Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Consolidated Alarm Management Software - TB

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

19.

CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE


Objectives :
i) Identify the functions of the CAMS for HIS
ii) Understand the layout of the Message Monitor of CAMS for HIS

CENTUM VP provides Consolidated Alarm Management Software for HIS (hereinafter


referred to as “CAMS for HIS”) customized for HIS applications. A CAMS for HIS supports
EEMUA No.191 that defines a set of guidelines for alarm management.

19.1. What is CAMS for HIS?


CAMS for HIS permits alarm and event (hereinafter referred to as “A&E”) messages like
system alarm messages, process alarm messages, operation guide messages to be centrally
managed.
After enabling the CAMS for HIS on [CAMS for HIS] tab of HIS Utility, System Alarm view and
Process Alarm view will be replaced by the Message Monitor of CAMS for HIS. Moreover,
after un-checking the option of [Exclude operation guide messages], (since operation guide
messages can also be handled by CAMS for HIS) the Operator Guide view will be replaced
by the Message Monitor of CAMS for HIS.

The Message Monitor of CAMS for HIS is shown below.

Figure: The Message Monitor of CAMS for HIS

YOKOGAWA SINGAPORE TRAINING CENTRE Page 1 of 1

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

System Configuration of CAMS for HIS


A CENTUM VP system configuration using CAMS for HIS is shown below.
By connecting an OPC A&E server, A&E messages generated in the connected STARDOM
or PRM systems can also be consolidated and managed on the HIS, along with A&E
messages generated in the CENTUM system.
A&E messages are equalized between multiple HISs in which CAMS for HIS is enabled.
Desired HISs can also be selected, from these multiple HISs, to implement A&E message
equalization. On the HISs in the Equalization Scope, all A&E messages including alarms
received via an OPC server are equalized. In each Equalization Scope, only one Download
Master exists for downloading data with Configurator of CAMS for HIS. Database files are
always downloaded to each HIS via the Download Master.

Figure: System Configuration of CAMS for HIS

If the power of Download Master is turned off, data cannot be downloaded to the database.
However, operation and monitoring of A&E messages is not affected

YOKOGAWA SINGAPORE TRAINING CENTRE Page 2 of 2

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.2. Functions of CAMS for HIS


CAMS for HIS provides various functions to make CENTUM VP system compliant with
EEMUA No.191.
A&E Message Processing by CAMS for HIS
The following describes the A&E message processing functions available in CAMS for HIS.

Alarm Acquisition
Receives A&E messages from PRM and STARDOM via an OPC server, in addition to which
generated within CENTUM VP.

Normalization
Adds attributes, such as source name, timestamp and priority, to received A&E messages
based on the settings file created by the Configurator of CAMS for HIS. Normalization
standardizes the way A&E messages are expressed in different systems, to make
comparison of these A&E messages easy.

Grouping
Consolidates associated alarms into an alarm group. The user defines the conditions for
grouping alarms.

Attribute Addition, or Change


Adds conditions for grouping alarms, or changes existing conditions.

Suppression
Suppresses unnecessary alarms.

Shelving
Temporarily moves (shelves) alarms of lower priorities to other location from the A&E
Messages pane, in order to facilitate the recognition of more important alarms in the A&E
Browser pane and A&E Messages pane. This prevents the operator from overlooking
important alarms among lower-priority alarms when many alarms are present.

Load shedding
Shows only those messages matching the pre-defined search conditions once the number of
alarms generating in a specified period exceeds the threshold.

Sorting
Sorts A&E messages based on desired items and shows the sorted A&E messages in the
A&E Messages pane.

Filtering
Shows, among the A&E messages displayed in the A&E Messages pane, only those alarms
meeting specific conditions. It is possible to reduce the number of displayed alarms.

Audit Trails
Manages audit trails regarding the settings information relating to CAMS for HIS created by
Configurator of CAMS for HIS.

User Security Policy


Restricts the permissions on A&E Messages monitoring, change of system settings and other
operations for each user.

Management of Alarms
Manages the statuses of alarms and alarm groups (acknowledged, unacknowledged, etc.)
and deletes unnecessary alarms.

