Safety of Household and Similar Electrical Appliances Part 2:particular Requirements For Humidifiers
Safety of Household and Similar Electrical Appliances Part 2:particular Requirements For Humidifiers
Safety of Household and Similar Electrical Appliances Part 2:particular Requirements For Humidifiers
TEST REPORT
IEC 60335-2-98 and / or EN 60335-2-98
Safety of household and similar electrical appliances
Part 2 :Particular requirements for humidifiers
Report Reference No. .................... : 12027605 001
Date of issue .................................... : 10 January 2013
Total number of pages ..................... : 157
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme
procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended
to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
If this Test Report Form is used by non-CCA members, the CIG logo and the reference to the CCA Procedure shall be
removed.
This report is not valid as a CCA Test Report unless signed by an approved CCA Testing Laboratory and
appended to a CCA Test Certificate issued by an NCB in accordance with CCA
Associated CB Laboratory:
Testing location/ address ...................... :
Tested by (name + signature) ..... : Rianto Yuwono
Summary of testing:
The samples tested Complies with the requirements of IEC 60335-2-98:2002 (2.Edition) + A1:2004,
IEC 60335-1:2001 (4. Edition) (incl. Corrigendum 1:2002) + A1:2004 + A2:2006 (incl. Corrigendum 1:2006)
and EN 60335-2-98:2003 + A1 :2004, EN 60335-1:2002 + A1:2004 + A11:2004 + A12:2006 + A2:2006
LCB Series :
CPL Series:
BM Series:
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Note: This TRF includes EN Group Differences together with National Differences and Special National
Conditions, if any. All Differences are located in the Appendix to the main body of this TRF.
Throughout this report a point is used as the decimal separator.
The appliance was an evaporative cooler, using evaporated water at ambient temperature to cool the air.
An axial fan draw an outside air, passing through wet frame pad to the building.
The water was circulated from the reservoir at the base of the enclosure to the frame pads using a pump,
and the water level in reservoir is maintained by a float valve connected to mains water supply. Reservoir
salinity is controlled by either a constant bleed-off, or via a drain water valve together with salinity probes
will open the drain valve when salinity level reaches a preset level, releasing some water and fresh water is
added through water inlet.
Installation of the appliance water supply using fixed piping must conform to local plumbing rules,
regulations and standards : AS/NZS 3500.1
A detachable hose set for connection to the water mains and a solenoid valve is supplied and used in
combination with the drain valve kit (optional in some models).
The appliance was a fixed appliance to be installed on the roof top by qualified installer, and an authorised
dealer is recommended for maintenance.
The differences between models LCB550-X, LCB450-X, LCB350-X, LCB250-X* , branded as Braemar :
- Model LCB550-X uses a 950W output Seeley manufactured motor, high capacity fan and large size
cabinet
- Model LCB450-X uses 560W output Seeley manufactured motor or 600W output Able manufactured
motor, high capacity fan and large size cabinet.
- Model LCB350-X uses 500W output Seeley manufactured motor or 430W output Able manufactured
motor, high capacity fan and medium size cabinet.
- Model LCB250-X uses 300W output Seeley manufactured motor or 340W output Able manufactured
motor, low capacity fan and medium size cabinet.
The differences between models TBA550-X, TBA450_X, TBA350-X, TBA250-X*, branded as Breezair
when compared to models LCB550-X, LCB450-X, LCB350-X, LCB250-X* :
- Model TBA550-X equivalent to LCB550-X, except it uses different style outer cabinet pad frame
and hard wired connection in lieu of plug.
- Model TBA450-X equivalent to LCB450-X, except it uses different style outer cabinet pad frame
and hard wired connection in lieu of plug.
- Model TBA350-X equivalent to LCB350-X, except it uses different style outer cabinet pad frame
and hard wired connection in lieu of plug.
- Model TBA250-X equivalent to LCB250-X, except it uses different style outer cabinet pad frame
and hard wired connection in lieu of plug.
The differences between model CPL1100X-X, CPL1100-X, CPL850-X, CPL700-X, CPL450-X*, branded as
Coolair, when compared to LCB550-X, LCB450-X, LCB350-X, LCB250-X* :
- Model CPL1100X-X equivalent to model LCB550-X, except it uses multi-piece high capacity fan ,
different decorative style outer cabinet and hard wired.
- Model CPL1100-X equivalent to model LCB550-X, except it uses multi-piece high capacity fan with
750W output Able manufactured motor and different style outer cabinet pad frame.
- Model CPL850-X equivalent to model LCB450-X, except it uses multi-piece high capacity fan with
600W output Able manufactured motor and different style outer cabinet pad frame.
- Model CPL7000-X equivalent to model LCB350-X, except it uses multi-piece low capacity fan with
430W output Able manufactured motor and different style outer cabinet pad frame.
- Model CPL450-X equivalent to model LCB250-X, except it uses multi-piece low capacity fan with
340W output Able manufactured motor and different style outer cabinet pad frame.
The differences between model BM1150X, BM900-X, BM750-X, BM500-X*, branded as Braemar, when
compared to LCB550-X, LCB450-X, LCB350-X, LCB250-X* :
- Model BM1150-X equivalent to model LCB550-X, except it uses multi-piece high capacity fan with
750W output Able manufactured motor and different style outer cabinet pad frame.
- Model BM900-X equivalent to model LCB450-X, except it uses multi-piece high capacity fan with
600W output Able manufactured motor and different style outer cabinet pad frame.
- Model BM750-X equivalent to model LCB350-X, except it uses multi-piece low capacity fan with
430W output Able manufactured motor and different style outer cabinet pad frame.
- Model BM500-X equivalent to model LCB250-X, except it uses multi-piece low capacity fan with
340W output Able manufactured motor and different style outer cabinet pad frame.
Note : “X” denotes colour: -“B” =Beige, -“G “=Grey, -“H”=Green, -“R”=Red
Due to similarity between model LCB550-X, LCB450-X, LCB350-X, LCB250-X, TBA550-X, TBA450-X,
TBA350-X, TBA250-X, CPL1100X-X, CPL1100-X, CPL850-X, CPL700-X, CPL450-X, BM 1150-X, BM900-
X, BM750-X and BM500-X, only model LCB550-X was subjected to full testing and partial testing were
performed on model LCB250-X, LCB350-X, LCB450-X, CPL1100-X, including all alternatives fan motor.
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
5 GENERAL CONDITIONS FOR THE TESTS -
Tests performed according to cl. 5, e.g. nature of P
supply, sequence of testing, etc.
5.6 Humidistats are short-circuited or rendered P
inoperative. (IEC 60335-2-98)
6 CLASSIFICATION -
6.1 Protection against electric shock: Class I P
Class 0, 0I, I, II, III ....................................................:
6.2 Protection against harmful ingress of water IPX4 P
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
If the temperature of the water vapour exceeds N/A
60 C, the appliance shall be marked with the
substance of the following:
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
7.11 Indication for direction of adjustment of controls N/A
7.12 Instructions for safe use provided P
The instructions state that: -
- the appliance is not to be used by children or P
persons with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge,
unless they have been given supervision or
instruction
- children being supervised not to play with the P
appliance
The instructions shall include details regarding P
filling, cleaning and descaling. (IEC 60335-2-98)
The instructions shall state the substance of the following: (IEC 60335-2-98) -
– care should be taken when using the appliance N/A
due to the emission of hot water vapour;
(IEC 60335-2-98)
– unplug the appliance during filling and cleaning. P
(IEC 60335-2-98)
The instructions for electrode-type appliances shall include the substance of the -
following: (IEC 60335-2-98)
– the composition and quantity of solution to be N/A
used and advice not to use an excessive amount of
salt; (IEC 60335-2-98)
– the appliance is not to be operated from a d.c. N/A
supply. (IEC 60335-2-98)
7.12.1 Sufficient details for installation supplied P
The installation instructions for appliances intended 800 kPa P
to be connected to the water mains shall state the
maximum permissible water pressure in pascals.
