seguridad Guía rápida del AF-650 GP
1 1 ADVERTENCIA
Indica situaciones potencialmente peligrosas que, si no se
evitan, pueden producir lesiones graves e incluso la
muerte.
PRECAUCIÓN
Indica una situación potencialmente peligrosa que, si no se
evita, puede producir lesiones leves o moderadas. También
puede utilizarse para alertar contra prácticas inseguras.
PRECAUCIÓN
Indica una situación que puede producir accidentes que
dañen únicamente al equipo o a otros bienes.
¡NOTA!
Indica información destacada que debe tenerse en cuenta
para evitar errores o utilizar el equipo con un rendimiento
inferior al óptimo.
Homologaciones
2 DET-758A/S
Introducción Guía rápida del AF-650 GP
2 Introducción
2 2
¡NOTA!
Consulte el manual de funcionamiento del AF-650 GP para otros tamaños.
DET-758A/S 3
Instalación Guía rápida del AF-650 GP
3 Instalación
• Guarde el manual, los dibujos y los diagramas a • Se requiere un espacio libre por encima y por
debajo para la refrigeración por aire.
mano para contar con instrucciones de
Generalmente, son necesarios 100-225 mm
instalación y funcionamiento detalladas. Es
(4-10 in). Consulte en la Ilustración 3.1 los
importante que el manual esté disponible para el
requisitos de espacio.
operador del equipo.
• Coloque el equipo lo más cerca posible del • Un montaje incorrecto puede provocar un
sobrecalentamiento y disminuir el rendimiento.
motor. Los cables del motor deben ser lo más
cortos que sea posible. Compruebe las caracte- • Debe tenerse en cuenta la reducción de potencia
rísticas del motor para averiguar las tolerancias para temperaturas entre 40 °C (104 °F) y 50 °C
actuales. No deben superarse los siguientes (122 °F) y una elevación de 1000 m (3300 ft)
valores: sobre el nivel del mar. Consulte la Guía de Diseño
del equipo para obtener más detalles.
• 300 m (1000 ft) para cables del motor
no apantallados.
4 DET-758A/S
Instalación Guía rápida del AF-650 GP
3.3.2 Elevación
El elemento A es una placa posterior instalada correc-
• Compruebe el peso de la unidad para determinar
un método de elevación seguro. tamente para que circule el flujo de aire necesario para
refrigerar la unidad.
• Asegúrese de que el dispositivo de elevación es
idóneo para la tarea.
3.3.3 Montaje
DET-758A/S 5
Instalación Guía rápida del AF-650 GP
• Después de aplicar potencia, comprobación de la potencia del motor y de entrada y programación de los
terminales de control según sus funciones previstas.
A = analógico, D = digital
El terminal 37 se utiliza para la parada de seguridad. Para ver las instrucciones sobre la instalación de parada de seguridad,
consulte la Guía de Diseño.
*Debe pedirse la opción de fábrica del chopper de frenado para utilizar resistencias de freno dinámicas
**Se encuentra disponible al pedir la opción del chopper de frenado de los convertidores de frecuencia de tamaño 23 y
superiores.
6 DET-758A/S
Instalación Guía rápida del AF-650 GP
PRECAUCIÓN
AISLAMIENTO DEL CABLEADO
Coloque el cableado de control, la potencia de entrada y el
cableado del motor en tres conductos metálicos indepen-
dientes o utilice cables apantallados separados para el
aislamiento del ruido de alta frecuencia. Si no se aísla el
cableado de control, de potencia y del motor, podría
reducirse el rendimiento óptimo del convertidor de
frecuencia y del equipo asociado.
DET-758A/S 7
Instalación Guía rápida del AF-650 GP
• Se necesita un cable de puesta a tierra específico 3.4.2.2 Puesta a tierra con un cable
para el cableado de control, de la potencia de apantallado
entrada y de potencia del motor.
• Utilice las abrazaderas suministradas con el Se suministran abrazaderas de conexión a tierra para el
equipo para una correcta conexión a tierra. cableado del motor (véase la Ilustración 3.6).
• Dos cables de toma de tierra separados • Consulte los tamaños de cable máximos en
conformes con las normas de dimensionamiento Tabla 10.1
Consulte el apartado 543.7 de la norma EN 60364-5-54 • Observe los códigos eléctricos locales y
para obtener más información. nacionales en las dimensiones de los cables.
8 DET-758A/S
Instalación Guía rápida del AF-650 GP
• Conecte el cableado del motor trifásico a los • Todos los convertidores de frecuencia pueden
terminales 96 (U), 97 (V) y 98 (W). utilizarse con una fuente de entrada aislada, así
como con líneas de alimentación con conexión a
• Ponga a tierra el cable según las instrucciones de
tierra. Si la alimentación proviene de una fuente
conexión a tierra.
de red aislada (red eléctrica IT o triángulo
• Apriete los terminales de acuerdo con la flotante) o de redes TT / TN-S con toma de tierra
información indicada en . (triángulo de puesta a tierra), desconecte
• Observe los requisitos de cableado del fabricante 14-50 Filtro RFI (póngalo en OFF). En la posición
del motor. OFF, los condensadores de filtro RFI internos que
hay entre el chasis y el circuito intermedio se
La Ilustración 3.7 representa la entrada de red, motor y
aíslan para evitar dañar al circuito intermedio y
toma de tierra para convertidores de frecuencia básicos.
reducir las corrientes capacitivas a tierra según
Las configuraciones actuales pueden variar según los tipos
CEI 61800-3.
de unidades y el equipo opcional.
DET-758A/S 9
Instalación Guía rápida del AF-650 GP
3 3
10 DET-758A/S
Instalación Guía rápida del AF-650 GP
DET-758A/S 11
Instalación Guía rápida del AF-650 GP
3 3
Como método alternativo, puede omitirse la conexión al
terminal 61:
Apantallamiento correcto
3.4.5.5 Funciones del terminal de control
En la mayoría de los casos, el método preferido consiste en
fijar los cables de control y comunicación serie con
Las funciones del Convertidor de frecuencia se efectúan a
abrazaderas de pantallas en ambos extremos para
través de las señales de entrada de control.
garantizar el mejor contacto posible con el cable de alta
frecuencia. • Cada terminal debe programarse para la función
Si el potencial de tierra entre el convertidor de frecuencia que va a asistir en los parámetros asociados con
y el PLC es distinto, puede producirse ruido eléctrico que ese terminal. Consulte en la Tabla 3.2 los
perturbará todo el sistema. Resuelva este problema terminales y los parámetros asociados.
instalando un cable ecualizador junto al cable de control.
• Es importante confirmar que el terminal de
Sección transversal mínima del cable: 16 mm2. control está programado para la función correcta.
Consulte en 5 Interfaz de usuario los detalles para
acceder a los parámetros y en , los detalles de
programación.
Evite el ruido de CEM en la comunicación serie • Configure los conmutadores A53 y A54 para
seleccionar el tipo de señal. U selecciona la
Este terminal se conecta a tierra mediante un enlace RC
tensión; I selecciona la intensidad.
interno. Utilice cables de par trenzado a fin de reducir la
interferencia entre conductores. El método recomendado • Puede accederse a los conmutadores cuando se
se muestra a continuación: ha retirado el Teclado (véase la Ilustración 3.13).
Tenga en cuenta que algunas tarjetas de opción
disponibles con la unidad podrían cubrir estos
conmutadores y, por tanto, es necesario quitarlas
para cambiar la configuración de los
conmutadores. Desconecte siempre la alimen-
12 DET-758A/S
Instalación Guía rápida del AF-650 GP
DET-758A/S 13
Instalación Guía rápida del AF-650 GP
14 DET-758A/S
Instalación Guía rápida del AF-650 GP
3 3
Ilustración 3.15 Instalación para conseguir una parada de categoría 0 (EN 60204-1) con categoría de seguridad 3 (EN 954-1) / PL «d» (ISO
13849-1).
DET-758A/S 15
Instalación Guía rápida del AF-650 GP
16 DET-758A/S
Arranque y pruebas de funci... Guía rápida del AF-650 GP
ADVERTENCIA 4 4
¡ALTA TENSIÓN!
Si las conexiones de entrada y salida se han conectado
incorrectamente, existe la posibilidad de que pase alta
tensión por estos terminales. Si los cables de potencia para
motores múltiples discurren incorrectamente por el mismo
conducto, existe la posibilidad de que la corriente de fuga
cargue los condensadores dentro del convertidor de
frecuencia, incluso estando desconectado de la entrada de
red. Para el arranque inicial, no dé nada por sentado sobre
los componentes de potencia. Siga los procedimientos
previos al arranque. Si no sigue estos procedimientos
previos al arranque podrían provocarse lesiones personales
o daños al equipo.
DET-758A/S 17
Arranque y pruebas de funci... Guía rápida del AF-650 GP
PRECAUCIÓN
Antes de aplicar potencia a la unidad, inspeccione toda la instalación tal y como se indica en la Tabla 4.1. Marque los
elementos una vez los haya inspeccionado.
Inspeccionar Descripción ☑
Equipo auxiliar • Busque los equipos auxiliares, conmutadores, desconectores, fusiblesde entrada
4 4 o magnetotérmicos que pueda haber en el lado de la potencia de entrada del
convertidor de frecuencia o en el de salida al motor. Asegúrese de que están
listos para un funcionamiento a máxima velocidad.
Recorrido de los cables • Asegúrese de que la potencia de entrada, el cableado del motor y el cableado
de control están separados o van por tres conductosmetálicos independientes
para el aislamiento del ruido de alta frecuencia.
Cableado de control • Compruebe que no existan cables rotos o dañados ni conexiones flojas.
Espacio libre para la refrige- • Realice las mediciones necesarias para comprobar que la zona despejada por
ración encima y por debajo es adecuada para garantizar el flujo de aire correcto para
su refrigeración.
Consideraciones sobre CEM • Compruebe que la instalación es correcta en cuanto a compatibilidad electro-
magnética.
• Compruebe que todos los fusibles estén bien insertados y en buen estado, y
que todos los magnetotérmicos estén en la posición abierta.
Toma de tierra • La unidad requiere un cable de conexión a tierra desde su chasis hasta la toma
de tierra de la planta.
• Compruebe que las conexiones a tierra son buenas y están bien apretadas y
libres de óxido.
Interior del panel • Compruebe que el interior de la unidad está libre de suciedad, virutas
metálicas, humedad y corrosión.
18 DET-758A/S
Arranque y pruebas de funci... Guía rápida del AF-650 GP
Inspeccionar Descripción ☑
Vibración • Compruebe que la unidad está montada de manera sólida, o bien sobre
soportes que amortigüen los golpes, en caso necesario.
DET-758A/S 19
Arranque y pruebas de funci... Guía rápida del AF-650 GP
8. Introduzca los requisitos de aplicación para 4a. Compruebe que el motor gira en sentido
4-13 Límite alto veloc. motor [RPM] o 4-14 Límite horario.
alto veloc. motor [Hz]. 5a. Compruebe que la flecha de dirección del
9. Introduzca los requisitos de aplicación para Teclado apunta hacia la derecha.
4-11 Límite bajo veloc. motor [RPM] o 4-12 Límite Cuando H-48 Clockwise Direction está ajustado en [1]
bajo veloc. motor [Hz]. Inversa (en sentido antihorario):
10. Ajuste 4-10 Dirección veloc. motor en sentido 4b. Compruebe que el motor gira en sentido
horario, en sentido antihorario o en ambas antihorario.
4 4 direcciones. 5b. Compruebe que la flecha de dirección del
11. En 1-29 Adaptación automática del motor (AMA) Teclado apunta hacia la izquierda.
seleccione Autoajuste reducido o Autoajuste
completo y siga las instrucciones de la pantalla.
Consulte 4.4 Autoajuste
4.6 Prueba de control local
Así concluye el procedimiento de configuración rápida.
Pulse [Status] (Estado) para volver al display de
PRECAUCIÓN
operaciones. ARRANQUE DEL MOTOR
Asegúrese de que el motor, el sistema y cualquier equipo
conectado están listos para arrancar. Es responsabilidad del
4.4 Autoajuste usuario garantizar un funcionamiento seguro bajo
cualquier circunstancia operativa. De lo contrario, podrían
El Autoajuste es un procedimiento de prueba que mide las
provocarse lesiones graves o daños al equipo.
características eléctricas del motor para optimizar la
compatibilidad entre el convertidor de frecuencia y el
motor. ¡NOTA!
La tecla Hand (Manual) del Teclado proporciona un
• El convertidor de frecuencia se basa en un
comando de arranque local para el convertidor de
modelo matemático para regular la intensidad del
frecuencia. La tecla [OFF] es la función de parada.
motor de salida. El procedimiento también
Cuando se funciona en modo local, las flechas arriba y
somete a prueba el equilibrio de la fase de
abajo en el Teclado aumentan o disminuyen la salida de
entrada de la potencia eléctrica y compara las
velocidad del convertidor de frecuencia. Las teclas de
características del motor con los datos
flecha de izquierda y derecha mueven el cursor por el
introducidos en los parámetros P-0#.
display numérico.
• Esto no hace que el motor funcione y tampoco lo
daña. 1. Pulse [Hand].
• Algunos motores pueden no ser capaces de 2. Acelere el convertidor de frecuencia pulsando [▲]
ejecutar toda la versión de la prueba. En ese caso, hasta la velocidad máxima. Si se mueve el cursor
seleccione Autoajuste reducido. a la izquierda de la coma decimal, se consiguen
• Si hay un filtro de salida conectado al motor, efectuar los cambios de entrada más
seleccione Autoajuste reducido. rápidamente.
20 DET-758A/S
Arranque y pruebas de funci... Guía rápida del AF-650 GP
¡NOTA!
Los apartados de 4.1 Arranque previo a 4.6 Prueba de
control local de este capítulo concluyen los procedimientos
para aplicar potencia al convertidor de frecuencia, la
programación básica, el arranque y las pruebas de funcio-
namiento.
PRECAUCIÓN
ARRANQUE DEL MOTOR
Asegúrese de que el motor, el sistema y cualquier equipo
conectado están listos para arrancar. Es responsabilidad del
usuario garantizar un funcionamiento seguro bajo
cualquier circunstancia operativa. De lo contrario, podrían
provocarse lesiones graves o daños al equipo.
1. Pulse [Auto].
2. Asegúrese de que las funciones de control
externo están correctamente conectadas al
convertidor de frecuencia y que toda la progra-
mación está completada.
3. Aplique un comando de ejecución externo.
4. Ajuste la referencia de velocidad en todo el
intervalo de velocidad.
5. Elimine el comando de ejecución externo.
6. Observe cualquier problema.
Si se producen advertencias o alarmas, consulte
7 Advertencias y alarmas.
DET-758A/S 21
Interfaz de usuario Guía rápida del AF-650 GP
5 Interfaz de usuario
¡NOTA!
Puede ajustar el contraste del display pulsando [STATUS] y
la tecla arriba / abajo.
22 DET-758A/S
Interfaz de usuario Guía rápida del AF-650 GP
Las teclas del menú se utilizan para acceder al menú para Registro de Muestra una relación de advertencias actuales,
configurar los parámetros, para cambiar entre los modos alarmas las últimas 10 alarmas y el registro de manteni-
del display de estado durante el funcionamiento normal y miento.
para visualizar los datos del registro de fallos. • Para obtener más información sobre el
convertidor de frecuencia antes de que
entrase en el modo de alarma, seleccione el
número de alarma utilizando las teclas de
navegación y pulse [OK] (Aceptar).
DET-758A/S 23
Interfaz de usuario Guía rápida del AF-650 GP
Las teclas de navegación se utilizan para programar Las teclas de funcionamiento están en la parte inferior del
funciones y desplazar el cursor de la pantalla. Las teclas de Teclado.
navegación también permiten el control de velocidad en
funcionamiento (manual) local. En esta área, también se
localizan tres luces indicadoras del estado del convertidor
de frecuencia.
5 5
Tecla Función
Hand Púlsela para arrancar el convertidor de frecuencia
en control local.
• Utilice las teclas de navegación para controlar
la velocidad del convertidor de frecuencia.
24 DET-758A/S
Interfaz de usuario Guía rápida del AF-650 GP
• Los datos pueden cargarse en la memoria del 6. Pulse [Hand] (Manual) o [Auto] (Automático) para
Teclado como copia de seguridad de almacena- volver al funcionamiento normal.
miento.
• Una vez almacenados en el Teclado, los datos 5.3 Restablecimiento de los ajustes
pueden descargarse de nuevo en el convertidor predeterminados
de frecuencia.
DET-758A/S 25
Interfaz de usuario Guía rápida del AF-650 GP
• ID-03 Arranques
• ID-04 Sobretemperat.
• ID-05 Sobretensión
26 DET-758A/S
6.1.1 Estructura del menú F-11 Ventilador externo motor E-24 Relé de función C-03 Velocidad bypass hasta [RPM] H-43 Características de par
principal F-12 Entrada termistor motor E-26 Retardo de conexión, relé C-04 Salto de frecuencia a [Hz] H-44 SC par constante o variable
F-18 Límite bajo veloc. motor [RPM] E-27 Retardo de desconexión, relé C-2# Ajuste Veloc. fija H-45 Configuración modo local
F-16 Límite bajo veloc. motor [Hz] E-3# X46 Entradas digitales C-20 Velocidad fija [Hz] H-48 Dirección en sentido horario
Ajuste teclado F-17 Límite alto veloc. motor [RPM] E-30 Terminal X46 / 1 Entrada digital C-21 Velocidad fija [RPM] H-46 Fuerza contraelectromotriz a 1000 RPM
K-0# Aj. básicos teclado F-15 Límite alto veloc. motor [Hz] E-31 Terminal X46 / 3 Entrada digital C-22 Tiempo veloc. fija acel. / decel. H-47 Desplaz. ángulo motor
K-01 Idioma F-2# Fundamental 2 E-32 Terminal X46 / 5 Entrada digital C-23 Tiempo decel. parada rápida H-5# Ajuste avanz.
K-02 Unidad de velocidad de motor F-24 Tiempo mantenido E-33 Terminal X46 / 7 Entrada digital C-24 Tipo rampa de parada rápida H-50 Magnet. motor a veloc. cero
K-03 Ajustes regionales F-25 Función de arranque E-34 Terminal X46 / 9 Entrada digital C-25 Relación rampa-S parada rápida en H-51 Veloc. mín. con magn. norm. [RPM]
K-04 Estado operación en arranque F-22 Veloc. arranque [RPM] E-35 Terminal X46 / 11 Entrada digital arranque de decel. H-52 Magnetización normal veloc. mín. [Hz]
K-09 Control de rendimiento F-23 Velocidad arranque [Hz] E-36 Terminal X46 / 13 Entrada digital C-26 Rel. rampa-S parada ráp. fin decel. H-53 Modelo despl. de frec.
K-1# Operac. aj. teclado F-29 Intensidad arranque E-5# Modo E / S / E / S adic. C-3# Aj. frecuencia 2 y 3 H-54 Reducción tensión en debilit. campo
K-10 Ajuste activo F-26 Ruido mot (fr port) E-51 Terminal 27 Modo C-30 Comando de frecuencia 2 H-55 Característica u / f - U
K-11 Editar ajuste F-27 Tono motor aleatorio E-52 Terminal 29 Modo C-34 Comando de frecuencia 3 H-56 Característica u / f - F
Estructura de menú de parám...
K-12 Ajuste actual enlazado a F-28 Compensación de tiempo muerto E-53 Terminal X30 / 2 Entrada digital P-## Datos de motor H-58 Intens. imp. prueba con motor en giro
K-13 Lectura: ajustes relacionados F-3# Fundamental 3 E-54 Terminal X30 / 3 Entrada digital P-0# Datos de motor H-59 Frec. imp. prueba con motor en giro
K-14 Lectura: Editar ajustes / canal F-37 Patrón de conmutación avanzado E-55 Terminal X30 / 4 Entrada digital P-07 Potencia motor [kW] H-6# Ajuste depend. de la carga
K-2# Display teclado F-38 Sobremodulación E-56 Sal. dig. term. X30/6 P-02 Potencia motor [CV] H-61 Compensación carga alta velocidad
K-20 Línea de pantalla pequeña 1.1 F-4# Fundamental 4 (OPCGPIO)OPCGPIO) P-03 Intensidad motor H-64 Amortiguación de resonancia
K-21 Línea de pantalla pequeña 1.2 F-40 Limitador de par (funcionam.) E-57 Sal. dig. term. X30/7 (OPCGPIO) P-06 Velocidad básica H-65 Const. tiempo amortigua. de
K-22 Línea de pantalla pequeña 1.3 F-41 Limitador de par (frenado) E-6# Entrada pulsos P-05 Par nominal continuo resonancia
K-23 Línea de pantalla grande 2 F-43 Límite intensidad E-60 Term. 29 baja frecuencia P-04 Autoajuste H-66 Intens. mín. a baja veloc.
K-24 Línea de pantalla grande 3 F-5# Refs ampliadas E-61 Term. 29 alta frecuencia P-01 Polos motor H-7# Ajuste Advert.
K-25 Arranque rápido F-50 Rango de referencia E-62 Term. 29 valor bajo ref. / realim. P-09 Compensación deslizam. H-70 Advert. intens. baja
K-3# Lec. pers. teclado F-51 Referencia / Unidad Realimentación E-63 Term. 29 valor alto ref. / realim. P-10 Tiempo compens. deslizam. constante H-71 Advert. intens. alta
K-30 Unidad para lectura personaliz. F-52 Referencia mínima E-64 Constante de tiempo del filtro de P-2# Selección de motor H-72 Advert. veloc. baja
K-31 Valor mínimo de lectura personalizada F-53 Referencia máxima pulsos #29 P-20 Construcción del motor H-73 Advert. veloc. alta
K-32 Valor máximo de lectura personalizada F-54 Función de referencia E-65 Term. 33 baja frecuencia P-3# Datos avanz. motor H-74 Advertencia referencia baja
K-37 Texto de display 1 F-6# Referencias E-66 Term. 33 alta frecuencia P-30 Resistencia estátor (Rs) H-75 Advertencia referencia alta
K-38 Texto de display 2 F-62 Valor de enganche arriba / abajo E-67 Term. 33 valor bajo ref. / realim. P-31 Resistencia rotor (Rr) H-76 Advertencia realimentación baja
K-39 Texto de display 3 F-64 Referencia interna relativa E-68 Term. 33 valor alto ref. / realim. P-33 Reactancia fuga estátor (X1) H-77 Advertencia realimentación alta
K-4# Botones teclado F-68 Recurso refer. escalado relativo E-69 Constante de tiempo del filtro de P-34 Reactancia de fuga del rotor (X2) H-78 Función falta una fase del motor
DET-758A/S
K-40 Botón [Hand] del teclado F-9# Potencióm. digital pulsos #33 P-35 Reactancia princ. (Xh) H-8# Ajustes de parada
Guía rápida del AF-650 GP
K-41 Botón [Off] del teclado F-90 Tamaño de paso E-7# Salida pulsos P-36 Resistencia pérdida hierro (Rfe) H-87 Tipo de carga
K-42 Botón [Auto] del teclado F-91 Tiempo acel. / decel. E-70 Terminal 27 salida de pulsos variable P-37 Inductancia eje d (Ld) H-88 Inercia mínima
K-43 Botón [Reset] del teclado F-92 Restitución de energía E-72 Frec. máx. salida de pulsos #27 H-## Parám. alto rendim. H-89 Inercia máxima
K-44 Botón [Off / Reset] en el teclado F-93 Límite máximo E-73 Terminal 29 salida de pulsos variable H-0# Func. alto rendim. H-80 Función de parada
K-5# Copiar / Guardar F-94 Límite mínimo E-75 Frec. máx. salida de pulsos #29 H-09 Modo arranque H-81 Vel. mín. para func. parada [RPM]
K-50 Copia teclado F-95 Acel. / decel. retardo de rampa E-76 Terminal X30 / 6 salida de pulsos H-07 Tipo tiempo acel / decel 1 H-82 Vel. mín. para func. parada [Hz]
K-51 Copia de ajuste E-## E / S digital variable H-08 Bloqueo inversión H-83 Función de parada precisa
K-6# Protec. contraseña E-0# Entradas digitales E-78 Frec. máx. salida de pulsos #X30 / 6 H-04 Desc. reinic. autom. H-84 Valor de contador para parada precisa
K-60 Contraseña menú principal E-00 Modo E / S digital E-8# Ent. encoder 24 V H-05 Reinic. autom. (Interv. rein.) H-85 Retardo comp. veloc. parada precisa
K-61 Acceso a menú princ. sin contraseña E-01 Terminal 18 Entrada digital E-80 Term 32 / 33 pulsos por revolución H-03 Rest. aj. de fábrica H-9# Temperatura motor
K-65 Contraseña menú rápido E-02 Terminal 19 Entrada digital E-81 Term. 32 / 33 direc. encoder H-2# Control realim. motor H-95 Tipo de sensor KTY
K-66 Acceso a menú rápido sin contraseña E-03 Terminal 27 Entrada digital E-9# Controlado por bus H-20 Función de pérdida de realim. del H-96 Entrada termistor KTY
K-67 Contraseña acceso al bus E-04 Terminal 29 Entrada digital E-90 Control de bus digital y de relé motor H-97 Nivel del umbral KTY
Datos de parámetros E-05 Terminal 32 Entrada digital E-93 Control de bus salida de pulsos #27 H-21 Error de velocidad en realim. del AN-## E / S analógica
F-## Parámetros fundamentales E-06 Terminal 33 Entrada digital E-94 Tiempo lím. predet. salida pulsos #27 motor AN-0# Modo E / S analógico
F-0# Fundamental 0 E-07 Terminal 37 Parada de seguridad E-95 Control de bus salida de pulsos #29 H-22 Tiempo lím. pérdida realim. del motor AN-00 Tiempo límite de cero activo
F-05 Tens. nominal motor E-1# Ramp acel / decel adic E-96 Tiempo lím. predet. salida pulsos #29 H-24 Func. error de seguimiento AN-01 Función de tiempo límite de cero
F-04 Frecuencia E-10 Tiempo acel. 2 E-97 Control de bus salida de pulsos H-25 Error de seguimiento activo
F-09 Refuerzo de par E-11 Tiempo decel. 2 #X30 / 6 H-26 T. lím. error de seguimiento AN-1# Entrada analógica 53
F-02 Método funcionamiento E-12 Tiempo acel. 3 E-98 Tiempo límite predet. salida pulsos H-27 Error de seguimiento rampa AN-10 Terminal 53 escala baja V
F-01 Ajuste frecuencia 1 E-13 Tiempo decel. 3 #X30 / 6 H-28 T. lím. error de seguimiento rampa AN-11 Terminal 53 escala alta V
F-07 Tiempo acel. 1 E-14 Tiempo acel. 4 C-## Func. control frec. H-29 Error seguim. tras tiempo lím. rampa AN-12 Terminal 53 escala baja mA
F-08 Tiempo decel. 1 E-15 Tiempo decel. 4 C-0# Func. control frec. H-4# Ajustes avanzados AN-13 Terminal 53 escala alta mA
F-03 Frecuencia salida máx. 1 E-2# Salida digital C-05 Frecuencia multiajuste 1 - 8 H-40 Modo Configuración AN-14 Term. 53 valor bajo ref. / realim.
F-1# Fundamental 1 E-20 Terminal 27 Salida digital C-02 Velocidad bypass desde [RPM] H-41 Principio control motor AN-15 Term. 53 valor alto ref. / realim.
F-10 Sobrec electr E-21 Terminal 29 Salida digital C-01 Salto de frecuencia desde [Hz] H-42 Fuente realimentación Flux motor
27
6 6
6 6
AN-16 Terminal 53 Constante del tiempo de SP-2# Funciones de reset SP-96 Rel. tiempo acel. 4 / rampa-S en fin de DN-05 Lectura contador errores transm. PB-93 Parámetros cambiados (4)
28
filtro SP-23 Ajuste de código descriptivo decel. DN-06 Lectura contador errores recepción PB-94 Parámetros cambiados (5)
AN-2# Entrada analógica 54 SP-24 Retardo descon. con lím. de int. SP-97 Rel. tiempo decel. 4 / rampa S en DN-07 Contador de lectura de datos de bus PB-99 Contador revisión de Profibus
AN-20 Terminal 54 escala baja V SP-25 Ret. de desc. con límite de par arranque de decel. desactivado EN-## Ethernet IP
AN-21 Terminal 54 escala alta V SP-26 Ret. de desc. en fallo del convert. SP-98 Rel. tiempo decel. 4 / rampa S en fin DN-1# DeviceNet EN-0# Ajustes de IP
AN-22 Terminal 54 escala baja mA SP-28 Aj. producción de decel. DN-10 Selección tipo de datos proceso EN-00 Asignación de dirección IP
AN-23 Terminal 54 escala alta mA SP-29 Código de servicio O-## Opciones / Comunic. DN-11 Escritura de configuración de datos del EN-01 Dirección IP
AN-24 Term. 54 valor bajo ref. / realim. SP-3# Ctrl. lím. intens. O-0# Ajustes generales proceso EN-02 Máscara de subred
AN-25 Term. 54 valor alto ref. / realim. SP-30 Control lím. intens, ganancia prop. O-01 Puesto de control DN-12 Lectura de configuración de datos del EN-03 Puerta de enlace predet.
AN-26 Terminal 54 Constante del tiempo de SP-31 Control lím. intens., tiempo integración O-02 Fuente de código de control proceso EN-04 Servidor DHCP
filtro SP-32 Control lím. inten., Tiempo de filtro O-03 Valor de tiempo límite cód. ctrl. DN-13 Parámetro de advertencia EN-05 Caducidad de asignación
AN-3# Entrada analógica X30 / 11 SP-35 Protección de bloqueo O-04 Función tiempo límite cód. ctrl. DN-14 Referencia de red EN-06 Servidores de nombres
AN-30 Terminal X30 / 11 Tensión baja SP-4# Ahorro energético O-05 Función Fin de tiempo límite DN-15 Control de red EN-07 Nombre de dominio
AN-31 Terminal X30 / 11 Tensión alta SP-40 Nivel VT O-06 Reiniciar tiempo límite del código DN-18 internal_process_data_config_write EN-08 Nombre de host
Estructura de menú de parám...