Alarm System Design


Using CAMS for HIS, this function sets various items needed to implement the specific alarm
processing desired by the user. This function is provided by Configurator of CAMS for HIS.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 3 of 3

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.3. Message Monitor of CAMS for HIS

This section explains the structure of the message monitor of CAMS for HIS.

Appearance of the Message Monitor of CAMS for HIS


The figure below shows the appearance of the message monitor of CAMS for HIS.

Menu Bar
Toolbar A&E Browser
Pane
Shelves Pane
A&E Messages
Filters Pane Pane

Details Pane

Dynamic Filters
Pane
Status Bar

Figure: Appearance of the Message Monitor of CAMS for HIS

YOKOGAWA SINGAPORE TRAINING CENTRE Page 4 of 4

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.4. Layout of the Message Monitor of CAMS for HIS

The CAMS for HIS consists of the following bars and panes.
•Menu Bar
•Toolbar
•Shelves Pane
•Filters
•A&E Browser Pane
•A&E Messages Pane
•Details Pane
•Dynamic Filters Pane
•Status Bar

Menu Bar
Operations available in the Message Monitor of CAMS for HIS can be selected using the
menu items in the menu bar. A list of menu items is shown below.

Table: Menu Items in the Message Monitor of CAMS for HIS

YOKOGAWA SINGAPORE TRAINING CENTRE Page 5 of 5

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

Toolbar
You can define the buttons such as Acknowledge, Acknowledge All, or Manual Reset on the
Toolbar. The figure below shows an example of Toolbar in the Message

Monitor of CAMS for HIS with defined buttons.

Figure: Toolbar Buttons in the Message Monitor of CAMS for HIS (Default)

The toolbar buttons are explained below.

Print: Prints the contents currently shown in the A&E messages pane.

Acknowledge: Acknowledges the A&E messages selected from the list in the A&E messages
pane.

Acknowledge All: Acknowledges all the A&E messages shown in the A&E messages
pane.

Manual Reset: Resets the acknowledged A&E messages selected from the list in the A&E
messages pane. (Only A&E messages that are allowed to reset manually)

Switch Alarm View: Switches between “Alarm list” and “Show Alarm Tree” in A&E messages
pane with each click.

Clear Details Pane: Deselects the selected A&E messages and clears the contents in Details
pane.

Clear Shelf: Removes all the A&E messages for shelving from the shelves.

Suppression: Displays the Suppression dialog box.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 6 of 6

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

Show Shelves Pane: Switches between “Show” and “Hide” Shelves pane with each click.

Show Filter Pane: Switches between “Show” and “Hide” Filter pane with each click.

Show A&E Browser Pane: Switches between “Show” and “Hide” A&E Browser Pane with
each click.

Show Details Pane: Switches between “Show” and “Hide” Details Pane with each click.

Change Window Layout: Changes the width of the A&E message displaying area on the A&E
Browser pane by one clicking.

Show/Hide A&E Browser Pane Background: Changes between the Standard and Zebra
patterns for the background pattern of the A&E Browser pane by one clicking.

Show/Hide A&E Messages Pane Background: Changes between the Standard and Zebra
patterns for the background pattern of the A&E Messages pane by one clicking.

Run...: Starts a pre-assigned application.

Call HIS Window: Calls the assigned operation and monitoring window.

Commit Changes: Saves the settings for the Message Monitor of CAMS for HIS.

Reset to System Default: Reverts all changes made by the operator to the original system
common settings.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 7 of 7

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

Shelves Pane
This pane is used to perform shelving of alarm messages. The Shelves pane shows shelf
icons, shelf names and information of alarms that are currently shelved. An example of the
Shelves pane is shown below.

Figure: Example of the Shelves Pane

Filter Pane
This pane is used to filter alarm messages. An example of the Filter pane is shown below.

