19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
If the power of Download Master is turned off, data cannot be downloaded to the database.
However, operation and monitoring of A&E messages is not affected
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Alarm Acquisition
Receives A&E messages from PRM and STARDOM via an OPC server, in addition to which
generated within CENTUM VP.
Normalization
Adds attributes, such as source name, timestamp and priority, to received A&E messages
based on the settings file created by the Configurator of CAMS for HIS. Normalization
standardizes the way A&E messages are expressed in different systems, to make
comparison of these A&E messages easy.
Grouping
Consolidates associated alarms into an alarm group. The user defines the conditions for
grouping alarms.
Suppression
Suppresses unnecessary alarms.
Shelving
Temporarily moves (shelves) alarms of lower priorities to other location from the A&E
Messages pane, in order to facilitate the recognition of more important alarms in the A&E
Browser pane and A&E Messages pane. This prevents the operator from overlooking
important alarms among lower-priority alarms when many alarms are present.
Load shedding
Shows only those messages matching the pre-defined search conditions once the number of
alarms generating in a specified period exceeds the threshold.
Sorting
Sorts A&E messages based on desired items and shows the sorted A&E messages in the
A&E Messages pane.
Filtering
Shows, among the A&E messages displayed in the A&E Messages pane, only those alarms
meeting specific conditions. It is possible to reduce the number of displayed alarms.
Audit Trails
Manages audit trails regarding the settings information relating to CAMS for HIS created by
Configurator of CAMS for HIS.
Management of Alarms
Manages the statuses of alarms and alarm groups (acknowledged, unacknowledged, etc.)
and deletes unnecessary alarms.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
This section explains the structure of the message monitor of CAMS for HIS.
Menu Bar
Toolbar A&E Browser
Pane
Shelves Pane
A&E Messages
Filters Pane Pane
Details Pane
Dynamic Filters
Pane
Status Bar
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
The CAMS for HIS consists of the following bars and panes.
•Menu Bar
•Toolbar
•Shelves Pane
•Filters
•A&E Browser Pane
•A&E Messages Pane
•Details Pane
•Dynamic Filters Pane
•Status Bar
Menu Bar
Operations available in the Message Monitor of CAMS for HIS can be selected using the
menu items in the menu bar. A list of menu items is shown below.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Toolbar
You can define the buttons such as Acknowledge, Acknowledge All, or Manual Reset on the
Toolbar. The figure below shows an example of Toolbar in the Message
Figure: Toolbar Buttons in the Message Monitor of CAMS for HIS (Default)
Print: Prints the contents currently shown in the A&E messages pane.
Acknowledge: Acknowledges the A&E messages selected from the list in the A&E messages
pane.
Acknowledge All: Acknowledges all the A&E messages shown in the A&E messages
pane.
Manual Reset: Resets the acknowledged A&E messages selected from the list in the A&E
messages pane. (Only A&E messages that are allowed to reset manually)
Switch Alarm View: Switches between “Alarm list” and “Show Alarm Tree” in A&E messages
pane with each click.
Clear Details Pane: Deselects the selected A&E messages and clears the contents in Details
pane.
Clear Shelf: Removes all the A&E messages for shelving from the shelves.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Show Shelves Pane: Switches between “Show” and “Hide” Shelves pane with each click.
Show Filter Pane: Switches between “Show” and “Hide” Filter pane with each click.
Show A&E Browser Pane: Switches between “Show” and “Hide” A&E Browser Pane with
each click.
Show Details Pane: Switches between “Show” and “Hide” Details Pane with each click.
Change Window Layout: Changes the width of the A&E message displaying area on the A&E
Browser pane by one clicking.
Show/Hide A&E Browser Pane Background: Changes between the Standard and Zebra
patterns for the background pattern of the A&E Browser pane by one clicking.
Show/Hide A&E Messages Pane Background: Changes between the Standard and Zebra
patterns for the background pattern of the A&E Messages pane by one clicking.
Call HIS Window: Calls the assigned operation and monitoring window.
Commit Changes: Saves the settings for the Message Monitor of CAMS for HIS.
Reset to System Default: Reverts all changes made by the operator to the original system
common settings.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Shelves Pane
This pane is used to perform shelving of alarm messages. The Shelves pane shows shelf
icons, shelf names and information of alarms that are currently shelved. An example of the
Shelves pane is shown below.