AN-34 Term. X30 / 11 valor bajo ref. / realim. SP-41 Ahorro energético Magnetización mín. control DN-19 internal_process_data_config_read EN-09 Dirección física
AN-35 Term. X30 / 11 valor alto ref. / realim. SP-42 Ahorro energético Frecuencia mín. O-07 Accionador diagnóstico DN-2# Filtros de CDE EN-1# Parámetros de enlace Ethernet
AN-36 Term. X30 / 11 Constante del tiempo SP-43 Cosphi del motor O-08 Filtro lectura de datos DN-20 Filtro de CDE 1 EN-10 Estado del vínculo
de filtro SP-5# Ambiente O-1# Ajustes de control DN-21 Filtro de CDE 2 EN-11 Duración del vínculo
AN-4# Ent. analóg. X30 / 12 SP-50 Filtro RFI O-10 Perfil del código de control DN-22 Filtro de CDE 3 EN-12 Negociación automática
AN-40 Terminal X30 / 12 Tensión baja SP-51 Comp. del enlace de CC O-13 Código de estado configurable STW DN-23 Filtro de CDE 4 EN-13 Velocidad del vínculo
AN-41 Terminal X30 / 12 Tensión alta SP-52 Func. ventilador O-14 CTW código de control configurable DN-3# Acceso parám. EN-14 Vínculo Dúplex
AN-44 Term. X30 / 12 valor bajo ref. / realim. SP-53 Monitor del ventilador O-3# Aj. puerto convert. DN-30 Índice Matriz EN-2# Datos de proceso
AN-45 Term. X30 / 12 valor alto ref. / realim. SP-55 Filtro de salida O-30 Protocolo DN-31 Grabar valores de datos EN-20 Instancia de control
AN-46 Term. X30 / 12 Constante del tiempo SP-56 Capacitancia del filtro de salida O-31 Dirección DN-32 Revisión DeviceNet EN-21 Escritura de configuración de datos del
de filtro SP-57 Inductancia del filtro de salida O-32 Veloc. baudios puerto conv. DN-33 Almacenar siempre proceso
AN-5# Salida analógica 42 SP-59 Número real de inversores O-33 Paridad de puerto convert. DN-34 Código de producto DeviceNet EN-22 Lectura de configuración de datos del
AN-50 Terminal 42 Salida SP-6# Reducción autom. O-34 Tiempo de ciclo estimado DN-39 Parámetros Devicenet F proceso
AN-51 Terminal 42 Salida esc. mín. SP-63 Opción sumin. por 24 V CC ext. O-35 Retardo respuesta mín. DN-5# Datos proc DeviceNet EN-28 Grabar valores de datos
AN-52 Terminal 42 Salida esc. máx. SP-7# Aj. adic. acel. / decel. O-36 Retardo respuesta máx. PB-## Profibus EN-29 Almacenar siempre
AN-53 Terminal 42 Control bus de salida SP-71 Rel. tiempo acel. 1 / rampa-S en O-37 Retardo máx. intercarac. K-11 Editar ajuste EN-3# EtherNet / IP
AN-54 Terminal 42 Tiempo lím. salida predet. arranque de decel. O-4# Conf. puerto MC conv PB-00 Valor de consigna EN-30 Parámetro de advertencia
AN-55 Terminal 42 Filtro de salida SP-72 Rel. tiempo acel. 1 / rampa-S en fin de O-40 Selección de telegrama PB-07 Valor real EN-31 Referencia de red
AN-6# Sal. analóg. X30 / 8 decel. O-41 Parámetros para señales PB-15 Config. escritura PCD EN-32 Control de red
DET-758A/S
Guía rápida del AF-650 GP
AN-60 Terminal X30 / 8 Salida SP-73 Rel. Tiempo decel. 1 / Rampa-S en O-42 Config. escritura PCD PB-16 Config. lectura PCD EN-33 Revisión CIP
AN-61 Terminal X30 / 8 Escala mín. arranque de decel. O-43 Config. lectura PCD PB-18 Dirección de nodo EN-34 Código de producto CIP
AN-62 Terminal X30 / 8 Escala máx. SP-74 Rel. Tiempo decel. 1 / Rampa-S en fin O-5# Digital / Bus PB-22 Selección de telegrama EN-35 Parámetro EDS
AN-63 Terminal X30 / 8 Control bus salida de decel. O-50 Selección de funcionamiento por PB-23 Parámetros para señales EN-37 Temporizador de inhibición COS
AN-64 Terminal X30 / 8 Tiempo límite salida SP-76 Tipo tiempo acel / decel 2 inercia PB-27 Editar parámetro EN-38 Filtro de CDE
predet. SP-79 Rel. tiempo acel. 2 / rampa-S en O-51 Selección parada rápida PB-28 Control de proceso EN-4# Modbus TCP
AN-7# Salida analóg. X45 / 1 arranque de decel. O-52 Selección freno de CC PB-44 Recuento de mensajes de fallo EN-40 Parám. de estado
AN-70 Terminal X45 / 1 Salida SP-80 Rel. tiempo acel. 2 / rampa-S en fin de O-53 Selección arranque PB-45 Código de fallo EN-41 Recuento de mensajes de esclavo
AN-71 Terminal X45 / 1 Escala mín. decel. O-54 Selec. sentido inverso PB-47 Número de fallo EN-42 Recuento mensajes de excep. de
AN-72 Terminal X45 / 1 Escala máx. SP-81 Rel. Tiempo decel. 2 / Rampa-S en O-55 Selección ajuste PB-52 Recuento de situaciones de fallo esclavo
AN-73 Terminal X45 / 1 Control bus salida arranque de decel. O-56 Selección referencia interna PB-53 Código de advertencia de Profibus EN-8# Otros servicios Ethernet
AN-74 Ter. X45 / 1 Tiem. lím. salida predet. SP-82 Rel. Tiempo decel. 2 / Rampa-S en fin O-57 Selección Profidrive OFF2 PB-63 Velocidad real en baudios EN-80 Servidor FTP
AN-8# Salida analóg. X45 / 3 de decel. O-58 Selección Profidrive OFF3 PB-64 Id. dispositivo EN-81 Servidor HTTP
AN-80 Terminal X45 / 3 salida SP-84 Tipo rampa acel / decel 3 O-8# Diag. puerto conv. PB-65 Número perfil EN-82 Servicio SMTP
AN-81 Terminal X45 / 3 Escala mín. SP-87 Rel. tiempo acel. 3 / rampa-S en O-80 Recuento de mensajes de bus PB-67 Código de control 1 EN-89 Puerto del canal de enchufe
AN-82 Terminal X45 / 3 Escala máx. arranque de decel. O-81 Recuento de errores de bus PB-68 Código de estado 1 transparente
AN-83 Terminal X45 / 3 Control bus salida SP-88 Rel. tiempo acel. 3 / rampa-S en fin de O-82 Mensajes de esclavo recibidos PB-71 Profibus guarda valores de datos EN-9# Servicios Ethernet avanzados
AN-84 Ter. X45 / 3 Tiem. lím. salida predet. decel. O-83 Recuento de errores de esclavo PB-72 Reiniciar unidad Profibus EN-90 Diagnóstico de cableado
SP-## Func. especiales SP-89 Rel. tiempo decel. 3 / rampa S en O-9# Velocidad fija / Realimentación PB-80 Parámetros definidos (1) EN-91 MDI-X
SP-0# Ajustes de fallo arranque de decel. O-90 Velocidad fija 1 PB-81 Parámetros definidos (2) EN-92 Intrusión IGMP
SP-00 Nivel de fallos SP-90 Rel. tiempo decel. 3 / rampa S en fin O-91 Velocidad fija 2 PB-82 Parámetros definidos (3) EN-93 Long. de cable errónea
SP-1# Línea On / Off de decel. DN-## Bus de c.Devicenet PB-83 Parámetros definidos (4) EN-94 Protección transmisión múltiple
SP-10 Fallo aliment SP-92 Tipo rampa acel / decel 4 DN-0# Ajustes comunes PB-84 Parámetros definidos (5) EN-95 Filtro transmisión múltiple
SP-11 Fallo en entrada tensión de red SP-95 Rel. tiempo acel. 4 / rampa-S en DN-00 Protocolo DeviceNet PB-90 Parámetros cambiados (1) EN-96 Espejo del puerto
SP-12 Función desequil. línea arranque de decel. DN-01 Selecc. veloc. en baudios PB-91 Parámetros cambiados (2) EN-98 Contadores de interfaz
SP-13 Factor medida fallo de red DN-02 ID MAC PB-92 Parámetros cambiados (3) EN-99 Contadores de medios
EC-## Opcs. realim. motor ID-53 N.º de serie de tarjeta de potencia DR-5# Ref. y realim. LC-5# Estados PI-39 Ancho de banda en referencia
EC-1# Inc. Enc. abs. ID-6# Identific. opción DR-50 Referencia externa LC-51 Evento del controlador lógico PI-4# PID de proc. av. I
EC-10 Tipo de señal ID-60 Opción instalada DR-51 Referencia de pulsos LC-52 Acción de controlador lógico PI-40 Reinicio parte I de PID proc.
EC-11 Resolución (PPR) ID-61 Versión de SW de la opción DR-52 Realimentación [Unidad] B-## Funciones de freno PI-41 Abrazadera salida PID de proc. pos.
EC-2# Interfaz encod. abs. ID-62 N.º pedido opción DR-53 Referencia Digi pot B-0# Freno CC PI-42 Abrazadera salida PID de proc. neg.
EC-20 Selección de protocolo ID-63 N.º serie opción DR-6# Entradas y salidas B-00 CC mantenida PI-43 Esc. ganancia PID proc. con ref. mín.
EC-21 Resolución (Posiciones / Rev) ID-70 Opción en ranura A DR-60 Entrada digital B-01 Intens. freno CC PI-44 Esc. ganancia PID proc. con ref. máx.
EC-24 Longitud de datos SSI ID-71 Versión de SW de la opción en ranura DR-61 Terminal 53 ajuste conex. B-02 Tiempo freno CC PI-45 Recurso FF de PID de proceso
EC-25 Velocidad del reloj A DR-62 Entrada analógica 53 B-03 Velocidad activación freno CC [RPM] PI-46 Ctrl. normal / inv. de FF de PID de
EC-26 Formato de datos SSI ID-72 Opción en ranura B DR-63 Terminal 54 ajuste conex. B-04 Velocidad de conexión del freno CC proceso
EC-34 Veloc. baudios HIPERFACE ID-73 Versión de SW de la opción en ranura DR-64 Entrada analógica 54 [Hz] PI-49 Ctrl. normal / inv. salida PID de
EC-6# Ctrl. y aplicación B DR-65 Salida analógica 42 [mA] B-05 Referencia máxima proceso
EC-60 Dirección de realimentación ID-74 Opción en ranura C1 DR-66 Salida digital [bin] B-1# Func. energ. freno PI-5# PID de proc. av. II
EC-61 Control de señal de realimentación ID-75 Versión de SW de la opción en ranura DR-67 Entr. frecuencia n.º 29 [Hz] B-10 Función de freno PI-50 PID de proceso PID ampliado
Estructura de menú de parám...
RS-## Interfaz resolvedor C0 DR-68 Entr. frecuencia n.º 33 [Hz] B-12 Límite potencia de freno (kW) PI-51 Ganancia FF de PID de proc.
RS-50 Polos ID-76 Opción en ranura C2 DR-69 Salida pulsos #27 [Hz] B-13 Sobrecarga térmica de frenado PI-52 Aceleración FF de PID de proceso
RS-51 Tensión de entrada ID-77 Versión de SW de la opción en ranura DR-70 Salida pulsos #29 [Hz] B-15 Comprobación freno PI-53 Deceleración FF de PID de proceso
RS-52 Frecuencia de entrada C1 DR-71 Salida Relé [bin] B-16 Intensidad máx. de frenado de CA PI-56 Tiempo de filtro ref. PID de proc.
RS-53 Relación de transformación ID-9# Inform. parámetro DR-72 Contador A B-17 Control de sobretensión PI-57 Tiempo de filtro realim. PID de proc.
RS-59 Interfaz resolvedor ID-92 Parámetros definidos DR-73 Contador B B-18 Estado comprobación freno PI-6# Lecturas PID
Compr. datos parám. ID-93 Parámetros modificados DR-74 Contador para parada precisa B-19 Ganancia sobretensión PI-60 Error PID proceso
Últimos 10 cambios ID-98 Id. dispositivo DR-75 Entr. analóg. X30 / 11 B-11 Resistencia freno (ohmios) PI-61 Salida PID de proceso
Desde ajuste fábrica ID-99 Metadatos de parámetros DR-76 Entr. analóg. X30 / 12 B-2# Freno mecánico PI-62 Salida grapada PID de proc.
Información convertidor de frecuencia Lecturas de datos DR-77 Salida analógica X30 / 8 [mA] B-20 Intensidad liber. freno PI-63 Salida con ganancia escal. PID de proc.
ID-0# Datos de funcionamiento DR-0# Estado general DR-78 Salida analógica X45 / 1 [mA] B-21 Velocidad activación freno [RPM] SF-## Func. especiales
ID-00 Horas de funcionamiento DR-00 Código de control DR-79 Salida analógica X45 / 3 [mA] B-22 Velocidad activación freno [Hz] SF-0# Vaivén
ID-01 Horas de funcionamiento DR-01 Referencia [Unidad] DR-8# Bus cam+pto. conv. B-23 Activar retardo de freno SF-00 Modo vaivén
ID-02 Contador kWh DR-02 Referencia % DR-80 Bus de campo CTW 1 B-24 Retardo parada SF-01 Frecuencia vaivén [Hz]
ID-03 Encendidos DR-03 estado amp DR-82 Bus de campo REF 1 B-25 Tiempo liberación de freno SF-02 Frecuencia vaivén [%]
ID-04 Sobretemperaturas DR-05 Valor real princ. [%] DR-84 Opción comun. STW B-26 Ref. par SF-03 Recurso escalado de frec. en
ID-05 Sobretensiones DR-09 Lectura personalizada DR-85 Puerto convertidor CTW 1 B-27 Tiempo de rampa de par triángulo de vaivén
ID-06 Reiniciar contador kWh DR-1# Estado motor DR-86 Puerto conv. REF 1 B-28 Factor de ganancia de refuerzo SF-04 Frec. salto vaivén [Hz]
DET-758A/S
ID-07 Reinicio contador de horas funciona- DR-10 Potencia [kW] 99-30 internal_ProfibusPCD_Config_Write PI-## Controles de PID SF-05 Frecuencia escalón vaivén [%]
Guía rápida del AF-650 GP
miento DR-11 Potencia [CV] 99-31 internal_ProfibusPCD_Config_Read PI-0# Contr. PID veloc. SF-06 Tiempo salto vaivén
ID-1# Aj. tendencia datos DR-12 Tensión motor DR-9# Lect. diagnóstico PI-00 Fuente de realim. PID de veloc. SF-07 Tiempo secuencia vaivén
ID-10 Tendencias DR-13 Frecuencia DR-90 Código de alarma PI-03 Tiempo integral PID veloc. SF-08 Tiempo acel. / decel. vaivén
ID-11 Intervalo tendencia DR-14 Intensidad motor DR-91 Código de alarma 2 PI-04 Tiempo diferencial PID veloc. SF-09 Función aleatoria vaivén
ID-12 Acontecimiento de disparo DR-15 Frecuencia [%] DR-92 Cód. de advertencia PI-05 Límite ganancia dif. PID de proceso SF-10 Relación vaivén
ID-13 Modo tendencias DR-16 Par [Nm] DR-93 Código de advertencia 2 PI-06 Tiempo de filtro paso bajo PID veloc. SF-11 Rel. aleatoria vaivén máx.
ID-14 Muestras antes de disparo DR-17 Velocidad [RPM] DR-94 Código de estado ext. PI-07 Relación engranaje realim. PID SF-12 Relación aleatoria vaivén mín.
ID-2# Registro histórico DR-18 Térmico motor Datos parám. avanz. velocidad SF-19 Recurso escalado de frec. en
ID-20 Registro histórico: evento DR-19 Temperatura del sensor KTY LC-## Controlador lógico PI-08 Factor directo de PID de velocidad triángulo de vaivén
ID-21 Registro histórico: realim. DR-20 Ángulo motor LC-0# Ajustes LC PI-02 Ganancia proporc. PID veloc. SF-2# Ajuste arranque avanz.
ID-22 Registro histórico: hora DR-21 Par [%] res. alto LC-00 Modo controlador lógico PI-1# Control de PI de par SF-20 Tiempo par arranque alto [s]
ID-3# Registro alarmas DR-22 Par [%] LC-01 Evento arranque PI-12 Ganancia proporcional PI de par SF-21 Intensidad par arranque alto [%]
ID-30 Registro fallos: código de error DR-25 Par [Nm] alto LC-02 Evento parada PI-13 Tiempo integral PI de par SF-22 Protección rotor bloqueado
ID-31 Registro fallos: valor DR-3# Estado conv. LC-03 Reiniciar contr lógico PI-2# Fuente real PID proc SF-23 Tiempo detección rotor bloqueado [s]
ID-32 Registro fallos: hora DR-30 Tensión Bus CC LC-1# Comparadores PI-20 Fuente 1 realim. lazo cerrado proceso
ID-4# Id. dispositivo DR-32 Energía freno/s LC-10 Operando comparador PI-22 Fuente 2 realim. lazo cerrado proceso
ID-40 Tipo convert. DR-33 Energía freno/2 min LC-11 Operador comparador PI-3# Control PID proceso
ID-41 Sección de alimentación DR-34 Temp. disipador LC-12 Valor comparador PI-30 Ctrl. normal / inverso de PID de
ID-42 Tensión DR-35 Térmico convertidor LC-2# Temporizadores proceso
ID-43 Versión de software DR-36 Intens. nominal convert. LC-20 Temporizador del controlador lógico PI-31 Saturación de PID de proceso
ID-46 N.º producto GE DR-37 Intens. máx. CA LC-4# Reglas lógicas PI-32 Velocidad arranque PID proceso
ID-47 N.º de pedido de tarjeta de potencia DR-38 Estado controlador lógico LC-40 Regla lógica booleana 1 PI-33 Ganancia proporc. PID de proc.
ID-48 Número ID del teclado DR-39 Temp. tarjeta control LC-41 Operador regla lógica 1 PI-34 Tiempo integral PID proc.
ID-49 Tarjeta de control de Id. del SW DR-40 Buffer de registro lleno LC-42 Regla lógica booleana 2 PI-35 Tiempo diferencial PID proc.
ID-50 Tarjeta de potencia de Id. del SW DR-41 Línea estado inf. teclado LC-43 Operador regla lógica 2 PI-36 Límite ganancia dif. PID de proceso
ID-51 Número serie dispos. DR-49 Origen del fallo de intensidad LC-44 Regla lógica booleana 3 PI-38 Factor de proalim. PID de proceso
29
6 6
Estructura de menú de parám... Guía rápida del AF-650 GP
30 DET-758A/S
Advertencias y alarmas Guía rápida del AF-650 GP
7 Advertencias y alarmas
DET-758A/S 31
Advertencias y alarmas Guía rápida del AF-650 GP
32 DET-758A/S
Advertencias y alarmas Guía rápida del AF-650 GP
DET-758A/S 33
Advertencias y alarmas Guía rápida del AF-650 GP
7 7
34 DET-758A/S
Especificaciones Guía rápida del AF-650 GP
8 Especificaciones
DET-758A/S 35
Especificaciones Guía rápida del AF-650 GP
Entradas digitales:
Entradas digitales programables 4 (6)1)
Número de terminal 18, 19, 271), 291),
32, 33,
Lógica PNP o NPN
Nivel de tensión 0-24 V CC
Nivel de tensión, «0» lógico PNP < 5 V CC
Nivel de tensión, «1» lógico PNP > 10 V CC
Nivel de tensión, «0» lógico NPN2) > 19 V CC
Nivel de tensión, «1» lógico NPN2) < 14 V CC
Tensión máxima de entrada 28 V CC
Rango de frecuencia de impulsos 0-110 kHz
(Ciclo de trabajo) Anchura de impulso mín. 4,5 ms
Resistencia de entrada, Ri 4 kΩ (aprox.)
2) Consulte 3.4.5.7 Terminal 37 para más información sobre el terminal 37 y la Parada de seguridad.
Entradas analógicas:
Nº de entradas analógicas 2
Número de terminal 53, 54
Modos Tensión o intensidad
Selección de modo Interruptor S201 e interruptor S202
Modo de tensión Interruptor S201 / Interruptor S202 = OFF (U)
Nivel de tensión De -10 a +10 V (escalable)
Resistencia de entrada, Ri aprox. 10 kΩ
Tensión máx. ± 20 V
Modo de intensidad Interruptor S201 / Interruptor S202 = ON (I)
Nivel de intensidad De 0 o 4 a 20 mA (escalable)
Resistencia de entrada, Ri 200 Ω aproximadamente
Intensidad máx. 30 mA
Resolución de entradas analógicas 10 bit (signo +)
Precisión de las entradas analógicas Error máx.: 0,5 % de la escala completa
Ancho de banda 100 Hz
Las entradas analógicas están aisladas galvánicamente de la tensión de alimentación (PELV) y de los demás terminales de alta
tensión.
36 DET-758A/S
Especificaciones Guía rápida del AF-650 GP
Entradas de pulsos/encoder:
Entradas de pulsos/encoder programables 2/1
Número de terminal de pulso/encoder 29, 331)/ 322),
332)
Frecuencia máx. en los terminales 29, 32, 33 110 kHz (en contrafase)
Frecuencia máx. en los terminales 29, 32, 33 5 kHz (colector abierto)
Frecuencia mínima en los terminales 29, 32, 33 4 Hz
Nivel de tensión Consulte 8.1.1 Entradas digitales:
Tensión máxima de entrada 28 V CC
Resistencia de entrada, Ri aprox. 4000 Ω
Precisión de la entrada de pulsos (0,1-1 kHz) Error máx.: un 0,1 % de la escala completa
Precisión de la entrada de encoder (1-11 kHz) Error máx.: 0,05 % de la escala completa
Las entradas de pulsos y encoder (terminales 29, 32, 33) se encuentran galvánicamente aisladas de la tensión de alimentación
(PELV) y demás terminales de alta tensión.
1) Las entradas de pulsos son la 29 y la 33
2) Entradas de encoder: 32 = A y 33 = B
Salida digital:
Salidas digitales / de pulsos programables 2
Número de terminal 27, 29 1)
Nivel de tensión en la salida digital / de frecuencia 0 - 24V
Intensidad de salida máx. (disipador o fuente) 40 mA
Carga máx. en salida de frecuencia
Carga capacitiva máx. en salida de frecuencia
1 kΩ
10 nF
8 8
Frecuencia de salida mín. en salida de frecuencia 0 Hz
Frecuencia de salida máx. en salida de frecuencia 32 kHz
Precisión de salida de frecuencia Error máx.: 0,1 % de la escala total
Resolución de salidas de frecuencia 12 bits
1) Los terminales 27 y 29 también pueden programarse como entradas.
La salida digital está aislada galvánicamente de la tensión de alimentación (PELV) y de los demás terminales de alta tensión.
Salida analógica:
Número de salidas analógicas programables 1
Número de terminal 42
Rango de intensidad en la salida analógica 0/4 - 20 mA
Carga máx. entre tierra y salida analógica 500Ω
Precisión en salida analógica Error máx.: un 0,5 % de la escala completa
Resolución en la salida analógica 12 bits
La salida analógica está aislada galvánicamente de la tensión de alimentación (PELV) y del resto de terminales de alta tensión.
Tarjeta de control, salida de 24 V CC:
Número de terminal 12, 13
Tensión de salida 24 V +1, -3 V
Carga máx. 200 mA
La alimentación de 24 V CC está aislada galvánicamente de la tensión de alimentación (PELV), aunque tiene el mismo potencial
que las entradas y salidas analógicas y digitales.
Tarjeta de control, salida de 10 V CC:
Número de terminal 50
Tensión de salida 10,5 V ± 0,5 V
Carga máx. 15 mA
La alimentación de 10 V CC está aislada galvánicamente de la tensión de alimentación (PELV) y de los demás terminales de alta
tensión.
Tarjeta de control, comunicación serie RS-485:
Número de terminal 68 (P,TX+, RX+), 69 (N,TX-, RX-)
N.º de terminal 61 Común para los terminales 68 y 69
El circuito de comunicación serie RS-485 se encuentra separado funcionalmente de otros circuitos y aislado galvánicamente de la
tensión de alimentación (PELV).
DET-758A/S 37
Especificaciones Guía rápida del AF-650 GP
3) Aplicaciones UL 300 V CA 2A
38 DET-758A/S
Especificaciones Guía rápida del AF-650 GP
• El control de la temperatura del disipador garantiza la desconexión del convertidor de frecuencia si la temperatura
alcanza un valor predeterminado. La señal de temperatura de sobrecarga no se puede desactivar hasta que la
temperatura del disipador térmico se encuentre por debajo de los valores indicados en las tablas de las siguientes
páginas (valores orientativos, estas temperaturas pueden variar para diferentes potencias, tamaños de unidad,
clasificaciones de protección, etc.).
• El convertidor de frecuencia está protegido frente a cortocircuitos entre los terminales U, V y W del motor. 8 8
• Si falta una fase de red, el convertidor de frecuencia se desconectará o emitirá una advertencia (en función de la
carga).
• El control de la tensión del circuito intermedio asegura que el convertidor de frecuencia se desconecte si la
tensión del circuito intermedio es demasiado baja o demasiado elevada.
DET-758A/S 39
Instalación Guía rápida del AF-650 GP
9 Instalación
9.1.1 Fusibles
¡NOTA!
Esto es obligatorio a fin de asegurar el cumplimiento de los requisitos de la norma CEI 60364 para CE y del NEC 2009 para
UL.
ADVERTENCIA
El personal y los bienes deben estar protegidos contra las consecuencias de la avería de componentes en el interior del
convertidor de frecuencia.
¡NOTA!
9 9 Las recomendaciones dadas no se aplican a la protección de circuito derivado para UL.
ADVERTENCIA
En caso de mal funcionamiento, el hecho de no seguir esta recomendación podría dar lugar a riesgos personales y daños al
convertidor de frecuencia y otros equipos.
En las tablas siguientes se indica la intensidad nominal recomendada. Los fusibles recomendados son de tipo gG para
potencias bajas y medias. Para potencias superiores, se recomiendan los fusibles aR. Los magnetotérmicos se emplearán
siempre que cumplan las normas nacionales / internacionales y que limiten la energía en el interior del convertidor de
frecuencia a un nivel igual o inferior al de los magnetotérmicos conformes.
Si los fusibles / magnetotérmicos se seleccionan siguiendo las recomendaciones, los posibles daños en el convertidor de
frecuencia se reducirán principalmente a daños en el interior de la unidad.
9.1.2 Cumplimiento de la normativa CE
Los fusibles o magnetotérmicos son obligatorios para cumplir con la norma IEC 60364. GE recomienda utilizar una selección
de los siguientes.
Los siguientes fusibles son adecuados para su uso en un circuito capaz de proporcionar 100 000 Arms (simétricos), 240 V, o
480 V, o 500 V, o 600 V, dependiendo de la clasificación de tensión del convertidor de frecuencia. Con los fusibles
adecuados, la clasificación de corriente de cortocircuito (SCCR) del convertidor de frecuencia es 100 000 Arms.
40 DET-758A/S
Instalación Guía rápida del AF-650 GP
DET-758A/S 41
Instalación Guía rápida del AF-650 GP
42 DET-758A/S
Instalación Guía rápida del AF-650 GP
DET-758A/S 43
Instalación Guía rápida del AF-650 GP
9 9 15 / 20
18,5 / 25
gG-32 gG-63
22 / 30 gG-40
30 / 40 gG-80
gG-63
37 / 50 gG-100
45 / 60 gG-80 gG-125
55 / 75 gG-100
gG-160
75 / 100 gG-125
90 / 125 aR-250 aR-250
110 / 150 aR-315 aR-315
132 / 200
aR-350 aR-350
160 / 250
200 / 300 aR-400 aR-400
250 / 350 aR-500 aR-500
315 / 400 aR-550 aR-550
355 / 500
aR-700 aR-700
400 / 550
500 / 650
aR-900 aR-900
560 / 750
630 / 900
710 / 1000
aR-1600 aR-1600
800 / 1150
900 / 1250
1000 / 1350 aR-2000 aR-2000
44 DET-758A/S
Instalación Guía rápida del AF-650 GP
Los fusibles o magnetotérmicos son obligatorios para cumplir con el NEC 2009. Recomendamos utilizar una selección de los
siguientes.
Los siguientes fusibles son adecuados para su uso en un circuito capaz de proporcionar 100 000 Arms (simétricos), 240 V,
480 V o 600 V, en función de la clasificación de tensión del convertidor de frecuencia. Con los fusibles adecuados, la clasifi-
cación de corriente de cortocircuito (SCCR) del convertidor de frecuencia es 100 000 Arms.
DET-758A/S 45
Instalación Guía rápida del AF-650 GP
1) Los fusibles KTS de Bussmann pueden sustituir a los KTN en los convertidores de frecuencia de 240 V.
9 9 2) Los fusibles FWH de Bussmann pueden sustituir a los FWX en los convertidores de frecuencia de 240 V.
3) Los fusibles A6KR de FERRAZ SHAWMUT pueden sustituir a los A2KR en los convertidores de frecuencia de
240 V.
4) Los fusibles A50X de FERRAZ SHAWMUT pueden sustituir a los A25X en los convertidores de frecuencia de
240 V.
46 DET-758A/S
Instalación Guía rápida del AF-650 GP
AF-650 GP Bussmann
Fusible máx. recomendado
Ferraz- Shawmut Ferraz- Shawmut Fusible Littel
9 9
kW / CV JFHR2 J JFHR21) JFHR2
0,37-0,75 / FWH-6 HSJ-6 - -
1/2-1
1,5-2,2 / 2- FWH-10 HSJ-10 - -
3
3,7 / 5 FWH-20 HSJ-20 - -
5,5 / 7,5 FWH-25 HSJ-25 - -
7,5 / 10 FWH-30 HSJ-30 - -
11 / 15 FWH-40 HSJ-40 - -
15 / 20 FWH-50 HSJ-50 - -
18,5 / 25 FWH-60 HSJ-60 - -
22 / 30 FWH-80 HSJ-80 - -
30 / 40 FWH-100 HSJ-100 - -
37 / 50 FWH-125 HSJ-125 - -
45 / 60 FWH-150 HSJ-150 - -
55 / 75 FWH-200 HSJ-200 A50-P-225 L50-S-225
75 / 100 FWH-250 HSJ-250 A50-P-250 L50-S-250
1) Los fusibles A50QS de Ferraz Shawmut pueden ser sustituidos por los A50P.
DET-758A/S 47
Instalación Guía rápida del AF-650 GP
1) Los fusibles 170M de Bussmann mostrados utilizan el indicador visual - / 80. Los fusibles con el indicador -
TN / 80 tipo T, - / 110 o TN / 110 tipo T del mismo tamaño y amperaje pueden ser sustituidos.
48 DET-758A/S
Instalación Guía rápida del AF-650 GP
9 9
DET-758A/S 49
Instalación Guía rápida del AF-650 GP
50 DET-758A/S
Instalación Guía rápida del AF-650 GP
**Para cumplir con los requerimientos UL puede utilizarse cualquier fusible UL que aparezca en la lista, mínimo 500 V, con la corriente nominal
correspondiente.
DET-758A/S 51
0 10
52
Potencia (kW / CV) Protecció Red Motor Carga compartida Freno Toma de
n tierra*
Par de Dimensione Par de Par de Dimensione Par de
Dimensiones Dimensiones Par de
apriete s de cable apriete apriete s de cable apriete
200-240V 380-480V 525-600V 525-690V 2 de cable de cable apriete
[Nm / in- [mm [Nm / in- [Nm / in- [mm2 [Nm / in-
10.1 Cables
[mm2 (AWG)] [mm2 (AWG)] [Nm / in-lb]
-lb] (AWG)] -lb] -lb] (AWG)] -lb]
0,25-2,2 k 0,37-4 kW 0,75-4 kW
IP20
W 1/3-3 CV 1/2-5 CV 1-5 CV
Terminal y cable aplicable
3,7 / 33 3,7 / 33
15 CV 25-30 CV 25-30 CV 15-30 CV IP66
18,5-22 kW 37-45 kW 37-45 kW
IP20 50 (1) 50 (1) 50 (1) 50 (1)
25-30 CV 50-60 CV 50-60 CV
10 / 89 10 / 89 10 / 89 10 / 89
15-22 kW 30-45 kW 30-45 kW IP55 o
90 (3/0) 90 (3/0) 90 (3/0) 90 (3/0)
20-30 CV 40-60 CV 40-60 CV IP66
30-37 kW 55-75 kW 55-75 kW 150 150
IP20 95 (4/0) 95 (4/0)
DET-758A/S
40-50 CV 75-100 CV 75-100 CV (300 mcm) (300 mcm)
Guía rápida del AF-650 GP
1 Sicherheit 1 1
WARNUNG HINWEIS
ENTLADUNGSZEIT! Kennzeichnet wichtige Hinweise, die beachtet werden
Die Zwischenkreiskondensatoren des Frequenzumrichters müssen, um Fehler oder Betrieb von Geräten, in dem nicht
können auch bei abgeschalteter und getrennter Netzver- die optimale Leistung erbracht wird, zu vermeiden.
sorgung geladen bleiben. Trennen Sie zum Schutz vor
elektrischen Gefahren die Netzversorgung vom Frequen- Zulassungen
zumrichter, bevor Sie Wartungs- oder Reparaturarbeiten
durchführen und halten Sie die in Tabelle 1.1 vorgegebene
Wartezeit ein. Wird diese Wartezeit nach Entfernen der
Netzversorgung vor Wartungs- oder Reparaturarbeiten am
Frequenzumrichter nicht eingehalten, kann dies Tod oder
schwere Verletzungen zur Folge haben.
DET-758A/D 1
Einführung AF-650 GP-Kurzanleitung
2 Einführung
2 2
HINWEIS
Weitere Einheitengrößen finden Sie im AF-650 GP-Produkthandbuch.
2 DET-758A/D
Installation AF-650 GP-Kurzanleitung
3 Installation
• Das Innere des Frequenzumrichters muss frei von 3.3 Mechanische Installation
Staub und Schmutz bleiben. Stellen Sie sicher,
dass die Komponenten so sauber wie möglich 3.3.1 Kühlung
bleiben. Im Bereich von Baustellen ist eine
Schutzabdeckung erforderlich. Optional werden • Sorgen Sie durch Montage des Geräts auf einer
ggf. Gehäuse mit Schutzart IP54 benötigt. ebenen, stabilen Oberfläche oder an der
optionalen Rückwand (siehe 3.3.3 Montage) für
• Bewahren Sie das Handbuch, die Zeichnungen
eine ausreichende Luftzirkulation zur Kühlung.
und die Schaltbilder für genaue Installations- und
Betriebsanweisungen leicht zugänglich auf. Das • Über und unter dem Frequenzumrichter muss zur
Handbuch muss für Bediener des Geräts Luftzirkulation ein ausreichender Abstand
unbedingt zugänglich sein. vorgesehen werden. In der Regel ist ein Abstand
von 100-225 mm erforderlich. Zu Abstandsanfor-
• Stellen Sie Geräte so nah wie möglich am Motor
derungen siehe Abbildung 3.1.
auf. Halten Sie die Motorkabel so kurz wie
möglich. Prüfen Sie die Motorkenndaten auf • Eine unsachgemäße Montage kann Überhitzung
tatsächliche Toleranzen. Überschreiten Sie die und reduzierte Leistung zur Folge haben.
folgenden Längen nicht: • Eine Leistungsreduzierung aufgrund hoher
• 300 m bei nicht abgeschirmten Temperaturen zwischen 40 °C und 50 °C und
Motorkabeln einer Höhenlage von 1000 m über dem Meeres-
spiegel muss berücksichtigt werden. Weitere
• 150 m bei abgeschirmten Kabeln
Informationen finden Sie im Projektierungs-
handbuch des Geräts.
3.2 Checkliste zur Vorbereitung der
Installation von Frequenzumrichter und
Motor
• Vergleichen Sie die Modellnummer des Geräts auf
dem Typenschild mit den Bestellangaben, um
sicherzustellen, dass Sie das richtige Gerät haben.
DET-758A/D 3
Installation AF-650 GP-Kurzanleitung
Nenn-
Nennleistung Abstand a/b
spannung
0,25 - 3,7 kW 100 mm
200 - 240 V 5,5 - 22 kW 200 mm
> 22 kW 225 mm
0,37 - 7,5 kW 100 mm
3 3 380 - 480 V 11 - 45 kW 200 mm
> 45 kW 225 mm
0,37 - 7,5 kW 100 mm
525 - 600 V 11 - 45 kW 200 mm
> 45 kW 225 mm
525 - 690 V Alle 225 mm
Tabelle 3.1 Mindestanforderungen für Luftströmungsabstände Abbildung 3.2 Korrekte Montage mit Rückwand
3.3.2 Heben
Element A ist eine Rückwand, die für die erforderliche
Luftzirkulation zum Kühlen des Geräts ordnungsgemäß
• Überprüfen Sie das Gewicht des Frequenzum-
richters, um ein sicheres Hebeverfahren zu montiert ist.
bestimmen.