Figure: Example of the Filter Pane

A&E Browser Pane


This pane is used to reference A&E messages. You cannot perform shelving or filtering,
acknowledgment operations or display detail information in this pane.
New A&E messages can be inserted either at the beginning or end of the display pane. By
default, they are inserted at the beginning of the display pane.
A&E messages can also be sorted. Where new A&E messages will be shown follows the
sorting conditions.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 8 of 8

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

A&E Messages Pane


This pane is used to display A&E messages. One message is shown in one line.Shelving,
filtering, acknowledgment operations, display detail pane and other operations are performed
on the messages shown in this pane.
New A&E messages can be inserted either at the beginning or end of the display pane. By
default, they are inserted at the beginning of the display pane. In the Filter pane, filter icons
associated with unacknowledged A&E messages, if any, also blink.
If the Emphases on Unread Alarms function is enabled, new A&E messages are shown in
bold, while the names of associated filters are also shown in bold.
A&E messages can also be sorted. Where new A&E messages will be shown follows the
sorting conditions.

Details Pane
This pane is linked to the A&E Messages pane, and when one alarm is selected in the A&E
Messages pane, the causes, actions to take and other detail information of the alarm are
shown here.
Clicking the [Clear Details Pane] in the toolbar cancels the alarm selections in the A&E
Messages pane. The Details pane is also cleared and only the background color is shown.

Dynamic Filter Pane


You can narrow down alarms by combining multiple filter conditions. Combinations of filter
conditions are set in the Dynamic Filter pane.
This pane is not normally displayed. To display the Dynamic Filter pane, select a filter icon in
the Filter pane and drag it to near the status bar.

Status Bar
On Status bar, the following items are displayed
•ALM: Number of A&E messages occurred per time unit (1 hour, 8 hours or 24 hours)
•RCV: Number of alarms recovered per time unit (1 hour, 8 hours or 24 hours)
•ACK: Number of A&E messages acknowledged per time unit (1 hour, 8 hours or 24 hours)
•MRCV: Number of manually reset alarms per time unit (1 hour, 8 hours or 24 hours)
•EVT: Number of events out of the A&E messages per time unit (1 hour, 8 hours or 24 hours)

YOKOGAWA SINGAPORE TRAINING CENTRE Page 9 of 9

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.5. Changing the Layout of the Message Monitor of CAMS for HIS

The layout of the Message Monitor of CAMS for HIS can be changed to enhance the visibility
of A&E messages.

Switching the Layout of the Message Monitor of CAMS for HIS


The Message Monitor of CAMS for HIS can be shown in two layout patterns: one in which the
A&E Browser pane is positioned to the right of the Shelves and Filter panes, and the other in
which the A&E Browser pane is positioned above the Shelves and Filter panes. To switch
between the two display patterns, click [View] in the menu bar and then select [Switch
Layout], or click the [Change Window Layout] button in the toolbar.

Menu bar
Toolbar
A&E
Browser
Pane

Shelves Pane
A&E
Messages
Pane
Filter Pane

Details Pane

Figure: Switching the Layout of the Message Monitor of CAMS for HIS (Example of A&E
Browser Pane Shown Above)

YOKOGAWA SINGAPORE TRAINING CENTRE Page 10 of 10

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.6. Screening Alarms

The Message Monitor of CAMS for HIS lets you effectively manage frequent alarms. With the
help from this window, there are no more oversights of important alarms.
The applicable functions are listed below.
•Shelving
•Filtering
•Dynamic Filtering
•Message Tree View
•Suppression

19.7. Shelving
Alarms of lower priorities can be temporarily moved (shelved) to other location from the A&E
Messages pane to make it easier to recognize more important alarms.

Display of Shelved Alarms


The Shelves pane is divided into several fields corresponding to different shelving conditions.
These fields are called “buttons.” The information of shelved alarms is shown below each
button with a shelf name.
A display example of button is shown below.

Figure: Button for Shelved Alarms

The alarm information shown on the button includes, from the left, the number of A&E
messages currently present, number of unacknowledged A&E messages, number of shelved
A&E messages, and A&E messages that remain shelved beyond the timeout period.
When a desired button associated with shelved alarms is selected, the shelved A&E
messages will be shown in the A&E Messages pane.

Types of Shelving
Three types of shelving are available.
•Continuous Shelving
•One-Shot Shelving
•Auto-Shelving
The following explains each of these shelving types.