(IEC 60335-2-98)
7.12.2 Stationary appliances not fitted with means for Installation manual stated: P
disconnection from the supply mains having a Fitted with accessible plug or
contact separation in all poles that provide full incorporating a switch in fixed
disconnection under overvoltage category III, the wiring
instructions state that means for disconnection must
be incorporated in the fixed wiring in accordance with
the wiring rules
7.12.3 Insulation of the fixed wiring in contact with parts N/A
exceeding 50 K during clause 11; instructions stating
that the fixed wiring must be protected
7.12.4 Instructions for built-in appliances: -
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
- dimensions of space N/A
- dimensions and position of supporting means N/A
- distances between parts and surrounding structure N/A
- dimensions of ventilation openings and N/A
arrangement
- connection to supply mains and interconnection of N/A
separate components
- allow disconnection of the appliance after N/A
installation, by accessible plug or a switch in the
fixed wiring, unless
a switch complying with 24.3 N/A
7.12.5 Replacement cord instructions, type X attachment N/A
with a specially prepared cord
Replacement cord instructions, type Y attachment P
Replacement cord instructions, type Z attachment N/A
7.12.6 Caution in the instructions for heating appliances N/A
with a non-self-resetting thermal cut-out
7.12.7 Instructions for fixed appliances stating how the P
appliance is to be fixed
7.12.8 Instructions for appliances connected to the water mains: -
- max. inlet water pressure (Pa) ...............................: 800 kPa P
- min. inlet water pressure, if necessary (Pa) ..........: N/A
Instructions concerning new and old hose-sets for P
appliances connected to the water mains by
detachable hose-sets
7.13 Instructions and other texts in an official language P
7.14 Marking clearly legible and durable P
7.15 Marking on a main part P
Marking clearly discernible from the outside, if P
necessary after removal of a cover
For portable appliances, cover can be removed or N/A
opened without a tool
For stationary appliances, name, trademark or N/A
identification mark and model or type reference
visible after installation
For fixed appliances, name, trademark or P
identification mark and model or type reference
visible after installation according to the instructions
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Indications for switches and controls placed on or P
near the components. Marking not on parts which
can be positioned or repositioned in such a way that
the marking is misleading
7.16 Marking of a possible replaceable thermal link or N/A
fuse link clearly visible with regard to replacing the
link
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
- for peak values over 15kV, the energy in the N/A
discharge not exceeding 350 mJ
8.1.5 Live parts protected at least by basic insulation before installation or assembly: -
- built-in appliances N/A
- fixed appliances P
- appliances delivered in separate units N/A
8.2 Class II appliances and constructions constructed so Class I appliance, Class II P
that there is adequate protection against accidental construction
contact with basic insulation and metal parts
separated from live parts by basic insulation only
Only possible to touch parts separated from live P
parts by double or reinforced insulation
11 HEATING -
11.1 No excessive temperatures in normal use P
11.2 Placing and mounting of appliance as described P
11.3 Temperature rises, other than of windings, P
determined by thermocouples
Temperature rises of windings determined by Fan motor, water pump P
resistance method, unless
the windings makes it difficult to make the necessary PCB mounted transformer and P
connections water drain motor
11.4 Electrode-type appliances are supplied at 1,06 N/A
times rated voltage. (IEC 60335-2-98)
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
If the temperature rise limits are exceeded in N/A
appliances incorporating motors, transformers or
electronic circuits, and the power input is lower
than the rated power input, the test is repeated with
the appliance supplied at 1,06 times rated voltage.
(IEC 60335-2-98)
11.5 Motor-operated appliances operated under normal 1.06 x 240V=254.4V P
operation at most unfavourable voltage between
0.94 and 1.06 times rated voltage ...........................:
11.6 Combined appliances are operated as heating N/A
appliances. (IEC 60335-2-98)
11.7 Appliances are operated until steady conditions are P
established. (IEC 60335-2-98)
11.8 Temperature rises not exceeding values in table 3 (see appended tables) P
The temperature rise limits of motors, transformers N/A
and components of electronic circuits,including
parts directly influenced by them, may be exceeded
when the appliance is operated at 1,15 times rated
power input. (IEC 60335-2-98)
Sealing compound does not flow out P
Protective devices do not operate, except P
components in protective electronic circuits tested for P
the number of cycles specified in 24.1.4
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
The leakage current shall not exceed 0,25 mA. N/A
(IEC 60335-2-98/A1)
Leakage current measurements (see appended table) P
13.3 The appliance is disconnected from the supply P
Electric strength tests according to table 4 (see appended table) P
No breakdown during the tests P
14 TRANSIENT OVERVOLTAGES -
Appliances withstand the transient overvoltages to N/A
which they may be subjected
Clearances having a value less than specified in (see appended table) N/A
table 16 subjected to an impulse voltage test, the test
voltage specified in table 6
No flashover during the test, unless of functional N/A
insulation
In case of flashover of functional insulation, the N/A
appliance complies with clause 19 with the clearance
short circuited
15 MOISTURE RESISTANCE -
15.1 Enclosure provides the degree of moisture protection P
according to classification of the appliance
Compliance checked as specified in 15.1.1, taking P
into account 15.1.2, followed by the electric strength
test of 16.3
No trace of water on insulation which can result in a P
reduction of clearances and creepage distances
below values specified in clause 29
15.1.1 Appliances, other than IPX0, subjected to tests as See Austest report no.8428 P
specified in IEC 60529 .............................................: dated on 25 October 2007
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Appliances normally fixed to a wall and appliances N/A
with pins for insertion into socket-outlets are
mounted on a wooden board
For IPX3 appliances, the base of wall mounted N/A
appliances is placed at the same level as the pivot
axis of the oscillating tube
For IPX4 appliances, the horizontal centre line of the P
appliance is aligned with the pivot axis of the
oscillating tube
However, for appliances normally used on the floor N/A
or table, the movement is limited to two times 90 for
a period of 5 min, the support being placed at the
level of the pivot axis of the oscillating tube
Appliances normally fixed to a ceiling are mounted N/A
underneath a horizontal unperforated support, the
pivot axis of the oscillating tube located at the level of
the underside of the support
For IPX4 appliances, the movement of the tube is P
limited to two times 90 from the vertical for a period
of 5 min
Wall-mounted appliances, take into account the N/A
distance to the floor stated in the instructions
Appliances with type X attachment fitted with a Type Y N/A
flexible cord as described
Detachable parts tested as specified N/A
15.2 Spillage of liquid does not affect the electrical P
insulation
Appliances with type X attachment fitted with a N/A
flexible cord as described
Appliances incorporating an appliance inlet tested With connector P
with or without an connector, whichever is most
unfavourable
Detachable parts removed N/A
Overfilling test with additional amount of Water level float disabled, P
water, over a period of 1 min (l) ...............................: water added until overflow
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Appliances intended to be connected to the water P
mains are operated until the maximum water level
is reached. The inlet valve is held open and the
filling continued for 15 min after the first evidence of
overflow or until the inflow stops automatically.