3.3.3 Montage
4 DET-758A/D
Installation AF-650 GP-Kurzanleitung
A=Analog, D=Digital
Klemme 37 wird für den sicheren Stopp verwendet. Anweisungen zur Installation des sicheren Stopps siehe Projektierungs-
handbuch.
*Die werkseitige Option eines Bremschoppers muss zur Verwendung dynamischer Bremswiderstände bestellt werden.
**Dies ist bei Bestellung der Bremschopperoption für Frequenzumrichter der Einheitengröße 23 und höher erhältlich.
DET-758A/D 5
Installation AF-650 GP-Kurzanleitung
VORSICHT
ISOLIERUNG VON KABELN
Verlegen Sie die Netzkabel, Motorkabel und Steuerkabel
zum Schutz vor Hochfrequenzstörgeräuschen in drei
getrennten Kabelkanälen oder verwenden Sie getrennte
abgeschirmte Kabel. Dies kann andernfalls die einwandfreie
und optimale Funktion des Frequenzumrichters und der
angeschlossenen Geräte beeinträchtigen.
6 DET-758A/D
Installation AF-650 GP-Kurzanleitung
• Beachten Sie alle örtlichen und nationalen Verwenden Sie netzseitig nur allstromsensitive
Elektroinstallationsvorschriften zur inwandfreien Fehlerschutzschalter (Typ B)
Erdung elektrischer Geräte und Betriebsmittel. Verwenden Sie RCDs mit Einschaltverzögerung,
• Bei Frequenzumrichtern mit Erdströmen von um Fehler durch transiente Erdströme zu
mehr als 3,5 mA muss eine verstärkte Schutz- vermeiden
erdung angeschlossen werden (siehe hierzu
Ableitstrom (>3,5 mA)
Bemessen Sie RCDs in Bezug auf Systemkonfigu-
ration und Umgebungsbedingungen
3 3
• Für Netz-, Motor- und Steuerkabel ist ein
spezieller Schutzleiter erforderlich. 3.4.2.2 Erdung über abgeschirmte Kabel
• Verwenden Sie die im Lieferumfang der Frequen-
zumrichter enthaltenen Kabelschellen, um die Erdungsschellen werden für Motorkabel mitgeliefert (siehe
Geräte großflächig zu erden. Abbildung 3.6).
• zwei getrennt verlegte Erdungskabel, die die • Angaben zu den maximalen Leitungsquer-
vorgeschriebenen Maße einhalten schnitten finden Sie unter Tabelle 10.1
DET-758A/D 7
Installation AF-650 GP-Kurzanleitung
• Installieren Sie Kondensatoren zur Korrektur des • Je nach Konfiguration der Geräte wird die
Leistungsfaktors nicht zwischen dem Frequen- Eingangsleistung an die Netzeingangsklemmen
zumrichter und dem Motor. oder den Netztrennschalter angeschlossen.
• Schalten Sie kein Anlass- oder Polwechselgerät • Erden Sie das Kabel gemäß den Erdungsanwei-
zwischen den Frequenzumrichter und den Motor. sungen in 3.4.2 Erdungsanforderungen
3.4.5 Steuerverdrahtung
3.4.4 Netzanschluss
8 DET-758A/D
Installation AF-650 GP-Kurzanleitung
3 3
DET-758A/D 9
Installation AF-650 GP-Kurzanleitung
Klemmenbeschreibung Klemmenbeschreibung
Werksein- Werksein-
Klemme Parameter stellung Beschreibung Klemme Parameter stellung Beschreibung
Digitaleingänge/-ausgänge Serielle Kommunikation
12, 13 - +24 V DC 24-V-DC-Versorgungs- 61 - Integriertes RC-Filter
spannung. Maximaler für Kabelabschirmung.
3 3 Ausgangsstrom ist 200 NUR zum Anschluss
mA insgesamt für alle der Abschirmung bei
24-V-Lasten. EMV-Problemen.
Verwendbar für Digita- 68 (+) O-3# RS-485-Schnittstelle.
leingänge und externe 69 (-) O-3# Ein Schalter auf der
Messwandler. Steuerkarte dient zum
18 E-01 [8] Start Zuschalten des
19 E-02 [10] Abschlusswiderstands.
Reversierung Relais
32 E-05 [0] Ohne Digitaleingänge. [0] Ohne Form-C-Relaisausgang.
Funktion 01, 02, 03 E-24 Funktion Verwendbar für
33 E-06 [0] Ohne 04, 05, 06 E-24 [0] Ohne Wechsel- oder Gleich-
Funktion Funktion spannung und
27 E-03 [0] Ohne Wählbar als Digitalein- ohmsche oder
Funktion oder -ausgang. induktive Lasten.
29 E-04 [14] Festdrz. Werkseinstellung ist
Tabelle 3.2 Klemmenbeschreibung
(JOG) Eingang.
20 - „Common“ für Digita-
leingänge und 0-V- 3.4.5.3 Verkabelung der Steuerklemmen
Potential für 24-V-
Stromversorgung. Steuerklemmenanschlüsse können zur einfacheren Instal-
37 - Sichere lation vom Frequenzumrichter abgezogen werden, wie in
Abschaltung Abbildung 3.10 dargestellt.
Motormoment Sicherer Eingang. Für 1. Lösen Sie den Kontakt, indem Sie einen kleinen
(STO) STO verwendet. Schraubendreher in den Schlitz über oder unter
Analogeingänge/-ausgänge dem Kontakt einführen, wie in Abbildung 3.12
39 - „Common“ für Analog- dargestellt.
ausgang
2. Führen Sie das 9-10 mm abisolierte Steuerkabel
42 AN-50 [0] Ohne Programmierbarer
in den Kontakt ein.
Funktion Analogausgang. Das
Analogsignal ist 0-20 3. Entfernen Sie den Schraubendreher. Das Kabel ist
mA oder 4-20 mA bei nun in der Klemme befestigt.
maximal 500 Ω 4. Stellen Sie sicher, dass der Kontakt fest hergestellt
50 - +10 V DC 10-V DC-Analogversor- ist. Lose Steuerkabel können Fehler oder einen
gungsspannung. Betrieb von Geräten zur Folge haben, in dem
Maximal 15 mA, in der nicht die optimale Leistung erbracht wird.
Regel für Potenti-
ometer oder
Thermistor verwendet.
53 AN-1# Sollwert Analogeingang.
54 AN-2# Istwert Programmierbar für
Spannung oder Strom.
Schalter A53 und A54
wählen mA oder V.
55 - „Common“ für Analog-
eingang
10 DET-758A/D
Installation AF-650 GP-Kurzanleitung
50/60-Hz-Erdschleife
Bei sehr langen Steuerkabeln können Erdschleifen
auftreten. Zur Eliminierung von Erdschleifen können Sie ein
Ende der Verbindung zwischen Abschirmung und Erdung
an einen 100-nF-Kondensator anschließen (Leitungen kurz
halten).
DET-758A/D 11
Installation AF-650 GP-Kurzanleitung
3.4.5.6 Schalter für die Klemmen 53 und 54 sich dreht. Wenn der sichere Stopp (T37) aktiviert wird,
gibt der Frequenzumrichter einen Alarm aus, schaltet die
• Bei den Analogeingangsklemmen 53 und 54 Einheit ab und versetzt den Motor in den Freilauf, bis er
können Sie als Eingangssignale Spannung (0 bis anhält. Der Neustart muss manuell erfolgen. Die Sicherer-
10 V) oder Strom (0/4-20 mA) wählen. Stopp-Funktion kann zum Stoppen des Frequenzumrichters
in Notfallsituationen verwendet werden. Verwenden Sie
3 3 • Trennen Sie vor Änderung der Schaltpositionen
dagegen im normalen Betriebsmodus, wenn kein sicherer
den Frequenzumrichter von der Stromversorgung
Stopp erforderlich ist, die reguläre Stoppfunktion des
• Stellen Sie die Schalter A53 und A54 zur Wahl des Frequenzumrichters. Wenn der automatische Wiederanlauf
Signaltyps ein: U wählt Spannung, I wählt Strom. verwendet wird, müssen die Anforderungen nach ISO
12100-2, Paragraph 5.3.2.5 erfüllt werden.
• Sie erreichen die Schalter, wenn Sie die Tastatur
abnehmen (siehe Abbildung 3.13). Die Options- Haftungsbedingungen
module in Steckplatz B decken diese Schalter ggf. Der Anwender ist dafür verantwortlich sicherzustellen, dass
ab. Entfernen Sie diese zum Ändern der Schalter- das Personal, das die Funktion „Sicherer Stopp“ installiert
einstellungen. (Trennen Sie vor Arbeiten am und bedient:
Frequenzumrichter immer die Energiezufuhr.)
• über die Sicherheitsvorschriften im Hinblick auf
• Werkseinstellung für Klemme 53 ist ein Drehzahl- Arbeitsschutz und Unfallverhütung in Kenntnis
sollwertsignal bei Regelung ohne Rückführung, gesetzt wurde
programmiert in 16-61 Terminal 53 Switch Setting.
• die allgemeinen und Sicherheitsrichtlinien in der
• Werkseinstellung für Klemme 54 ist ein vorliegenden Beschreibung sowie der erweiterten
Istwertsignal bei Regelung mit Rückführung, Beschreibung im Projektierungshandbuch
programmiert in 16-63 Terminal 54 Switch Setting versteht
12 DET-758A/D
Installation AF-650 GP-Kurzanleitung
• Der Frequenzumrichter muss in einem Schalt- 1. Entfernen Sie die Drahtbrücke zwischen den
schrank mit Schutzart IP54 oder einer
vergleichbaren Umgebung installiert werden.
Steuerklemmen 37 und 12 oder 13. Ein
Durchschneiden oder Brechen der Drahtbrücke
3 3
reicht zur Vermeidung von Kurzschlüssen nicht
• Das Kabel zwischen Klemme 37 und der externen
aus. (Siehe Drahtbrücke in Abbildung 3.14.)
Sicherheitsvorrichtung muss gemäß ISO 13849-2
Tabelle D.4 gegen Kurzschluss geschützt werden. 2. Schließen Sie ein externes Sicherheitsüberwa-
chungsrelais über eine stromlos geöffnete
• Falls externe Kräfte auf die Motorachse wirken (z.
Sicherheitsfunktion an Klemme 37 (Sicherer
B. hängende Lasten), sind zur Vermeidung von
Gefahren zusätzliche Maßnahmen (z. B. eine Stopp) und entweder Klemme 12 oder 13 (24 V
sichere Haltebremse) erforderlich. DC) an (hierbei muss die Anleitung der Sicher-
heitsvorrichtung genau beachtet werden). Das
Installation und Einrichtung Sicherer Stopp Sicherheitsrelais muss Kategorie 3 (EN 954-1) / PL
WARNUNG „d“ (ISO 13849-1) erfüllen.
SICHERER-STOPP-FUNKTION!
Die Sicherer-Stopp-Funktion isoliert den Frequenzumrichter
oder weitere Schaltungen NICHT gegen die Netzspannung.
Führen Sie Arbeiten an stromführenden Teilen des
Frequenzumrichters oder des Motors erst nach Isolierung
der Netzspannungsversorgung und Abwarten der unter
„Sicherheit“ in diesem Handbuch angegebenen Dauer
durch. Wird die Einheit nicht gegen die Netzspannungsver-
sorgung isoliert und die vorgegebene Wartezeit nicht
beachtet, kann dies zu schweren Verletzungen oder zum
Tod führen.
DET-758A/D 13
Installation AF-650 GP-Kurzanleitung
3 3
Abbildung 3.15 Installation zum Erreichen einer Stoppkategorie 0 (EN 60204-1) mit Sicherheitskat. 3 (EN 954-1) / PL „d“ (ISO 13849-1).
14 DET-758A/D
Installation AF-650 GP-Kurzanleitung
DET-758A/D 15
Start- und Funktionsprüfung... AF-650 GP-Kurzanleitung
4 4 WARNUNG
HOCHSPANNUNG!
Wenn Ein- und Ausgangsklemmen falsch angeschlossen
werden, besteht die Gefahr, dass an diesen Hochspannung
anliegt. Wenn Stromversorgungsleitungen für mehrere
Motoren fälschlicherweise im selben Kabelkanal geführt
werden, können Ableitströme entstehen, durch die
Kondensatoren im Frequenzumrichter aufgeladen werden
können, selbst wenn sie vom Netzeingang getrennt sind.
Beim ersten Start sollten keine Annahmen über die
Frequenzumrichter getroffen werden. Führen Sie
stattdessen die vor dem Start erforderlichen Verfahren
durch. Werden diese Verfahren nicht durchgeführt, kann
dies zu Verletzungen von Personen sowie Schäden am
Gerät führen.
16 DET-758A/D
Start- und Funktionsprüfung... AF-650 GP-Kurzanleitung
VORSICHT
Prüfen Sie vor Anlegen der Netzspannung an den Frequenzumrichter die gesamte Anlage, wie in Tabelle 4.1 beschrieben.
Markieren Sie die geprüften Punkte anschließend mit einem Haken.
Prüfpunkt Beschreibung ☑
Zusatzeinrichtungen • Erfassen Sie Zusatzeinrichtungen, Zubehör, Schalter, Trenner oder
Netzsicherungen bzw. Hauptschalter, die netz- oder motorseitig angeschlossen 4 4
sein können. Stellen Sie sicher, dass diese für einen Berieb bei voller Drehzahl
bereit sind.
• Überprüfen Sie die Funktionalität und Installation aller Sensoren für die
Rückführung zum Frequenzumrichter.
Steuerkabel • Prüfen Sie, ob Kabel gebrochen oder beschädigt sind und ob lose Verbin-
dungen vorliegen.
Umgebungsbedingungen • Beachten Sie die Grenzwerte der maximalen Umgebungs- und Betriebstem-
peratur auf dem Typenschild.
Sicherungen und Trennschalter • Stellen Sie sicher, dass die richtigen Sicherungen oder Trennschalter eingebaut
sind.
• Prüfen Sie, dass alle Sicherungen fest eingesetzt und in einem betriebsfähigen
Zustand sowie alle Trennschalter geöffnet sind.
Erdung • Stellen Sie sicher, dass ein Erdleiter zwischen dem Frequenzumrichter und der
Gebäudeerdung angeschlossen ist.
• Prüfen Sie, dass die Anlage eine Erdverbindung besitzt und die Kontakte fest
angezogen sind und keine Oxidation aufweisen.
Netz- und Motorkabel • Prüfen Sie, dass alle Kontakte fest angeschlossen sind.
Gehäuseinneres • Stellen Sie sicher, dass das Innere des Frequenzumrichters frei von Schmutz,
Metallspänen, Feuchtigkeit und Korrosion ist.
DET-758A/D 17
Start- und Funktionsprüfung... AF-650 GP-Kurzanleitung
Prüfpunkt Beschreibung ☑
Schalter • Stellen Sie sicher, dass alle Schalter und Trennschalter in der richtigen Schaltpo-
sition sind.
Vibrationen • Stellen Sie sicher, dass der Frequenzumrichter je nach Anforderung stabil
montiert ist oder Schwingungsdämpfer verwendet werden.
WARNUNG
HOCHSPANNUNG! 4.3 Grundlegende Programmierung
Frequenzumrichter führen bei Anschluss an die
Eine grundlegende Programmierung des Frequenzum-
Netzspannung Hochspannung. Installation, Inbetriebnahme
richters vor dem eigentlichen Betrieb ist für eine optimale
und Wartung dürfen daher nur von qualifiziertem
Leistung erforderlich. Hierzu werden die Typenschilddaten
Fachpersonal durchgeführt werden. Werden Installation,
des betriebenen Motors sowie die minimale und maximale
Inbetriebnahme und Wartung nicht von qualifiziertem
Motordrehzahl eingegeben. Geben Sie die Daten wie
Personal durchgeführt, kann dies Tod oder schwere Verlet-
nachstehend beschrieben ein. Die empfohlenen Parameter-
zungen zur Folge haben.
einstellungen sind lediglich für die Inbetriebnahme und
eine erste Funktionsprüfung bestimmt. Anwendungsein-
WARNUNG stellungen können abweichen. Eine genaue Anleitung zur
Eingabe von Daten über die Tastatur finden Sie in
UNERWARTETER ANLAUF!
5 Benutzerschnittstelle.
Bei Anschluss des Frequenzumrichters an die
Netzspannung kann der Motor jederzeit unerwartet
anlaufen. Der Frequenzumrichter, der Motor und alle Geben Sie die Daten ein, während die Energiezufuhr zum
angetriebenen Geräte müssen betriebsbereit sein. Sind sie Frequenzumrichter EIN, jedoch noch keine Funktion des
beim Anschluss des Frequenzumrichters an das Wechsel- Frequenzumrichters aktiviert ist.
stromnetz nicht betriebsbereit, kann dies zu schweren
Verletzungen oder zum Tod sowie zu Sachschäden und 1. Drücken Sie auf [Quick Menu] an der Tastatur.
Schäden an der Ausrüstung führen. 2. Navigieren Sie mit den Navigationstasten zu
Kurzinbetriebnahme und drücken Sie auf [OK].
1. Stellen Sie sicher, dass die Abweichung in der
3. Wählen Sie die Sprache und drücken Sie auf [OK].
Spannungssymmetrie höchstens ±3 % beträgt. Ist
Geben Sie dann die Motordaten in Parametern
dies nicht der Fall, so korrigieren Sie die
P-02, P-03, P-06, P-07, F-04 und F-05 ein. Die
Unsymmetrie der Eingangsspannung, bevor Sie
entsprechenden Angaben finden Sie auf dem
fortfahren. Wiederholen Sie das Verfahren nach
Motor-Typenschild.
der Spannungskorrektur.
1-20 Motor Power [kW] oder 1-21 Motor
2. Stellen Sie sicher, dass die Verkabelung optionaler
Power [HP]
Geräte, sofern vorhanden, dem Zweck der Anlage
entspricht. 1-22 Motor Voltage
18 DET-758A/D
Start- und Funktionsprüfung... AF-650 GP-Kurzanleitung
DET-758A/D 19
Start- und Funktionsprüfung... AF-650 GP-Kurzanleitung
20 DET-758A/D
Benutzerschnittstelle AF-650 GP-Kurzanleitung
5 Benutzerschnittstelle
HINWEIS
Der Displaykontrast kann durch Drücken der Taste
[STATUS] sowie der Pfeiltaste eingestellt werden.
a. Displaybereich.
b. Menütasten zur Änderung der Zustandsanzeige,
zum Programmieren oder zum Zugriff auf den
Alarm- und Fehlerspeicher.
c. Navigationstasten zur Programmierung von
Funktionen, Bewegen des Cursors und Drehzahl-
regelung bei Hand-Steuerung. Hier befinden sich
Kontrollanzeigen zur Anzeige des Zustands.
d. Tasten zur Wahl der Betriebsart und zum
Quittieren (Reset).
DET-758A/D 21
Benutzerschnittstelle AF-650 GP-Kurzanleitung
22 DET-758A/D
Benutzerschnittstelle AF-650 GP-Kurzanleitung
Navigationstasten dienen zum Navigieren der Program- Bedientasten befinden sich unten an der Tastatur.
mierungsfunktionen und Bewegen des Displaycursors. Die
Navigationstasten ermöglichen zudem eine Drehzahlre-
gelung im Handbetrieb (Ortsteuerung). In diesem Bereich
befinden sich darüber hinaus die drei Kontrollanzeigen
(LEDs) des Frequenzumrichters zur Anzeige des Zustands.
Taste Funktion
5 5
Hand Drücken Sie diese Taste, um den
Frequenzumrichter mit Hand-Steuerung zu
starten.
• Mit den Navigationstasten können Sie die
Drehzahl des Frequenzumrichters regeln.
DET-758A/D 23
Benutzerschnittstelle AF-650 GP-Kurzanleitung
24 DET-758A/D
Benutzerschnittstelle AF-650 GP-Kurzanleitung
DET-758A/D 25
6 6
F-12 Thermistoranschluss E-26 Ein Verzög., Relais C-24 Rampenzeit Schnellstopp H-52 Min. Drehzahl norm. Magnetis. [Hz]
26
6.1.1 Hauptmenüaufbau
F-18 Min. Motordrehzahl [UPM] E-27 Aus Verzög., Relais C-25 Schnellstopp S-Form Anfang H-53 Steuerprinzip Umschaltpunkt
F-16 Min. Motordrehzahl [Hz] E-3# X46 Digitaleingänge C-26 Schnellstopp S-Form Ende H-54 Sp.-Reduz. bei Feldschwächung
Tastenfeldsatz F-17 Max. Motordrehzahl [UPM] E-30 Klemme X46/1 Digitaleingang C-3# Frequenzeinstell. 2&3 H-55 U/f-Kennlinie - U [V]
K-0# Tastenfeld-Einstell. F-15 Max. Motordrehzahl [Hz] E-31 Klemme X46/3 Digitaleingang C-30 Frequenzbefehl 2 H-56 U/f-Kennlinie - f [Hz]
K-01 Sprache F-2# Grundlegend 2 E-32 Klemme X46/5 Digitaleingang C-34 Frequenzbefehl 3 H-58 Fangschaltung Testimpulse Strom
K-02 Hz/UPM Umschaltung F-24 Haltezeit E-33 Klemme X46/7 Digitaleingang P-## Motordaten H-59 Fangschaltung Testimpulse Frequenz
K-03 Ländereinstellungen F-25 Startfunktion E-34 Klemme X46/9 Digitaleingang P-0# Motordaten H-6# Lastabh. Einstell.
K-04 Netz-Ein Modus F-22 Startdrehzahl [UPM] E-35 Klemme X46/11 Digitaleingang P-07 Motorleistung [kW] H-61 Lastausgleich hoch
K-09 Leistungsüberwachung F-23 Startdrehzahl [Hz] E-36 Klemme X46/13 Digitaleingang P-02 Motorleistung [HP] H-64 Resonanzdämpfung
K-1# Parametersätze
Parametermenüaufbau
DET-758A/D
K-42 [Auto]-Taste auf Keypad F-91 Beschl.-/Verzög.-Zeit E-75 Ausgang 29 Max. Frequenz H-05 Auto-Quittieren (Quittierintervall) H-95 KTY-Sensortyp
K-43 [Reset]-Taste auf Tastenfeld F-92 Digitalpoti speichern bei Netz-Aus E-76 Klemme X30/6 Pulsausgang H-03 Auf Werkseinst. H-96 KTY-Thermistoranschluss
K-44 [Off/Reset]-Taste auf Tastenfeld F-93 Digitalpoti Max. Grenze E-78 Ausgang X30/6 Max. Frequenz H-2# Drehgeberüberwachung H-97 KTY-Schwellwert
K-5# Kopie/Speichern F-94 Digitalpoti Min. Grenze E-8# 24V Drehgeber H-20 Drehgeberüberwachung Funktion AN-## Analoge Ein-/Ausg.
K-50 Tastenfeldkopie F-95 Rampenverzögerung E-80 Kl. 32/33 Drehgeber Aufl. [Pulse/U] H-21 Drehgeber max. Fehlabweichung AN-0# Grundeinstellungen
K-51 Parametersatzkopie E-## Digit. Ein-/Ausgänge E-81 Kl. 32/33 Drehgeber Richtung H-22 Drehgeber Timeout-Zeit AN-00 Signalausfall Zeit
K-6# Passwortschutz E-0# Digitaleingänge E-9# Bussteuerung H-24 Drehgeberüberwachung Funktion AN-01 Signalausfall Funktion
K-60 Hauptmenü Passwort E-00 Schaltlogik E-90 Dig./Relais Ausg. Bussteuerung H-25 Drehgeber Fehler AN-1# Analogeingang 53
K-61 Hauptmenü Zugriff ohne PW E-01 Klemme 18 Digitaleingang E-93 Klemme 27, Wert bei Bussteuerung H-26 Drehgeber-Fehler Timeout-Zeit AN-10 Klemme 53 Skal. Min.Spannung
K-65 Quick-Menü-Passwort E-02 Klemme 19 Digitaleingang E-94 Klemme 27, Wert bei Bus-Timeout H-27 Drehgeber-Fehler Rampe AN-11 Klemme 53 Skal. Max.Spannung
K-66 Quickmenü Zugriff ohne PW E-03 Klemme 27 Digitaleingang E-95 Klemme 29, Wert bei Bussteuerung H-28 Drehgeber-Fehler Rampe Timeout-Zeit AN-12 Klemme 53 Skal. Min.Strom
K-67 Passwort Bus-Zugriff E-04 Klemme 29 Digitaleingang E-96 Klemme 29, Wert bei Bus-Timeout H-29 Drehgeber-Fehler nach Rampen- AN-13 Klemme 53 Skal. Max.Strom
Parameterdatensatz E-05 Klemme 32 Digitaleingang E-97 Klemme X30/6, Wert bei Bussteuerung Timeout AN-14 Klemme 53 Skal. Min.-Soll/ Istwert
F-## Grundlegende Parameter E-06 Klemme 33 Digitaleingang E-98 Klemme X30/6, Wert bei Bus-Timeout H-4# Erweiterte Einstell. AN-15 Klemme 53 Skal. Max.-Soll/ Istwert
F-0# Grundlegend 0 E-07 Klemme 37 Sicherer Stopp C-## Freq.-Regelfunktionen H-40 Regelverfahren AN-16 Klemme 53 Filterzeit
F-05 Motornennspannung E-1# Weitere Rampen C-0# Freq.-Regelfunktionen H-41 Steuerprinzip AN-2# Analogeingang 54
F-04 Grundfrequenz E-10 Beschl.-Zeit 2 C-05 Mehrstufenfrequenz 1-8 H-42 Drehgeber Anschluss AN-20 Klemme 54 Skal. Min.Spannung
F-09 Kick-Start E-11 Verzög.-Zeit 2 C-02 Ausbl. Drehzahl von [UPM] H-43 Drehmomentkennlinie AN-21 Klemme 54 Skal. Max.Spannung
F-02 Betriebsart E-12 Beschl.-Zeit 3 C-01 Ausbl. Drehzahl von [Hz] H-44 Überlast Konst. o. Quadr. Moment AN-22 Klemme 54 Skal. Min.Strom
F-01 Frequenzeinstellung 1 E-13 Verzög.-Zeit 3 C-03 Ausbl. Drehzahl bis [UPM] H-45 Hand/Ort-Betrieb Konfiguration AN-23 Klemme 54 Skal. Max.Strom
F-07 Beschl.-Zeit 1 E-14 Beschl.-Zeit 4 C-04 Ausbl. Drehzahl bis [Hz] H-48 Rechtslauf AN-24 Klemme 54 Skal. Min.-Soll/ Istwert
F-08 Verzög.-Zeit 1 E-15 Verzög.-Zeit 4 C-2# Jog-Einstell. H-46 Gegen-EMK bei 1000 UPM AN-25 Klemme 54 Skal. Max.-Soll/ Istwert
F-03 Max. Ausgangsfrequenz 1 E-2# Digitalausgänge C-20 Festdrehzahl Jog [Hz] H-47 Geber-Offset AN-26 Klemme 54 Filterzeit
F-1# Grundlegend 1 E-20 Klemme 27 Digitalausgang C-21 Festdrehzahl Jog [UPM] H-5# Lastunabh. Einstell. AN-3# Analogeingang X30/11
F-10 Elektronische Überlast E-21 Klemme 29 Digitalausgang C-22 Beschl./Verzög.-Zeit JOG H-50 Motormagnetisierung bei 0 UPM AN-30 Kl.X30/11 Skal. Min. Spannung
F-11 Fremdbelüftung E-24 Relaisfunktion C-23 Verzög.-Zeit Schnellstopp H-51 Min. Drehzahl norm. Magnetis. [UPM] AN-31 Kl.X30/11 Skal. Max.Spannung
AN-34 Kl. X30/11 Skal. Min.-Soll/ Istwert SP-5# Umgebung O-5# Betr. Bus/Klemme PB-44 Zähler: Fehler im Speicher EN-42 Anzahl Slave-Ausnahme-Meldungen
AN-35 Kl. X30/11 Skal. Max.-Soll/ Istwert SP-50 EMV-Filter O-50 Motorfreilauf PB-45 Speicher: Alarmworte EN-8# Dienste
AN-36 Kl. X30/11 Filterzeit SP-51 Zwischenkreiskompensation O-51 Schnellstopp PB-47 Speicher: Fehlercode EN-80 FTP-Server
AN-4# Analogeingang X30/12 SP-52 Lüfterbetrieb O-52 DC Bremse PB-52 Zähler: Fehler Gesamt EN-81 HTTP-Server
AN-40 Klemme X30/12 Skal. Min.Spannung SP-53 Lüfterüberwachung O-53 Start PB-53 Profibus-Warnwort EN-82 SMTP-Service
AN-41 Klemme X30/12 Skal. Max.Spannung SP-55 Ausgangsfilter O-54 Reversierung PB-63 Aktive Baudrate EN-89 Transparent Socket Channel Port
AN-44 Kl. X30/12 Skal. Min.-Soll/ Istwert SP-56 Kapazität Ausgangsfilter O-55 Satzanwahl PB-64 Bus-ID EN-9# Erweiterte Dienste
AN-45 Kl. X30/12 Skal. Max.-Soll/ Istwert SP-57 Induktivität Ausgangsfilter O-56 Festsollwertanwahl PB-65 Profilnummer EN-90 Kabeldiagnose
AN-46 Kl. X30/12 Filterzeit SP-59 Anzahl aktiver Wechselrichter O-57 Auswahl Profidrive OFF2 PB-67 Steuerwort 1 EN-91 MDI-X
AN-5# Analogausgang 42 SP-6# Auto-Reduzier. O-58 Auswahl Profidrive OFF3 PB-68 Zustandswort 1 EN-92 IGMP-Snooping
Parametermenüaufbau
AN-50 Klemme 42 Analogausgang SP-63 Ext. 24 VDC für Option O-8# Drive Ser.-Diagnose PB-71 Datenwerte speichern EN-93 Fehler Kabellänge
AN-51 Kl. 42, Ausgang min. Skalierung SP-7# Weitere Beschl./Verzög. O-80 Zähler Busmeldungen PB-72 Freq.umr. Reset EN-94 Broadcast Storm Schutz
AN-52 Kl. 42, Ausgang max. Skalierung SP-71 S-Form Anfang (Beschl.-Zeit 1) Anfang O-81 Zähler Busfehler PB-80 Definierte Parameter (1) EN-95 Broadcast Storm Filter
AN-53 Klemme X45/3, Wert bei Bussteuerung SP-72 S-Form Anfang (Beschl.-Zeit 1) Ende O-82 Zähler Slavemeldungen PB-81 Definierte Parameter (2) EN-96 Port Mirroring
AN-54 Kl. 42, Wert bei Bus-Timeout SP-73 S-Form Anfang (Verzög.-Zeit 1) Anfang O-83 Zähler Slavefehler PB-82 Definierte Parameter (3) EN-98 Schnittstellenzähler
AN-55 Klemme 42, Ausgangsfilter SP-74 S-Form Anfang (Verzög.-Zeit 1) Ende O-9# Bus-Festdr./Istwerte PB-83 Definierte Parameter (4) EN-99 Medienzähler
AN-6# Analogausgang X30/8 SP-76 Beschl.-/Verzög.-Typ 2 O-90 Bus-Festdrehzahl 1 PB-84 Definierte Parameter (5) EC-## Drehgeber Opt.
AN-60 Klemme X30/8 Analogausgang SP-79 S-Form Anfang (Beschl.-Zeit 2) Anfang O-91 Bus-Festdrehzahl 2 PB-90 Geänderte Parameter (1) EC-1# Inkrementalgeber Schnittstelle
AN-61 Kl. X30/8, Ausgang min. Skalierung SP-80 S-Form Anfang (Beschl.-Zeit 2) Ende DN-## DeviceNet-Feldbus PB-91 Geänderte Parameter (2) EC-10 Signaltyp
AN-62 Kl. X30/8, Ausgang max. Skalierung SP-81 S-Form Anfang (Verzög.-Zeit 2) Anfang DN-0# Grundeinstellungen PB-92 Geänderte Parameter (3) EC-11 Inkremental Auflösung [Pulse/U]
AN-63 Kl. X30/8, Wert bei Bussteuerung SP-82 S-Form Anfang (Verzög.-Zeit 2) Ende DN-00 DeviceNet-Protokoll PB-93 Geänderte Parameter (4) EC-2# Abs.- Wert geber
AN-64 Kl. X30/8, Wert bei Bus-Timeout SP-84 Beschl.-/Verzög.-Typ 3 DN-01 Baudratenauswahl PB-94 Geänderte Parameter (5) EC-20 Protokollauswahl
AN-7# Analogausgang X45/1 SP-87 S-Form Anfang (Beschl.-Zeit 3) Anfang DN-02 MAC-ID Adresse PB-99 Profibus-Versionszähler EC-21 Absolut Auflösung [Positionen/U]
AN-70 Kl. X45/1 Ausgang SP-88 S-Form Anfang (Beschl.-Zeit 3) Ende DN-05 Zähler Übertragungsfehler EN-## Ethernet IP EC-24 SSI-Datenlänge
AN-71 Klemme X45/1 Min. Skalierung SP-89 S-Form Anfang (Verzög.-Zeit 3) Anfang DN-06 Zähler Empfangsfehler EN-0# IP-Einstellungen EC-25 Taktgeschwindigkeit
AN-72 Klemme X45/1 Max. Skalierung SP-90 S-Form Anfang (Verzög.-Zeit 3) Ende DN-07 Zähler Bus-Off EN-00 IP-Adresszuweisung EC-26 SSI-Datentyp
AN-73 Klemme X45/1, Wert bei Bussteuerung SP-92 Beschl.-/Verzög.-Typ 4 DN-1# DeviceNet EN-01 IP-Adresse EC-34 HIPERFACE-Baudrate
AN-74 Kl. X45/1, Wert bei Bus-Timeout SP-95 S-Form Anfang (Beschl.-Zeit 4) Anfang DN-10 Prozessdatentyp EN-02 Subnet Mask EC-6# Überw./Anwend.