Continuous Shelving
A&E messages identical to each A&E message specified for shelving are shelved
continuously. Any reset messages associated with these messages are also shelved
continuously.
Once the specified time elapses, CAMS for HIS notifies that A&E messages remain shelved.
Thereafter, CAMS for HIS will not shelve any of those identical messages even when they are
issued.

One-Shot Shelving
Only the A&E message specified for shelving is shelved.
Once the specified time elapses, CAMS for HIS notifies that the A&E message remains
shelved.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 11 of 11

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

Auto-Shelving
Applicable alarms are shelved continuously in accordance with the filter conditions set for
these alarms specified for shelving.
Once the specified time elapses, CAMS for HIS notifies that A&E messages remain shelved.
Thereafter, CAMS for HIS will not shelve any of those identical messages even when they are
issued.
The filters that use Batch ID as criterion are not subject to Auto-Shelving.

Starting Shelving
In CAMS for HIS, shelving conditions are set for each button in the Shelves pane. To start
shelving, select an A&E message to be shelved, or a filter condition, and drag and drop it onto
a desired button.

An example of how shelving is started is shown below.

Figure: Shelving Start Operation

The following explains the operation to start each type of shelving.

•Continuous Shelving
Select an A&E message you want to shelve, and then drag and drop it onto a button of
Continuous attribute.

•One-Shot Shelving
Select an A&E message you want to shelve, and then drag and drop it onto a button of One-
Shot attribute. When A&E messages are displayed in a tree, if you select a desired message
at the top of the tree and then drag and drop it onto the desired button, all A&E messages
under the selected message will be shelved.

•Auto-Shelving
In the Filter pane, select a filter condition meeting the desired shelving purpose, and then
drag and drop the condition onto a button of Auto attribute. All A&E messages matching the
specified filter condition will be specified as the target of shelving. All new A&E messages
matching the filter condition will also be shelved.
Moreover, after selecting the A&E messages for shelving, or select the filter for shelving,
choose [Operation] - [Shelve] from menu bar and then choose a name of shelf from the list of
shelves.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 12 of 12

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

Resetting Shelving
The following explains the operation to reset shelving.
1.Select the shelf icon associated with the shelving you want to reset.
2.Select an A&E message that you want to remove from the shelf, and then click the [Clear
Shelf] button in the toolbar or choose [Operation] - [Reset Shelf] from the menu bar. Or drag
and drop the message to a filter area.
However, if an A&E message stays on the shelf for too long and becomes timeout, the
message will be automatically excluded from the shelving. If the same A&E message occurs,
the message will no longer be shelved.

Timeout Notification for Shelved Alarms


If a timeout occurs for any shelved A&E message, the applicable shelf icon will change to the
alarm clock to notify the operator that shelf contains a timeout message. When the applicable
shelf icon is selected to display the content of the shelf in the A&E Messages pane, you will
see an alarm clock icon at the beginning of the timeout A&E message.

Figure: Alarm Clock Icon of the Timeout A&E Message

Extent of Shelving
The entire system or an individual user can be selected as the extent of shelving in CAMS for
HIS. However, this setting needs to be uniform within the Equalization Scope.
The following explains different extents of shelving.

•SYSTEM
Shelving applies to the entire system. Shelved A&E messages are also shelved in all
Message Monitor of CAMS for HISs within the same system.

•USER
Shelving applies to the Message Monitor of CAMS for HIS associated with the same HIS
logon user. Shelved A&E messages are also shelved in all Message Monitor of CAMS for HIS
associated with the same HIS logon user.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 13 of 13

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.8. Filtering
Selects A&E messages that meet the criteria you specify.

Display of Filtered Alarms


Information of filtered alarms is shown next to the selected filter name (or below the filter
name in the Favorites tab).
A display example of filtered alarms is shown below.

Figure: Filtered Alarms

The alarm information shown when filtering is enabled includes, from the left, the number of
A&E messages currently present, number of unacknowledged A&E messages, and total
number of A&E messages.
When an active filter icon is selected, the filtered A&E messages will be shown in the A&E
Messages pane.

Starting Filtering
Select a desired filter icon to start filtering.

Activation of Filters
The filters of CAMS for HIS are functioning only on the CAMS for HIS message monitor that
started the filters. The filters will no longer function after switching HIS users.