(IEC 60335-2-98)
The appliance withstands the electric strength test of P
16.3
No trace of water on insulation that can result in a P
reduction of clearances and creepage distances
below values specified in clause 29
15.3 Appliances proof against humid conditions P
Humidity test for 48 h in a humidity cabinet P
The appliance withstands the tests of clause 16 P
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Temperature of the winding not exceeding the value P
specified in table 8,
however limits do not apply to fail-safe transformers P
complying with sub-clause 15.5 of IEC 61558-1
19 ABNORMAL OPERATION -
19.1 The risk of fire or mechanical damage under P
abnormal or careless operation obviated
Electronic circuits so designed and applied that a P
fault will not render the appliance unsafe
Appliances incorporating contactors or relays P
subjected to the test of 19.14, being carried out
before the tests of 19.11
19.2 Test of appliance with heating elements with No heating element N/A
restricted heat dissipation; test voltage (V): power
input of 0.85 times rated power input.......................:
The container of electrode-type appliances is filled N/A
with a saturated solution of NaCl at 20 C ± 5 C,
the appliance being supplied at rated voltage.
(IEC60335-2-98)
19.3 Test of 19.2 repeated; test voltage (V): power input N/A
of 1.24 times rated power input................................:
The test is not applicable to electrode-type N/A
appliances. (IEC60335-2-98)
19.4 Appliances are only filled with sufficient water to No heating element N/A
cover the heating elements. (IEC60335-2-98)
Fans are switched off. (IEC60335-2-98) N/A
19.5 Test of 19.4 repeated on Class 0I and I appliances No heating element N/A
with tubular sheathed or embedded heating
elements. No short-circuiting, but one end of the
element connected to the elements sheath
The test repeated with reversed polarity and the N/A
other end of the heating element connected to the
sheath
The test is not carried out on appliances intended to N/A
be permanently connected to fixed wiring and on
appliances where an all-pole disconnection occurs
during the test of 19.4
19.6 Appliances with PTC heating elements tested at N/A
rated voltage, establishing steady conditions
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
The working voltage of the PTC heating element is N/A
increased by 5% and the appliance is operated until
steady conditions are re-established. The voltage is
then increased in similar steps until 1.5 times
working voltage or until the PTC heating element
ruptures
19.7 Stalling test by locking the rotor if the locked rotor 1) Fan motor, self resetting P
torque is smaller than the full load torque or locking thermal cut-off disabled
moving parts of other appliances
2) Water pump motor
Locked rotor, motor capacitors open-circuited or P2 capacitor N/A
short-circuited, if required
Locked rotor, capacitors open-circuited one at a time N/A
Test repeated with capacitors short-circuited one at a N/A
time, if required
Appliances with timer or programmer supplied with N/A
rated voltage for each of the tests, for a period equal
to the maximum period allowed
Other appliances supplied with rated voltage for a P
period as specified
Winding temperatures not exceeding values (see appended table) P
specified in table 8
19.8 Three-phase motors operated at rated voltage with N/A
one phase disconnected
19.9 Running overload test on appliances incorporating 1) Fan motor, thermal fuse P
motors intended to be remotely or automatically protected, self resetting
controlled or liable to be operated continuously thermal cut-off disabled
2) Water pump motor,
thermally protected
Winding temperatures not exceeding values as (see appended table) P
specified
19.10 Series motor operated at 1.3 times rated voltage for N/A
1 min .........................................................................:
During the test, parts not being ejected from the N/A
appliance
19.11 Electronic circuits, compliance checked by P
evaluation of the fault conditions specified in 19.11.2
for all circuits or parts of circuits, unless they comply
with the conditions specified in 19.11.1
Appliances incorporating a protective electronic N/A
circuit subjected to the tests of 19.11.3 and 19.11.4
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Appliances having a switch with an off position N/A
obtained by electronic disconnection, or a switch
placing the appliance in a stand-by mode, subjected
to the tests of 19.11.4
Appliances incorporating an electronic circuit that P
relies upon a programmable component to function
correctly, subjected to the test of 19.11.4.8
19.11.1 Before applying the fault conditions a) to f) in 19.11.2, it is checked if circuits or parts -
of circuit meet both of the following conditions:
- the electronic circuit is a low-power circuit, that is, N/A
the maximum power at low-power points does not
exceed 15 W according to the tests specified
- the protection against electric shock, fire hazard, N/A
mechanical hazard or dangerous malfunction in
other parts of the appliance does not rely on the
correct functioning of the electronic circuit
19.11.2 Fault conditions applied one at a time, the appliance operated under conditions -
specified in cl. 11, but supplied at rated voltage, the duration of the tests as specified:
a) short circuit of functional insulation if clearances or Short circuit secondary DC P
creepage distances are less than the values outpur. No hazard
specified in 29
b) open circuit at the terminals of any component Open circuit R 3, fan non P
operational. No hazard
c) short circuit of capacitors, unless they comply with Approved capacitor N/A
IEC 60384-14
d) short circuit of any two terminals of an electronic Short circuit C28, seems to run P
component, other than integrated circuits. This fault normally. No hazard
condition is not applied between the two circuits of
an optocoupler
e) failure of triacs in the diode mode U1, fan always run at highest P
speed. No hazard
f) failure of an integrated circuit Failure of U11, red light P
indicator on, water pump non
operational. No hazard.
g) failure of an electronic power switching device No power switching device N/A
19.11.3 If the appliance incorporates a protective electronic N/A
circuit which operates to ensure compliance with
clause 19, the relevant test is repeated with a single
fault simulated, as indicated in a) to f) of 19.11.2
During and after each test the following is checked: -
- the temperature rise of the windings do not exceed P
the values specified in table 8
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
- the appliance complies with the conditions specified P
in 19.13
- any current flowing through protective impedance N/A
not exceeding the limits specified in 8.1.4
If a conductor of a printed board becomes open-circuited, the appliance is considered -
to have withstood the particular test, provided all three of the following conditions are
met:
- the material of the printed circuit board withstands N/A
the burning test of annex E
- any loosened conductor does not reduce the N/A
clearances or creepage distances between live parts
and accessible metal parts below the values
specified in cl. 29
- the appliance withstands the tests of 19.11.2 with N/A
open-circuited conductor bridged
19.11.4 Appliances having a device with an off position See summary page and N/A
obtained by electronic disconnection, or attachment 3
a device that can be placed in the stand-by mode, N/A
subjected to the tests of 19.11.4.1 to 19.11.4.7 N/A
Appliances incorporating a protective electronic N/A
circuit subjected to the tests of 19.11.4.1 to
19.11.4.7, except that
appliances operated for 30 s or 5 min during the test N/A
of 19.7 are not subjected to the tests for
electromagnetic phenomena.