AN-8# Analogausgang X45/3 SP-96 S-Form Anfang (Beschl.-Zeit 4) Ende DN-11 Prozessdaten Schreiben Konfiguration EN-03 Standard-Gateway EC-60 Positive Drehgeberrichtung
AN-80 Kl. X45/3 Ausgang SP-97 S-Form Anfang (Verzög.-Zeit 4) Anfang DN-12 Prozessdaten Lesen Konfiguration EN-04 DHCP-Server EC-61 Drehgeber Überwachung
AN-81 Klemme X45/3 Min. Skalierung SP-98 S-Form Anfang (Verzög.-Zeit 4) Ende DN-13 Warnungsparameter EN-05 Lease läuft ab RS-## Resolver aktivier.
AN-82 Klemme X45/3 Max. Skalierung O-## Opt./Schnittstellen DN-14 DeviceNet Sollwert EN-06 Namensserver RS-50 Resolver Pole
DET-758A/D
AN-83 Klemme X45/3, Wert bei Bussteuerung O-0# Grundeinstellungen DN-15 DeviceNet Steuerung EN-07 Domain Name RS-51 Resolver Eingangsspannung
AF-650 GP-Kurzanleitung
AN-84 Kl. X45/3, Wert bei Bus-Timeout O-01 Führungshoheit DN-18 internal_process_data_config_write EN-08 Host-Name RS-52 Resolver Eingangsfrequenz
SP-## Sonderfunktionen O-02 Aktives Steuerwort DN-19 internal_process_data_config_read EN-09 Phys. Adresse RS-53 Übersetzungsverhältnis
SP-0# Fehlereinstellungen O-03 Steuerwort Timeout-Zeit DN-2# COS-Filter EN-1# Verbindung RS-59 Resolver aktivier.
SP-00 Fehlerebenen O-04 Steuerwort Timeout-Funktion DN-20 COS-Filter 1 EN-10 Verb.status Parameterdatenprüfung
SP-1# Netzausfall O-05 Steuerwort Timeout-Ende DN-21 COS-Filter 2 EN-11 Verb.dauer Letzte 10 Änderng.
SP-10 Netzausfall O-06 Timeout Steuerwort quittieren DN-22 COS-Filter 3 EN-12 Auto. Verbindung Seit Werkseinstell.
SP-11 Netzausfall-Spannung O-07 Diagnose Trigger DN-23 COS-Filter 4 EN-13 Verb.geschw. Info/Wartung
SP-12 Netzphasen-Unsymmetrie O-08 Anzeigefilter DN-3# Parameterzugriff EN-14 Verb.duplex ID-0# Betriebsdaten
SP-13 Netzausfall-Schrittfaktor O-1# Regeleinstellungen DN-30 Array Index EN-2# Prozessdaten ID-00 Betriebsstunden
SP-2# Reset/Initialisieren O-10 Steuerwortprofil DN-31 Datenwerte speichern EN-20 Steuerinstanz ID-01 Motorlaufstunden
SP-23 Typencodeeinstellung O-13 Zustandswort Konfiguration DN-32 DeviceNet Revision EN-21 Prozessdaten Schreiben Konfiguration ID-02 kWh-Zähler
SP-24 Stromgrenze Verzögerungszeit O-14 Konfigurierbares Steuerwort STW DN-33 EEPROM speichern EN-22 Prozessdaten Lesen Konfiguration ID-03 Anzahl Netz-Ein
SP-25 Drehmom.grenze Verzögerungszeit O-3# Ser. FU-Schnittstelle DN-34 DeviceNet-Produktcode EN-28 Datenwerte speichern ID-04 Anzahl Übertemperaturen
SP-26 FU-Fehler Abschaltverzögerung O-30 FC-Protokoll DN-39 DeviceNet F-Parameter EN-29 EEPROM speichern ID-05 Anzahl Überspannungen
SP-28 Produktionseinstellungen O-31 Adresse DN-5# DeviceNet-Daten EN-3# EtherNet/IP ID-06 Reset Zähler-kWh
SP-29 Servicecode O-32 FU-Baudrate PB-## Profibus EN-30 Warnungsparameter ID-07 Reset Motorlaufstundenzähler
SP-3# Stromgrenze O-33 Parität/Stoppbits K-11 Programm Satz EN-31 DeviceNet Sollwert ID-1# Trenddaten-Einstellungen
SP-30 Regler P-Verstärkung O-34 Geschätzte Zykluszeit PB-00 Sollwert EN-32 DeviceNet Steuerung ID-10 Trendquelle
SP-31 Regler I-Zeit O-35 FC-Antwortzeit Min.-Delay PB-07 Istwert EN-33 CIP Revision ID-11 Trend-Abtastrate
SP-32 Regler, Filterzeit O-36 FC-Antwortzeit Max.-Delay PB-15 PCD-Schreibkonfiguration EN-34 CIP Produktcode ID-12 Echtzeitkanal Triggerereignis
SP-35 Stall Protection O-37 FC Interchar. Max.-Delay PB-16 PCD-Lesekonfiguration EN-35 EDS-Parameter ID-13 Protokollart
SP-4# Energieeinsparungen O-4# Ser.FU/MC-Schnittst. PB-18 Teilnehmeradresse EN-37 COS Sperrtimer ID-14 Echtzeitkanal Werte vor Trigger
SP-40 Quadr.Mom. Anpassung O-40 Telegrammtyp PB-22 Telegrammtyp EN-38 COS Filter ID-2# Protokollierung
SP-41 Energieeinspar. Min. Magnetisierung O-41 Signal-Parameter PB-23 Signal-Parameter EN-4# Modbus TCP ID-20 Protokoll: Ereignis
SP-42 Energieeinspar. Min. Frequenz O-42 PCD-Schreibkonfiguration PB-27 Parameter bearbeiten EN-40 Status Parameter ID-21 Protokoll: Istwert
SP-43 Motor Cos-Phi O-43 PCD-Lesekonfiguration PB-28 Profibus Steuerung deaktivieren EN-41 Anzahl Slave-Meldungen ID-22 Protokoll: Zeit
27
6 6
6 6
ID-3# Alarm Log DR-32 Bremsleistung/s LC-10 Vergleicher-Operand PI-30 Auswahl Normal-/Invers-Regelung
28
ID-30 Fehlerspeicher: Fehlercode DR-33 Bremsleistung/2 min LC-11 Vergleicher-Funktion PI-31 PID-Prozess Anti-Windup
ID-31 Fehlerspeicher: Wert DR-34 Kühlkörpertemperatur LC-12 Vergleicher-Wert PI-32 PID-Prozess Reglerstart bei
ID-32 Fehlerspeicher: Zeit DR-35 Gerätetemperatur LC-2# Timer PI-33 PID-Prozess P-Verstärkung
ID-4# Typendaten DR-36 Nenn-FU-Strom LC-20 LC-Timer PI-34 PID-Prozess I-Zeit
ID-40 FU-Typ DR-37 Max. Strom Frequenzumrichter LC-4# Logikregeln PI-35 PID-Prozess D-Zeit
ID-41 Leistungsteil DR-38 Logic Contr.Zustand LC-40 Logikregel Boolesch 1 PI-36 PID-Prozess D-Verstärkung/ Grenze
ID-42 Nennspannung DR-39 Steuerkartentemp. LC-41 Logikregel Verknüpfung 1 PI-38 PID-Prozess Vorsteuerung
ID-43 Softwareversion DR-40 Trendspeicher voll LC-42 Logikregel Boolesch 2 PI-39 Bandbreite Ist=Sollwert
ID-46 GE Produkt-Nr. DR-41 Untere Tastenfeld-Statuszeile LC-43 Logikregel Verknüpfung 2 PI-4# Adv. PID-Prozess I
Parametermenüaufbau
ID-47 Leistungsteil Bestellnummer DR-49 Stromfehlerquelle LC-44 Logikregel Boolesch 3 PI-40 PID-Prozess Reset I-Teil
ID-48 Tastenfeld-ID-Nr. DR-5# Soll- & Istwerte LC-5# SL-Programm PI-41 PID-Prozessausgang neg. Begrenzung
ID-49 Steuerkarte SW-Version DR-50 Externer Sollwert LC-51 Logic Controller Ereignis PI-42 PID-Prozessausgang pos. Begrenzung
ID-50 Leistungsteil SW-Version DR-51 Pulssollwert LC-52 Logic Controller Aktion PI-43 PID-Prozess P-Skal.Min.Sollw.
ID-51 Typ Seriennummer DR-52 Istwert [Einheit] B-## Bremsfunktionen PI-44 PID-Prozess P-Skal.Max.Sollw.
ID-53 Leistungsteil Seriennummer DR-53 DigiPot Sollwert B-0# DC Halt/DC Bremse PI-45 PID-Prozess Vorsteuerungsfaktor
ID-6# Install. Optionen DR-6# Anzeig. Ein-/Ausg. B-00 DC-Haltestrom PI-46 Auswahl FF-Normal-/Invers- Steuerwort
ID-60 Option installiert DR-60 Digitaleingänge B-01 DC-Bremsstrom PI-49 PID-Ausgang Normal/Invers- Steuerkar-
ID-61 SW-Version Option DR-61 Schaltereinstellung Klemme 53 B-02 DC-Bremszeit tentemp.
ID-62 Optionsbestellnr. DR-62 Analogeingang 53 B-03 DC-Bremse Ein [UPM] PI-5# Adv. PID-Prozess II
ID-63 Optionsseriennr. DR-63 Schaltereinstellung Klemme 54 B-04 DC-Bremse Ein [Hz] PI-50 PID-Prozess erw. PID
ID-70 Option A DR-64 Analogeingang 54 B-05 Maximaler Sollwert PI-51 PID-Prozess FF-Verstärkung
ID-71 Option A - Softwareversion DR-65 Analogausgang 42 [mA] B-1# Generator. Bremsen PI-52 PID-Prozess FF-Rampe Auf
ID-72 Option B DR-66 Digitalausgänge B-10 Bremsfunktion PI-53 PID-Prozess FF-Rampe Ab
ID-73 Option B - Softwareversion DR-67 Pulseingang 29 [Hz] B-12 Bremswiderstand Leistung (kW) PI-56 PID-Prozess Sollw. Filterzeit
ID-74 Option C1 DR-68 Pulseingang 33 [Hz] B-13 Thermische Überlast Bremsung PI-57 PID-Prozess Istw. Filterzeit
ID-75 Option C0 - Softwareversion DR-69 Pulsausgang 27 [Hz] B-15 Bremswiderstand Test PI-6# PID-Anzeigen
ID-76 Option C2 DR-70 Pulsausgang 29 [Hz] B-16 AC-Bremse max. Strom PI-60 PID-Prozess Abweichung
ID-77 Option C1 - Softwareversion DR-71 Relaisausgänge B-17 Überspannungssteuerung PI-61 PID-Prozessausgang
ID-9# Parameterinfo DR-72 Zähler A B-18 Bremswiderstand Testbedingung PI-62 PID-Prozess begrenz. Ausgang
ID-92 Definierte Parameter DR-73 Zähler B B-19 Überspannungsverstärkung PI-63 PID-Prozess verstärkungsskal. Ausgang
ID-93 Geänderte Parameter DR-74 Präziser Stopp-Zähler B-11 Bremswiderstand (Ohm) SF-## Sonderfunktionen
ID-98 Typendaten DR-75 Analogeingang X30/11 B-2# Mech. Bremse SF-0# Wobbler
AF-650 GP-Kurzanleitung
DET-758A/D
ID-99 Parameter-Metadaten DR-76 Analogeingang X30/12 B-20 Bremse öffnen bei Motorstrom SF-00 Wobbel-Modus
Datenanzeigen DR-77 Analogausgang X30/8 [mA] B-21 Bremse schließen bei Motordrehzahl SF-01 Wobbel Delta-Frequenz [Hz]
DR-0# Anzeigen-Allgemein DR-78 Analogausgang X45/1 [mA] B-22 Bremse schließen bei Motorfrequenz SF-02 Wobbel Delta-Frequenz [%]
DR-00 Steuerwort DR-79 Analogausgang X45/3 [mA] B-23 Mech. Bremse Verzögerungszeit SF-03 Wobbel Deltafreq. Skalierung
DR-01 Sollwert [Einheit] DR-8# Anzeig. Schnittst. B-24 Stopp-Verzögerung SF-04 Wobbel Sprung-Frequenz [%]
DR-02 Sollwert % DR-80 Bus Steuerwort 1 B-25 Bremse lüften Zeit SF-05 Wobbel Sprung-Frequenz [%]
DR-03 Zustandswort DR-82 Feldbus Sollwert 1 B-26 Drehmomentsollw. SF-06 Wobbel Sprungzeit
DR-05 Hauptistwert [%] DR-84 Feldbus-Komm. Option STW B-27 Drehmoment Rampenzeit SF-07 Wobbel-Sequenzzeit
DR-09 Spezielle Anzeige DR-85 FC Steuerwort 1 B-28 Verstärkungsfaktor SF-08 Wobbel Auf/Ab-Zeit
DR-1# Anzeigen-Motor DR-86 FU Sollwert 1 PI-## PID-Regler SF-09 Wobbel-Zufallsfunktion
DR-10 Leistung [kW] 99-30 internal_ProfibusPCD_Config_Write PI-0# PID-Drehzahlregler SF-10 Wobbel-Verhältnis
DR-11 Leistung 99-31 internal_ProfibusPCD_Config_Read PI-00 Drehgeberrückführung SF-11 Max. Wobbel-Verhältnis Zufall
DR-12 Motorspannung DR-9# Bus Diagnose PI-03 Drehzahlregler I-Zeit SF-12 Min. Wobbel-Verhältnis Zufall
DR-13 Frequenz DR-90 Alarmwort PI-04 Drehzahlregler D-Zeit SF-19 Wobbel Deltafreq. skaliert
DR-14 Motorstrom DR-91 Alarmwort 2 PI-05 Drehzahlregler D-Verstärk./ Grenze SF-2# Adv. Startfunktion
DR-15 Frequenz [%] DR-92 Warnwort PI-06 Drehzahlregler Tiefpassfilterzeit SF-20 Hohe Anlaufmomentzeit [s]
DR-16 Drehmoment [Nm] DR-93 Warnwort 2 PI-07 Drehzahlregler Getriebefaktor SF-21 Hoher Anlaufmomentstrom [%]
DR-17 Drehzahl [UPM] DR-94 Ext. Zustandswort PI-08 Drehzahlregler Vorsteuerung SF-22 Blockierter Rotorschutz
DR-18 Therm. Motorschutz Erw. Par.-Datensatz PI-02 Drehzahlregler P-Verstärkung SF-23 Erkennungszeit blockierter Rotor [s]
DR-19 KTY-Sensortemperatur LC-## Logic Controller PI-1# Drehmom. PI-Regler
DR-20 Rotor-Winkel LC-0# LC-Einstellungen PI-12 Drehmom.Regler P-Verstärkung
DR-21 Max. Drehmoment [%] Auflösung LC-00 Logic Controller PI-13 Drehmom.Regler I-Zeit
DR-22 Drehmoment [%] LC-01 SL-Controller Start PI-2# PID-Prozess Istwert
DR-25 Max. Drehmoment [Nm] LC-02 SL-Controller Stopp PI-20 PID-Prozess Istwert 1
DR-3# Anzeigen-FU LC-03 Reset PI-22 PID-Prozess Istwert 2
DR-30 DC-Spannung LC-1# Vergleicher PI-3# PID-Prozessregler
Parametermenüaufbau AF-650 GP-Kurzanleitung
DET-758A/D 29
Warnungen und Alarmmeldunge... AF-650 GP-Kurzanleitung
• Digitaler Reset-Eingangsbefehl
• Auto-Reset
Abschaltsperre
Ein Alarm, der zu einer Abschaltsperre des
Frequenzumrichters führt, erfordert ein Ein- und
Ausschalten des Eingangsstroms. Der Motor läuft aus, bis
LED Warn. LED Alarm
er anhält. Die Logik des Frequenzumrichter funktioniert
Warnung ON OFF
weiter und der Frequenzumrichter-Status wird überwacht.
Alarm OFF ON (blinkt)
Trennen Sie den Eingangsstrom vom Frequenzumrichter
Abschaltblockierung ON ON (blinkt)
und beheben Sie die Fehlerursache. Schalten Sie den
Eingangsstrom dann wieder ein. Dadurch wird der
Frequenzumrichter in einen Abschaltzustand versetzt, wie
30 DET-758A/D
Warnungen und Alarmmeldunge... AF-650 GP-Kurzanleitung
DET-758A/D 31
Warnungen und Alarmmeldunge... AF-650 GP-Kurzanleitung
7 7 50
51
Auto tune Kalibrierungsfehler
Auto tune Motordaten überprüfen:
X
X
52 Auto tune Motornennstrom: X
53 Auto tune Motor zu groß X
54 Auto tune Motor zu klein X
55 Auto tune Daten außerhalb des Bereichs X
56 Auto tune Abbruch X
57 Auto tune Timeout X
58 Auto tune interner Fehler X X
59 Stromgrenze X 4-18 Stromgrenze
61 Istwertfehler (X) (X) 4-30 Drehgeberüber-
wachung Funktion
62 Ausgangsfrequenz Grenze X
63 Mechanische Bremse Fehler (X) 2-20 Bremse öffnen bei
Motorstrom
64 Motorspannung Grenze X
65 Steuerkarte Übertemperatur X X X
66 Temperatur zu niedrig X
67 Optionenmodul neu X
68 Sicherer Stopp (X) (X)1) 5-19 Terminal 37 Safe
Stop
69 Umr. Übertemperatur X X
70 Ung. FU-Konfiguration X
76 Leistungsteil Konfiguration X
77 Red.Leistung X 14-59 Actual Number of
Inverter Units
78 Drehg. Abw. (X) (X) 4-34 Tracking Error
Function
79 Ung. LT-Konfig. X X
80 Werkseinstellungen wiederhergestellt X
83 Illegale Optionskombination X
90 Drehgeber Überwachung (X) (X) 17-61 Drehgeber
Überwachung
91 AI54 Einstellungsfehler X S202
243 Bremse IGBT X X X
244 Kühlkörpertemp. X X X
245 Kühlkörpersensor X X
32 DET-758A/D
Warnungen und Alarmmeldunge... AF-650 GP-Kurzanleitung
7 7
DET-758A/D 33
Technische Daten AF-650 GP-Kurzanleitung
8 Technische Daten
34 DET-758A/D
Technische Daten AF-650 GP-Kurzanleitung
Digitaleingänge:
Programmierbare Digitaleingänge 4 (6)1)
Klemmennummer 18, 19, 271), 291),
32, 33,
Logik PNP oder NPN
Spannungsbereich 0-24 V DC
Spannungsniveau, logisch „0“ PNP < 5 V DC
Spannungsniveau, logisch „1“ PNP > 10 V DC
Spannungsniveau, logisch „0“ NPN2) > 19 V DC
Spannungsniveau, logisch „1“ NPN2) < 14 V DC
Maximale Spannung am Eingang 28 V DC
Pulsfrequenzbereich 0-110 kHz
(Arbeitszyklus) Min. Pulsbreite 4,5 ms
Eingangswiderstand, Ri ca. 4 kΩ
2) Zu weiteren Informationen über Klemme 37 und Sicherer Stopp siehe 3.4.5.7 Klemme 37.
Analogeingänge:
Anzahl Analogeingänge 2
Klemmennummer 53, 54
Betriebsarten Spannung oder Strom
Betriebsartwahl Schalter S201 und Schalter S202
Einstellung Spannung Schalter S201/Schalter S202 = AUS (U)
Spannungsniveau -10 bis +10 V DC (skalierbar)
Eingangswiderstand, Ri ca. 10 kΩ
Max. Spannung ± 20 V
Einstellung Strom Schalter S201/Schalter S202 = EIN (I)
Strombereich 0/4 bis 20 mA (skalierbar)
Eingangswiderstand, Ri ca. 200 Ω
Max. Strom 30 mA
Auflösung der Analogeingänge 10 Bit (+ Vorzeichen)
Genauigkeit der Analogeingänge Max. Abweichung 0,5 % der Gesamtskala
Bandbreite 100 Hz
Die Analogeingänge sind galvanisch von der Versorgungsspannung (PELV) und anderen Hochspannungsklemmen getrennt.
DET-758A/D 35
Technische Daten AF-650 GP-Kurzanleitung
Puls-/Drehgeber-Eingänge:
Programmierbare Puls-/Drehgeber-Eingänge 2/1
Klemmennummer Puls-/Drehgeber 29, 331)
/ 322),
332)
Max. Frequenz an Klemme 29, 32, 33 110 kHz (Gegentakt)
Max. Frequenz an Klemme 29, 32, 33 5 kHz (offener Kollektor)
Min. Frequenz an Klemme 29, 32, 33 4 Hz
Spannungsbereich siehe 8.1.1 Digitaleingänge:
Maximale Spannung am Eingang 28 V DC
Eingangswiderstand, Ri ca. 4kΩ
Pulseingangsgenauigkeit (0,1-1 kHz) Max. Abweichung: 0,1 % der Gesamtskala
Genauigkeit des Drehgebereingangs (1-11 kHz) Max. Abweichung: 0,05 % der Gesamtskala
Die Puls- und Drehgebereingänge (Klemmen 29, 32, 33) sind galvanisch von der Versorgungsspannung PELV (Schutzklein-
spannung – Protective extra low voltage) und anderen Hochspannungsklemmen getrennt.
1) Pulseingänge sind 29 und 33
2) Drehgebereingänge: 32 = A und 33 = B
Digitalausgang:
Programmierbare Digital-/Pulsausgänge 2
Klemmennummer 27, 29 1)
Spannungsniveau bei Digital-/Frequenzausgang 0 – 24 V
Max. Ausgangsstrom (Senke oder Quelle) 40 mA
8 8 Max. Last am Frequenzausgang
Max. kapazitive Last am Frequenzausgang
1 kΩ
10 nF
Minimale Ausgangsfrequenz am Frequenzausgang 0 Hz
Maximale Ausgangsfrequenz am Frequenzausgang 32 kHz
Genauigkeit des Frequenzausgangs Max. Fehler: 0,1 % des vollen Umfangs
Auflösung der Frequenzausgänge 12 Bit
1) Klemme 27 und 29 können auch als Eingang programmiert werden.
Der Digitalausgang ist galvanisch von der Versorgungsspannung PELV (Schutzkleinspannung – Protective extra low voltage) und
anderen Hochspannungsklemmen getrennt.
Analogausgänge:
Anzahl programmierbarer Analogausgänge 1
Klemmennummer 42
Strombereich am Analogausgang 0/4 - 20 mA
Max. Last gegen Masse am Analogausgang 500 Ω
Genauigkeit am Analogausgang Max. Fehler: 0,5 % der Gesamtskala
Auflösung am Analogausgang 12 Bit
Der Analogausgang ist galvanisch von der Versorgungsspannung (PELV) und anderen Hochspannungsklemmen getrennt.
Steuerkarte, 24 V DC-Ausgang:
Klemmennummer 12, 13
Ausgangsspannung 24 V +1, -3 V
Max. Last 200 mA
Die 24-V-DC-Versorgung ist galvanisch von der Versorgungsspannung (PELV) getrennt, hat jedoch das gleiche Potential wie die
Analog- und Digitalein- und -ausgänge.
Steuerkarte, 10 V DC-Ausgang:
Klemmennummer 50
Ausgangsspannung 10,5 V ±0,5 V
Max. Last 15 mA
Die 10-V-DC-Versorgung ist von der Versorgungsspannung (PELV (Schutzkleinspannung - Protective extra low voltage)) und
anderen Hochspannungsklemmen galvanisch getrennt.
36 DET-758A/D
Technische Daten AF-650 GP-Kurzanleitung
3) UL-Anwendungen 300 V AC 2 A
DET-758A/D 37
Technische Daten AF-650 GP-Kurzanleitung
• Die Temperaturüberwachung des Kühlkörpers stellt sicher, dass der Frequenzumrichter abgeschaltet wird, wenn
die Temperatur einen vordefinierten Wert erreicht. Eine Überlastabschaltung durch hohe Temperatur kann erst
zurückgesetzt werden, nachdem die Kühlkörpertemperatur wieder unter die in den folgenden Tabellen festge-
legten Werte gesunken ist (dies ist nur eine Richtschnur: Temperaturen können je nach Leistungsgröße,
Gerätegröße, Schutzart usw. verschieden sein).
• Wenn eine Netzphase fehlt, schaltet der Frequenzumrichter ab oder gibt eine Warnung aus (abhängig von der
Last).
• Die Überwachung der Zwischenkreisspannung stellt sicher, dass der Frequenzumrichter abgeschaltet wird, wenn
die Zwischenkreisspannung zu gering oder zu hoch ist.
• Der Frequenzumrichter überprüft ständig, ob kritische Werte von Innentemperatur, Laststrom, Hochspannung im
Zwischenkreis oder niedrige Motordrehzahlen vorliegen. Als Reaktion auf einen kritischen Wert kann der
Frequenzumrichter die Taktfrequenz anpassen und/oder den Schaltmodus zur Leistungssicherung des
Frequenzumrichters ändern.
38 DET-758A/D
Installation AF-650 GP-Kurzanleitung
9 Installation
9.1.1 Sicherungen
Es wird empfohlen, versorgungsseitig Sicherungen und/oder Trennschalter als Schutz bei Defekt von Bauteilen im
Frequenzumrichter (erster Fehler) zu verwenden.
HINWEIS
Dies ist obligatorisch, um Übereinstimmung mit IEC 60364 für CE oder NEC 2009 für UL sicherzustellen.
WARNUNG
Personal und Anlagen müssen gegen die Folgen eines Bauteildefekts im Frequenzumrichter geschützt werden.
Abzweigschutz
Zum Schutz der Installation vor elektrischen Gefahren und Bränden müssen alle Abzweigkreise in einer Installation, in
Getrieben, Maschinen usw. gemäß nationalen und internationalen Richtlinien vor Kurzschluss und Überstrom geschützt sein.
HINWEIS
Die gegebenen Empfehlungen bieten keinen Abzweigschutz zur Erfüllung der UL-Anforderungen.
Kurzschluss-Schutz:
GE empfiehlt die Verwendung der unten aufgeführten Sicherungen / Trennschalter zum Schutz von Wartungspersonal und
Gegenständen im Falle einer Bauteilstörung im Frequenzumrichter.
9 9
Überstromschutz:
Der Frequenzumrichter bietet Überlastschutz, um Lebensgefahren zu begrenzen und Sachschäden sowie Brandgefahr
aufgrund überhitzender Kabel in der Installation zu vermeiden. Der Frequenzumrichter verfügt über einen externen
Überstromschutz (4-18 Stromgrenze), der zum vorgeschalteten Überlastschutz verwendet werden kann (außer für UL-
Anwendungen). Darüber hinaus können Sicherungen oder Trennschalter verwendet werden, um der Installation den
erforderlichen Überstromschutz zu bieten. Überstromschutz muss immer gemäß den einschlägigen Vorschriften ausgeführt
werden.
WARNUNG
Im Falle einer Fehlfunktion kann das Nichtbeachten der Empfehlung zu Gefahren für den Bediener und Schäden am
Frequenzumrichter und anderen Geräten führen.
In den folgenden Tabellen werden die empfohlenen Nennströme aufgelistet. Empfohlene Sicherungen für kleine bis mittlere
Leistungsgrößen entsprechen dem Typ gG. Bei größeren Leistungen werden aR-Sicherungen empfohlen. Leistungstrenn-
schalter können unter der Voraussetzung verwendet werden, dass sie die dem Frequenzumrichter zugeführte Energie auf
ein Niveau begrenzen, das dem der Sicherungen entspricht oder niedriger ist.
Wenn Sicherungen/Trennschalter gemäß den Empfehlungen verwendet werden, werden mögliche Schäden am Frequen-
zumrichter hauptsächlich auf Schäden innerhalb des Geräts beschränkt.
DET-758A/D 39
Installation AF-650 GP-Kurzanleitung
9.1.2 CE-Konformität
Sicherungen und Trennschalter müssen zwingend der IEC 60364 entsprechen. GE empfiehlt die Auswahl eines der folgenden
Elemente.
Die unten stehenden Sicherungen sind für die Verwendung in einer Schaltung geeignet, die 100.000 Aeff (symmetrisch),
240 V, 480 V, 500 V oder 600 V liefert (je nach Nennspannung des Frequenzumrichters). Mit der korrekten Sicherung liegt
der Nennkurzschlussstrom (SCCR) des Frequenzumrichters bei 100.000 Aeff.
9 9 30
37 / 50
aR-200
aR-250
aR-200
aR-250
40 DET-758A/D
Installation AF-650 GP-Kurzanleitung
90 gG-300 gG-300
DET-758A/D 41
Installation AF-650 GP-Kurzanleitung
42 DET-758A/D
Installation AF-650 GP-Kurzanleitung
DET-758A/D 43
Installation AF-650 GP-Kurzanleitung
Sicherungen und Trennschalter müssen obligatorisch der NEC 2009 entsprechen. Wir empfehlen die Auswahl eines der
folgenden Bauteile.
Die unten stehenden Sicherungen sind für die Verwendung in einer Schaltung geeignet, die 100.000 Aeff (symmetrisch), 240
V, 480 V oder 600 V liefert (je nach Nennspannung des Frequenzumrichters). Mit der korrekten Sicherung liegt der
Nennkurzschlussstrom (SCCR) des Frequenzumrichters bei 100.000 A.
44 DET-758A/D
Installation AF-650 GP-Kurzanleitung
DET-758A/D 45
Installation AF-650 GP-Kurzanleitung
9 9 [kW]
0,37-0,75
JFHR2
FWH-6
J
HSJ-6
JFHR21)
-
JFHR2
-
1,5-2,2 FWH-10 HSJ-10 - -
3,7 FWH-20 HSJ-20 - -
5,5 FWH-25 HSJ-25 - -
7,5 FWH-30 HSJ-30 - -
11 FWH-40 HSJ-40 - -
15 FWH-50 HSJ-50 - -
18,5 FWH-60 HSJ-60 - -
22 FWH-80 HSJ-80 - -
30 FWH-100 HSJ-100 - -
37 FWH-125 HSJ-125 - -
45 FWH-150 HSJ-150 - -
55 FWH-200 HSJ-200 A50-P-225 L50-S-225
75 FWH-250 HSJ-250 A50-P-250 L50-S-250
46 DET-758A/D
Installation AF-650 GP-Kurzanleitung
1) Die dargestellten 170M-Sicherungen von Bussmann verwenden den optischen -/80-Kennmelder. Die Kennmelder-
sicherungen –TN/80 Typ T, -/110 oder TN/110 Typ T derselben Größe und Stromstärke können ersetzt werden.
DET-758A/D 47
Installation AF-650 GP-Kurzanleitung
48 DET-758A/D
Installation AF-650 GP-Kurzanleitung
** Zur Erfüllung der UL-Anforderungen kann jede UL-gelistete Sicherung mit mindestens 500 V und dazugehörigem Nennstrom verwendet werden.
DET-758A/D 49
0 10
50
Leistung [kW] Schutzart Netz Motor Zwischenkreiskopplung Bremse Masse*
Anzugs- Anzugs- Leiterquer- Anzugs-
Leiterquer- Leiterquer- Anzugs- Anzugs- Leiterquer-
drehmo- drehmo- schnitt drehmo-
200-240V 380-480V 525-600V 525-690V schnitt [mm2 schnitt [mm2 drehmo- drehmo- schnitt [mm2
ment ment [mm2 ment
(AWG)] (AWG)] ment [Nm] ment [Nm] (AWG)]
[Nm] [Nm] (AWG)] [Nm]
10.1 Kabel
0,25-2,2 k
0,37-4 kW 0,75-4 kW IP20
W
3,7 kW 5,5-7,5 kW 5,5-7,5 kW IP20
4 (10) 4 (10) 4 (10) 4 (10)
IP55 1,8 1,8
0,25-3,7 k
0,37-7,5 kW 0,75-7,5 kW oder
W 1,8 1,8
IP66
Klemme und entsprechender D...
DET-758A/D
IP55 14 / 124 14 / 124 14 / 124 14 / 124
30-37 kW 55-75 kW 55-75 kW 30-75 kW oder 120 (4/0) 120 (4/0) 120 (4/0) 120 (4/0)
IP66
90-132 k 2x70
90-110 kW Alle 2x70 (2x2/0) 2x70 (2x2/0) 2x70 (2x2/0)
W (2x2/0)
9.5 / 84 2x185
160-315 k 2x185 2x185
132-200 kW Alle (2x350 MC
W (2x350 MCM) (2x350 MCM)
M) 2x185
4x240 (2x350 MCM)
355-560 k 19 / 168 4x240 19 / 168 4x240 9.5 / 84 19 / 168
250-400 kW Alle (4x500 MC
W (4x500 MCM) (4x500 MCM)
M)
630-800 k 8x150 19 / 168 4x185
450-630 kW Alle 4x120
W 8x240 (8x300 MCM) (4x350 MCM)
(4x250 MC
900-1000 (8x500 MCM) 12x150 6x185
710-800 kW Alle M)
kW (12x300 MCM) (6x350 MCM)
* Maximale Leitungsgröße gemäß nationalen Vorschriften
Sécurité Guide rapide de l'AF-650 GP
1 Sécurité 1 1
AVERTISSEMENT AVERTISSEMENT
DÉMARRAGE IMPRÉVU ! Indique une situation potentiellement dangereuse qui, si
Lorsque le variateur de fréquence est connecté à l'alimen- elle n'est pas évitée, peut entraîner des blessures graves ou
tation secteur CA, le moteur peut démarrer à tout le décès.
moment. Le variateur de fréquence, le moteur et tout
équipement entraîné doivent être prêts à fonctionner. S'ils
ne sont pas en état prêt à fonctionner alors que le ATTENTION
variateur est relié au secteur, cela peut entraîner la mort, Indique une situation potentiellement dangereuse qui, si
des blessures graves ou des dégâts matériels. elle n'est pas évitée, peut entraîner des blessures superfi-
cielles à modérées. Ce signe peut aussi être utilisé pour
Démarrage imprévu mettre en garde contre des pratiques non sûres.