Display Formats of the Filters Pane


The Filters pane can be displayed in two formats: one in which all filter conditions are shown
in a tree, and the other in which frequently used filter conditions are selected and shown in a
list. You can switch between these two display formats using the corresponding tabs.
•All Filters tab: Tree format
•Favorites tab: List format

The following illustrates how the Filter pane display is switched.

Figure: Switching of Filter Pane Display

In both formats, a filter condition is indicated by an icon and a filter name. The icons shown in
this pane are called “filter icons.”
Among all filter icons, the icon shown at the beginning of the tree (root) is called the “user
icon.” When a user icon is selected, all A&E messages that can be viewed by the user of the
applicable Message Monitor of CAMS for HIS will be shown in the A&E Messages pane. The
Filter pane will open in the tree format by default, where the user icon is already selected.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 14 of 14

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.9. Dynamic Filtering

Dynamic Filtering lets you screen alarms by combining multiple filter conditions, to make it
easier to recognize desired A&E messages.

Display of the Dynamic Filter Pane


The Message Monitor of CAMS for HIS showing the Dynamic Filter Pane is illustrated below.

Figure: Message Monitor of CAMS for HIS Showing the Dynamic Filter Pane

Starting Dynamic Filtering


To start dynamic filtering, select multiple filter icons in the Filter pane, arrange them in the
Dynamic Filter pane, and then define operators to connect the filter icons. However, the filters
that use Batch ID as criterion are not subject to Dynamic Filtering.
The specific operation is explained below.
1.Select a filter icon in the Filter pane, and then drag it to near the status bar.
The Dynamic Filter pane appears at the bottom of the Details pane.
2.Drop the filter icon into the Dynamic Filter pane.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 15 of 15

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

By following the same steps, drag and drop all desired filter conditions.

Figure: Operation to Start Dynamic Filtering - Select a Filter Conditions

3.Drag and drop the icons to define the operators connecting the filter icons.
Filter rules are defined.

Figure: Operation to Start Dynamic Filtering - Filter Rules Definition

4.To register the defined Filter rules as a new filter condition, click the [Set Filter Rules]
button.

Figure: Filter Rules Setting

Closing the Dynamic Filter pane also clears the filter rules.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 16 of 16

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

Setting Operators in the Dynamic Filter Pane


The following explains the operation that can be set in the Dynamic Filters pane.

Drag and drop this icon onto the Dynamic Filter pane to define an OR operator among the
filter conditions.

Drag and drop this icon onto the Dynamic Filter pane to define a NOT operator.

Drag and drop this icon onto the Dynamic Filter pane to define parentheses. The positions of
parentheses are adjustable.

Click this button to register the Filter rules you have defined in the Dynamic Filter pane, to the
Filters pane.
If no operator is dragged and dropped, the filter conditions will be connected by an AND
operator.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 17 of 17

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.10. Suppression

Suppression is a general term for the functions provided by CAMS for HIS to suppress A&E
messages. Suppressing unnecessary A&E messages makes it easier for operators to
recognize the more important A&E messages.

Suppression in CAMS for HIS


Suppressible processing and A&E messages are listed below.
•Show Alarm Tree (Eclipsing): Displays the related A&E messages in a tree structure.
•Obvious messages:
Suppresses the A&E messages of the specified stations or alarm groups.
•Chattering messages:
Suppresses the repeated A&E messages after displaying the first 10 messages.

Suppression Processing–Obvious Messages


The A&E messages of specified stations and alarm groups will be suppressed so as not to be
displayed on the CAMS for HIS message monitor. The suppressed A&E messages cannot be
displayed anymore. However, the messages displayed before the suppression of an alarm
will not be removed from the display after the alarm is specified for suppression.
The stations and alarm groups subject to suppression can be found on the Suppression
dialog box. Choose [View] - [Suppression...] from the menu bar on the message monitor of
CAMS for HIS, or click [Suppression...] button on the toolbar. The Suppression dialog box will
appear. The suppressed stations and alarm groups displayed on the Suppression dialog box
are marked as “Suppressed” in the [Status] column.
The Suppression dialog box is shown below.