Filter Pane
This pane is used to filter alarm messages. An example of the Filter pane is shown below.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Details Pane
This pane is linked to the A&E Messages pane, and when one alarm is selected in the A&E
Messages pane, the causes, actions to take and other detail information of the alarm are
shown here.
Clicking the [Clear Details Pane] in the toolbar cancels the alarm selections in the A&E
Messages pane. The Details pane is also cleared and only the background color is shown.
Status Bar
On Status bar, the following items are displayed
•ALM: Number of A&E messages occurred per time unit (1 hour, 8 hours or 24 hours)
•RCV: Number of alarms recovered per time unit (1 hour, 8 hours or 24 hours)
•ACK: Number of A&E messages acknowledged per time unit (1 hour, 8 hours or 24 hours)
•MRCV: Number of manually reset alarms per time unit (1 hour, 8 hours or 24 hours)
•EVT: Number of events out of the A&E messages per time unit (1 hour, 8 hours or 24 hours)
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
19.5. Changing the Layout of the Message Monitor of CAMS for HIS
The layout of the Message Monitor of CAMS for HIS can be changed to enhance the visibility
of A&E messages.
Menu bar
Toolbar
A&E
Browser
Pane
Shelves Pane
A&E
Messages
Pane
Filter Pane
Details Pane
Figure: Switching the Layout of the Message Monitor of CAMS for HIS (Example of A&E
Browser Pane Shown Above)
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
The Message Monitor of CAMS for HIS lets you effectively manage frequent alarms. With the
help from this window, there are no more oversights of important alarms.
The applicable functions are listed below.
•Shelving
•Filtering
•Dynamic Filtering
•Message Tree View
•Suppression
19.7. Shelving
Alarms of lower priorities can be temporarily moved (shelved) to other location from the A&E
Messages pane to make it easier to recognize more important alarms.
The alarm information shown on the button includes, from the left, the number of A&E
messages currently present, number of unacknowledged A&E messages, number of shelved
A&E messages, and A&E messages that remain shelved beyond the timeout period.
When a desired button associated with shelved alarms is selected, the shelved A&E
messages will be shown in the A&E Messages pane.
Types of Shelving
Three types of shelving are available.
•Continuous Shelving
•One-Shot Shelving
•Auto-Shelving
The following explains each of these shelving types.
Continuous Shelving
A&E messages identical to each A&E message specified for shelving are shelved
continuously. Any reset messages associated with these messages are also shelved
continuously.
Once the specified time elapses, CAMS for HIS notifies that A&E messages remain shelved.
Thereafter, CAMS for HIS will not shelve any of those identical messages even when they are
issued.
One-Shot Shelving
Only the A&E message specified for shelving is shelved.
Once the specified time elapses, CAMS for HIS notifies that the A&E message remains
shelved.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Auto-Shelving
Applicable alarms are shelved continuously in accordance with the filter conditions set for
these alarms specified for shelving.
Once the specified time elapses, CAMS for HIS notifies that A&E messages remain shelved.
Thereafter, CAMS for HIS will not shelve any of those identical messages even when they are
issued.
The filters that use Batch ID as criterion are not subject to Auto-Shelving.
Starting Shelving
In CAMS for HIS, shelving conditions are set for each button in the Shelves pane. To start
shelving, select an A&E message to be shelved, or a filter condition, and drag and drop it onto
a desired button.
•Continuous Shelving
Select an A&E message you want to shelve, and then drag and drop it onto a button of
Continuous attribute.
•One-Shot Shelving
Select an A&E message you want to shelve, and then drag and drop it onto a button of One-
Shot attribute. When A&E messages are displayed in a tree, if you select a desired message
at the top of the tree and then drag and drop it onto the desired button, all A&E messages
under the selected message will be shelved.
•Auto-Shelving
In the Filter pane, select a filter condition meeting the desired shelving purpose, and then
drag and drop the condition onto a button of Auto attribute. All A&E messages matching the
specified filter condition will be specified as the target of shelving. All new A&E messages
matching the filter condition will also be shelved.
Moreover, after selecting the A&E messages for shelving, or select the filter for shelving,
choose [Operation] - [Shelve] from menu bar and then choose a name of shelf from the list of
shelves.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Resetting Shelving
The following explains the operation to reset shelving.
1.Select the shelf icon associated with the shelving you want to reset.