Lorsque le variateur de fréquence est connecté à l'alimen-
tation secteur CA, le moteur peut être démarré par un
commutateur externe, un ordre du bus série, un signal de
ATTENTION
Indique une situation qui peut entraîner des dégâts
référence d'entrée ou du fait d'une condition de panne
matériels.
supprimée. Prendre les précautions appropriées pour éviter
tout démarrage imprévu.
REMARQUE!
AVERTISSEMENT Met en évidence une information qui doit être attenti-
TEMPS DE DÉCHARGE ! vement prise en considération pour éviter toute erreur ou
Les variateurs de fréquence contiennent des condensateurs toute utilisation non optimale de l'équipement.
dans le circuit intermédiaire qui peuvent rester chargés
même lorsque l'alimentation CA est déconnectée. Pour Homologations
éviter les dangers liés à l'électricité, couper l'alimentation
CA du variateur de fréquence avant d'entreprendre tout
entretien ou réparation et attendre pendant le temps
spécifié dans le Tableau 1.1. Le non-respect du temps
d'attente spécifié après la mise hors tension avant tout
entretien ou réparation peut entraîner le décès ou des
blessures graves.
DET-758A/F 1
Introduction Guide rapide de l'AF-650 GP
2 Introduction
2 2
REMARQUE!
Se reporter au Manuel d'utilisation de l'AF-650 GP pour les autres tailles d'unité.
2 DET-758A/F
Installation Guide rapide de l'AF-650 GP
3 Installation
• Garder le manuel, les dessins et les schémas à • Un dégagement en haut et en bas doit être
portée de main pour consulter les instructions prévu pour le refroidissement. Généralement, un
d'installation et de fonctionnement détaillées. Le dégagement de 100-225 mm (4-10 pouces) est
présent manuel doit rester à portée de main des nécessaire. Voir l'Illustration 3.1 pour connaître les
opérateurs de l'équipement. exigences de dégagement.
• Placer l'équipement aussi près que possible du • Le montage incorrect peut entraîner une
moteur. Maintenir les câbles du moteur aussi surchauffe et une performance réduite.
courts que possible. Vérifier les caractéristiques • Le déclassement doit être envisagé en cas de
du moteur pour connaître les tolérances exactes. températures entre 40 °C (104 °F) et 50 °C (122
Ne pas dépasser °F) et d'une altitude de 1000 m (3300 pieds) au-
• 300 m (1000 pieds) pour les câbles du dessus du niveau de la mer. Consulter le Manuel
moteur non blindés de configuration de l'équipement pour des
renseignements détaillés.
• 150 m (500 pieds) pour les câbles
blindés.
DET-758A/F 3
Installation Guide rapide de l'AF-650 GP
3.3.2 Levage
L'élément A est une plaque arrière correctement installée
pour que la circulation d'air nécessaire refroidisse l'unité.
• Vérifier le poids de l'unité pour déterminer la
méthode de levage la plus sûre.
3.3.3 Installation
4 DET-758A/F
Installation Guide rapide de l'AF-650 GP
• Une fois que la tension a été appliquée, vérification de la puissance d'entrée et de la puissance du moteur ;
programmation des bornes de commande selon leurs fonctions prévues
A = analogique, D = digitale
La borne 37 est utilisée pour l'arrêt de sécurité. Pour les instructions relatives à l'installation de l'arrêt de sécurité, se reporter
au Manuel de configuration.
*L'option hâcheur de freinage installée en usine doit être commandée pour utiliser les résistances de freinage dynamique.
**Disponible lors de la commande de l'option hâcheur de freinage sur les variateurs de taille d'unité 23 ou supérieure.
DET-758A/F 5
Installation Guide rapide de l'AF-650 GP
ATTENTION
ISOLATION DU CÂBLAGE !
Acheminer les câbles d'alimentation d'entrée, du moteur et
de commande dans trois conduits métalliques ou utiliser
un câble blindé pour une bonne isolation du bruit haute
fréquence. Le non-respect de cette séparation des câbles
peut entraîner une performance amoindrie du variateur de
fréquence et des équipements liés.
6 DET-758A/F
Installation Guide rapide de l'AF-650 GP
• Un fil de terre dédié est nécessaire pour l'alimen- 3.4.2.2 Mise à la terre à l'aide d'un câble
tation d'entrée, la puissance du moteur et le blindé
câblage de commande.
• Utiliser les brides fournies avec l'équipement pour Les brides de mise à la terre sont fournies pour le câblage
des raccordements à la terre corrects. du moteur (voir l'Illustration 3.6).
DET-758A/F 7
Installation Guide rapide de l'AF-650 GP
AVERTISSEMENT
TENSION INDUITE !
Acheminer séparément les câbles moteur de sortie
3 3 provenant de plusieurs variateurs de fréquence. La tension
induite des câbles moteur de sortie acheminés ensemble
peut charger les condensateurs de l'équipement, même
lorsque l'équipement est hors tension et verrouillé. Le fait
de ne pas acheminer les câbles moteur de sortie
séparément peut entraîner le décès ou des blessures
graves.
• Des caches amovibles pour câbles moteur ou des Illustration 3.7 Exemple de câblage du moteur, du secteur et de
panneaux d'accès sont prévus en bas des unités la terre
IP21 et supérieures (NEMA 1, 12 et 4/4X intérieur).
8 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 9
Installation Guide rapide de l'AF-650 GP
10 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 11
Installation Guide rapide de l'AF-650 GP
3.4.5.6 Commutateurs des bornes 53 et 54 sécurité désactive la tension de contrôle des semi-
conducteurs de puissance de l'étage de sortie du variateur,
• Les bornes d'entrées analogiques 53 et 54 ce qui empêche la génération de la tension requise pour
permettent de choisir des signaux d'entrée de faire tourner le moteur. Lorsque l'arrêt de sécurité (borne
tension (-10 à 10 V) ou de courant (0/4-20 mA). 37) est activé, le variateur émet une alarme, arrête l'unité
et fait tourner le moteur en roue libre jusqu'à l'arrêt. Un
3 3 • Couper l'alimentation du variateur avant de
redémarrage manuel est nécessaire. La fonction d'arrêt de
changer la position des commutateurs.
sécurité peut être utilisée pour arrêter le variateur dans les
• Régler les commutateurs A53 et A54 pour situations d'urgence. En mode de fonctionnement normal
sélectionner le type de signal. U sélectionne la lorsque l'arrêt de sécurité n'est pas nécessaire, utiliser
tension, I sélectionne le courant. plutôt la fonction d'arrêt habituelle du variateur de
fréquence. Lorsque le redémarrage automatique est utilisé,
• Les commutateurs sont accessibles lorsque le
les exigences de la norme ISO 12100-2, paragraphe 5.3.2.5
Clavier a été retiré (voir l'Illustration 3.13). Noter
que certaines cartes d'option disponibles pour doivent être remplies.
l'unité peuvent cacher ces commutateurs. Elles Conditions de responsabilité
doivent donc être retirées pour modifier les Il incombe à l'utilisateur de s'assurer que le personnel qui
réglages des commutateurs. Toujours mettre installe et utilise la fonction d'arrêt de sécurité :
l'unité hors tension avant de démonter les cartes
d'option.
• a lu et compris les réglementations de sécurité
concernant la santé et la sécurité, et la
• La valeur par défaut de la borne 53 concerne le prévention des accidents ;
signal de référence de vitesse en boucle ouverte
réglé dans le par. DR-61 Régl.commut.born.53.
• a compris les consignes générales et de sécurité
fournies dans cette description et dans la
• La valeur par défaut de la borne 54 concerne le description détaillée du Manuel de configuration ;
signal de retour en boucle fermée réglé dans le
par. DR-63 Régl.commut.born.54.
• a une bonne connaissance des normes générales
et de sécurité applicables à l'application
spécifique.
L'utilisateur est défini comme : l'intégrateur, l'opérateur, le
personnel d'entretien, le personnel de maintenance.
Normes
L'utilisation de l'arrêt de sécurité sur la borne 37 oblige
l'utilisateur à se conformer à toutes les dispositions de
sécurité, à savoir les lois, les réglementations et les
directives concernées. La fonction d'arrêt de sécurité
optionnelle est conforme aux normes suivantes :
EN 954-1 : 1996 catégorie 3
CEI 60204-1 : 2005 catégorie 0 - arrêt non
contrôlé
CEI 61508 : 1998 SIL2
CEI 61800-5-2 : 2007 – fonction d'arrêt sûr du
couple
CEI 62061 : 2005 SIL CL2
ISO 13849-1 : 2006 catégorie 3 PL "d"
130BT310.10
ISO 14118 : 2000 (EN 1037) – prévention d'un
Illustration 3.13 Emplacement des commutateurs des bornes 53 démarrage imprévu
et 54 et du commutateur de terminaison du bus Les informations et instructions du Manuel d'utilisation ne
sont pas suffisantes pour utiliser la fonctionnalité d'arrêt de
sécurité de manière correcte et sûre. Les informations et
3.4.5.7 Borne 37 instructions correspondantes du Manuel de configuration
doivent être suivies.
Borne 37, Fonction d'arrêt de sécurité
Le AF-650 GP est disponible avec une fonctionnalité d'arrêt
de sécurité via la borne de commande 37. L'arrêt de
12 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 13
Installation Guide rapide de l'AF-650 GP
3 3
Illustration 3.15 Installation pour obtenir une catégorie d'arrêt 0 (EN 60204-1) avec catégorie de sécurité 3 (EN 954-1)/PL "d" (ISO 13849-1).
14 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 15
Démarrage et test de foncti... Guide rapide de l'AF-650 GP
4.1 Pré-démarrage
4.1.1 Inspection de sécurité
4 4 AVERTISSEMENT
HAUTE TENSION !
Si les connexions d'entrée et de sortie ont été raccordées
de manière incorrecte, il y a un risque de haute tension à
ces bornes. Si les fils d'alimentation de plusieurs moteurs
sont mal acheminés dans un même conduit, il existe un
risque de courant de fuite qui charge les condensateurs au
sein du variateur, même si celui-ci est déconnecté de
l'entrée secteur. Pour le démarrage initial, ne faire aucune
supposition concernant les composants de puissance.
Suivre les procédures de pré-démarrage. Le non-respect de
ces procédures pourrait entraîner des blessures ou
endommager l'équipement.
16 DET-758A/F
Démarrage et test de foncti... Guide rapide de l'AF-650 GP
ATTENTION
Avant de mettre l'appareil sous tension, inspecter l'ensemble de l'installation de la façon décrite dans le Tableau 4.1. Cocher
les éléments une fois l'inspection finie.
Inspecter Description ☑
Équipement auxiliaire • Rechercher les équipements auxiliaires, commutateurs, sectionneurs ou fusibles
d'entrée/disjoncteurs qui peuvent se trouver du côté puissance d'entrée du 4 4
variateur de fréquence ou du côté sortie du moteur. S'assurer qu'ils sont prêts
pour une exploitation à plein régime.
Passage des câbles • Vérifier que le câblage de l'alimentation, le câblage du moteur et le câblage de
commande sont séparés ou placés dans trois conduits métalliques distincts
pour obtenir une isolation des bruits haute fréquence.
Espace pour le refroidissement • Veiller à ce que le dégagement en haut et en bas soit adéquat pour assurer la
circulation de l'air à des fins de refroidissement.
Considérations environne- • Consulter l'étiquette de l'équipement pour connaître les limites de température
mentales ambiante de fonctionnement maximum.
Fusibles et disjoncteurs • Vérifier que les fusibles et les disjoncteurs sont adaptés.
• Vérifier que tous les fusibles sont correctement insérés et en bon état et que
tous les disjoncteurs sont en position ouverte.
Mise à la terre • L'unité nécessite un fil de terre dédié depuis son châssis jusqu'à la terre du
bâtiment.
Intérieur du panneau • Vérifier que l'intérieur de l'unité est exempt de saletés, de particules
métalliques, d'humidité et de corrosion.
DET-758A/F 17
Démarrage et test de foncti... Guide rapide de l'AF-650 GP
Inspecter Description ☑
Vibrations • Vérifier que l'unité est montée solidement ou que des supports amortisseurs
sont utilisés si nécessaire.
18 DET-758A/F
Démarrage et test de foncti... Guide rapide de l'AF-650 GP
Lorsque le par. H-48 Clockwise Direction est réglé sur [0]* • Augmenter la limite de courant au par.
Normal (sens horaire par défaut) : F-43 Limite de courant.
4a. Vérifier que le moteur tourne dans le sens • Augmenter la limite de couple au par.
horaire. F-40 Limiteur couple (entraînement).
5a. Vérifier que la flèche de direction du Clavier Si des problèmes de décélération sont décelés :
est dans le sens horaire.
Lorsque le par. H-48 Clockwise Direction est réglé sur [1] • Si des avertissements ou des alarmes se
Inverse (sens antihoraire) : produisent, consulter le chapitre 7 Avertissements
4b. Vérifier que le moteur tourne en sens et alarmes.
antihoraire.
• Vérifier que les données du moteur ont été
5b. Vérifier que la flèche de direction du Clavier correctement saisies.
est dans le sens antihoraire.
• Augmenter le temps de rampe au par. F-08 Temps
décél. 1
DET-758A/F 19
Démarrage et test de foncti... Guide rapide de l'AF-650 GP
REMARQUE!
Les sections 4.1 Pré-démarrage à 4.6 Test de commande
4 4 locale de ce chapitre concernent les procédures de mise
sous tension du variateur, de la programmation de base,
de la configuration et du test de fonctionnement.
ATTENTION
DÉMARRAGE DU MOTEUR !
S'assurer que le moteur, le système et tous les
équipements rattachés sont prêts à démarrer. Il incombe à
l'utilisateur de garantir le fonctionnement sûr dans toutes
les conditions d'exploitation. S'ils n'étaient pas prêts, cela
pourrait entraîner des blessures ou des dégâts matériels.
20 DET-758A/F
Interface utilisateur Guide rapide de l'AF-650 GP
5 Interface utilisateur
REMARQUE!
Le contraste de l'affichage peut être réglé en appuyant sur
[STATUS] et les touches haut/bas.
a. Zone d'affichage.
b. Touches de menu de l'écran pour changer
l'affichage afin de montrer les options d'état, la
programmation ou l'historique des messages
d'erreur.
c. Touches de navigation pour les fonctions de
programmation, le déplacement du curseur et la
commande de vitesse en mode local. Des voyants
d'état se trouvent aussi dans cette zone.
DET-758A/F 21
Interface utilisateur Guide rapide de l'AF-650 GP
22 DET-758A/F
Interface utilisateur Guide rapide de l'AF-650 GP
Les touches de navigation servent à programmer des Les touches d'exploitation se trouvent en bas du Clavier.
fonctions et à déplacer le curseur à l'écran. Elles peuvent
aussi permettre de commander la vitesse en mode local
(hand). Trois voyants d'état du variateur se trouvent
également dans cette zone.
Touche Fonction
Hand Appuyer sur cette touche pour démarrer le
variateur en commande locale.
• Utiliser les touches de navigation pour
contrôler la vitesse du variateur.
DET-758A/F 23
Interface utilisateur Guide rapide de l'AF-650 GP
24 DET-758A/F
Interface utilisateur Guide rapide de l'AF-650 GP
8. L'alarme 80 s'affiche.
9. Appuyer sur [Reset] pour revenir au mode
d'exploitation.
• ID-04 Surtemp.
• ID-05 Surtension
DET-758A/F 25
6 6
F-11 Ventil. ext. mot. E-24 Fonction relais C-23 Temps décél. arrêt rapide H-50 Magnétisation moteur à vitesse nulle
26
6.1.1 Structure du menu
principal F-12 Entrée thermistance mot. E-26 Relais, retard ON C-24 Type rampe arrêt rapide H-51 Magnétis. normale vitesse min [tr/min]
F-18 Vit. mot., limite infér. [tr/min] E-27 Relais, retard OFF C-25 Rapport rampe S arrêt rapide début H-52 Magnétis. normale vitesse min [Hz]
F-16 Vit.mot., limite infér. [Hz] E-3# Entrées dig. X46 déc H-53 Changement de modèle fréquence
Process clavier F-17 Vit.mot., limite supér. [tr/min] E-30 E.digit.born. X46/1 C-26 Rapport rampe S arrêt rapide fin déc H-54 Réduct° tens° en affaiblisst de champ
K-0# Régl. basiq. clavier F-15 Vit.mot., limite supér. [Hz] E-31 E.digit.born. X46/3 C-3# Fréq. régl. 2 et 3 H-55 Caract. V/f - U
K-01 Langue F-2# Fondamental 2 E-32 E.digit.born. X46/5 C-30 Ctrl de fréquence 2 H-56 Caract. V/f - F
K-02 Unité vit. mot. F-24 Tps maintien E-33 E.digit.born. X46/7 C-34 Ctrl de fréquence 3 H-58 Courant impuls° test démarr. volée
K-03 Réglages régionaux F-25 Fonction au démar. E-34 E.digit.born. X46/9 P-## Données moteur H-59 Fréq. test démarr. à la volée
K-04 État exploi. à mise ss tension F-22 Vit.de dém.[tr/mn] E-35 E.digit.born. X46/11 P-0# Données moteur H-6# Par.dépend. charge
K-09 Surv. performance F-23 Vit.de dém.[Hz] E-36 E.digit.born. X46/13 P-07 Puissance moteur [kW] H-61 Compens. de charge à vitesse élevée
K-1# Gest° proc.clavier F-29 Courant Démar. E-5# ModeE/S-extens°E/S P-02 Puissance moteur [HP] H-64 Amort. résonance
K-10 Process actuel F-26 Bruit (fréq.port.) E-51 Mode born.27 P-03 Courant moteur H-65 Tps amort.résonance
K-11 Edit process F-27 Tonalité mot. aléatoire E-52 Mode born.29 P-06 Vitesse de base H-66 Courant min. à faible vitesse
Structure du menu des param...
K-12 Ce réglage lié à F-28 Compensation temps mort E-53 E.digit.born. X30/2 P-05 Couple nominal cont. moteur H-7# Avert. réglables
K-13 Lecture : réglages joints F-3# Fondamental 3 E-54 E.digit.born. X30/3 P-04 Réglage automatique H-70 Avertis. courant bas
K-14 Lecture : édition réglages/canal F-37 Type modulation av. E-55 E.digit.born. X30/4 P-01 Pôles moteur H-71 Avertis. courant haut
K-2# Affichage clavier F-38 Surmodulation E-56 S.digit.born. X30/6 (OPCGPIO) P-09 Comp. gliss. H-72 Avertis. vitesse basse
K-20 Affich. ligne 1.1 petit F-4# Fondamental 4 E-57 S.digit.born. X30/7 (OPCGPIO) P-10 Cste tps comp.gliss. H-73 Avertis. vitesse haute
K-21 Affich. ligne 1.2 petit F-40 Limiteur couple (entraînement) E-6# Entrée impulsions P-2# Sélection Moteur H-74 Avertis. référence basse
K-22 Affich. ligne 1.3 petit F-41 Limiteur couple (freinage) E-60 F.bas born.29 P-20 Construction moteur H-75 Avertis. référence haute
K-23 Affich. ligne 2 grand F-43 Limite de courant E-61 F.haute born.29 P-3# Données av. moteur H-76 Avertis.retour bas
K-24 Affich. ligne 3 grand F-5# Réf. étendues E-62 Val.ret./Réf.bas.born. 29 P-30 Résistance stator (Rs) H-77 Avertis.retour haut
K-25 Démarrage rapide F-50 Plage de réf. E-63 Val.ret./Réf.haut.born. 29 P-31 Résistance rotor (Rr) H-78 Surv. phase mot.
K-3# Lect.par. clavier F-51 Unité référence/retour E-64 Tps filtre pulses/29 P-33 Réactance fuite stator (X1) H-8# Réglages arrêts
K-30 Unité pour affich. client. F-52 Référence minimale E-65 F.bas born.33 P-34 Réactance de fuite rotor (X2) H-87 Type de charge
K-31 Valeur min. de lect.paramétr. F-53 Réf. max. E-66 F.haute born.33 P-35 Réactance secteur (Xh) H-88 Inertie min.
K-32 Valeur max de lect.paramétr. F-54 Fonction référence E-67 Val.ret./Réf.bas.born. 33 P-36 Résistance perte de fer (Rfe) H-89 Inertie maximale
K-37 Affich. texte 1 F-6# Références E-68 Val.ret./Réf.haut.born. 33 P-37 Inductance axe d (Ld) H-80 Fonction à l'arrêt
K-38 Affich. texte 2 F-62 Rattrap/ralentiss E-69 Tps filtre pulses/33 H-## Param. haute perf H-81 Vit. min. pour fonct. à l'arrêt [tr/min]
K-39 Affich. texte 3 F-64 Réf.prédéf.relative E-7# Sortie impulsions H-0# Opérat° haute perf H-82 Vit. min. pour fonct. à l'arrêt [Hz]
K-4# Touches du clavier F-68 Échelle réf.relative E-70 Fréq.puls./S.born.27 H-09 Mode démar. H-83 Fonction de stop précis
K-40 Touche [Hand] du clavier F-9# Potentiomètre digit E-72 Fréq. max. sortie impulsions 27 H-07 Type tps accél./décél. 1 H-84 Valeur compteur stop précis
DET-758A/F
K-41 Touche [Off] du clavier F-90 Dimension de pas E-73 Fréq.puls./S.born.29 H-08 Verrouillage inversion H-85 Tempo. arrêt compensé en vitesse
Guide rapide de l'AF-650 GP
K-42 Touche [Auto] sur clavier F-91 Tps accél./décél. E-75 Fréq. max. sortie impulsions 29 H-04 Auto-reset (nb) H-9# T° moteur
K-43 Touche [Reset] du clavier F-92 Restauration de puissance E-76 Fréq.puls./S.born.X30/6 H-05 Reset auto (intervalle de reset) H-95 Type de capteur KTY
K-44 Touche [Off/Reset] sur clavier F-93 Limite maximale E-78 Fréq. max. sortie impulsions X30/6 H-03 Restaura° régl.usine H-96 Entrée thermistance KTY
K-5# Copie/Sauvegarde F-94 Limite minimale E-8# Entrée cod. 24V H-2# Surv. retour mot. H-97 Niveau de seuil KTY
K-50 Copie clavier F-95 Retard rampe accél./décél. E-80 Impuls./tour born. 32/33 H-20 Fonction perte signal de retour moteur AN-## E/S ana.
K-51 Copie process E-## E/S Digitale E-81 Sens cod.born.32 33 H-21 Erreur vitesse signal de retour moteur AN-0# Mode E/S ana.
K-6# Protection par mdp E-0# Entrées digitales E-9# Contrôle par bus H-22 Fonction tempo. signal de retour AN-00 Temporisation/60
K-60 Mt de passe menu princ. E-00 Mode E/S digital E-90 Ctrl bus sortie dig.&relais moteur AN-01 Fonction/Tempo60
K-61 Accès menu princ. ss mt de passe E-01 E.digit.born.18 E-93 Ctrl par bus sortie impulsions 27 H-24 Fonction err. traînée AN-1# Entrée ANA 53
K-65 Mot de passe menu rapide E-02 E.digit.born.19 E-94 Tempo. prédéfinie sortie impulsions 27 H-25 Erreur de traînée AN-10 Éch.min.U/born.53
K-66 Accès menu rapide ss mt de passe. E-03 E.digit.born.27 E-95 Ctrl par bus sortie impulsions 29 H-26 Tempo erreur de traînée AN-11 Éch.max.U/born.53
K-67 Mot de passe accès bus E-04 E.digit.born.29 E-96 Tempo. prédéfinie sortie impulsions 29 H-27 Erreur de trainée pendant la rampe AN-12 Éch.min.I/born.53
Régl. données par. E-05 E.digit.born.32 E-97 Ctrl bus sortie impuls.X30/6 H-28 Tempo err. traînée rampe AN-13 Éch.max.I/born.53
F-## Par. fondamentaux E-06 E.digit.born.33 E-98 Tempo. prédéf.sortie impuls.X30/6 H-29 Erreur de traînée après tempo rampe AN-14 Val.ret./Réf.bas.born. 53
F-0# Fondamental 0 E-07 Arrêt de sécurité borne 37 C-## Fonctions ctrl fréq. H-4# Régl. avancés AN-15 Val.ret./Réf.haut.born. 53
F-05 Tension nominale du moteur E-1# Ramp. acc/déc supp C-0# Fonctions ctrl fréq. H-40 Mode Config. AN-16 Const.tps.fil.born.53
F-04 Fréquence de base E-10 Temps d'accél. 2 C-05 Fréq. multiple 1-8 H-41 Principe Contrôle Moteur AN-2# Entrée ANA 54
F-09 Surcouple E-11 Temps décél. 2 C-02 Saut de vit. de [tr/mn] H-42 Source codeur arbre moteur AN-20 Éch.min.U/born.54
F-02 Méthode de fct E-12 Temps d'accél. 3 C-01 Saut de fréq. de [Hz] H-43 Caract.couple AN-21 Éch.max.U/born.54
F-01 Régl. de fréquence 1 E-13 Temps décél. 3 C-03 Saut de vit. à [tr/mn] H-44 Surcouple variable ou constant AN-22 Éch.min.I/born.54
F-07 Temps d'accél. 1 E-14 Temps d'accél. 4 C-04 Saut de fréq. à [Hz] H-45 Configuration mode Local AN-23 Éch.max.I/born.54
F-08 Temps décél. 1 E-15 Temps décél. 4 C-2# Régl. jogging H-48 Sens horaire AN-24 Val.ret./Réf.bas.born. 54
F-03 Frq.sort.lim.hte 1 E-2# Sortie digitale C-20 Vit.Jog. [Hz] H-46 FCEM à 1000 tr/min. AN-25 Val.ret./Réf.haut.born. 54
F-1# Fondamental 1 E-20 S.digit.born.27 C-21 Vit.Jog. [tr/min] H-47 Décalage angle moteur AN-26 Const.tps.fil.born.54
F-10 Surcharge électronique E-21 S.digit.born.29 C-22 Tps accél. et décél. jog. H-5# Proc.indép. av.
AN-3# Entrée ANA X30/11 SP-41 Magnétis. min. pour éco. d'énergie O-41 Signaux pour PAR PB-23 Signaux pour PAR EN-4# Modbus TCP
AN-30 Éch.min.U/born. X30/11 SP-42 Magnétis. min. pour Fréquence O-42 Config. écriture PCD PB-27 Edition param. EN-40 Par. d'état
AN-31 Éch.max.U/born. X30/11 SP-43 Cos phi moteur O-43 Config. lecture PCD PB-28 CTRL process EN-41 Compt.message esclave
AN-34 Val. ret./Réf.bas.born. X30/11 SP-5# Environnement O-5# Digital/Bus PB-44 Compt. message déf. EN-42 Compt.mess. except° esclave
AN-35 Val. ret./Réf.haut.born. X30/11 SP-50 Filtre RFI O-50 Roue libre PB-45 Code déf. EN-8# +services Ethernet
AN-36 Constante tps filtre borne X30/11 SP-51 Compensation bus CC O-51 Sélect. arrêt rapide PB-47 N° déf. EN-80 Serveur FTP
AN-4# Entrée ANA X30/12 SP-52 Fct ventilateur O-52 Sélect.frein CC PB-52 Compt. situation déf. EN-81 Serveur HTTP
AN-40 Éch.min.U/born. X30/12 SP-53 Surveillance ventilateur O-53 Sélect.dém. PB-53 Mot d'avertissement profibus. EN-82 Service SMTP
AN-41 Éch.max.U/born. X30/12 SP-55 Filtre de sortie O-54 Sélect.Invers. PB-63 Vit. Trans. réelle EN-89 Port canal fiche transparent
AN-44 Val. ret./Réf.bas.born. X30/12 SP-56 Capacitance filtre sortie O-55 Sélect.proc. PB-64 Identific. dispositif EN-9# Ethernet avancé
AN-45 Val. ret./Réf.haut.born. X30/12 SP-57 Inductance filtre de sortie O-56 Sélect. réf. par défaut PB-65 N° profil EN-90 Diagnostic câble
AN-46 Constante tps filtre borne X30/12 SP-59 Nombre effectif d'onduleurs O-57 Sélect OFF2 Profidrive PB-67 Mot de contrôle 1 EN-91 MDI-X
AN-5# Sortie ANA 42 SP-6# Déclassement auto O-58 Profidrive OFF3 Select PB-68 Mot d'Etat 1 EN-92 Surveillance IGMP
AN-50 S.born.42 SP-63 Option alimentée par 24 V CC externe O-8# Diagnos. port var. PB-71 Sauv.Données Profibus EN-93 Longueur erreur câble
Structure du menu des param...
AN-51 Échelle min s.born.42 SP-7# Régl. acc/déc supp. O-80 Compt.message bus PB-72 Reset Var.Profibus EN-94 Protection tempête de diffusion
AN-52 Échelle max s.born.42 SP-71 Tps acc rapport ramp.S1 début acc. O-81 Compt.erreur bus PB-80 Paramètres définis (1) EN-95 Filtre tempête de diffusion
AN-53 Ctrl bus sortie born. 42 SP-72 Tps acc rapport ramp.S1 fin acc. O-82 Compt.message esclave PB-81 Paramètres définis (2) EN-96 Duplicat° port
AN-54 Tempo préréglée sortie born. 42 SP-73 Tps déc rapport rampe S 1 début déc O-83 Compt.erreur esclave PB-82 Paramètres définis (3) EN-98 Compteurs interface
AN-55 Filtre de sortie borne 42 SP-74 Tps déc rapport rampe S 1 fin déc O-9# Bus jog./retour PB-83 Paramètres définis (4) EN-99 Compteurs médias
AN-6# Sortie ANA X30/8 SP-76 Type tps accél./décél. 2 O-90 Vitesse Bus Jog 1 PB-84 Paramètres définis (5) EC-## Opt. retour codeur
AN-60 Sortie borne X30/8 SP-79 Tps acc rapport ramp.S 2 début acc. O-91 Vitesse Bus Jog 2 PB-90 Paramètres modifiés (1) EC-1# Interface inc. codeur
AN-61 Mise échelle min. borne X30/8 SP-80 Tps acc rapport ramp.S 2 fin acc. DN-## Bus rés. DeviceNet PB-91 Paramètres modifiés (2) EC-10 Type de signal
AN-62 Mise échelle max. borne X30/8 SP-81 Tps déc rapport rampe S 2 début déc DN-0# Réglages communs PB-92 Paramètres modifiés (3) EC-11 Résolution (PPR)
AN-63 Ctrl par bus sortie borne X30/8 SP-82 Tps déc rapport rampe S 2 fin déc DN-00 Protocole DeviceNet PB-93 Paramètres modifiés (4) EC-2# Abs. interface codeur
AN-64 Tempo prédéfinie sortie borne X30/8 SP-84 Type tps accél./décél. 3 DN-01 Sélection de la vitesse de transmission PB-94 Paramètres modifiés (5) EC-20 Sélection de protocole
AN-7# Sortie ANA X45/1 SP-87 Tps acc rapport rampe S 3 début acc. DN-02 MAC ID PB-99 Compteur révision Profibus EC-21 Résolution (points/tour)
AN-70 Sortie borne X45/1 SP-88 Tps acc rapport ramp.S 3 fin acc. DN-05 Cptr lecture erreurs transmis. EN-## Ethernet IP EC-24 Longueur données SSI
AN-71 Mise échelle min. s.born.X45/1 SP-89 Tps déc rapport rampe S 3 début déc DN-06 Cptr lecture erreurs reçues EN-0# Réglages IP EC-25 Fréquence d'horloge
AN-72 Mise échelle max. s.born.X45/1 SP-90 Tps déc rapport rampe S 3 fin déc DN-07 Cptr lectures val.bus désact. EN-00 Attribution adresse IP EC-26 Format données SSI
AN-73 Ctrl par bus sortie borne X45/1 SP-92 Type tps accél./décél. 4 DN-1# DeviceNet EN-01 Adresse IP EC-34 Vitesse de transmission HIPERFACE
AN-74 Tempo prédéfinie sortie borne X45/1 SP-95 Tps acc rapport rampe S 4 début acc. DN-10 Proc. sélect° type données EN-02 Masque sous-réseau EC-6# Surveillance et app.
AN-8# Sortie ANA X45/3 SP-96 Tps acc rapport rampe S 4 fin acc. DN-11 Proc./Ecrit.config.données EN-03 Passerelle par défaut EC-60 Sens de rotation positif du codeur
DET-758A/F
AN-80 Sortie borne X45/3 SP-97 Tps déc rapport rampe S 4 début déc DN-12 Proc./Lect.config.données EN-04 Serveur DHCP EC-61 Surveillance signal codeur
AN-81 Mise échelle min. s.born.X45/3 SP-98 Tps déc rapport rampe S 4 fin déc DN-13 Avertis.par. EN-05 Bail expire RS-## Interface résolveur
Guide rapide de l'AF-650 GP
AN-82 Mise échelle max. s.born.X45/3 O-## Options/Comms DN-14 Réf.NET EN-06 Nom serveurs RS-50 Pôles
AN-83 Ctrl par bus sortie borne X45/3 O-0# Réglages généraux DN-15 Ctrl.NET EN-07 Nom de domaine RS-51 Tension d'entrée
AN-84 Tempo prédéfinie sortie borne X45/3 O-01 Type contrôle DN-18 internal_process_data_config_write EN-08 Nom d'hôte RS-52 Fréquence d'entrée
SP-## Fonct.particulières O-02 Source mot de contrôle DN-19 internal_process_data_config_read EN-09 Adresse physique RS-53 Rapport de transformation
SP-0# Régl. panne O-03 Mot de ctrl.Action dépas.tps DN-2# Filtres COS EN-1# Par. lien Ethernet RS-59 Interface résolveur
SP-00 Niveau panne O-04 Mot de ctrl.Fonct.dépas.tps DN-20 Filtre COS 1 EN-10 État lien Vérif. données par.