Figure: Suppression Dialog Box

The details of the setting items are as follows:


•[Modify]:
Clicking this button will update the display on the Suppression dialog box. Since the
Suppression dialog box is not updated automatically, it is necessary to click this button when
checking the latest information.

•[Cancel]:
Clicking this button will stop updating the display on the Suppression dialog box.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 18 of 18

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

•[Group]:
Shows the names of the groups or stations subject to suppression.

•[Status]:
The groups undergoing the suppression are marked as Suppresses.

•[On/Off]:
Clicking the Off button will release the suppressed group from the suppression.

•[Description]:
Displays the descriptions on the suppressed alarm group. For the field control station, the
comment text defined on the builder for the FCS will be displayed. The description for the
alarm group cannot be modified.

Enable Alarm Suppression


Using the touch targets, push buttons or soft keys in the graphic view can enable
suppression. Click an above described object and enter the command script for enabling
suppression. The command script to be assigned to the object for enabling the alarm
suppression is shown as follows. Where the GroupName argument should be specified with
the name of an alarm group or a station that the alarms need to be suppressed.
(CENTUM VPInstalledFolder)\program\ BKHCAMS_SON.exeΔGroupName
Δ: Space character

Disable Alarm Suppression


There are two ways to disable the alarm suppression:
•Disabling the suppression on HIS graphic view.
Using the touch targets, push buttons or soft keys in the graphic view can disable
suppression. Click an above described object and enter the command script for disabling
suppression. The command script to be assigned to the object for disabling the alarm
suppression is shown as follows. Where the GroupName argument should be specified with
the name of an alarm group or a station that the alarms suppression need to be released.
(CENTUM VPInstalledFolder)\program\ BKHCAMS_SOF.exeΔGroupName
Δ: Space character
•Disabling Alarm Suppression on Message Monitor of CAMS for HIS
Open the Suppression dialog box; click the Off button in the On/Off field of the corresponding
alarm group.

Affects of Alarm Suppression


The alarm suppression of CAMS for HIS will affect all the alarms of equalization scope and
the alarms handled by the Message Monitor of CAMS for HIS regardless the operator (user)
privilege.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 19 of 19

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.11. Customizing the Message Monitor of CAMS for HIS

The Message Monitor of CAMS for HIS is customizable to the extent allowed by the
Configurator of CAMS for HIS for each user.

Window for Customizing the Message Monitor of CAMS for HIS


To customize (i.e., change the settings of) the Message Monitor of CAMS for HIS, open
Option window from the Message Monitor of CAMS for HIS:
From the menu bar for the Message Monitor of CAMS for HIS, select [Tools] and [Options].
Option window appears.
The Option window contains the following tabs:
•General tab
•Toolbar tab
•Status Bar tab
•Shelves Pane tab
•Filter Pane tab
•A&E Browser Pane tab
•A&E Messages Pane tab
•Dynamic Filters Pane tab
•Print tab

Buttons Common on All Tabs


The following buttons are common on all the tabs.

•[Reset to System Default] Button


Clicking this button will revert the settings on the Option window to the default settings.
After clicking this button, the default settings will not be kept unless the [Apply] or [OK] button
is clicked.

•[Apply] Button
Clicking this button will save the modified contents of all the tabs. After clicking this button, the
contents prior to the modification can no longer be reverted. However, if the contents on the
tabs are unchanged, the [Apply] button will be displayed as shaded (grayed).

•[OK] Button
Saves the modified contents and exits.

•[Cancel] Button
Exits without saving the modified contents.

YOKOGAWA SINGAPORE TRAINING CENTRE Page 20 of 20

VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE

19.12. Customizing General items on Message Monitor of CAMS for HIS

To customize General items on the Message Monitor of CAMS for HIS, click the General tab
in the Option window and do the settings.

General Tab in the Option Window


The figure below shows the General tab in Option window.

Figure: General Tab in Option Window

General Settings of the Message Monitor of CAMS for HIS


The general setting items relating to the Message Monitor of CAMS for HIS are shown below.

Table: General Setting Items for the Message Monitor of CAMS for HIS

YOKOGAWA SINGAPORE TRAINING CENTRE Page 21 of 21

VPOP_R4_TB_Ed.1_February 2009

You might also like