19.11.4.1 The appliance is subjected to electrostatic See summary page and N/A
discharges in accordance with IEC 61000-4-2, test attachment 3
level 4
19.11.4.2 The appliance is subjected to radiated fields in See summary page and N/A
accordance with IEC 61000-4-3, test level 3 attachment 3
19.11.4.3 The appliance is subjected to fast transient bursts in See summary page and N/A
accordance with IEC 61000-4-4, test level 3 or 4 as attachment 3
specified
19.11.4.4 The power supply terminals of the appliance See summary page and N/A
subjected to voltage surges in accordance with IEC attachment 3
61000-4-5, test level 3 or 4 as specified
Earthed heating elements in class I appliances N/A
disconnected
19.11.4.5 The appliance is subjected to injected currents in See summary page and N/A
accordance with IEC 61000-4-6, test level 3 attachment 3
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
19.11.4.6 The appliance is subjected to the Class 3 voltage See summary page and N/A
dips and interruptions in accordance with IEC 61000- attachment 3
4-11
19.11.4.7 The appliance is subjected to mains signals in See summary page and N/A
accordance with IEC 61000-4-13, test level class 2 attachment 3
19.11.4.8 The appliance is supplied at rated voltage and The appliance stopped P
operated under normal operation. After 60s the operating (fan off) at
power supply is reduces to a level such that the V=150VAC.
appliance ceases to respond or a programmable
component cease to operate.
The appliance continues to operate normally or The appliance resume to P
requires a manual operation to restart previous operation at V = 192
VAC
19.12 If the safety of the appliance for any of the fault N/A
conditions specified in 19.11.2 depends on the
operation of a miniature fuse-link complying with
IEC 60127, the test is repeated, measuring the
current flowing through the fuse-link; measured
current (A); rated current of the fuse-link (A) ...........:
19.13 During the tests the appliance does not emit flames, P
molten metal, poisonous or ignitable gas in
hazardous amounts
Temperature rises not exceeding the values shown (see appended table) P
in table 9
Compliance with cl. 8 not impaired P
If the appliance can still be operated it complies with P
20.2
Insulation, other than of class III appliance, withstand the electric strength test of 16.3, -
the test voltage specified in table 4:
- basic insulation .......................................................: 1250V P
- supplementary insulation .......................................: N/A
- reinforced insulation ...............................................: 3000V P
After operation or interruption of a control, P
clearances and creepage distances across the
functional insulation withstanding the electric
strength test of 16.3. the test voltage being twice the
working voltage
The appliance does not undergo a dangerous P
malfunction, and
no failure of protective electronic circuits, if the P
appliance is still operable
Appliances tested with an electronic switch in the off position, or in the stand-by mode: -
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
- do not become operational, or See summary page and N/A
attachment 3
- if they become operational, do not result in a See summary page and N/A
dangerous malfunction during or after the tests of attachment 3
19.11.4
19.14 Appliances operated under the conditions of Clause K1 = Fan relay, appliance P
11. Contactors or relays contacts operating under seems run normally, no
the conditions of clause 11 short-circuited hazard.
K2 = Water pump relay, water
pump circulating water
continuously. No hazard.
K3 = Drain water relay, water
drain valve opened
continuously. No hazard.
K4 = Water inlet relay, solenoid
opened continuously, water
tank overflow, no hazard.
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
21 MECHANICAL STRENGTH -
21.1 Appliance has adequate mechanical strength and is P
constructed as to withstand rough handling
Checked by applying blows to the appliance in P
accordance with test Ehb of IEC 60068-2-75, spring
hammer test, impact energy 0,5 J
If necessary, supplementary or reinforced insulation P
subjected to the electric strength test of 16.3
If necessary, repetition of groups of three blows on a P
new sample
21.2 Accessible parts of solid insulation having strength to No accessible insulation N/A
prevent penetration by sharp implements
The insulation is tested as specified, unless N/A
the thickness of supplementary insulation is at least N/A
1 mm and reinforced insulation is at least 2 mm
22 CONSTRUCTION -
22.1 Appliance marked with the first numeral of the IP IPX4 P
system, relevant requirements of IEC 60529 are
fulfilled
22.2 Stationary appliance: means to provide all-pole disconnection from the supply -
provided, the following means being available:
- a supply cord fitted with a plug For Australia and New Zealand P
model LCB, CPL and BM
series
- a switch complying with 24.3 N/A
- a statement in the instruction sheet that a P
disconnection incorporated in the fixed wiring is to be
provided
- an appliance inlet Model TBA series and P
CPL1100X-X
Singe-pole switches and single-pole protective N/A
devices for the disconnection of heating elements in
single-phase, permanently connected class 01 and
class I appliances, connected to the phase
conductor
22.3 Appliance provided with pins: no undue strain on N/A
socket-outlets
Applied torque not exceeding 0.25 Nm N/A
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Pull force of 50N to each pin after the appliance has N/A
being placed in the heating cabinet; when cooled to
room temperature the pins are not displaced by
more than 1mm
Each pin subjected to a torque of 0.4Nm; the pins N/A
are not rotating unless rotating does not impair
compliance with the standard
22.4 Appliance for heating liquids and appliance causing N/A
undue vibration not provided with pins for insertion
into socket-outlets
22.5 No risk of electric shock when touching the pins of < 1V after 1sec P
the plug, for appliances having a capacitor with rated
capacitance exceeding 0,1F, the appliance being
disconnected from the supply at the instant of
voltage peak
22.6 Electrical insulation not affected by condensing water Electrical connection protected P
or leaking liquid by a splash cover
Electrical insulation of Class II appliances not P
affected in case of a hose rupture or seal leak
Drain holes shall be at least 5 mm in diameter or Drain hole overflow, 16mm in P
20 mm² in area with a minimum dimension of at diameter
least 3 mm. (IEC60335-2-
98)
22.7 Adequate safeguards against the risk of excessive No hot vapour N/A
pressure in appliances provided with steam-
producing devices
22.8 Electrical connections not subject to pulling during P
cleaning of compartments to which access can be
gained without the aid of a tool, and that are likely to
be cleaned in normal use
22.9 Insulation, internal wiring, windings, commutators P
and slip rings not exposed to oil, grease or similar
substances
Adequate insulating properties of oil or grease to No exposure to oil or grease N/A
which insulation is exposed
22.10 Not possible to reset voltage-maintained non-self- Non-self resetting circuit P
resetting thermal cut-outs by the operation of an breaker non accessible without
automatic switching device incorporated within the tools
appliance
Non-self resetting thermal motor protectors have a P
trip-free action, unless
they are voltage maintained N/A
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Location or protection of reset buttons of non-self- Non-self resetting circuit P
resetting controls is so that accidental resetting is breaker non accessible without
unlikely tools
22.11 Reliable fixing of non-detachable parts that provide Snap in cover (Pad) , non P
the necessary degree of protection against electric detachable
shock, moisture or contact with moving parts
Obvious locked position of snap-in devices used for P
fixing such parts
No deterioration of the fixing properties of snap-in P
devices used in parts that are likely to be removed
during installation or servicing
Tests as described Push: 50N, Pull: 50N P
22.12 Handles, knobs etc. fixed in a reliable manner No such device N/A
Fixing in wrong position of handles, knobs etc. N/A
indicating position of switches or similar components
not possible
Axial force 15 N applied to parts, the shape being so N/A
that an axial pull is unlikely to be applied
Axial force 30 N applied to parts, the shape being so N/A
that an axial pull is likely to be applied
22.13 Unlikely that handles, when gripped as in normal N/A
use, make the operators hand touch parts having a
temperature rise exceeding the value specified for
handles which are held for short periods only
22.14 No ragged or sharp edges creating a hazard for the P
user in normal use, or during user maintenance
No exposed pointed ends of self tapping screws etc., P
liable to be touched by the user in normal use or
during user maintenance
22.15 Storage hooks and the like for flexible cords smooth P
and well rounded
22.16 Automatic cord reels cause no undue abrasion or N/A
damage to the sheath of the flexible cord, no
breakage of conductors strands, no undue wear of
contacts
Cord reel tested with 6000 operations, as specified N/A
Electric strength test of 16.3, voltage of 1000 V N/A
applied
22.17 Spacers not removable from the outside by hand or No spacers N/A
by means of a screwdriver or a spanner
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
22.18 Current-carrying parts and other metal parts resistant P
to corrosion under normal conditions of use
22.19 Driving belts not used as electrical insulation No driving belt N/A
22.20 Direct contact between live parts and thermal P
insulation effectively prevented, unless material used
is non-corrosive, non-hygroscopic and non-
combustible
Compliance is checked by inspection and, if P
necessary, by appropriate test
22.21 Wood, cotton, silk, ordinary paper and fibrous or P
hygroscopic material not used as insulation, unless
impregnated
This requirement does not apply to magnesium P
oxide and mineral ceramic fibres used for the
electrical insulation of heating elements
22.22 Appliances not containing asbestos P
22.23 Oils containing polychlorinated biphenyl (PCB) not P
used
22.24 Bare heating elements adequately supported No heating element N/A
In case of rupture, the heating conductor is unlikely N/A
to come in contact with accessible metal parts
22.25 Sagging heating conductors cannot come into N/A
contact with accessible metal parts
22.26 The insulation between parts operating at safety P
extra-low voltage and other live parts complies with
the requirements for double or reinforced insulation
22.27 Parts connected by protective impedance separated No protective impedance N/A
by double or reinforced insulation
22.28 Metal parts of Class II appliances conductively N/A
connected to gas pipes or in contact with water:
separated from live parts by double or reinforced
insulation
22.29 Class II appliances permanently connected to fixed P
wiring so constructed that the required degree of
access to live parts is maintained after installation
22.30 Parts serving as supplementary or reinforced P
insulation fixed so that they cannot be removed
without being seriously damaged, or
so constructed that they cannot be replaced in an P
incorrect position, and so that if they are omitted, the
appliance is rendered inoperable or manifestly
incomplete
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
22.31 Clearances and creepage distances over P
supplementary and reinforced insulation not reduced
below values specified in clause 29 as a result of
wear
Clearances and creepage distances between live P
parts and accessible parts not reduced below values
for supplementary insulation, if wires, screws etc.