2.Select an A&E message that you want to remove from the shelf, and then click the [Clear
Shelf] button in the toolbar or choose [Operation] - [Reset Shelf] from the menu bar. Or drag
and drop the message to a filter area.
However, if an A&E message stays on the shelf for too long and becomes timeout, the
message will be automatically excluded from the shelving. If the same A&E message occurs,
the message will no longer be shelved.
Extent of Shelving
The entire system or an individual user can be selected as the extent of shelving in CAMS for
HIS. However, this setting needs to be uniform within the Equalization Scope.
The following explains different extents of shelving.
•SYSTEM
Shelving applies to the entire system. Shelved A&E messages are also shelved in all
Message Monitor of CAMS for HISs within the same system.
•USER
Shelving applies to the Message Monitor of CAMS for HIS associated with the same HIS
logon user. Shelved A&E messages are also shelved in all Message Monitor of CAMS for HIS
associated with the same HIS logon user.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
19.8. Filtering
Selects A&E messages that meet the criteria you specify.
The alarm information shown when filtering is enabled includes, from the left, the number of
A&E messages currently present, number of unacknowledged A&E messages, and total
number of A&E messages.
When an active filter icon is selected, the filtered A&E messages will be shown in the A&E
Messages pane.
Starting Filtering
Select a desired filter icon to start filtering.
Activation of Filters
The filters of CAMS for HIS are functioning only on the CAMS for HIS message monitor that
started the filters. The filters will no longer function after switching HIS users.
In both formats, a filter condition is indicated by an icon and a filter name. The icons shown in
this pane are called “filter icons.”
Among all filter icons, the icon shown at the beginning of the tree (root) is called the “user
icon.” When a user icon is selected, all A&E messages that can be viewed by the user of the
applicable Message Monitor of CAMS for HIS will be shown in the A&E Messages pane. The
Filter pane will open in the tree format by default, where the user icon is already selected.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Dynamic Filtering lets you screen alarms by combining multiple filter conditions, to make it
easier to recognize desired A&E messages.
Figure: Message Monitor of CAMS for HIS Showing the Dynamic Filter Pane
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
By following the same steps, drag and drop all desired filter conditions.
3.Drag and drop the icons to define the operators connecting the filter icons.
Filter rules are defined.
4.To register the defined Filter rules as a new filter condition, click the [Set Filter Rules]
button.
Closing the Dynamic Filter pane also clears the filter rules.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
Drag and drop this icon onto the Dynamic Filter pane to define an OR operator among the
filter conditions.
Drag and drop this icon onto the Dynamic Filter pane to define a NOT operator.
Drag and drop this icon onto the Dynamic Filter pane to define parentheses. The positions of
parentheses are adjustable.
Click this button to register the Filter rules you have defined in the Dynamic Filter pane, to the
Filters pane.
If no operator is dragged and dropped, the filter conditions will be connected by an AND
operator.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
19.10. Suppression
Suppression is a general term for the functions provided by CAMS for HIS to suppress A&E
messages. Suppressing unnecessary A&E messages makes it easier for operators to
recognize the more important A&E messages.
•[Cancel]:
Clicking this button will stop updating the display on the Suppression dialog box.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
•[Group]:
Shows the names of the groups or stations subject to suppression.
•[Status]:
The groups undergoing the suppression are marked as Suppresses.
•[On/Off]:
Clicking the Off button will release the suppressed group from the suppression.
•[Description]:
Displays the descriptions on the suppressed alarm group. For the field control station, the
comment text defined on the builder for the FCS will be displayed. The description for the
alarm group cannot be modified.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
The Message Monitor of CAMS for HIS is customizable to the extent allowed by the
Configurator of CAMS for HIS for each user.
•[Apply] Button
Clicking this button will save the modified contents of all the tabs. After clicking this button, the
contents prior to the modification can no longer be reverted. However, if the contents on the
tabs are unchanged, the [Apply] button will be displayed as shaded (grayed).
•[OK] Button
Saves the modified contents and exits.
•[Cancel] Button
Exits without saving the modified contents.
VPOP_R4_TB_Ed.1_February 2009
19. CONSOLIDATED ALARM MANAGEMENT SOFTWARE
To customize General items on the Message Monitor of CAMS for HIS, click the General tab
in the Option window and do the settings.
Table: General Setting Items for the Message Monitor of CAMS for HIS
VPOP_R4_TB_Ed.1_February 2009