SP-1# Ligne on/off O-05 Fonction fin dépass.tps. DN-21 Filtre COS 2 EN-11 Durée lien 10 dernières modif.
SP-10 Panne de ligne O-06 Reset dépas. temps DN-22 Filtre COS 3 EN-12 Négociation auto Depuis régl. d'usine
SP-11 Tension ligne si panne entrée O-07 Activation diagnostic DN-23 Filtre COS 4 EN-13 Vitesse lien Info.variateur
SP-12 Fonct.sur désiqui.ligne O-08 Filtrage affichage DN-3# Accès param. EN-14 Lien duplex ID-0# Données exploit.
SP-13 Facteur pas défaut secteur O-1# Régl. contrôle DN-30 Indice de tableau EN-2# Données de process ID-00 Heures ss tens°
SP-2# Fonctions reset O-10 Profil mot contrôle DN-31 Stock.val.données EN-20 Instance de ctrl ID-01 Heures fonction.
SP-23 Réglage code de type O-13 Mot état configurable DN-32 Révision DeviceNet EN-21 Proc./Ecrit.config.données ID-02 Compteur kWh
SP-24 Délais Al./Limit.C O-14 Mot contrôle configurable DN-33 Toujours stocker EN-22 Proc./Lect.config.données ID-03 Mise sous tension
SP-25 Délais Al./C.limit ? O-3# Régl. port variat. DN-34 Code produit DeviceNet EN-28 Stock.val.données ID-04 Surtemp.
SP-26 Temps en U limit. O-30 Protocole DN-39 Paramètres Devicenet F EN-29 Toujours stocker ID-05 Surtension
SP-28 Réglages production O-31 Adresse DN-5# Process DeviceNet EN-3# EtherNet/IP ID-06 Reset comp. kWh
SP-29 Code service O-32 Vit. Trans. port variateur PB-## Profibus EN-30 Avertis.par. ID-07 Reset compt. heures de fonction.
SP-3# Ctrl I lim. courant O-33 Parité port variateur K-11 Edit process EN-31 Réf.NET ID-1# Régl.tend.données
SP-30 Ctrl.I limite, Gain P O-34 Tps cycle estimé PB-00 Pt de cons. EN-32 Ctrl.NET ID-10 Source tendance
SP-31 Ctrl.I limite, tps Intég. O-35 Retard réponse min. PB-07 Valeur réelle EN-33 Révision CIP ID-11 Intervalle enr.tend.
SP-32 Ctrl.I limite, tps filtre O-36 Retard réponse max PB-15 Config. écriture PCD EN-34 Code produit CIP ID-12 Événement déclencheur
SP-35 Protec. anti-immobilisation O-37 Retard inter-char max PB-16 Config. lecture PCD EN-35 Paramètre EDS ID-13 Mode tendance
SP-4# Éco. d'énergie O-4# Régl. port var. MC PB-18 Adresse station EN-37 Retard inhibition COS ID-14 Échantillons avant déclenchement
SP-40 Niveau VT O-40 Sélection Télégramme PB-22 Sélection Télégramme EN-38 Filtre COS
27
6 6
6 6
ID-2# Journal historique DR-22 Couple [%] LC-01 Événement de démarrage PI-2# Retour PID process
28
ID-20 Journal historique : événement DR-25 Couple [Nm] élevé LC-02 Événement d'arrêt PI-20 PID proc./1 retour
ID-21 Journal historique : valeur DR-3# État variateur LC-03 Reset ctrleur log. PI-22 PID proc./2 retours
ID-22 Journal historique : heure DR-30 Tension DC Bus LC-1# Comparateurs PI-3# Régulat. PID proc.
ID-3# Journal d'alarme DR-32 Puis.Frein. /s LC-10 Opérande comparateur PI-30 PID proc./Norm.Inv.
ID-30 Mémoire déf. : code d'erreur DR-33 Puis.Frein. /2 min LC-11 Opérateur comparateur PI-31 PID proc./anti satur
ID-31 Mémoire déf. : valeur DR-34 Temp. radiateur LC-12 Valeur comparateur PI-32 PID proc./Fréq.dém.
ID-32 Mémoire déf. : heure DR-35 Thermique variateur LC-2# Temporisations PI-33 PID proc./Gain P
ID-4# Type.VAR. DR-36 Inom variateur LC-20 Tempo.contrôleur logique PI-34 PID proc./Tps intégral.
ID-40 Type variateur DR-37 Imax variateur LC-4# Règles de Logique PI-35 PID proc./Tps diff.
ID-41 Partie puiss. DR-38 État contrôleur logique LC-40 Règle de Logique Booléenne 1 PI-36 PID proc./Limit. gain D
ID-42 Tension DR-39 Temp. carte cmde LC-41 Opérateur de Règle Logique 1 PI-38 Facteur d'anticipation process PID
ID-43 Version logiciel DR-40 Tampon enr.tendance saturé LC-42 Règle de Logique Booléenne 2 PI-39 Largeur de bande sur réf.
ID-46 N° produit GE DR-41 Ligne d'état inf. clavier LC-43 Opérateur de Règle Logique 2 PI-4# Process PID av. I
Structure du menu des param...
ID-47 Code carte puissance DR-49 Source défaut courant LC-44 Règle de Logique Booléenne 3 PI-40 PID proc./Reset facteur I
ID-48 N° d'identif. clavier DR-5# Réf.& retour LC-5# États PI-41 PID proc./Sortie lim. nég.
ID-49 N°logic.carte cmde DR-50 Réf.externe LC-51 Événement contr. logique PI-42 PID proc./Sortie lim. pos.
ID-50 N°logic.carte puis DR-51 Référence d'impulsions LC-52 Action contrôleur logique PI-43 PID proc./Échelle gain à réf. min.
ID-51 N° série variateur DR-52 Signal de retour [Unité] B-## Fonc° de freinage PI-44 PID proc./Échelle gain à réf. min.
ID-53 N° série carte puissance DR-53 Référence pot. dig. B-0# Freinage PI-45 PID proc./Ressource anticip.
ID-6# Identif.Option DR-6# Entrées et sorties B-00 I maintien CC PI-46 PID proc./Fact. anticip. Décélération
ID-60 Option montée DR-60 Entrée dig. B-01 Courant frein CC PI-49 PID proc./Sortie Décélération
ID-61 Version logicielle option DR-61 Régl.commut.born.53 B-02 Temps frein CC PI-5# Process PID av. II
ID-62 N° code option DR-62 Entrée ANA 53 B-03 Vitesse frein CC [tr/min] PI-50 PID proc./PID étendu
ID-63 N° série option DR-63 Régl.commut.born.54 B-04 Vitesse frein CC [Hz] PI-51 PID proc./Gain anticip.
ID-70 Option A DR-64 Entrée ANA 54 B-05 Réf. max. PI-52 PID proc./Rampe accél anticip.
ID-71 Vers.logic.option A DR-65 Sortie ANA 42 [mA] B-1# Fonct.Puis.Frein. PI-53 PID proc./Rampe décél anticip.
ID-72 Option B DR-66 Sortie digitale [bin] B-10 Fonction frein PI-56 PID proc./Tps filtre retour
ID-73 Vers.logic.option B DR-67 Fréq. entrée 29 [Hz] B-12 Lim. puis. freinage (kW) PI-57 PID proc./Tps filtre retour
ID-74 Option C1 DR-68 Fréq. entrée 33 [Hz] B-13 Surcharge thermique frein PI-6# Affichages PID
ID-75 Vers.logic.option C0 DR-69 Sortie impulsions 27 [Hz] B-15 Contrôle freinage PI-60 PID proc./Erreur
ID-76 Option C2 DR-70 Sortie impulsions 29 [Hz] B-16 Courant max. frein CA PI-61 PID proc./Sortie
ID-77 Vers.logic.option C1 DR-71 Sortie relais [bin] B-17 Contrôle Surtension PI-62 PID proc./Sortie lim. verr.
DET-758A/F
ID-9# Infos paramètre DR-72 Compteur A B-18 Condition ctrl frein. PI-63 PID proc./Sortie à l'éch. gain
Guide rapide de l'AF-650 GP
ID-92 Paramètres définis DR-73 Compteur B B-19 Gain surtension SF-## Caract. spéciales
ID-93 Paramètres modifiés DR-74 Compteur stop précis B-11 Frein Res (ohm) SF-0# Wobbler
ID-98 Type.VAR. DR-75 Entrée ANA X30/11 B-2# Frein mécanique SF-00 Mode modul. (Wobble)
ID-99 Métadonnées param.? DR-76 Entrée ANA X30/12 B-20 Activation courant frein. SF-01 Fréq. delta modulation [Hz]
Lecture données DR-77 Sortie ANA X30/8 [mA] B-21 Activation vit.frein[tr/mn] SF-02 Fréq. delta modulation [%]
DR-0# État général DR-78 Sortie ANA X45/1 [mA] B-22 Activation vit. Frein[Hz] SF-03 Ressource éch. fréq. delta modul.
DR-00 Mot contrôle DR-79 Sortie ANA X45/3 [mA] B-23 Activation retard frein SF-04 Saut de fréq. modul. [Hz]
DR-01 Réf. [unité] DR-8# Bus et port var. B-24 Retard d'arrêt SF-05 Saut de fréq. modul. [%]
DR-02 Réf. % DR-80 Mot ctrl.1 bus B-25 Tps déclchment frein SF-06 Tps saut modulation
DR-03 Mot d'état DR-82 Réf.1 port bus B-26 Réf. couple SF-07 Tps séquence modulation
DR-05 Valeur réelle princ. [%] DR-84 Mot d'état opt° comm. B-27 Tps de rampe couple SF-08 Tps accél/décél modul.
DR-09 Lect.paramétr. DR-85 Mot ctrl.1 port variateur B-28 Facteur amplification gain SF-09 Fonct. aléatoire modul.(wobble)
DR-1# État Moteur DR-86 Réf.1 port variateur PI-## Ctrls du PID SF-10 Rapport de modul. (Wobble)
DR-10 Puiss. moteur [kW] 99-30 internal_ProfibusPCD_Config_Write PI-0# Régulat. PID vit. SF-11 Rapport aléatoire modul. max.
DR-11 Puis. moteur [HP] 99-31 internal_ProfibusPCD_Config_Read PI-00 PID vit.source ret. SF-12 Ratio aléatoire modul. min.
DR-12 Tension nominale du moteur DR-9# Lect. diagnostic PI-03 PID vit.tps intég. SF-19 Mise à éch. fréq. delta modul.
DR-13 Fréquence DR-90 Mot d'alarme PI-04 PID vit.tps diff. SF-2# Type av.
DR-14 Courant moteur DR-91 Mot d'alarme 2 PI-05 PID vit.limit gain diff SF-20 Couple de dém. élevé Tps [s]
DR-15 Fréquence [%] DR-92 Mot avertis. PI-06 PID vit.tps filtre SF-21 Couple de dém. élevé Courant [%]
DR-16 Couple [Nm] DR-93 Mot d'avertissement 2 PI-07 Rapport démultiplic. ret.PID vit. SF-22 Protec. rotor verrouillé
DR-17 Vitesse moteur [tr/min] DR-94 Mot état élargi PI-08 Facteur d'anticipation PID vitesse SF-23 Tps détect° rotor bloqué [s]
DR-18 Thermique moteur Régl.données par. av PI-02 PID vit.gain P
DR-19 Température du capteur KTY LC-## Contrôleur logique PI-1# Mode couple ctrl PI
DR-20 Angle moteur LC-0# Réglages CL PI-12 PI couple/Gain P
DR-21 Couple [%] haute rés. LC-00 Mode contr. logique PI-13 Tps intégr. PI couple
Structure du menu des param... Guide rapide de l'AF-650 GP
DET-758A/F 29
Avertissements et alarmes Guide rapide de l'AF-650 GP
7 Avertissements et alarmes
• réinitialisation automatique
Alarme verrouillée
Une alarme qui entraîne un arrêt verrouillé du variateur
Voyant Warn. Voyant Alarm
nécessite un cycle de déconnexion/connexion de l'alimen-
Avertissement Allumé Éteint
tation d'entrée. Le moteur s'arrêtera en roue libre. La
Alarme Éteint Allumé (clignotant)
logique du variateur continue à fonctionner et à surveiller
Alarme verrouillée Allumé Allumé (clignotant)
l'état du variateur. Couper l'alimentation d'entrée vers le
variateur et corriger la cause de la panne avant de
réappliquer l'alimentation. Cette action place le variateur
dans un état de déclenchement comme décrit ci-dessus et
peut être réinitialisée de l'une des quatre manières
indiquées.
30 DET-758A/F
Avertissements et alarmes Guide rapide de l'AF-650 GP
DET-758A/F 31
Avertissements et alarmes Guide rapide de l'AF-650 GP
7 7 56
57
Réglage automatique interrompu par l'utilisateur
Régl. auto tempo.
X
X
58 Erreur interne réglage automatique X X
59 Limite de courant X 4-18 Limite courant
61 Erreur du signal de retour (X) (X) 4-30 Fonction perte
signal de retour moteur
62 Limite fréquence de sortie X
63 Frein mécanique bas (X) 2-20 Activation courant
frein.
64 Limite tension X
65 Température excessive de la carte de commande X X X
66 Température radiateur basse X
67 La configuration du module des options a changé X
68 Arrêt de sécurité (X) (X)1) 5-19 Terminal 37 Safe
Stop
69 T° carte puis. X X
70 Configuration variat. illégale X
76 Config alim. X
77 Modepuiss. réduit X 14-59 Actual Number of
Inverter Units
78 Erreur de traînée (X) (X) H-24 Fonction err.
traînée
79 ConfigPSprohibé X X
80 Variateur remis aux réglages d'usine X
83 Combinaison d'options illégale X
90 Surveillance codeur (X) (X) 17-61 Surveillance
signal codeur
91 Réglages incorrects entrée analogique 54 X S202
243 Frein IGBT X X X
244 Temp. radiateur X X X
245 Capteur radiatr X X
246 Alim. carte puis. X
247 T° carte puis. X X
248 ConfigPSprohibé X
249 T° basse redres X
250 Nouvelles pièces X
32 DET-758A/F
Avertissements et alarmes Guide rapide de l'AF-650 GP
7 7
DET-758A/F 33
Spécifications Guide rapide de l'AF-650 GP
8 Spécifications
34 DET-758A/F
Spécifications Guide rapide de l'AF-650 GP
2) Voir 3.4.5.7 Borne 37 pour plus d'informations sur la borne 37 et sur l'arrêt de sécurité.
Entrées analogiques :
Nombre d'entrées analogiques 2
8 8
N° de borne 53, 54
Modes Tension ou courant
Sélection du mode Commutateurs S201 et S202
Mode tension Commutateur S201/commutateur S202 = Inactif (U)
Niveau de tension -10 à +10 V (échelonnable)
Résistance d'entrée, Ri env. 10 kΩ
Tension max. ± 20 V
Mode courant Commutateur S201/commutateur S202 = Actif (I)
Niveau de courant 0/4 à 20 mA (échelonnable)
Résistance d'entrée, Ri env. 200 Ω
Courant max. 30 mA
Résolution des entrées analogiques 10 bits (+ signe)
Précision des entrées analogiques Erreur max. 0,5 % de l'échelle totale
Largeur de bande 100 Hz
Les entrées analogiques sont isolées galvaniquement de la tension d'alimentation (PELV) et d'autres bornes haute tension.
Entrées codeur/impulsions :
Entrées codeur/impulsions programmables 2/1
Numéro de borne impulsion/codeur 29, 331) / 322), 332)
Fréquence max. à la borne 29, 32, 33 110 kHz (activation push-pull)
Fréquence max. à la borne 29, 32, 33 5 kHz (collecteur ouvert)
Fréquence min. à la borne 29, 32, 33 4 Hz
Niveau de tension Voir 8.1.1 Entrées digitales :
Tension maximale sur l'entrée 28 V CC
DET-758A/F 35
Spécifications Guide rapide de l'AF-650 GP
8 8 La sortie digitale est isolée galvaniquement de la tension d'alimentation (PELV) et d'autres bornes haute tension.
Sortie analogique :
Nombre de sorties analogiques programmables 1
N° de borne 42
Plage de courant à la sortie analogique 0/4 - 20mA
Charge max. à la terre - sortie analogique 500 Ω
Précision de la sortie analogique Erreur max. : 0,5 % de l'échelle totale
Résolution de la sortie analogique 12 bits
La sortie analogique est isolée galvaniquement de la tension d'alimentation (PELV) et d'autres bornes haute tension.
Carte de commande, sortie 24 V CC :
N° de borne 12, 13
Tension de sortie 24V +1, -3 V
Charge max. 200 mA
L'alimentation 24 V CC est isolée galvaniquement de la tension secteur (PELV) tout en ayant le même potentiel que les entrées et
sorties analogiques et digitales.
Carte de commande, sortie 10 V CC :
N° de borne 50
Tension de sortie 10,5 V ±0,5 V
Charge max. 15 mA
L'alimentation 10 V CC est isolée galvaniquement de la tension secteur (PELV) et d'autres bornes haute tension.
Carte de commande, communication série RS-485 :
N° de borne 68 (P,TX+, RX+), 69 (N,TX-, RX-)
Borne n° 61 Masse des bornes 68 et 69
Le circuit de communication série RS-485 est séparé fonctionnellement des autres circuits centraux et isolé galvaniquement de la
tension d'alimentation (PELV).
Carte de commande, communication série USB :
Norme USB 1.1 (Full speed)
Fiche USB Fiche "appareil" USB de type B
La connexion au PC est réalisée via un câble USB standard hôte/dispositif.
La connexion USB est isolée de façon galvanique de la tension d'alimentation (PELV) et d'autres bornes sous haute tension.
La mise à la terre USB n'est pas isolée de façon galvanique de la terre de protection. Utiliser uniquement un ordinateur portable
isolé en tant que connexion PC au connecteur USB sur le variateur.
36 DET-758A/F
Spécifications Guide rapide de l'AF-650 GP
Sorties de relais :
Sorties de relais programmables 2 en forme de C
N° de borne relais 01 1-3 (interruption), 1-2 (établissement)
Charge max. sur les bornes (CA-1)1) sur 1-3 (NF), 1-2 (NO) (charge résistive) 240 V CA, 2 A
Charge max. sur les bornes (CA-15)1) (charge inductive à cosφ 0,4) 240 V CA, 0,2 A
Charge max. sur les bornes (CC-1)1) sur 1-2 (NO), 1-3 (NF) (charge résistive) 60 V CC, 1 A
Charge max. sur les bornes (CC-13)1) (charge inductive) 24 V CC, 0,1 A
N° de borne relais 02 4-6 (interruption), 4-5 (établissement)
1) 2)3)
Charge max. sur les bornes (CA-1) sur 4-5 (NO) (charge résistive) Surtension cat. II 400 V CA, 2 A
Charge max. sur les bornes (CA-15)1) sur 4-5 (NO) (charge inductive à cosφ 0,4) 240 V CA, 0,2 A
Charge max. sur les bornes (CC-1)1) sur 4-5 (NO) (charge résistive) 80 V CC, 2 A
Charge max. sur les bornes (CC-13)1) sur 4-5 (NO) (charge inductive) 24 V CC, 0,1 A
Charge max. sur les bornes (CA-1)1) sur 4-6 (NF) (charge résistive) 240 V CA, 2 A
Charge max. sur les bornes (CA-15)1) sur 4-6 (NF) (charge inductive à cosφ 0,4) 240 V CA, 0,2 A
Charge max. sur les bornes (CC-1)1) sur 4-6 (NF) (charge résistive) 50 V CC, 2 A
Charge max. sur les bornes (CC-13)1) sur 4-6 (NF) (charge inductive) 24 V CC, 0,1 A
Charge min. sur les bornes 1-3 (NF), 1-2 (NO), 4-6 (NF), 4-5 (NO) 24 V CC 10 mA, 24 V CA 20 mA
Environnement conforme à la norme EN 60664-1 catégorie de surtension III/degré de pollution 2
1) CEI 60947 parties 4 et 5
Les contacts de relais sont isolés galvaniquement du reste du circuit par une isolation renforcée (PELV).
2) Catégorie de surtension II 8 8
3) Applications UL 300 V CA, 2 A
DET-758A/F 37
Spécifications Guide rapide de l'AF-650 GP
Environnement :
Essai de vibration 1,0 g
Humidité relative max. 5 %-93 % (CEI 721-3-3) ; classe 3K3 (non condensante) pendant le fonctionnement
Environnement agressif (CEI 60068-2-43) test H2S classe Kd
Température ambiante Max. 50 °C
1)Déclassement pour température ambiante élevée, voir le chapitre Conditions spéciales du Manuel de configuration
Température ambiante min. en pleine exploitation 0 °C
Température ambiante min. en exploitation réduite - 10 °C
Température durant le stockage/transport -25-+65/70 °C
Altitude max. au-dessus du niveau de la mer sans déclassement 1000 m
Déclassement pour haute altitude, voir le chapitre Conditions spéciales dans le Manuel de configuration
Normes CEM, Émission EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
Normes CEM, Immunité EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Se reporter au chapitre Conditions spéciales du Manuel de configuration de l'AF-650 GP.
Protection et caractéristiques :
• La surveillance de la température du radiateur assure l'arrêt du variateur lorsque la température atteint un niveau
8 8 prédéfini. Le reset d'une surtempérature n'est possible que lorsque la température du radiateur est inférieure aux
valeurs mentionnées dans les tableaux des pages suivantes (remarque : ces températures peuvent varier en
fonction de la puissance, des tailles d'unité, des niveaux de protection, etc.).
• En cas d'absence de l'une des phases secteur, le variateur s'arrête ou émet un avertissement (en fonction de la
charge).
• Le contrôle de la tension du circuit intermédiaire garantit l'arrêt du variateur si la tension du circuit intermédiaire
est trop basse ou trop élevée.
• Le variateur contrôle en permanence les niveaux critiques de température interne, courant de charge, haute
tension sur le circuit intermédiaire et les vitesses faibles du moteur. Pour répondre à un niveau critique, le
variateur peut ajuster la fréquence de commutation ou changer le type de modulation pour garantir la
performance du variateur.
38 DET-758A/F
Installation Guide rapide de l'AF-650 GP
9 Installation
9.1.1 Fusibles
Il est recommandé d'utiliser des fusibles et/ou des disjoncteurs du côté de l'alimentation comme protection en cas de
panne d'un composant interne au variateur (première panne).
REMARQUE!
Ceci est obligatoire pour assurer la conformité à la norme CEI 60364 pour la conformité CE et au NEC 2009 pour la
conformité UL.
AVERTISSEMENT
Le personnel et les biens doivent être protégés contre les conséquences éventuelles d'une panne de composant interne au
variateur.
REMARQUE!
Pour UL, les recommandations données ne traitent pas la protection du circuit de dérivation.
9 9
Protection contre les courts-circuits :
GE recommande d'utiliser les fusibles/disjoncteurs mentionnés ci-dessous afin de protéger le personnel d'entretien et l'équi-
pement en cas de panne d'un composant interne au variateur.
AVERTISSEMENT
Le non-respect des recommandations peut entraîner des risques pour le personnel et endommager le variateur et d'autres
équipements en cas de dysfonctionnement.
Les tableaux suivants donnent la liste des courants nominaux recommandés. Les fusibles de type gG sont recommandés
pour des puissances faibles à moyennes. Pour des puissances plus élevées, les fusibles aR sont recommandés. Il faut utiliser
des disjoncteurs à condition qu'ils répondent aux réglementations nationales/internationales et que leur énergie dans le
variateur se limite à une valeur inférieure ou égale à celle des disjoncteurs conformes.
Si des fusibles/disjoncteurs conformes aux recommandations sont utilisés, les dommages éventuels au variateur se limiteront
principalement à des dommages internes à l'unité.
9.1.2 Conformité CE
Les fusibles et les disjoncteurs doivent obligatoirement être conformes à la norme CEI 60364. GE recommande l'utilisation
de la sélection suivante :
L'utilisation des fusibles ci-dessous convient sur un circuit capable de délivrer 100 000 Arms (symétriques), 240 V, 480 V, 500
V ou 600 V en fonction de la tension nominale du variateur. Avec des fusibles adaptés, le courant nominal de court-circuit
du variateur (SCCR) s'élève à 100 000 Arms.
DET-758A/F 39
Installation Guide rapide de l'AF-650 GP
9 9 0,75 / 1
1,5 / 2
gG-20 gG-32
2,2 / 3
3,7 / 5
5,5 / 7,5
gG-63 gG-80
7,5 / 10
11 / 15 gG-80 gG-100
15 / 20
gG-125 gG-160
18,5 / 25
22 / 30 aR-160 aR-160
30 / 40 aR-200 aR-200
37 / 50 aR-250 aR-250
40 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 41
Installation Guide rapide de l'AF-650 GP
42 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 43
Installation Guide rapide de l'AF-650 GP
Les fusibles et les disjoncteurs doivent obligatoirement être conformes au NEC 2009. Il est recommandé d'utiliser des
composants appartenant à la liste ci-dessous.
L'utilisation des fusibles ci-dessous convient sur un circuit capable de délivrer 100 000 Arms (symétriques), 240 V, 480 V, ou
600 V en fonction de la tension nominale du variateur. Avec des fusibles adaptés, le courant nominal de court-circuit du
variateur (SCCR) s'élève à 100 000 Arms.
9 9 20-25
22 / 30 KTN-R-150 JKS-150 JJN-150 - - -
30 / 40 KTN-R-200 JKS-200 JJN-200 - - -
37 / 50 KTN-R-250 JKS-250 JJN-250 - - -
44 DET-758A/F
Installation Guide rapide de l'AF-650 GP
1) Les fusibles KTS de Bussmann peuvent remplacer les fusibles KTN pour les variateurs de fréquence 240 V.
2) Les fusibles FWH de Bussmann peuvent remplacer les fusibles FWX pour les variateurs de fréquence de 240 V.
3) Les fusibles A6KR de FERRAZ SHAWMUT peuvent remplacer les fusibles A2KR pour les variateurs de fréquence 9 9
240 V.
4) Les fusibles A50X de FERRAZ SHAWMUT peuvent remplacer les fusibles A25X pour les variateurs de fréquence
240 V.
DET-758A/F 45
Installation Guide rapide de l'AF-650 GP
9 9 AF-650 GP Bussmann
Taille de fusible max. recommandée
Ferraz-Shawmut Ferraz-Shawmut Littel fuse
[kW] / [HP] JFHR2 J JFHR21) JFHR2
0,37-0,75 / FWH-6 HSJ-6 - -
1/2-1
1,5-2,2 / FWH-10 HSJ-10 - -
2-3
3,7 / 5 FWH-20 HSJ-20 - -
5,5 / 7,5 FWH-25 HSJ-25 - -
7,5 / 10 FWH-30 HSJ-30 - -
11 / 15 FWH-40 HSJ-40 - -
15 / 20 FWH-50 HSJ-50 - -
18,5 / 25 FWH-60 HSJ-60 - -
22 / 30 FWH-80 HSJ-80 - -
30 / 40 FWH-100 HSJ-100 - -
37 / 50 FWH-125 HSJ-125 - -
45 / 60 FWH-150 HSJ-150 - -
55 / 75 FWH-200 HSJ-200 A50-P-225 L50-S-225
75 / 100 FWH-250 HSJ-250 A50-P-250 L50-S-250
46 DET-758A/F
Installation Guide rapide de l'AF-650 GP
1) Les fusibles 170M de Bussmann présentés utilisent l'indicateur visuel -/80 : les fusibles avec indicateur –TN/80
Type T, -/110 ou TN/110 Type T de même taille et même intensité peuvent être substitués.
DET-758A/F 47
Installation Guide rapide de l'AF-650 GP
9 9
48 DET-758A/F
Installation Guide rapide de l'AF-650 GP
DET-758A/F 49
Installation Guide rapide de l'AF-650 GP
9 9 [kW] / [HP]
630 / 900 170M8611 1100 A, 1000 V 20 781 32.1000
710 / 1000 170M8611 1100 A, 1000 V 20 781 32.1000
800 / 1150 170M8611 1100 A, 1000 V 20 781 32.1000
900 / 1250 170M8611 1100 A, 1000 V 20 781 32.1000
1000 / 1350 170M8611 1100 A, 1000 V 20 781 32.1000
1200 / 1600 170M8611 1100 A, 1000 V 20 781 32.1000
** Les fusibles répertoriés d'au moins 500 V UL avec courant nominal associé peuvent être utilisés pour respecter les exigences UL.
50 DET-758A/F
Puissance [kW/HP] Protectio Secteur Moteur Répartition de la charge Frein Terre*
n
Couple
Couple de Couple de
Taille du de Taille du Couple de Taille du Taille du Couple de
serrage serrage
200-240V 380-480V 525-600V 525-690V câble [mm2 serrage câble [mm2 serrage câble [mm2 câble [mm2 serrage
[Nm/in- [Nm/in-
10.1 Câbles
(AWG)] [Nm/in- (AWG)] [Nm/in-lbs] (AWG)] (AWG)] [Nm/in-lbs]
lbs] lbs]
lbs]
Borne et fil approprié
0,25-2,2 k
0,37-4 kW 0,75-4 kW
W IP20
1/2-5 HP 1-5 HP
1/3-3 HP
3,7 kW 5,5-7,5 kW 5,5-7,5 kW
IP20 4 (10) 4 (10) 4 (10) 4 (10)
5 HP 7,5-10 HP 7,5-10 HP
1,8/16 1,8/16
0,25-3,7 k
0,37-7,5 kW 0,75-7,5 kW IP55 ou 1,8/16 1,8/16
W
1/2-10 HP 1-10 HP IP66
1/3-5 HP
5,5-7,5 kW 11-15 kW 11-15 kW
10 Borne et fil approprié
IP20
7,5-10 HP 15-20 HP 15-20 HP
16 (6) 16 (6) 16 (6) 16 (6)
5,5-7,5 kW 11-15 kW 11-15 kW IP55 ou
1,5/14 1,5/14
7,5-10 HP 15-20 HP 15-20 HP IP66
3 / 27
11-15 kW 18,5-30 kW 18,5-30 kW
IP20 4,5/40 4,5/40
15-20 HP 25-40 HP 25-40 HP
4,5/40 35 (2) 4,5/40 35 (2) 35 (2) 35 (2)
11 kW 18,5-22 kW 18,5-22 kW 11-22 kW IP55 ou
3,7/33 3,7/33
15 HP 25-30 HP 25-30 HP 15-30 HP IP66
18,5-22 kW 37-45 kW 37-45 kW
IP20 50 (1) 50 (1) 50 (1) 50 (1)
25-30 HP 50-60 HP 50-60 HP
DET-758A/F
10 / 89 10 / 89 10 / 89 10 / 89
15-22 kW 30-45 kW 30-45 kW IP55 ou
90 (3/0) 90 (3/0) 90 (3/0) 90 (3/0)
20-30 HP 40-60 HP 40-60 HP IP66
Guide rapide de l'AF-650 GP
51
10 10
Sicurezza Guida rapida AF-650 GP
1 Sicurezza 1 1
AVVISO
TEMPO DI SCARICA!
I convertitori di frequenza contengono condensatori del
bus CC che rimangono carichi anche dopo aver scollegato
l'alimentazione. Per evitare il rischio di scariche elettriche,
scollegare l'alimentazione di rete dal convertitore di
frequenza prima di eseguire qualsiasi intervento di
manutenzione e attendere il tempo specificato da
Tabella 1.1. Non attendere per il tempo indicato dopo il
disinserimento dell'alimentazione, può causare lesioni gravi
o anche mortali.
DET-758A/I 1
Introduzione Guida rapida AF-650 GP
2 Introduzione
2 2
NOTA!
Fare riferimento al Manuale di Funzionamento AF-650 GP per ulteriori dettagli.
2 DET-758A/I
Installazione Guida rapida AF-650 GP
3 Installazione
DET-758A/I 3
Installazione Guida rapida AF-650 GP
Tabella 3.1 Requisiti relativi alla distanza minima per il flusso d'aria
Disegno 3.2 Montaggio corretto con la piastra posteriore
3.3.2 Sollevamento
L'elemento A è una piastra posteriore correttamente
• Controllare il peso dell'unità per determinare un
metodo di sollevamento sicuro. montata per il flusso d'aria richiesto per raffreddare l'unità.
3.3.3 Montaggio
4 DET-758A/I
Installazione Guida rapida AF-650 GP
• Una volta inserita l'alimentazione, controllare l'ingresso e la potenza motore; programmazione dei morsetti di
controllo per le loro funzioni previste
A = analogico, D = digitale
Il morsetto 37 è utilizzato per l'Arresto di Sicurezza. Per le istruzioni per l'installazione dell'Arresto di sicurezza, consultare
Guida alla Progettazione.
*L'opzione di fabbrica chopper di frenatura deve essere ordinata per poter usare resistenze di frenatura dinamiche
**Questa è disponibile ordinando l'opzione chopper di frenatura su convertitore di frequenza unità di taglio 23 e superiori.
DET-758A/I 5
Installazione Guida rapida AF-650 GP
ATTENZIONE
ISOLAMENTO DEI CAVI!