become loose
22.32 Supplementary and reinforced insulation designed or P
protected against deposition of dirt or dust
Supplementary insulation of natural or synthetic Not used N/A
rubber resistant to ageing, or arranged and
dimensioned so that creepage distances are not
reduced below values specified in 29.2
Ceramic material not tightly sintered, similar material N/A
or beads alone not used as supplementary or
reinforced insulation
Oxygen bomb test at 70 C for 96 h and 16 h at room N/A
temperature
Insulating material in which heating conductors are N/A
embedded is considered to be basic insulation and
not reinforced insulation
22.33 Conductive liquids that are or may become P
accessible in normal use are not in direct contact
with live parts
Liquids may be heated using electrodes and may N/A
be in direct contact with their live parts.
(IEC60335-2-98)
For class II constructions, conductive liquids that are P
or may become accessible in normal use, not in
direct contact with basic or reinforced insulation
For class II constructions, conductive liquids which No contact with live parts N/A
are in contact with live parts, not in direct contact
with reinforced insulation
22.34 Shafts of operating knobs, handles, levers etc. not No such device N/A
live, unless the shaft is not accessible when the part
is removed
22.35 Handles, levers and knobs, held or actuated in Wired remote control P
normal use, not becoming live in the event of a
failure of basic insulation
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Such parts being of metal, and their shafts or fixings No metal parts N/A
are likely to become live in the event of a failure of
basic insulation, are either adequately covered by
insulation material or their accessible parts are
separated from their shafts or fixings by
supplementary insulation
This requirement does not apply to handles, levers N/A
and knobs on stationary appliances other than those
of electrical components, provided they are either
reliably connected to an earthing terminal or earthing
contact, or separated from live parts by earthed
metal
22.36 Handles continuously held in the hand in normal use N/A
are so constructed that when gripped as in normal
use, the operators hand is not likely to touch metal
parts, unless they are separated from live parts by
double or reinforced insulation
22.37 Capacitors in Class II appliances not connected to N/A
accessible metal parts, unless complying with 22.42
Metal casings of capacitors in Class II appliances N/A
separated from accessible metal parts by
supplementary insulation, unless complying with
22.42
22.38 Capacitors not connected between the contacts of a P
thermal cut-out
22.39 Lamp holders used only for the connection of lamps N/A
22.40 Motor-operated appliances and combined Fixed appliance and no N/A
appliances intended to be moved while in operation, accessible moving parts
or having accessible moving parts, fitted with a
switch to control the motor. The actuating member of
the switch being easily visible and accessible
Unless the appliance can operate continuously, The appliance can operate N/A
automatically or remotely without giving rise to a continuously, automatically and
hazard, appliances for remote operation being fitted remotely without giving rise to
with a switch. The actuating member of the switch a hazard.
being easily visible and accessible.
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
22.43 Appliances adjustable for different voltages, Not adjustable N/A
accidental changing of the setting of the voltage
unlikely to occur
22.44 Appliances shall not have an enclosure that is P
shaped or decorated like a toy
22.45 When air is used as reinforced insulation, clearances N/A
not reduced below the values specified in 29.1.4 due
to deformation as a result of an external force
applied to the enclosure
22.46 Software used in protective electronic circuits is N/A
software class B or C ..............................................:
22.47 Appliances connected to the water mains withstand Tested at 1.6 Mpa for 5 P
the water pressure expected in normal use minutes
No leakage from any part, including any inlet water P
hose
22.48 Appliances connected to the water mains P
constructed to prevent backsiphonage of non-
potable water
22.49 For remote operation, the duration of operation shall N/A
be set before the appliance can be started, unless
the appliance switches off automatically or can Can operate continuously P
operate continuously without hazard without hazard
22.50 Controls incorporated in the appliance take priority Main on/off switch P
over controls actuated by remote operation
22.51 A control on the appliance being manually adjusted N/A
to the setting for remote operation before the
appliance can be operated in this mode
There is a visual indication showing that the N/A
appliance is adjusted for remote operation
Manual setting and visual indication not necessary on appliances that can operate as -
follows, without giving rise to a hazard:
- operate continuously, P
- operate automatically, or P
- be operated remotely P
22.52 Socket-outlets on appliances accessible to the user No socket outlet N/A
in accordance with the socket-outlet system used in
the country in which the appliance is sold
22.101 The vapour outlet of appliances incorporating No heating element N/A
means for heating water shall be free from
obstructions that could give rise to a significant
pressure within the container. (IEC 60335-2-98)
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
The container shall be vented to the atmosphere, N/A
the aperture being at least 5 mm in diameter or
20 mm² in area with a minimum dimension of at
least 3 mm. . (IEC 60335-2-98)
22.102 Appliances for wall mounting shall have reliable N/A
provision for fixing to a wall, independent of the
connection to the water mains. (IEC 60335-2-98)
22.103 Electrode-type appliances shall be constructed to N/A
ensure that when the filling aperture of the
container is open, both electrodes are
disconnected to provide all-pole disconnection
under overvoltage category III conditions.
(IEC 60335-2-98)
This requirement does not apply to an appliance N/A
that requires the withdrawal of an appliance
connector in order to gain access to the filling
aperture. (IEC 60335-2-98/A1)
22.104 Appliances intended to be connected to the water Tested at 1.6 Mpa for 5 P
mains shall withstand the water pressure expected minutes
in normal use. (IEC 60335-2-98)
23 INTERNAL WIRING -
23.1 Wireways smooth and free from sharp edges P
Wires protected against contact with burrs, cooling P
fins etc.
