Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Datasheet Gen

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

®

DSEGenset

DSE8660 ENVIRONMENTAL TESTING STANDARDS

AUTO TRANSFER SWITCH & MAINS ELECTRO MAGNETIC COMPATIBILITY


BS EN 61000-6-2

CONTROL MODULE EMC Generic Immunity Standard for the


Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
FEATURES Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE8660 is an easy-to-use Comprehensive communications With all communication ports
capable of being active at the same TEMPERATURE
single or multi-mains controller with are also available via RS232, BS EN 60068-2-1
automatic transfer switch capability. RS485 & Ethernet for remote PC time, the DSE8xxx Series is ideal Ab/Ae Cold Test -30oC
Designed to synchronise single or control and monitoring, and for a wide variety of demanding BS EN 60068-2-2
load share applications. Bb/Be Dry Heat +70oC
multiple DSE8610s and DSE8680s integration into building
with single or multiple mains (utility) management systems. VIBRATION
KEY LOAD SHARE FEATURES BS EN 60068-2-6
supplies, the DSE8660 will The comprehensive event log will (WITH DSE8x10) : Ten sweeps in each of three major axes
automatically control the change record up to 250 events to facilitate • Peak lopping/shaving 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
over from mains (utility) to generator maintenance. • Sequential set start HUMIDITY
supply or run generators in • Manual voltage/frequency BS EN 60068-2-30
synchronisation with the mains An extensive number of fixed and Db Damp Heat Cyclic 20/55oC @ 95% RH 48
adjustment Hours
(utility) to provide no-break, peak flexible monitoring and protection • R.O.C.O.F. and vector shift BS EN 60068-2-78
lopping and peak shaving power features are included. Easy protection Cab Damp Heat Static 40oC @ 93% RH 48
solutions. alteration of the sequences, timers • Generator load demand Hours
and alarms can be made using the • Automatic hours run balancing SHOCK
The module can indicate DSE PC Configuration Suite • Mains (Utility) de-coupling BS EN 60068-2-27
Three shocks in each of three major axes
operational status and fault Software. Selected configuration is • Mains (Utility) de-coupling 15gn in 11mS
conditions on the LCD screen also available via the module’s front test mode
(multiple languages available), by panel. DEGREES OF PROTECTION
• Bus failure detection PROVIDED BY ENCLOSURES
illuminated LED, audible sounder • Volts and frequency matching. BS EN 60529
and SMS messaging. IP65 - Front of module when installed into the
• kW & kV Ar load sharing control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE


VARIETY OF LOAD SHARE APPLICATIONS
DSE2130
DSE2131 MODEM MODBUS PC
DSE2133
DSE2152 11 6
DSE2157
DSE2548 232 485

DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS DC POWER
EXPANSION RS485 PORT HOST INPUTS SUPPLY 8-35V
+
ETHERNET

DSE8660 MSC

7
5510 ­7510 ­8xxx
OTHER

MAINS (UTILITY) SENSING N/C VOLT FREE N/O VOLT BUS


OUTPUTS FREE OUTPUT SENSING
CURRENT VOLTS

1ph 1ph 1 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N N

ISSUE 2
®

DSEGenset

DSE8660 SPECIFICATION

DC SUPPLY
AUTO TRANSFER SWITCH & MAINS CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CONTROL MODULE CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
FEATURES and supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT


160 mA at 12 V, 80 mA at 24 V

MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUTS C & D
8 A at 250 V AC (Volt free)
KEY FEATURES
• Mains (utility) failure detection • Customisable status screens • Can be integrated into building AUXILIARY OUTPUTS E,F,G,H, I & J
2 A DC at supply voltage
• Mains (utility) power monitoring • Configurable inputs (11) management systems (BMS) and
(kW, kV Ar, kV A and pf) • Configurable outputs (8) programmable logic control (PLC) DIMENSIONS
• Comprehensive synchronising • Configurable timers and alarms • Increased input and output OVERALL
240 mm x 181 mm x 42 mm
and loadsharing capabilities • Multiple entry scheduler expansion capability via DSENet® 9.4” x 7.1” x 1.6”
• Peak lopping & shaving • Configurable event log (250) • Licence-free PC software
functionality • Easy access diagnostic pages • IP65 rating (with supplied gasket) PANEL CUT-OUT
220 mm x 160 mm
• Mains (utility) kW export • LED and LCD alarm indication offers increased resistance to water 8.7” x 6.3”
protection • USB connectivity ingress
• Mains (utility) de-coupling • Backed up real time clock • Advanced Internal PLC editor allows MAXIMUM PANEL THICKNESS
8 mm
protection • Fully configurable via DSE user configurable functions to meet 0.3”
• Advanced integral PLC editor Configuration Suite PC Software specific application requirements.
• User configurable RS232, RS485 OPERATING TEMPERATURE RANGE
-30°C to +70°C
& Ethernet communications KEY BENEFITS EXPANSION DEVICES
• MODBUS RTU & TCP support • A single flexible solution for • DSE124 CAN/MSC Extender STORAGE TEMPERATURE RANGE
• User configurable MODBUS multiple applications • DSE2130 Input Expansion Module -40°C to +85°C
pages • Compatible with DSE5510, • DSE2131 Ratiometric Input
• Advanced SMS control and fault DSE7510 & DSE8x10 series of Expansion Module
messaging (additional GSM modules • DSE2133 RTD & Thermocouple
modem required) • 132 x 64 pixel ratio display for Expansion Module
• DSENet expansion compatible clarity • DSE2152 Analogue Output
• Data logging and trending • Real-time clock provides accurate Expansion Module
• 4-Line back-lit LCD text display event logging • DSE2157 Output Expansion
• Multiple display languages • Ethernet communication provided Module
• Five key menu navigation builit in advanced remote • DSE2548 LED Expansion Module
• Front panel editing with PIN monitoring.
protection

RELATED MATERIALS
TITLE PART NO’S
DSE8660 Installation Instructions 053-070
DSE8660 Operator Manual 057-120
DSE8600 PC Configuration Suite Manual 057-119
DSE8610 Data Sheet 055-083
DSE8680 Data Sheet 055-091
DSE8700 Data Sheet 055-090
DSE8810 Data Sheet 055-116
DSE8860 Data Sheet 055-139

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-086/04/11 (4)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457