Introdurre la potenza di ingresso, il cablaggio motore e i
cavi di controllo in tre condotti metallici separati o usare
un cavo schernato separato per l'isolamento dai disturbi ad
alta frequenza. Il mancato isolamento dei cavi di alimen-
tazione, motore e controllo potrebbe causare prestazioni
del convertitore di frequenza e dell'apparecchiatura non Disegno 3.5 Fusibili
ottimali.
Per garantire la sicurezza, considerare quanto segue. Tipi e caratteristiche dei cavi
6 DET-758A/I
Installazione Guida rapida AF-650 GP
terra superiori a 3,5 mA, vedere Corrente di 3.4.2.2 Messa a terra con cavo schermato
dispersione (>3,5mA)
• È necessario un cavo di terra dedicato per Sono in dotazione morsetti di messa a terra per il
l'alimentazione di ingresso, , l'alimentazione del cablaggio del motore (vedere Disegno 3.6).
motore e i cavi di controllo
Rispettare le norme locali vigenti relative alla messa a terra Disegno 3.6 Messa a terra con cavo schermato
di apparati con correnti di dispersione > 3,5 mA.
La tecnologia dei Convertitore di frequenza implica
commutazione ad alta frequenza e alta potenza. Questo 3.4.3 Collegamento del motore
genera correnti di dispersione a terra. Una corrente di
guasto nel convertitore di frequenza sui morsetti di
potenza di uscita può contenere una componente CC in AVVISO
grado di caricare i condensatori filtro causando delle TENSIONE INDOTTA!
correnti transitorie verso terra. La corrente di dispersione Posare separatamente i cavi motore da convertitori di
verso terra dipende dalle diverse configurazioni del frequenza multipli. La tensione indotta da cavi motore in
sistema, inclusi i circuiti di filtraggio RFI, i cavi motore uscita posati insieme può caricare i condensatori dell'appa-
schermati e la potenza del convertitore di frequenza. recchiatura anche quando questa è spenta e disinserita. Il
La norma EN/IEC61800-5-1 (Azionamenti elettrici a velocità mancato rispetto della posa separata dei cavi di uscita del
variabile ) prevede particolari precauzioni se la corrente di motore può causare morte o lesioni gravi.
dispersione supera i 3,5 mA,. La messa a terra deve essere
potenziata in uno dei modi seguenti: • Per le dimensioni massime dei cavi vedi
Tabella 10.1
• Cavo di terra di sezione minima 10 mm2
• Due cavi di terra separati, entrambi di dimensioni • Rispettare le normative locali e nazionali per le
dimensioni dei cavi
adeguate a quanto previsto dalla norma
Per ulteriori informazioni vedere la norma EN 60364-5-54 § • Sono forniti passacavi per i cavi del motore o
pannelli di accesso per unità IP21 e superiori
543.7
(Nema 1, 12, e 4/4X Indoor)
Utilizzare i RCD
Quando si utilizzano dispositivi a corrente residua (RCD), • Non montare condensatori di rifasamento tra il
convertitore di frequenza e il motore.
detti anche interruttori automatici (ELCB) con dispersione a
terra, rispettare le seguenti regole: • Non collegare un dispositivo di avviamento o a
commutazione di polo tra il convertitore di
Utilizzare solo RCD di tipo B, in grado di rilevare
frequenza e il motore
correnti CA e CC.
Utilizzare RCD con ritardo per i picchi in ingresso • Collegare il cablaggio trifase del motore ai
morsetti 96 (U), 97 (V) e 98 (W)
per evitare guasti dovuti a correnti di terra
transitorie. • Collegare a massa il cavo seguendo le istruzioni
di messa a terra fornite
Dimensionare l'RCD in funzione della configu-
razione del sistema e di considerazioni ambientali. • Serrare i morsetti in base alle informazioni fornite
in
DET-758A/I 7
Installazione Guida rapida AF-650 GP
• Rispettare i requisiti del costruttore del motore condensatori del filtro RFI interno fra il telaio e il
relativi al cablaggio circuito intermedio sono isolati per evitare danni
Disegno 3.7 rappresenta i collegamenti per ingresso di rete, al circuito intermedio e ridurre le correnti
capacitive di terra in conformità a IEC 61800-3.
motore e massa messa a terra per convertitori di frequenza
di base. Le configurazioni effettive variano in base ai tipi di
unità e alle attrezzature opzionali. 3.4.5 Cavi di controllo
3 3
• Isolare i cavi del controllo dai componenti ad alta
potenza nel convertitore di frequenza.
8 DET-758A/I
Installazione Guida rapida AF-650 GP
3.4.5.2 Tipi di morsetti di comando Vedere 8.1 Dati tecnici generali per dettagli sui valori
nominali dei morsetti.
Disegno 3.10 e mostra i connettori removibili del conver- Descrizione dei morsetti
titore di frequenza. Le funzioni dei morsetti e le relative
Riferiment Impostazione
impostazioni predefinite sono elencate in Tabella 3.2.
Morsetto o di default Descrizione
Ingressi/uscite digitali
12, 13 - +24V CC Tensione di alimen-
tazione 24 V CC. La
corrente in uscita
massima è di 200 mA
in totale per tutti i
carichi a 24 V. Utiliz-
zabile per ingressi
digitali e trasduttori
esterni.
18 E-01 [8] Avviam.
19 E-02 [10] Inversione
Disegno 3.10 Posizioni dei morsetti di controllo
32 E-05 [0] Nessuna
Ingressi digitali.
funzione
33 E-06 [0] Nessuna
funzione
27 E-03 [0] Nessuna Selezionabile come
funzione ingresso o uscita
29 E-04 [14] JOG digitale. L'impo-
stazione predefinita è
ingresso.
20 - Comune per gli
Disegno 3.11 Numeri dei morsetti ingressi digitali e 0 v
per l'alimentazione 24
V.
37 - Safe Torque Ingresso sicuro.
• Connettore 1 mette a disposizione quattro
morsetti ingressi digitali programmabili, due Off (STO) Utilizzato per STO.
morsetti digitali aggiuntivi programmabili come Ingressi/uscite analogici
ingressi o uscite, un morsetto tensione di alimen- 39 - Comune per uscita
tazione da 24V CC, e un morsetto comune per analogica
DET-758A/I 9
Installazione Guida rapida AF-650 GP
10 DET-758A/I
Installazione Guida rapida AF-650 GP
3.4.5.7 Morsetto 37
DET-758A/I 11
Installazione Guida rapida AF-650 GP
12 DET-758A/I
Installazione Guida rapida AF-650 GP
DET-758A/I 13
Installazione Guida rapida AF-650 GP
3 3
Disegno 3.15 Installazione per arresto di Categoria 0 (EN 60204-1) con Sicurezza Cat. 3 (EN 954-1) / PL “d” (ISO 13849-1).
14 DET-758A/I
Installazione Guida rapida AF-650 GP
DET-758A/I 15
Avviamento e test funzional... Guida rapida AF-650 GP
4.1 Pre-avvio
4.1.1 Controllo di sicurezza
4 4 AVVISO
ALTA TENSIONE!
Se i collegamenti di ingresso e uscita sono stati collegati in
modo non ottimale, possono presentarsi tensioni elevate
su questi morsetti. Se i conduttori di alimentazione per più
motori sono posati in modo erroneo nella stessa canalina,
sussiste il rischio che la corrente di dispersione carichi i
condensatori all'interno del convertitore di frequenza
anche se scollegati dall'alimentazione di rete. Per l'avvio
iniziale, attenersi alle procedure relative ai componenti di
alimentazione. Attenersi alle procedure di pre-avvio. Il
mancato rispetto delle procedure di pre-avvio potrebbe
causare lesioni personali o danni all'apparecchiatura.
16 DET-758A/I
Avviamento e test funzional... Guida rapida AF-650 GP
ATTENZIONE
Prima di alimentare l'unità, controllare l'intera installazione in base a quanto riportato in Tabella 4.1. In seguito marcare
quegli elementi.
Controllare Descrizione ☑
Apparecchiatura ausiliaria • Controllare l'apparecchiatura ausiliaria, interruttori, sezionatori o interruttori
automatici/fusibili di ingresso eventualmente presenti sul lato di alimentazione 4 4
di ingresso del convertitore di frequenza e sul lato di uscita verso il motore.
Assicurarsi che sono pronti per il funzionamento a piena velocità.
Cavi di controllo • Controllare che non vi siano eventuali fili rotti o danneggiati e collegamneti
non serrati
Distanza per il raffreddamento • Misurare lo spazio superiore e inferiore per assicurare un flusso d'aria
sufficiente per il raffreddamento.
Considerazioni EMC • Controllare che l'installazione sia conforme ai requisiti di compatibilità elettro-
magnetica.
Considerazioni ambientali • Vedere l'etichetta dell'apparecchiatura per i limiti della temperatura di esercizio
ambiente massima.
Messa a terra • L'unità richiede un cavo di massa dal suo telaio alla massa dell'edificio.
Pannello interno • Verificare che l'interno dell'unità sia priva di sporcizia, trucioli di metallo,
umidità e corrosione.
Interruttori • Assicurarsi che tutti gli interruttori e sezionatori siano impostati nelle posizioni
corrette.
DET-758A/I 17
Avviamento e test funzional... Guida rapida AF-650 GP
Controllare Descrizione ☑
Vibrazioni • Assicurarsi che l'unità sia montata saldamente o che vengano usati supporti
antivibrazioni, se necessario.
18 DET-758A/I
Avviamento e test funzional... Guida rapida AF-650 GP
Quando H-48 Senso orario è impostato su [0]* Normale (per • Aumentare il limite di corrente in F-43 Limite
default in senso orario): corrente
4a. Verificare che il motore giri in senso orario. • Aumentare il limite di coppia in F-40 Limitatore di
5a. Verificare che la freccia di direzione coppia (marcia)
dell'Tastierino indichi il senso orario. Se si sono presentati problemi di decelerazione
Quando H-48 Senso orario è impostato su [1] Inverso (senso
antiorario): • In presenza di avvisi o allarmi, vedere 7 Avvisi e
4b. Verificare che il motore giri in senso allarmi
antiorario.
• Controllare che i dati del motore siano inseriti
5b. Verificare che la freccia di direzione correttamente
dell'Tastierino indichi il senso antiorario.
• Aumentare il tempo rampa in F-08 Tempo decel 1
DET-758A/I 19
Avviamento e test funzional... Guida rapida AF-650 GP
NOTA!
Le sezioni 4.1 Pre-avvio fino a 4.6 Test di controllo locale in
questo capitolo completano le procedure di alimentazione
del convertitore di frequenza, la programmazione di base,
la messa a punto e il collaudo funzionale.
4 4
4.7 Avvio del sistema
La procedura in questa sezione richiede il completamento
del cablaggio da parte dell'utente e la programmazione
dell'applicazione. Si consiglia la procedura seguente dopo
il completamento della configurazione dell'applicazione da
parte dell'utente.
ATTENZIONE
AVVIAMENTO DEL MOTORE!
Assicurarsi che motore, sistema e ogni apparecchiatura
collegata siano pronti per l'avviamento. È la responsabilità
dell'utente assicurare un funzionamento sicuro in tutte le
condizioni di funzionamento. Se il motore, il sistema e ogni
apparecchiatura collegata non sono pronti per
l'avviamento potrebbero verificarsi danneggiamenti alle
apparecchiature o lesioni personali.
1. Premere [Auto].
2. Assicura il corretto cablaggio delle funzioni di
controllo esterno al convertitore di frequenza e
che tutta la programmazione sia completata.
3. Applicare un comando di avvio esterno.
4. Regolare il riferimento di velocità nell'intervallo di
velocità.
5. Togliere il comando di avvio esterno.
6. Annotare eventuali problemi.
In presenza di avvisi o allarmi, vedere 7 Avvisi e allarmi.
20 DET-758A/I
Interfaccia utente Guida rapida AF-650 GP
5 Interfaccia utente
NOTA!
Il contrasto del display può essere regolato premendo
[STATUS] e il tasto Su/Giù.
a. Area di visualizzazione.
b. I tasti del menu display consentono di modificare
la visualizzazione per mostrare opzioni di stato,
programmazione e cronologia dei messaggi di
errore.
c. I tasti di navigazione consentono di programmare
funzioni, spostare il cursore dei display e regolare
la velocità nel funzionamento in modalità locale.
Sono presenti anche indicatori di stato.
d. Tasti per il modo di funzionamento e ripristino.
DET-758A/I 21
Interfaccia utente Guida rapida AF-650 GP
Le informazioni visualizzate sull'Tastierino sono personaliz- • Il simbolo nell'angolo in alto a destra del
zabili per l'applicazione dell'utente. display mostra il verso di rotazione del
motore e il setup attivo. Non è program-
mabile.
5 5 • Ogni visualizzazione del display ha un parametro
associato. Menu rapido Permette di accedere ai parametri di program-
mazione necessari per le istruzioni di
• Le opzioni vengono selezionate nel menu
configurazione iniziale e molte istruzioni
principale K-2#
dettagliate relative all'applicazione.
• Lo stato del convertitore di frequenza nell'ultima • Premere per accedere a Avviamento rapido
riga del display viene generato automaticamente per istruzioni passo passo per programmare
e non è selezionabile. la configurazione di base del controllore in
frequenza
Display Numero del parametro Impostazione di default
1.1 K-20 Velocità [giri/m] • Premere per accedere a Tendenza per la
registrazione in tempo reale sul display del
1.2 K-21 Corrente motore
tastierino.
1.3 K-22 Potenza [kW]
2 K-23 Frequenza • Premere per accedere a Controllo dati
3 K-24 Riferimento [%] parametrici per modifiche nel set di dati
parametrici.
I tasti menu sono utilizzati per l'impostazione dei parametri Log allarme Visualizza un elenco di avvisi correnti, gli ultimi
di accesso menu, per passare tra le varie modalità di 10 allarmi e il log di manutenzione.
visualizzazione dello stato durante il normale funzio- • Per dettagli sul convertitore di frequenza
namento e per la visualizzazione dei dati del log guasti. prima che entrasse nella modalità di
allarme, selezionare il numero di allarme
utilizzando i tasti di navigazione e premere
[OK].
22 DET-758A/I
Interfaccia utente Guida rapida AF-650 GP
Tasto Funzione
Man. Premere per avviare il convertitore di frequenza
nel controllo locale.
• Utilizzare i tasti di navigazione per regolare la
velocità del convertitore di frequenza
5 5
• Un segnale di arresto esterno dall'ingresso di
comando o dalla comunicazione seriale
esclude il comando locale
DET-758A/I 23
Interfaccia utente Guida rapida AF-650 GP
I dati di programmazione sono memorizzati internamente 5.3 Ripristino delle impostazioni di fabbrica
al convertitore di frequenza.
24 DET-758A/I
Interfaccia utente Guida rapida AF-650 GP
7. Alimentare l'unità.
Durante l'avvio avviene il ripristino delle impostazioni
predefinite dei parametri. Questo può richiedere un tempo
leggermente più lungo del normale.
• ID-03 Accensioni
• ID-04 Sovratemp.
• ID-05 Sovratensioni
DET-758A/I 25
6 6
F-11 Ventilaz. est. motore E-24 Funzione relè C-21 Velocità marcia jog [RPM] H-50 Magnetizz. motore a vel. nulla
26
6.1.1 Struttura del menu
principale F-12 Ingresso termistore motore E-26 Ritardo attiv., relè C-22 Tempo accel/decel marcia jog H-51 Min velocità magnetizz. norm. [RPM]
F-18 Lim. basso vel. motore [giri/min] E-27 Ritardo disatt., relè C-23 Tempo decel arresto rapido H-52 Min. velocità magnetizz. normale [Hz]
F-16 Limite basso velocità motore [Hz] E-3# X46 Ingressi digitali C-24 Tipo rampa arresto rapido H-53 Frequenza di shift del modello
Configurazione del tastierino F-17 Lim. alto vel. motore [giri/min] E-30 Ingr. digitale morsetto X46/1 C-25 Rapp. rampa S arr. rap. a inizio decel. H-54 Rid. d. tensione nell'ind. di campo
K-0# Imp.di base tastier. F-15 Limite alto velocità motore [Hz] E-31 Ingr. digitale morsetto X46/3 C-26 Rapp. rampa S arr. rap. a fine decel. H-55 Caratteristica U/f - U
K-01 Lingua F-2# 2 fondamentale E-32 Ingr. digitale morsetto X46/5 C-3# Impostaz. di freq. 2 e 3 H-56 Caratteristica U/f - F
K-02 Unità velocità motore F-24 T. di mant. E-33 Ingr. digitale morsetto X46/7 C-30 Comando di frequenza 2 H-58 Impulsi corr. test riagg. al volo
K-03 Impostazioni locali F-25 Funz. di avv. E-34 Ingr. digitale morsetto X46/9 C-34 Comando di frequenza 3 H-59 Frequenza imp. test riagg. al volo
K-04 Stato di funz. all'accens. F-22 Velocità di avviam. [giri/min] E-35 Ingr. digitale morsetto X46/11 P-## Dati del motore H-6# Imp. dip. dal carico
K-09 Monitor prestazioni F-23 Velocità avviamento [Hz] E-36 Ingr. digitale morsetto X46/13 P-0# Dati del motore H-61 Compensaz. del carico ad alta vel.
K-1# Oper. di setup tastier. F-29 Corrente di avviam. E-5# Mod. I/O / I/O agg. P-07 Potenza motore [kW] H-64 Smorzamento risonanza
K-10 Setup attivo F-26 Rumore. mot. (freq. port.) E-51 Mod. morsetto 27 P-02 Potenza motore [HP] H-65 Smorzamento ris. tempo costante
Struttura del menu dei para...
K-11 Modifica setup F-27 Tono motore casuale E-52 Mod. morsetto 29 P-03 Corrente motore H-66 Corrente min. a velocità bassa
K-12 Questo setup collegato a F-28 Compensazione tempi inattività E-53 Ingr. digitale morsetto X30/2 P-06 Velocità di base H-7# Adattam. avvisi
K-13 Visualizzazione: Setup collegati F-3# 3 fondamentale E-54 Ingr. digitale morsetto X30/3 P-05 Coppia motore nominale cont. H-70 Avviso corrente bassa
K-14 Visualizzazione: Modifica setup / canale F-37 Modello di commutaz. avanzato E-55 Ingr. digitale morsetto X30/4 P-04 Auto Tune H-71 Avviso corrente alta
K-2# Visualizz. sul tast. F-38 Sovramodulazione E-56 Uscita dig. mors. X30/6 (OPCGPIO) P-01 Poli motore H-72 Avviso velocità bassa
K-20 Visualiz.ridotta del display- riga 1.1 F-4# 4 fondamentale E-57 Uscita dig. mors. X30/7 (OPCGPIO) P-09 Compens. scorrim. H-73 Avviso velocità alta
K-21 Visualiz.ridotta del display- riga 1.2 F-40 Limitatore di coppia (marcia) E-6# Ingr. impulsi P-10 Costante di tempo compens. scorrim. H-74 Avviso rif. basso
K-22 Visualizz. ridotta del display riga - 1.3 F-41 Limitatore di coppia (frenatura) E-60 Bassa frequenza morsetto 29 P-2# Selezione motore H-75 Avviso riferimento alto
K-23 Visualizz. estesa del display riga 2 F-43 Limite corrente E-61 Frequenza alta mors. 29 P-20 Struttura motore H-76 Avviso retroazione bassa
K-24 Visualizz. estesa del display riga 3 F-5# Riferimenti estesi E-62 Rif. basso/val. retroaz. mors. 29 P-3# Dati motore avanz. H-77 Avviso retroazione alta
K-25 Avviamento rapido F-50 Intervallo di rif. E-63 Rif. alto/val. retroaz. mors. 29 P-30 Resistenza di statore (Rs) H-78 Funzione fase motore mancante
K-3# Visual. pers. tast. F-51 Unità riferimento/Retroazione E-64 Costante di tempo del filtro impulsi P-31 Resistenza rotore (Rr) H-8# Adattam. arresto
K-30 Unità per la visualizz. person. F-52 Riferimento minimo #29 P-33 Reatt. dispers. statore (X1) H-87 Tipo di carico
K-31 Valore min. della visual. person. F-53 Riferimento massimo E-65 Bassa frequenza morsetto 33 P-34 Reattanza dispers. rotore (X2) H-88 Inerzia minima
K-32 Valore max della visual. person. F-54 Funzione di riferimento E-66 Frequenza alta mors. 33 P-35 Reattanza principale (Xh) H-89 Inerzia massima
K-37 Testo display 1 F-6# Riferimenti E-67 Rif. basso/val. retroaz. mors. 33 P-36 Resist. perdite ferro (Rfe) H-80 Funzione all'arresto
K-38 Testo display 2 F-62 Valore catch-up/slow-down E-68 Rif. alto/val. retroaz. mors. 33 P-37 Induttanza asse d (Ld) H-81 Vel.min. per funz.all'arresto [RPM]
K-39 Testo display 3 F-64 Rif. relativo preimpostato E-69 Costante di tempo del filtro impulsi H-## Parametri High Perf H-82 Vel.min. per funz.all'arresto [Hz]
K-4# Pulsanti sul tast. F-68 Risorsa rif. in scala relativa #33 H-0# Operazioni High Perf H-83 Funzione arresto preciso
Guida rapida AF-650 GP
DET-758A/I
F-9# Potenziom.digit. E-7# Uscita imp. H-09 Modalità avvio H-84 Valore del contatore arresti precisi
K-41 Pulsante [Off] sul tastierino F-90 Dimensione passo E-70 Uscita impulsi variabile morsetto 27 H-07 Tempo accel/decel tipo 1 H-85 Ritardo compens. velocità stop preciso
K-42 Pulsante [Auto] sul tastierino F-91 Tempo accel/decel E-72 Freq. max. uscita impulsi #27 H-08 Bloccaggio invertito H-9# Temp. motore
K-43 Pulsante [Reset] sul tastierino F-92 Ripristino della potenza E-73 Uscita impulsi variabile morsetto 29 H-04 Ripristino automatico (tempi) H-95 Tipo di sensore KTY
K-44 Tasto [Off/Reset] sul tastierino F-93 Limite massimo E-75 Freq. max. uscita impulsi #29 H-05 Riprist. aut. (interv. di reset) H-96 Ingresso termistore KTY
K-5# Copia/Salva F-94 Limite minimo E-76 Uscita imp. var. morsetto X30/6 H-03 Ripr. imp. di fabbrica H-97 Livello soglia KTY
K-50 Copia tastiera F-95 Ritardo rampa di acc./decel. E-78 Freq. max. uscita impulsi #X30/6 H-2# Monitoraggio retrazione motore AN-## I/O analogici
K-51 Copia setup E-## I/O digitali E-8# Ingr. encoder 24V H-20 Funzione di perdita retroazione motore AN-0# Mod. I/O anal.
K-6# Prot. password E-0# Ingressi digitali E-80 Impulsi per giro mors. 32/33 H-21 Errore di velocità retroazione motore AN-00 Tempo timeout tensione zero
K-60 Passw. menu princ. E-00 Modo I/O digitale E-81 Direz. encoder mors. 32/33 H-22 Timeout perdita retroazione motore AN-01 Funz. temporizz. tensione zero
K-61 Accesso al menu princ. senza passw. E-01 Ingr. digitale morsetto 18 E-9# Controllato da bus H-24 Funz. errore di inseguim. AN-1# Ingr. analog. 53
K-65 Password menu rapido E-02 Ingr. digitale morsetto 19 E-90 Controllo bus digitale e a relè H-25 Errore di inseguimento AN-10 Tens. bassa morsetto 53
K-66 Accesso menu rapido senza password E-03 Ingr. digitale morsetto 27 E-93 Controllo bus uscita impulsi #27 H-26 Tempor. errore inseguim. AN-11 Tensione alta morsetto 53
K-67 Accesso password bus E-04 Ingr. digitale morsetto 29 E-94 Preimp. timeout uscita impulsi #27 H-27 Err. di inseguim. dur. rampa AN-12 Corr. bassa morsetto 53
Set di dati param. E-05 Ingr. digitale morsetto 32 E-95 Controllo bus uscita impulsi #29 H-28 Tempor. err. inseg. durante la rampa AN-13 Corrente alta morsetto 53
F-## Parametri fondamentali E-06 Ingr. digitale morsetto 33 E-96 Preimp. timeout uscita impulsi #29 H-29 Err. di inseguim. dopo tempor. rampa AN-14 Rif.basso/val.retroaz mors. 53
F-0# 0 fondamentale E-07 Arr. sic. mors. 37 E-97 Controllo bus uscita impulsi #X30/6 H-4# Impostaz. avanzate AN-15 Rif. alto/valore retroaz. mors. 53
F-05 Tens. nom. mot. E-1# Rampe acc./dec. suppl. E-98 Preimp. timeout uscita impulsi #X30/6 H-40 Modo configurazione AN-16 Costante di tempo filtro del morsetto
F-04 Frequenza di base E-10 Tempo accel 2 C-## Funzioni controllo freq. H-41 Principio controllo motore 53
F-09 Boost di coppia E-11 Tempo decel 2 C-0# Funzioni controllo freq. H-42 Fonte retroazione motore a flusso AN-2# Ingr. analog. 54
F-02 Metodo di funzionamento E-12 Tempo accel 3 C-05 Freq. di uscita multi fase 1 - 8 H-43 Caratteristiche di coppia AN-20 Tens. bassa morsetto 54
F-01 Impostazione frequenza 1 E-13 Tempo decel 3 C-02 Velocità di movimento da [giri/min] H-44 Sovracc. coppia cost. o var. AN-21 Tensione alta morsetto 54
F-07 Tempo accel 1 E-14 Tempo accel 4 C-01 Frequenza di salto da [Hz] H-45 Configurazione modo locale AN-22 Corr. bassa morsetto 54
F-08 Tempo decel 1 E-15 Tempo decel 4 C-03 Velocità di movimento a [giri/min] H-48 Senso orario AN-23 Corrente alta morsetto 54
F-03 Freq. di uscita max 1 E-2# Uscite digitali C-04 Frequenza di movimento a [Hz] H-46 Forza c.e.m. a 1000 giri/minuto AN-24 Rif.basso/val.retroaz. mors. 54
F-1# 1 fondamentale E-20 Uscita dig. morsetto 27 C-2# Setup jog H-47 Scostamento angolo motore AN-25 Rif. alto/valore retroaz. mors. 54
F-10 Sovraccarico elettronico E-21 Uscita dig. morsetto 29 C-20 Velocità marcia jog [Hz] H-5# Impostaz. indip. dal carico
AN-26 Costante di tempo filtro del morsetto SP-32 Reg. lim. corr., tempo filtro O-04 Funzione temporizz. parola di controllo DN-20 Filtro COS 1 EN-10 Stato del collegamento
54 SP-35 Prot. dallo stallo O-05 Funz. fine temporizzazione DN-21 Filtro COS 2 EN-11 Durata del collegamento
AN-3# Ingresso anal. X30/11 SP-4# Risparmi energetici O-06 Riprist. tempor. parola di contr. DN-22 Filtro COS 3 EN-12 Negoziazione automatica
AN-30 Val. di tens. bassa mors. X30/11 SP-40 Livello VT O-07 Diagnosi trigger DN-23 Filtro COS 4 EN-13 Velocità di collegamento
AN-31 Val. tensione alta mors. X30/11 SP-41 Magn. min. risparmio energ. O-08 Filtraggio lettura DN-3# Accesso ai par. EN-14 Link duplex
AN-34 Val. rif./retr. basso mors. mors. X30/11 SP-42 Frequenza min. risparmio energetico O-1# Imp. di controllo DN-30 Ind. array EN-2# Dati di processo
AN-35 Val. alto/val. retroaz. mors. mors. SP-43 Cosphi motore O-10 Profilo parola di com. DN-31 Memorizzare i valori di dati EN-20 Istanza di controllo
X30/11 SP-5# Ambiente O-13 Parola di stato configurabile (STW) DN-32 Revisione Devicenet EN-21 Dati processo scrittura config.
AN-36 Costante di tempo filtro mors. X30/11 SP-50 Filtro RFI O-14 Parola di controllo configurabile CTW DN-33 Memorizzare sempre EN-22 Dati processo lettura config.
AN-4# Ingresso anal. X30/12 SP-51 Compensazione bus CC O-3# Imp. porta conv. freq. DN-34 Codice prodotto DeviceNet EN-28 Memorizzare i valori di dati
AN-40 Val. tens. bassa morsetto X30/12 SP-52 Funzionamento ventola O-30 Protocollo DN-39 Parametri Devicenet F EN-29 Memorizzare sempre
AN-41 Val. tens. alta morsetto X30/12 SP-53 Monitor. ventola O-31 Indirizzo DN-5# Dati di proc. DeviceNet EN-3# EtherNet/IP
AN-44 Val. basso/val. retroaz. mors. X30/12 SP-55 Filtro di uscita O-32 Baud rate porta conv. di freq. PB-## Profibus EN-30 Parametro di avviso
Struttura del menu dei para...
AN-45 Val. alto/val. retroaz. mors. X30/12 SP-56 Capacità filtro di uscita O-33 Parità porta conv. di freq. K-11 Modifica setup EN-31 Riferimento rete
AN-46 Costante di tempo filtro mors. X30/12 SP-57 Induttanza filtro di uscita O-34 Durata del ciclo stimata PB-00 Setpoint EN-32 Controllo rete
AN-5# Uscita analogica 42 SP-59 Numero effettivo di unità inverter O-35 Ritardo minimo risposta PB-07 Valore reale EN-33 Revisione CIP
AN-50 Uscita morsetto 42 SP-6# Declassam. automat. O-36 Ritardo max. risposta PB-15 Config. scrittura PCD EN-34 Codice prodotto CIP
AN-51 Mors. 42, usc. scala min. SP-63 Opzione alimentata da alim. 24 V CC O-37 Ritardo max. intercar. PB-16 Config. lettura PCD EN-35 Parametro EDS
AN-52 Mors. 42, usc. scala max. est. O-4# Imp. porta MC c. freq. PB-18 Indirizzo nodo EN-37 Timer con inibizione COS
AN-53 Morsetto 42, uscita controllata via bus SP-7# Impostazioni aggiuntive ACC/DEC O-40 Selezione telegramma PB-22 Selezione telegramma EN-38 Filtro COS
AN-54 Preimp. timeout uscita morsetto 42 SP-71 Tempo di accel. 1 rapporto rampa S a O-41 Parametri per segnali PB-23 Parametri per segnali EN-4# Modbus TCP
AN-55 Morsetto 42 Filtro uscita inizio accel. O-42 Config. scrittura PCD PB-27 Modifica parametri EN-40 Parametro di stato
AN-6# Uscita anal. X30/8 SP-72 Tempo di accel. 1 rapporto rampa S a O-43 Config. lettura PCD PB-28 Controllo di processo EN-41 Conteggio messaggi slave
AN-60 Uscita morsetto X30/8 fine accel. O-5# Digitale / Bus PB-44 Contatore messaggi di guasto EN-42 Conteggio messaggi eccezione slave
AN-61 Morsetto X30/8, scala min. SP-73 Tempo di accel. 1 rapporto rampa S a O-50 Selezione ruota libera PB-45 Codice di guasto EN-8# Altri servizi Ethernet
AN-62 Morsetto X30/8, scala max inizio decel. O-51 Selez. arresto rapido PB-47 Numero guasto EN-80 Server FTP
AN-63 Mors. X30/8 controllato da bus SP-74 Tempo di accel. 1 rapporto rampa S a O-52 Selez. freno CC PB-52 Contatore situazione guasto EN-81 Server HTTP
AN-64 Preimp. timeout uscita mors. X30/8 fine decel. O-53 Selez. avvio PB-53 Parola di avviso Profibus EN-82 Servizio SMTP
AN-7# Uscita anal. X45/1 SP-76 Tempo accel/decel tipo 2 O-54 Selez. inversione PB-63 Baud rate attuale EN-89 Porta socket channel trasparente
AN-70 Uscita morsetto X45/1 SP-79 Tempo di accel. 2 rapporto rampa S a O-55 Selez. setup PB-64 Identif. apparecchio EN-9# Servizi Ethernet avanz.
AN-71 Morsetto X45/1, scala min. inizio accel. O-56 Selezione rif. preimpostato PB-65 Numero di profilo EN-90 Diagnosi cavo
DET-758A/I
AN-72 Mors. X45/1, scala max SP-80 Tempo di accel. 2 rapporto rampa S a O-57 Selezione Profidrive OFF2 PB-67 Parola di contr. 1 EN-91 MDI-X
Guida rapida AF-650 GP
AN-73 Mors. X45/1, controllato via bus fine accel. O-58 Selezione Profidrive OFF3 PB-68 Parola di stato 1 EN-92 IGMP Snooping
AN-74 Uscita mors. X45/1 Timeout preimp. SP-81 Tempo decel. 2 rapporto rampa S a O-8# Diagn. porta c. freq. PB-71 Salva valori di dati Profibus EN-93 Lunghezza errore cavo
AN-8# Uscita anal. X45/3 inizio decel. O-80 Conteggio messaggi bus PB-72 Ripr. conv.freq. Profibus EN-94 Protezione Broadcast Storm
AN-80 Uscita morsetto X45/3 SP-82 Tempo decel. 2 rapporto rampa S a O-81 Conteggio errori bus PB-80 Parametri definiti (1) EN-95 Filtro di protezione Broadcast Storm
AN-81 Morsetto X45/3, scala min. fine decel. O-82 Conteggio messaggi slave PB-81 Parametri definiti (2) EN-96 Mirroring della porta
AN-82 Mors. X45/3, scala max SP-84 Rampa tipo 3 accel/decel O-83 Conteggio errori slave PB-82 Parametri definiti (3) EN-98 Contatori di interfaccia
AN-83 Mors. X45/3, controllato via bus SP-87 Tempo di accel. 3 rapporto rampa S a O-9# Bus Jog / retroaz. PB-83 Parametri definiti (4) EN-99 Media Counters
AN-84 Uscita mors. X45/3 Timeout preimp. inizio accel. O-90 Velocità bus jog 1 PB-84 Parametri definiti (5) EC-## Opzione retroaz.