Wire holes in metal well rounded or provided with P
bushings
Wiring effectively prevented from coming into contact P
with moving parts
23.2 Beads etc. On live wires cannot change their Not used N/A
position, and are not resting on sharp edges or
corners
Beads inside flexible metal conduits contained within N/A
an insulating sleeve
23.3 Electrical connections and internal conductors No moving parts N/A
movable relatively to each other not exposed to
undue stress
Flexible metallic tubes not causing damage to N/A
insulation of conductors
Open-coil springs not used N/A
Adequate insulating lining provided inside a coiled N/A
spring, the turns of which touch one another
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
No damage after 10 000 flexings for conductors N/A
flexed during normal use or 100 flexings for
conductors flexed during user maintenance
Electric strength test, 1000 V between live parts and N/A
accessible metal parts
23.4 Bare internal wiring sufficiently rigid and fixed P
23.5 The insulation of internal wiring withstanding the N/A
electrical stress likely to occur in normal use
No breakdown when a voltage of 2000 V is applied P
for 15 min between the conductor and metal foil
wrapped around the insulation
23.6 Sleeving used as supplementary insulation on Not used N/A
internal wiring retained in position by positive means
23.7 The colour combination green/yellow used only for P
earthing conductors
23.8 Aluminium wires not used for internal wiring P
23.9 No lead-tin soldering of stranded conductors where N/A
they are subject to contact pressure, unless
clamping means so constructed that there is no risk N/A
of bad contact due to cold flow of the solder
23.10 The insulation and sheath of internal wiring, N/A
incorporated in external hoses for the connection of
an appliance to the water mains, at least equivalent
to that of light polyvinyl chloride sheathed flexible
cord (60227 IEC 52)
24 COMPONENTS -
24.1 Components comply with safety requirements in P
relevant IEC standards
List of components (see appended table) P
Components not tested and found to comply with P
relevant IEC standard for the number of cycles
specified are tested in accordance with 24.1.1 to
24.1.9
Components not tested and found to comply with P
relevant IEC standard, components not marked or
not used in accordance with its marking, tested
under the conditions occurring in the appliance
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Lampholders and starterholders not being tested and N/A
found to comply with the relevant IEC standard,
tested as a part of the appliance and additionally
according to the gauging and interchangeability
requirements of the relevant IEC standard
24.1.1 Capacitors likely to be permanently subjected to the Approved capacitor P
supply voltage and used for radio interference
suppression or for voltage dividing, complying with
IEC 60384-14, or
tested according to annex F N/A
24.1.2 Safety isolating transformers complying with IEC N/A
61558-2-6, or
tested according to annex G P
24.1.3 Switches complying with IEC 61058-1, the number of Approved switch P
cycles of operation being at least 10 000, or
tested according to annex H N/A
If the switch operates a relay or contactor, the N/A
complete switching system is subjected to the test
24.1.4 Automatic controls complying with IEC 60730-1 with relevant part 2. The number of -
cycles of operation being:
- thermostats: 10 000 N/A
- temperature limiters: 1 000 N/A
- self-resetting thermal cut-outs: 300 Approved motor protector P
- voltage maintained non-self-resetting thermal cut- N/A
outs: 1000
- other non-self-resetting thermal cut-outs: 30 N/A
- timers: 3 000 N/A
- energy regulators: 10 000 N/A
Thermal motor protectors are tested in combination N/A
with their motor under the conditions specified in
Annex D
For water valves containing live parts and that are N/A
incorporated in external hoses for connection of an
appliance to the water mains, the degree of
protection declared for subclause 6.5.2 of IEC
60730-2-8 is IPX7
24.1.5 Appliance couplers complying with IEC 60320-1 P
However, appliances classified higher than IPX0, the Coupler protected from spray N/A
appliance couplers complying with IEC 60320-2-3 or spillage of liquid by splash
cover.
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Interconnection couplers complying with IEC 60320- N/A
2-2
24.1.6 Small lamp holders similar to E10 lampholders N/A
complying with IEC 60238, the requirements for E10
lampholders being applicable
24.1.7 If the remote operation of the appliance is via a N/A
telecommunication network, the relevant standard for
the telecommunication interface circuitry in the
appliance is IEC 62151
24.1.8 The relevant standard for thermal links is IEC 60691. No thermal link N/A
Thermal links not complying with IEC 60691 are
considered to be an intentionally weak part for the
purposes of Clause 19
24.1.9 Relays, other than motor starting relays, tested as Approved relay N/A
part of the appliance
They are also tested in accordance with Clause 17 N/A
of IEC 60730-1, the number of operations in 24.1.4
selected according to the relay function in the
appliance ..................................................................:
24.2 No switches or automatic controls in flexible cords P
No devices causing the protective device in the fixed P
wiring to operate in the event of a fault in the
appliance
No thermal cut-outs that can be reset by soldering P
24.3 Switches intended for all-pole disconnection of N/A
stationary appliances are directly connected to the
supply terminals and having a contact separation in
all poles, providing full disconnection under
overvoltage category III conditions
24.4 Plugs and socket-outlets for extra-low voltage P
circuits and heating elements, not interchangeable
with plugs and socket-outlets listed in IEC 60083 or
IEC 60906-1 or with connectors and appliance inlets
complying with the standard sheets of IEC 60320-1
24.5 Capacitors in auxiliary windings of motors marked P
with their rated voltage and capacitance and used
accordingly
Voltage across capacitors in series with a motor V=264V, Vcap=327V P
winding does not exceed 1,1 times rated voltage,
Rated capacitor = 425-500V
when the appliance is supplied at 1,1 times rated
voltage under minimum load
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
24.6 Working voltage of motors connected to the supply N/A
mains and having basic insulation that is inadequate
for the rated voltage of the appliance, not exceeding
42V
In addition, the motors are complying with the N/A
requirements of Annex I
24.7 Hose-sets for connection of appliances to the water See summary page P
mains, complying with IEC 61770 and supplied with
the appliance
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Appliance provided with a set of supply leads N/A
accommodated in a suitable compartment
Appliance provided with a set of terminals and cable N/A
entries, conduit entries, knock-outs or glands,
allowing connection of appropriate type of cable or
conduit
25.4 Cable and conduit entries, rated current of appliance N/A
not exceeding 16 A, dimension according to table 10
Introduction of conduit or cable does not reduce N/A
clearances or creepage distances below values
specified in 29
25.5 Method for assemble supply cord with the appliance: -
- type X attachment N/A
- type Y attachment P
- type Z attachment, if allowed in part 2 N/A
Type X attachment, other than those with a specially N/A
prepared cord, not used for flat twin tinsel cords
25.6 Plugs fitted with only one flexible cord P
25.7 Supply cords being one of the following types: -
- rubber sheathed (at least 60245 IEC 53) N/A
- polychloroprene sheathed (at least 60245 IEC 57) N/A
- cross-linked polyvinyl chloride sheathed (at least N/A
60245 IEC 87)
Polyvinyl chloride sheathed: -
Not used if they are likely to touch metal parts having a temperature rise exceeding
75K during the test of Clause 11.
- light polyvinyl chloride sheathed cord (at least N/A
60227 IEC 52), appliances not exceeding 3 kg
- ordinary polyvinyl chloride sheathed cord (at least H05VVF-3G P
60227 IEC 53), other appliances
Heat resistant polyvinyl chloride sheathed: -
Not used for type X attachment other than specially prepared cords.
- Heat-resistant light polyvinyl chloride sheathed cord N/A
(at least 60227 IEC 56), appliances not exceeding
3 kg
- heat-resistant polyvinyl chloride sheathed cord N/A
(60227 IEC 57), other appliances
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
2
25.8 Nominal cross-sectional area of supply cords < 6.0 A : 1.0mm P
according to table 11; rated current (A); cross-
sectional area (mm²) ................................................:
25.9 Supply cord not in contact with sharp points or edges P
25.10 Green/yellow core for earthing purposes in Class I P
appliance
25.11 Conductors of supply cords not consolidated by N/A
lead-tin soldering where they are subject to contact
pressure, unless
clamping means so constructed that there is no risk N/A
of bad contacts due to cold flow of the solder
25.12 Moulding the cord to part of the enclosure does not N/A
damage the insulation of the supply cord
25.13 Inlet opening so shaped as to prevent damage to the P
supply cord
Unless the enclosure at the inlet opening is of P
insulation material, a non-detachable lining or
bushing complying with 29.3 for supplementary
insulation provided
If unsheathed supply cord, a similar additional N/A
bushing or lining is required, unless
the appliance is class 0 N/A
25.14 Supply cords adequately protected against Fixed appliance N/A
excessive flexing
Flexing test: N/A
- applied force (N).....................................................: N/A
- number of lexing ..................................................: N/A
The test does not result in: N/A
- short circuit between the conductors N/A
- breakage of more than 10% of the strands of any N/A
conductor
- separation of the conductor from its terminal N/A
- loosening of any cord guard N/A
- damage, within the meaning of the standard, to the N/A
cord or the cord guard
- broken strands piercing the insulation and N/A
becoming accessible
25.15 Conductors of the supply cord relieved from strain, P
twisting and abrasion by use of cord anchorage
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
The cord cannot be pushed into the appliance to P
such an extent that the cord or internal parts of the
appliance can be damaged
Pull and torque test of supply cord, values shown in Pull force = 100N P
table 10: pull (N); torque (not on automatic cord reel)
Torque = 0.35Nm
(Nm) ..........................................................................:
Max. 2 mm displacement of the cord, and P
conductors not moved more than 1 mm in the
terminals
Creepage distances and clearances not reduced P
below values specified in 29.1
25.16 Cord anchorages for type X attachments constructed and located so that: -
- replacement of the cord is easily possible N/A
- it is clear how the relief from strain and the N/A
prevention of twisting are obtained
- they are suitable for different types of cord N/A
- cord cannot touch the clamping screws of cord N/A
anchorage if these screws are accessible, unless
separated from accessible metal parts by
supplementary insulation
- the cord is not clamped by a metal screw which N/A
bears directly on the cord
- at least one part of the cord anchorage securely N/A
fixed to the appliance, unless part of a specially
prepared cord
- screws which have to be operated when replacing N/A
the cord do not fix any other component, if applicable
- if labyrinths can be bypassed the test of 25.15 is N/A
nevertheless withstood
- for Class 0, 0I and I appliances: they are of N/A
insulating material or are provided with an insulating
lining, unless a failure of the insulation of the cord
does not make accessible metal parts live
- for Class II appliances: they are of insulating N/A
material, or if of metal, they are insulated from
accessible metal parts by supplementary insulation
25.17 Adequate cord anchorages for type Y and Z P
attachment
25.18 Cord anchorages only accessible with the aid of a N/A
tool, or
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
so constructed that the cord can only be fitted with N/A
the aid of a tool
25.19 Type X attachment, glands not used as cord N/A
anchorage in portable appliances
Tying the cord into a knot or tying the cord with string N/A
not used
25.20 Conductors of the supply cord for type Y and Z N/A
attachment adequately additionally insulated
25.21 Space for supply cord for type X attachment or for N/A
connection of fixed wiring constructed to permit
checking of conductors with respect to correct
positioning and connection before fitting any cover,
no risk of damage to the conductors when fitting the
cover, no contact with accessible metal parts if a
conductor becomes loose, etc.
For portable appliances, the uninsulated end of a N/A
conductor prevented from any contact with
accessible metal parts, unless the end of the cord is
such that the conductors are unlikely to slip free
25.22 Appliance inlet: -
- live parts not accessible during insertion or removal P
- connector can be inserted without difficulty For fixed wiring , installed by N/A
qualified installer
- the appliance is not supported by the connector P
- is not for cold conditions if temp. Rise of external No metal part N/A
metal parts exceeds 75 K, unless the supply cord is
not likely to touch such metal parts
25.23 Interconnection cords comply with the requirements Wired remote control P
for the supply cord, except as specified
If necessary, electric strength test of 16.3 Test 16.3 P
25.24 Interconnection cords not detachable without the aid Wired remote control SELV P
of a tool if compliance with the standard is impaired
when they are disconnected
25.25 Dimensions of pins compatible with the dimensions N/A
of the relevant socket-outlet. Dimensions of pins and
engagement face in accordance with the relevant
plug in IEC 60083
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
26.1 Appliances provided with terminals or equally Appliance coupler N/A
effective devices for connection of external
conductors
Terminals only accessible after removal of a non- N/A
detachable cover
However, earthing terminals may be accessible if a N/A
tool is required to make the connections and means
are provided to clamp the wire independently from its
connection
26.2 Appliances with type X attachment and appliances N/A
for connection to fixed wiring provided with terminals
in which connections are made by means of screws,
nuts or similar devices, unless the connections are
soldered
Screws and nuts serve only to clamp supply N/A
conductors, except
internal conductors, if so arranged that they are N/A
unlikely to be displaced when fitting the supply
conductors
If soldered connections used, the conductor so N/A
positioned or fixed that reliance is not placed on
soldering alone
Soldering alone used, barriers provided, clearances N/A
and creepage distances satisfactory if the conductor
becomes free at the soldered joint
26.3 Terminals for type X attachment and for connection N/A
to fixed wiring so constructed that the conductor is
clamped between metal surfaces with sufficient
contact pressure and without damaging the
conductor
Terminals for type X attachment and those for connection to fixed wiring so fixed that -
when tightening or loosening the clamping means:
- the terminal does not loosen N/A
- internal wiring is not subjected to stress N/A
- clearances and creepage distances are not N/A
reduced below the values in 29
Compliance checked by inspection and by the test of N/A
subclause 9.6 of IEC 60999-1, the torque applied
being equal to two-thirds of the torque specified.