SP-## Funzioni speciali SP-88 Tempo di accel. 3 rapporto rampa S a O-91 Velocità bus jog 2 PB-90 Parametri cambiati (1) EC-1# Interf. enc. inc.
SP-0# Impostaz. guasti fine accel. DN-## Bus di c. DeviceNet PB-91 Parametri cambiati (2) EC-10 Tipo segnale
SP-00 Livello di guasto SP-89 Tempo decel. 3 rapporto rampa S a DN-0# Impostaz. di base PB-92 Parametri cambiati (3) EC-11 Risoluzione (PPR)
SP-1# Linea On/Off inizio accel. DN-00 Protocollo DeviceNet PB-93 Parametri cambiati (4) EC-2# Interfaccia enc. ass.
SP-10 Guasto linea SP-90 Rampa 3 pend. rampa-S a fine accel. DN-01 Selez. baud rate PB-94 Parametri cambiati (5) EC-20 Selezione protocollo
SP-11 Tensione di linea con guasto in SP-92 Rampa tipo 4 accel/decel DN-02 MAC ID PB-99 Profibus Revision Counter EC-21 Risoluzione (posizioni/giro)
ingresso SP-95 Tempo di accel. 4 rapporto rampa S a DN-05 Visual. contatore errori trasmissione EN-## Ethernet IP EC-24 Lunghezza dei dati SSI
SP-12 Funz. durante sbilanciamento di linea inizio accel. DN-06 Visual. contatore errori ricezione EN-0# Impostazioni IP EC-25 Frequenza di clock
SP-13 Fattore gradino guasto di rete SP-96 Tempo di accel. 4 rapporto rampa S a DN-07 Visual. contatore bus off EN-00 Assegnazione indirizzo IP EC-26 Formato di dati SSI
SP-2# Funzione di ripristino fine accel. DN-1# DeviceNet EN-01 Indirizzo IP EC-34 Baudrate HIPERFACE
SP-23 Imp. codice tipo SP-97 Tempo decel. 4 rapporto rampa S a DN-10 Selez. tipo dati di processo EN-02 Subnet Mask EC-6# Monitor. e appl.
SP-24 Ritardo scatto al limite di corrente inizio decel. DN-11 Dati processo scrittura config. EN-03 Gateway default EC-60 Verso retroazione
SP-25 Ritardo scatto al limite di coppia SP-98 Tempo decel. 4 rapporto rampa S a DN-12 Dati processo lettura config. EN-04 Server DHCP EC-61 Monitoraggio segnale di retroaz.
SP-26 Ritardo scatto per guasto conv. di freq. fine decel. DN-13 Parametro di avviso EN-05 Scadenza rilascio RS-## Interf. resolver
SP-28 Impostaz. produz. O-## Opzioni / Comm DN-14 Riferimento rete EN-06 Name server RS-50 Poli
SP-29 Codice del servizio O-0# Impostazioni generali DN-15 Controllo rete EN-07 Nome dominio RS-51 Intervallo della tensione di ingresso
SP-3# Contr. lim. di corr. O-01 Sito di comando DN-18 scrittura_config_dati_processo_interno EN-08 Nome dell'host RS-52 Frequenza di ingresso max.
SP-30 Contr. lim. corr., guadagno proporz. O-02 Fonte parola di controllo DN-19 lettura_config_dati_processo_interno EN-09 Indirizzo fisico RS-53 Rapporto di trasformaz.
SP-31 Contr. lim. corr. , tempo integraz. O-03 Tempo timeout parola di controllo DN-2# Filtri COS EN-1# Parametri collegamento Ethernet RS-59 Interf. resolver
27
6 6
6 6
Controllo dati par. DR-00 Parola di controllo DR-79 Uscita analogica X45/3 [mA] B-23 Ritardo attivaz. freno SF-0# Oscillatore
28
Ultime 10 modif. DR-01 Riferimento [unità] DR-8# Bus di c. e porta c. freq. B-24 Ritardo di arresto SF-00 Mod. oscillaz.
Dall'imp. di fabbrica DR-02 Riferimento % DR-80 Par. com. 1 F.bus B-25 Tempo di rilascio del freno SF-01 Oscillazione frequenza delta [Hz]
Inform. conv. freq. DR-03 Parola di stato DR-82 RIF bus di campo 1 B-26 Rif. coppia SF-02 Oscillazione frequenza delta [%]
ID-0# Dati di funzion. DR-05 Val. reale princ. [%] DR-84 Opz. com. par. stato B-27 Tempo di rampa della coppia SF-03 Risorsa messa in scala oscillazione
ID-00 Ore di funzionamento DR-09 Visual. personaliz. DR-85 Par. com. 1 p. conv. B-28 Fattore di boost del guadagno freq. delta
ID-01 Ore esercizio DR-1# Stato motore DR-86 RIF 1 porta convertitore di frequenza PI-## Controlli PID SF-04 Frequenza salto oscillaz. [Hz]
ID-02 Contatore kWh DR-10 Potenza [kW] 99-30 Scrittura_config_ProfibusPCD_interno PI-0# Reg. di vel. PID SF-05 Frequenza salto oscillaz. [%]
ID-03 Accensioni DR-11 Potenza [hp] 99-31 lettura_config_ProfibusPCD_interno PI-00 Fonte retroazione PID di velocità SF-06 Tempo di salto oscillaz.
ID-04 Sovratemp. DR-12 Tensione motore DR-9# Visualizz. diagn. PI-03 Tempo integrale PID vel. SF-07 Tempo sequenza di oscill.
ID-05 Sovratensioni DR-13 Frequenza DR-90 Parola d'allarme PI-04 Tempo differenz. PID velocità SF-08 Tempo accel./decel. oscillaz.
ID-06 Riprist. contat. kWh DR-14 Corrente motore DR-91 Parola d'allarme 2 PI-05 Limite guad. diff. PID velocità SF-09 Funz. random di oscillaz.
ID-07 Ripristino contatore ore di esercizio DR-15 Frequenza [%] DR-92 Parola di avviso PI-06 Tempo filtro passa-basso PID di SF-10 Rapp. di oscillaz.
Struttura del menu dei para...
ID-1# Impostaz. tend. dati DR-16 Coppia [Nm] DR-93 Parola di avviso 2 velocità SF-11 Rapporto random oscillaz. max.
ID-10 Sorgente tendenza DR-17 Velocità [giri/m] DR-94 Parola di stato estesa PI-07 Retroazione rapporto di trasmissione SF-12 Rapp. random oscillaz. min.
ID-11 Intervallo tendenza DR-18 Term. motore Config. dati par. avanz. PID di velocità SF-19 Oscillazione frequenza delta messa in
ID-12 Evento d’attivazione DR-19 Temperatura sensore KTY LC-## Controllore logico PI-08 Fattore feed forward PID vel. scala
ID-13 Modo tendenza DR-20 Angolo motore LC-0# Impostazioni LC PI-02 Vel. guad. proporz. PID SF-2# Regolaz. avv. avanz.
ID-14 Campionamenti prima dell’attivazione DR-21 Coppia [%] alta ris. LC-00 Modo controllore logico PI-1# Contr. coppia PI SF-20 Tempo alta coppia di spunto [s]
ID-2# Log storico DR-22 Coppia [%] LC-01 Evento avviamento PI-12 Guadagno proporzionale PI di coppia SF-21 Corrente alta coppia di spunto [%]
ID-20 Log storico: Evento DR-25 Coppia [Nm] alta LC-02 Evento arresto PI-13 Tempo di integrazione PI di coppia SF-22 Protezione rotore bloccato
ID-21 Log storico: Valore DR-3# Stato conv. freq. LC-03 Ripr. il contr. logico PI-2# Retr. PID di proc. SF-23 Tempo di rilev. rot. bloccato [s]
ID-22 Log storico: Tempo DR-30 Tensione bus CC LC-1# Comparatori PI-20 Risorsa retroazione 1 processo CL
ID-3# Log allarme DR-32 Energia freno/s LC-10 Operando comparatore PI-22 Risorsa retroazione 2 processo CL
ID-30 Log guasti: Codice di errore DR-33 Energia freno/2 min LC-11 Operatore comparatore PI-3# Contr. PID di proc.
ID-31 Log guasti: Valore DR-34 Temp. dissip. LC-12 Valore comparatore PI-30 Contr. norm./inv. PID di proc.
ID-32 Log guasti: Tempo DR-35 Term. conv LC-2# Timer PI-31 Anti saturazione PID di processo
ID-4# Identif. conv. freq. DR-36 Corr. nom. c. di freq. LC-20 Timer controllore logico PI-32 Veloc. avv. PID proc.
ID-40 Tipo di c. di f. DR-37 Corrente max conv. di freq. LC-4# Regole logiche PI-33 Guadagno proporzionale PID di
ID-41 Sezione potenza DR-38 Stato controllore logico LC-40 Regola logica Booleana 1 processo
ID-42 Tensione DR-39 Temp. scheda di controllo LC-41 Operatore regola logica 1 PI-34 Tempo d’integrazione PID di processo
ID-43 Versione software DR-40 Buffer tendenza pieno LC-42 Regola logica Booleana 2 PI-35 Tempo di derivazione PID di processo
Guida rapida AF-650 GP
DET-758A/I
ID-46 N. di prodotto GE DR-41 Riga di stato inferiore tastierino LC-43 Operatore regola logica 2 PI-36 Limite di guadagno diff. PID velocità
ID-47 N. d'ordine scheda di potenza DR-49 Sorgente corrente di guasto LC-44 Regola logica Booleana 3 PI-38 Fattore canale alim. del PID di
ID-48 N. ID tastierino DR-5# Rif. e retroaz. LC-5# Stati processo
ID-49 Scheda di contr. SW id DR-50 Riferimento esterno LC-51 Evento controllore logico PI-39 Ampiezza di banda riferimento a
ID-50 Scheda di pot. SW id DR-51 Rif. impulsi LC-52 Azione del controllore logico PI-4# Processo avanz. PID I
ID-51 Numero di serie del conv. di freq. DR-52 Retroazione [unità] B-## Funzioni freno PI-40 Ripristino PID proc. parte I
ID-53 N. di serie scheda di potenza DR-53 Riferim. pot. digit. B-0# Freno CC PI-41 Blocco uscita PID di proc. neg.
ID-6# Ident. opz. DR-6# Ingressi e uscite B-00 Corrente CC di mantenimento PI-42 Blocco uscita PID di proc. pos.
ID-60 Opzione installata DR-60 Ingr. digitale B-01 Corrente di frenatura CC PI-43 Scala guadagno PID di proc. a rif. min.
ID-61 Versione SW opzione DR-61 Impost. commut. mors. 53 B-02 Tempo di frenata CC PI-44 Scala guadagno PID di proc. a rif. min.
ID-62 N. ordine opzione DR-62 Ingr. analog. 53 B-03 Vel. inserim. frenatura CC [RPM] PI-45 Risorsa Feed Fwd PID di processo
ID-63 N. di serie opzione DR-63 Impost. commut. mors. 54 B-04 Velocità inserimento frenatura CC [Hz] PI-46 PID di processo, com. Feed Fwd norm./
ID-70 Opzione nello slot A DR-64 Ingr. analog. 54 B-05 Riferimento massimo inv.
ID-71 Versione SW opzione slot A DR-65 Uscita analogica 42 [mA] B-1# Funz. energia freno PI-49 Com. uscita PID di processo norm./inv.
ID-72 Opzione nello slot B DR-66 Uscita digitale [bin] B-10 Funzione freno PI-5# PID di proc. avanz. II
ID-73 Versione SW opzione slot B DR-67 Ingr. freq. #29 [Hz] B-12 Limite di potenza freno (kW) PI-50 PID di processo PID esteso
ID-74 Opzione nello slot C1 DR-68 Ingr. freq. #33 [Hz] B-13 Sovraccarico termico frenata PI-51 Guadagno Feed Fwd PID di proc.
ID-75 Versione SW opzione slot C0 DR-69 Uscita impulsi #27 [Hz] B-15 Controllo freno PI-52 Rampa accel. Feed Fwd PID di proc.
ID-76 Opzione nello slot C2 DR-70 Uscita impulsi #29 [Hz] B-16 Corrente max. freno CA PI-53 Rampa decel. Feed Fwd PID di proc.
ID-77 Versione SW opzione slot C1 DR-71 Uscita relè [bin] B-17 Controllo sovratensione OVC PI-56 Tempo di rif. filtro PID di processo
ID-9# Inform. parametri DR-72 Contatore A B-18 Condiz. controllo freno PI-57 Tempo di retroaz. filtro PID di processo
ID-92 Parametri definiti DR-73 Contatore B B-19 Guadagno sovratensione PI-6# Visualizzaz. PID
ID-93 Parametri modificati DR-74 Contat. arresti precisi B-11 Resistenza freno (ohm) PI-60 Errore PID di proc.
ID-98 Identif. conv. freq. DR-75 Ingr. anal. X30/11 B-2# Freno meccanico PI-61 Usc. PID di proc.
ID-99 Metadati parametri DR-76 Ingr. anal. X30/12 B-20 Corrente rilascio freno PI-62 Uscita bloccata PID processo
Visualizzazione dati DR-77 Uscita analogica X30/8 [mA] B-21 Vel. attivazione freno [giri/min] PI-63 Uscita scalata guadagno PID proc.
DR-0# Stato generale DR-78 Uscita analogica X45/1 [mA] B-22 Velocità di attivazione del freno [Hz] SF-## Caratter. spec.
Struttura del menu dei para... Guida rapida AF-650 GP
DET-758A/I 29
Avvisi e allarmi Guida rapida AF-650 GP
7 Avvisi e allarmi
7 7 7.2 Tipi di avvisi e allarmi Un allarme o un allarme di scatto bloccato lampeggia sul
display con il numero di allarme.
Avvisi
Viene emesso un avviso quando esiste una condizione di
allarme imminente oppure in presenza di condizioni di
funzionamento anomale che causano l'emissione di un
allarme da parte del convertitore di frequenza. Un avviso si
cancella automaticamente all'eliminazione della condizione
anomala.
critici
Scatto
Un allarme viene generato allo scatto del convertitore di
frequenza, vale a dire che il convertitore di frequenza Oltre alla visualizzazione del testo e del codice di allarme
interrompe il funzionamento per evitare danneggiamenti al sul display convertitore di frequenza si utilizzano indicatori
sistema o al convertitore di frequenza stesso. Il motore di stato.
raggiungerà lo stato di arresto a ruota libera. La logica del
convertitore di frequenza è utilizzato per programmare,
gestire e monitorare lo stato del convertitore di frequenza.
Dopo aver eliminato la consizione di guasto, è possibile
ripristinare il convertitore di frequenza. Sarà nuovamente
pronto per il funzionamento.
Uno scatto può essere ripristinato in 4 modi:
• Ripristino automatico
Scatto bloccato
Un allarme che provoca uno scatto bloccato del
convertitore di frequenza richiede il disinserimento e il
reinserimento della tensione di ingresso. Il motore
LED di avviso LED di allarme
raggiungerà lo stato di arresto a ruota libera. La logica del
Avviso ON OFF
convertitore di frequenza continuerà a gestire e monitorare
Allarme OFF ON (Lampeggiante)
lo stato del convertitore di frequenza. Rimuovere la
Scatto bloccato ON ON (Lampeggiante)
tensione di ingresso al convertitore di frequenza ed
eliminare la causa del guasto, quindi ripristinare l'alimen-
tazione. Questa azione commuta il convertitore di
30 DET-758A/I
Avvisi e allarmi Guida rapida AF-650 GP
DET-758A/I 31
Avvisi e allarmi Guida rapida AF-650 GP
7 7 52
53
Taratura automatica Inom bassa
Taratura automatica motore troppo grande
X
X
54 Taratura automatica motore troppo piccolo X
55 Parametro taratura automatica fuori intervallo X
56 Taratura automatica interrotta dall'utente X
57 Timeout Auto Tune X
58 Guasto interno taratura automatica X X
59 Limite di corrente X 4-18 Limite di corrente
61 Errore retroazione (X) (X) 4-30 Funzione di
perdita retroazione
motore
62 Frequenza di uscita al limite massimo X
63 Fr. mecc. basso (X) 2-20 Corrente rilascio
freno
64 Limite di tensione X
65 Sovratemperatura scheda di controllo X X X
66 Temp. dissip. bassa X
67 Configurazione opzioni Modulo cambiata X
68 Arresto di sicurezza (X) (X)1) 5-19 Terminal 37 Safe
Stop
69 Temp. scheda pot. X X
70 Convertitore di frequenza n.cons. X
76 Setup unità pot. X
77 Modo pot. rid. X 14-59 Actual Number of
Inverter Units
78 Errore di inseguimento (X) (X) H-24 Funz. errore di
inseguim.
79 Config. PS non ammessa X X
80 Convertitore di frequenza ripristinato alle X
impostazioni di fabbrica
83 Combinazione opzione non ammessa X
90 Mon. retroaz. (X) (X) 17-61 Monitoraggio
segnale di retroaz.
91 Errato setup ingresso analogico 54 X S202
243 IGBT freno X X X
244 Temp. dissip. X X X
245 Sensore dissipatore X X
32 DET-758A/I
Avvisi e allarmi Guida rapida AF-650 GP
7 7
DET-758A/I 33
Specifiche Guida rapida AF-650 GP
8 Specifiche
34 DET-758A/I
Specifiche Guida rapida AF-650 GP
Ingressi digitali:
Ingressi digitali programmabili 4 (6)1)
Numero morsetto 18, 19, 271), 291),32, 33,
Logica PNP o NPN
Livello di tensione 0 - 24V CC
Livello di tensione, '0' logico PNP < 5V CC
Livello di tensione, '1' logico PNP > 10V CC
Livello di tensione, '0' logico NPN2) > 19V CC
Livello di tensione, '0' logico NPN2) < 14V CC
Tensione massima sull’ingresso 28V CC
Intervallo di frequenza impulsi 0 - 110kHz
(Duty cycle) Ampiezza impulso min. 4,5ms
Resistenza d’ingresso, Ri circa 4 kΩ
2) Vedere 3.4.5.7 Morsetto 37 per ulteriori informazioni sul morsetto 37 e l'arresto di sicurezza.
Ingressi analogici:
Numero di ingressi analogici 2
Numero morsetto 53, 54
Modalità Tensione o corrente
Selezione modo Interruttore S201 e interruttore S202
Modo tensione Interruttore S201/interruttore S202 = OFF (U)
Livello di tensione Da -10 a +10 V (scalabile)
Resistenza d’ingresso, Ri ca. 10 kΩ
Tensione max. ± 20 V
Modo corrente Interruttore S201/interruttore S202 = ON (I)
Livello di corrente Da 0/4 a 20 mA (scalabile)
Resistenza d’ingresso, Ri ca. 200 Ω
Corrente max. 30 mA
Risoluzione per gli ingressi analogici 10 bit (+ segno)
Precisione degli ingressi analogici Errore max. 0,5% del fondo scala
Larghezza di banda 100 Hz
Gli ingressi analogici sono isolati galvanicamente dalla tensione di alimentazione (PELV) e dagli altri morsetti ad alta tensione.
DET-758A/I 35
Specifiche Guida rapida AF-650 GP
Ingressi a impulsi/encoder:
Ingressi a impulsi/encoder programmabili 2/1
Numero morsetto a impulsi/encoder 29, 331)/ 322),
332)
Frequenza max. ai morsetti 29, 32, 33 110kHz (comando push-pull)
Frequenza max. ai morsetti 29, 32, 33 5 kHz (collettore aperto)
Frequenza min. ai morsetti 29, 32, 33 4 Hz
Livello di tensione vedere 8.1.1 Ingressi digitali:
Tensione massima sull’ingresso 28V CC
Resistenza d’ingresso, Ri ca. 4kΩ
Precisione dell'ingresso impulsi (0,1 - 1 kHz) Errore max: 0,1% del fondo scala
Precisione dell'ingresso encoder (1 - 11 kHz) Errore max: 0,05% dell'intera scala
Gli ingressi a impulsi e encoder (morsetti 29, 32, 33) sono isolati galvanicamente dalla tensione di alimentazione (PEL V) nonché
da altri morsetti ad alta tensione.
1) Gli ingressi a impulsi sono 29 e 33
2) Ingressi encoder: 32 = A e 33 = B
Uscita digitale:
Uscite programmabili digitali/a impulsi 2
Numero morsetto 27, 29 1)
Livello di tensione sull'uscita digitale/frequenza 0 - 24V
Corrente in uscita max. (sink o source) 40 mA
8 8 Carico max. sull’uscita in frequenza
Carico capacitivo max. sull’uscita in frequenza
1kΩ
10 nF
Frequenza di uscita minima per l'uscita in frequenza 0Hz
Frequenza di uscita massima per l'uscita in frequenza 32 kHz
Precisione dell'uscita di frequenza Errore max: 0,1 % del fondo scala
Risoluzione delle uscite di frequenza 12 bit
1) I morsetti 27 e 29 possono essere programmati come ingressi digitali.
L’uscita digitale è isolata galvanicamente dalla tensione di alimentazione (PELV) e dagli altri morsetti ad alta tensione.
Uscita analogica:
Numero delle uscite analogiche programmabili 1
Numero morsetto 42
Intervallo di corrente sull'uscita analogica 0/4 - 20 mA
Carico max a massa - uscita analogica 500Ω
Precisione sull'uscita analogica Errore max: 0,5% del fondo scala
Risoluzione sull'uscita analogica 12 bit
L'ingresso è isolato galvanicamente dalla tensione di alimentazione (PELV) nonché dagli altri morsetti ad alta tensione.
Scheda di controllo, uscita 24V CC:
Numero morsetto 12, 13
Tensione di uscita 24V +1, -3 V
Carico max. 200mA
L'alimentazione 24 V CC è isolata galvanicamente dalla tensione di alimentazione (PELV) ma ha lo stesso potenziale degli
ingressi e delle uscite analogici e digitali.
Scheda di controllo, uscita 10 V CC:
Numero morsetto 50
Tensione di uscita 10,5V ±0,5V
Carico max. 15mA
L’alimentazione 10V CC è isolata galvanicamente dalla tensione di alimentazione (PELV) nonché da altri morsetti ad alta
tensione.
Scheda di controllo, comunicazione seriale RS-485:
Numero morsetto 68 (P,TX+, RX+), 69 (N,TX-, RX-)
Numero morsetto 61 Comune per i morsetti 68 e 69.
Il circuito di comunicazione seriale RS-485 è separato funzionalmente da altri circuiti centrali e isolato galvanicamente dalla
tensione di alimentazione (PELV).
36 DET-758A/I
Specifiche Guida rapida AF-650 GP
3) Applicazioni UL 300V CA 2A
DET-758A/I 37
Specifiche Guida rapida AF-650 GP
Ambiente:
Prova di vibrazione 1,0 g
Umidità relativa massima 5% - 93%(IEC 721-3-3; classe 3K3 (senza condensa) durante il funzionamento
Ambiente aggressivo (IEC 60068-2-43) Test H2S classe Kd
Temperatura ambiente Max. 50°C
1) Declassamento in caso di temperatura ambiente elevata, vedere le condizioni speciali nella Guida alla Progettazione
Temperatura ambiente minima durante operazioni a pieno regime 0°C
Temperatura ambiente minima con prestazioni ridotte - 10°C
Temperatura durante il magazzinaggio/trasporto -25 - +65/70°C
Altezza massima sopra il livello del mare senza declassamento 1000m
Per eventuale declassamento in caso di altezza elevata, consultare le condizioni speciali nella Guida alla progettazione
Standard EMC, emissione EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
Standard EMC, immunità EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Vedere la sezione sulle condizioni speciali nella AF-650 GP Guida alla Progettazione.
Protezione e caratteristiche:
• Il monitoraggio termico del dissipatore garantisce lo scatto del convertitore di frequenza nel caso in cui la
8 8 temperatura raggiunga un livello predefinito. La sovratemperatura non può essere ripristinata finché la
temperatura del dissipatore non scende sotto i valori indicati nelle tabelle sulle pagine seguenti (linee guida -
queste temperature possono variare per taglia di potenza, dimensioni unità, gradi di protezione ecc.).
• In mancanza di una fase di rete, il convertitore di frequenza scatta o emette un avviso (a seconda del carico).
• Il monitoraggio della tensione del circuito intermedio garantisce l’esclusione del convertitore di frequenza nel caso
in cui la tensione del circuito intermedio sia troppo bassa o troppo alta.
• Il convertitore di frequenza sorveglia continuamente i livelli critici di temperatura interna, la corrente di carico,
l'alta tensione sul circuito intermedio e le basse velocità motore. Come risposta a un livello critico, il convertitore di
frequenza può regolare la frequenza di commutazione e/o modificare il modello di commutazione al fine di
assicurare le prestazioni del convertitore di frequenza.
38 DET-758A/I
Installazione Guida rapida AF-650 GP
9 Installazione
9.1.1 Fusibili
Si raccomanda di usare fusibili e/o interruttori automatici sul lato di alimentazione come protezione nel caso di un guasto di
un componente all'interno del convertitore di frequenza (primo guasto).
NOTA!
Questo è obbligatorio per assicurare la conformità con IEC 60364 per CE o NEC 2009 per UL.
AVVISO
Il personale e la proprietà devono essere protetti dalle conseguenze di un guasto di un componente all'interno del
convertitore di frequenza.
NOTA!
I consigli dati non coprono la protezione del circuito di derivazione per UL.
Protezione da sovracorrente:
Il convertitore di frequenza fornisce una protezione da sovraccarico per limitare le minacce alla vita umana, danni all'attrez-
zatura e per evitare il rischio di incendi a causa di un surriscaldamento dei cavi nell'impianto. Il convertitore di frequenza è
dotato di una protezione interna contro la sovracorrente (4-18 Limite di corrente) che può essere utilizzata per la protezione
da sovraccarico a monte (escluse le applicazioni UL). Inoltre possono essere utilizzati fusibili o interruttori automatici per
garantire la protezione da sovracorrente nell'impianto. La protezione da sovracorrente deve essere eseguita sempre nel
rispetto delle norme nazionali.
AVVISO
Nel caso di un malfunzionamento, la mancata osservanza delle raccomandazioni potrebbe provocare rischi al personale e
danni al convertitore di frequenza o ad altre attrezzature.
Le seguenti tabelle elencano la corrente nominale raccomandata. I fusibili raccomandati sono del tipo gG per potenze da
ridotte a medie. Per potenze maggiori sono raccomandati fusibili aR. Possono essere utilizzati interruttori a condizione che
siano conformi alle norme nazionali e internazionali e che limitino l'energia al convertitore di frequenza a un valore uguale
o inferiore a quello degli interruttori a norma.
Se vengono scelti fusibili/interruttori automatici secondo le raccomandazioni, i possibili danni al convertitore di frequenza si
limiteranno soprattutto a danni all'interno dell'unità.
9.1.2 Conformità CE
Fusibili o interruttori automatici sono obbligatori per assicurare la conformità con l'IEC 60364. GE raccomanda l'uso di una
selezione delle seguenti.
I fusibili in basso sono adatti per l'uso su un circuito in grado di fornire 100,000 ampere simmetrici (rms), 240V, 480V, o
500V, o 600V in funzione della tensione nominale del convertitore di frequenza. Con i fusibili appropriati , la corrente
nominale di corto circuito (SCCR) del convertitore di frequenza è pari a 100.000 Arm.
DET-758A/I 39
Installazione Guida rapida AF-650 GP
9 9 0,75 / 1
1,5 / 2
gG-20 gG-32
2,2 / 3
3,7 / 5
5,5 / 7,5
gG-63 gG-80
7,5 / 10
11 / 15 gG-80 gG-100
15 / 20
gG-125 gG-160
18,5 / 25
22 / 30 aR-160 aR-160
30 / 40 aR-200 aR-200
37 / 50 aR-250 aR-250
40 DET-758A/I
Installazione Guida rapida AF-650 GP
DET-758A/I 41
Installazione Guida rapida AF-650 GP
42 DET-758A/I
Installazione Guida rapida AF-650 GP
DET-758A/I 43
Installazione Guida rapida AF-650 GP
Fusibili o interruttori automatici sono obbilgatori per soddisfare la NEC 2009. Raccomandiamo di usare una selezione dei
seguenti
I fusibili in basso sono adatti per l'uso su un circuito in grado di fornire 100.000 ampere simmetrici (rms), 240V, 480V, o
600V in funzione della tensione nominale del convertitore di frequenza. Con la fusione appropriata, la corrente nominale di
corto circuito (SCCR) è pari a 100.000 Arm.
9 9 22 / 30
30 / 40
KTN-R-150
KTN-R-200
JKS-150
JKS-200
JJN-150
JJN-200
-
-
-
-
-
-
37 / 50 KTN-R-250 JKS-250 JJN-250 - - -
44 DET-758A/I
Installazione Guida rapida AF-650 GP
1) I fusibili KTS della Bussmann possono sostituire i fusibili KTN nei convertitori di frequenza a 240 V.
2) I fusibili FWH della Bussmann possono sostituire i fusibili FWX nei convertitori di frequenza a 240 V.
3) I fusibili A6KR della FERRAZ SHAWMUT possono sostituire i fusibili A2KR nei convertitori di frequenza a 240 V. 9 9
4) I fusibili A50X della FERRAZ SHAWMUT possono sostituire i fusibili A25X nei convertitori di frequenza a 240 V.
DET-758A/I 45
Installazione Guida rapida AF-650 GP
46 DET-758A/I
Installazione Guida rapida AF-650 GP
1)I fusibili 170M Bussmann mostrati utilizzano l'indicatore visivo -/80. È possibile sostituirli con i fusibili con
indicatore -TN/80 tipo T, -/110 o TN/110 tipo T di uguali dimensione e amperaggio.
DET-758A/I 47
Installazione Guida rapida AF-650 GP
9 9
48 DET-758A/I
Installazione Guida rapida AF-650 GP
DET-758A/I 49
Installazione Guida rapida AF-650 GP
9 9 [kW] / [HP]
630 / 900 170M8611 1100A, 1000V 20 781 32.1000
710 / 1000 170M8611 1100A, 1000V 20 781 32.1000
800 / 1150 170M8611 1100A, 1000V 20 781 32.1000
900 / 1250 170M8611 1100A, 1000V 20 781 32.1000
1000 / 1350 170M8611 1100A, 1000V 20 781 32.1000
1200 / 1600 170M8611 1100A, 1000V 20 781 32.1000
**È possibile utilizzare qualsiasi fusibile UL di almeno 500 V con il valore nominale di corrente adatto per soddisfare i requisiti UL.
50 DET-758A/I
Potenza [kW / HP] Protezion Rete Motore Condivisione del carico Freno Terra*
e
Dimensione Dimensione Dimensione Dimensione
Coppia di Coppia di Coppia di Coppia di Coppia di
del filo del filo del filo del filo
10.1 Cavi
serraggio serraggio serraggio serraggio serraggio
200-240V 380-480V 525-600V 525-690V elettrico elettrico elettrico elettrico
[Nm / in- [Nm / in- [Nm / in- [Nm / in- [Nm / in-
[mm2 [mm2 [mm2 [mm2
lbs] lbs] lbs] lbs] lbs]
(AWG)] (AWG)] (AWG)] (AWG)]
0,25-2,2kW 0,37-4kW 0,75-4kW
IP20
1/3-3HP 1/2-5HP 1-5HP
Morsetto e filo elettrico a...
5,5-7,5kW 5,5-7,5kW
3,7kW 5HP IP20 4 (10) 4 (10) 4 (10) 4 (10)
7,5-10HP 7,5-10HP
1,8 / 16 1,8 / 16
0,25-3,7kW 0,37-7,5kW 0,75-7,5kW IP55 o
1,8 / 16 1,8 / 16
1/3-5HP 1/2-10HP 1-10HP IP66
5,5-7,5kW 11-15kW 11-15kW
IP20
7,5-10HP 15-20HP 15-20HP
16 (6) 16 (6) 16 (6) 16 (6)
5,5-7,5kW 11-15kW 11-15kW IP55 o
1,5 / 14 1,5 / 14
7,5-10HP 15-20HP 15-20HP IP66
11-15kW 18,5-30kW 18,5-30kW
IP20 4,5 / 40 4,5 / 40 3 / 27
15-20HP 25-40HP 25-40HP
4,5 / 40 35 (2) 4,5 / 40 35 (2) 35 (2) 35 (2)
11kW 18,5-22kW 18,5-22kW 11-22kW IP55 o
3,7 / 33 3,7 / 33
15HP 25-30HP 25-30HP 15-30HP IP66
18,5-22kW 37-45kW 37-45kW
IP20 50 (1) 50 (1) 50 (1) 50 (1)
25-30HP 50-60HP 50-60HP
10 / 89 10 / 89 10 / 89 10 / 89
15-22kW 30-45kW 30-45kW IP55 o
90 (3/0) 90 (3/0) 90 (3/0) 90 (3/0)
20-30HP 40-60HP 40-60HP IP66
DET-758A/I
10 Morsetto e filo elettrico applicabile
Guida rapida AF-650 GP
51
10 10
GE Energy
Industrial Solutions GE
AF-650 GPTM
Industrial Solutions (formerly Power Protection),
a division of GE Energy, is a fi rst class European
supplier of low and medium voltage products
General Purpose Drive
including wiring devices, residential and
industrial electrical distribution components,
Quick Guide
automation products, enclosures and switchboards. Guia rapida
Demand for the company’s products comes from
wholesalers, installers, panelboard builders, Kurzanleitung
@
contractors, OEMs and utilities worldwide.
Guide rapide
Guida rapida
www.ge.com/ex/industrialsolutions
GE imagination at work
130R0287 DET-758/S/D/F/I