Nominal diameter of thread (mm); screw category;
torque (Nm):
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
26.4 Terminals for type X attachment, except those with a N/A
specially prepared cord, and those for connection to
fixed wiring, no special preparation of conductors
required, and so constructed or placed that
conductors prevented from slipping out
26.5 Terminals for type X attachment so located or N/A
shielded that if a wire of a stranded conductor
escapes, no risk of accidental connection to other
parts that result in a hazard
Stranded conductor test, 8 mm insulation removed N/A
No contact between live parts and accessible metal N/A
parts and, for class II constructions, between live
parts and metal parts separated from accessible
metal parts by supplementary insulation only
26.6 Terminals for type X attachment and for connection N/A
to fixed wiring suitable for connection of conductors
with required cross-sectional area according to
table 13; rated current (A); nominal cross-sectional
area (mm²) ................................................................:
Terminals only suitable for a specially prepared cord N/A
26.7 Terminals for type X attachment accessible after N/A
removal of a cover or part of the enclosure
26.8 Terminals for the connection to fixed wiring, including N/A
the earthing terminal, located close to each other
26.9 Terminals of the pillar type constructed and located N/A
as specified
26.10 Terminals with screw clamping and screwless N/A
terminals not used for flat twin tinsel cords, unless
conductors ends fitted with a device suitable for
screw terminals
Pull test of 5 N to the connection N/A
26.11 For type Y and Z attachment: soldered, welded, N/A
crimped and similar connections may be used
For Class II appliances: the conductor so positioned N/A
or fixed that reliance is not placed on soldering,
welding or crimping alone
For Class II appliances: soldering, welding or N/A
crimping alone used, barriers provided, clearances
and creepage distances satisfactory if the conductor
becomes free
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
27.1 Accessible metal parts of Class 0I and I appliances, No accessible metal N/A
permanently and reliably connected to an earthing
terminal or contact of the appliance inlet
Earthing terminals not connected to neutral terminal P
Class 0, II and III appliance have no provision for N/A
earthing
Safety extra-low voltage circuits not earthed, unless Not earthed P
protective extra-low voltage circuits
27.2 Clamping means adequately secured against N/A
accidental loosening
Terminals used for the connection of external N/A
equipotential bonding conductors allow connection of
conductors of 2.5 to 6 mm², and
do not provide earthing continuity between different N/A
parts of the appliance
Conductors cannot be loosened without the aid of a N/A
tool
27.3 For detachable parts that are plugged into another Wired remote, not earthed P
part of the appliance, and having an earth
connection, the earth connection made before and
separated after current-carrying connections when
removing the part
For appliances with supply cord, current-carrying N/A
conductors become taut before earthing conductor, if
the cord slips out of the cord anchorage
27.4 No risk of corrosion resulting from contact between P
metal of earthing terminal and other metal
Adequate resistance to corrosion of coated or P
uncoated parts providing earthing continuity, other
than parts of a metal frame or enclosure
Parts of steel providing earthing continuity provided N/A
at the essential areas with an electroplated coating,
thickness at least 5 µm
Adequate protection against rusting of parts of N/A
coated or uncoated steel, only intended to provide or
transmit contact pressure
In case of aluminium alloys precautions taken to N/A
avoid risk of corrosion
27.5 Low resistance of connection between earthing P
terminal and earthed metal parts
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
This requirement does not apply to connections N/A
providing earthing continuity in the protective extra-
low voltage circuit, provided that clearances of basic
insulation are based on the rated voltage of the
appliance
Resistance not exceeding 0,1 Ω at the specified low- Between earth contact of P
resistance test appliance inlet and pump
connector on PCB.
Fan motor = 0.066 Ω
Pump motor = 0.065 Ω
27.6 The printed conductors of printed circuit boards shall N/A
not be used to provide earthing continuity in hand-
held appliances.
They may be used to provide earthing continuity in P
other appliances if at least two tracks are used with
independent soldering points and the appliance
complies with 27.5 for each circuit
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
28.2 Electrical connections and connections providing N/A
earthing continuity constructed so that contact
pressure not transmitted through insulating material
liable to shrink or distort, unless shrinkage or
distortion compensated
This requirement does not apply to electrical Water pump, 0.2 A P
connections in circuits carrying a current not
exceeding 0.5A
28.3 Space-threaded (sheet metal) screws only used for Not used N/A
electrical connections if they clamp the parts
together
Thread-cutting (self-tapping) screws and thread N/A
rolling screws only used for electrical connections if
they generate a full form standard machine screw
thread
Thread-cutting (self-tapping) screws not used if they N/A
are likely to be operated by the user or installer
Thread-cutting, thread rolling and space threaded screws may be used in connections -
providing earthing continuity provided it is not necessary to disturb the connection:
- in normal use, N/A
- during user maintenance, N/A
- when replacing a supply cord having a type X N/A
attachment, or
- during installation N/A
At least two screws being used for each connection N/A
providing earthing continuity, unless
the screw forms a thread having a length of at least N/A
half the diameter of the screw
Thread-cutting and space-threaded screws may be N/A
used in connections providing earthing continuity,
provided unnecessary to disturb the connection and
at least two screws are used for each connection
28.4 Screws and nuts that make mechanical connection No such screws N/A
secured against loosening if they also make
electrical connections or connections providing
earthing continuity
Rivets for electrical connections or connections Not used N/A
providing earthing continuity secured against
loosening if subjected to torsion
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Clearances, creepage distances and solid insulation P
withstand electrical stress
For coatings used on printed circuits boards to N/A
protect the microenvironment (Type 1) or to provide
basic insulation (Type 2), annex J applies ..............:
The microenvironment is pollution degree 1 under N/A
Type 1 coating
No clearance or creepage distance requirements N/A
under Type 2 coating
29.1 Clearances not less than the values specified in P
table 16, taking into account the rated impulse
voltage for the overvoltage categories of table 15,
unless
for basic insulation and functional insulation they N/A
comply with the implulse voltage test of clause 14
However, if the construction is affected by wear, N/A
distortion, movement of the parts or during
assembly, the clearances for rated impulse voltages
of 1500V and above are increased by 0,5 mm and
the impulse voltage test is not applicable
Impulse voltage test not applicable: -
- when the microenvironment is pollution degree 3 N/A
- for basic insulation of class 0 and class 01 N/A
appliances
Appliances are in overvoltage category II P
Clearances less than specified in table 16 not N/A
allowed for basic insulation of class 0 and class 0I
appliances,
or if pollution degree 3 is applicable N/A
Compliance is checked by inspection and P
measurements as specified
29.1.1 Clearances of basic insulation withstand the P
overvoltages, taking into account the rated impulse
voltage
Clearance at the terminals of tubular sheathed N/A
heating elements may be reduced to 1mm if the
microenvironment is pollution degree 1
Lacquered conductors of windings considered to be P
bare conductors
29.1.2 Clearances of supplementary insulation not less than P
those specified for basic insulation in table 16
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
29.1.3 Clearances of reinforced insulation not less than P
those specified for basic insulation in table 16, but
using the next higher step for rated impulse voltage
29.1.4 For functional insulation, the values of table 16 are P
applicable, unless
the appliance complies with clause 19 with the P
functional insulation short-circuited
Lacquered conductors of windings considered to be P
bare conductors
However, clearances at crossover points are not P
measured
Clearance between surfaces of PTC heating N/A
elements may be reduced to 1mm
29.1.5 Appliances having higher working voltage than rated P
voltage, the voltage used for determining clearances
from table 16 is the sum of the rated impulse voltage
and the difference between the peak value of the
working voltage and the peak value of the rated
voltage
If the secondary winding of a step-down transformer N/A
is earthed, or if there is an earthed screen between
the primary and secondary windings, clearances of
basic insulation on the secondary side not less than
those specified in table 16, but using the next lower
step for rated impulse voltage
Circuits supplied with a voltage lower than rated P
voltage, clearances of functional insulation based on
the working voltage used as the rated voltage in
table 15
29.2 Creepage distances not less than those appropriate P
for the working voltage, taking into account the
material group and the pollution degree
Pollution degree 2 applies, unless P
precautions taken to protect the insulation; pollution Pump winding filled with P
degree 1 impregnation
insulation subjected to conductive pollution; pollution Insulation of fan motor and N/A
degree 3 control box housing is
enclosed and unlikely to be
exposed
For electrode-type appliances, the N/A
microenvironment of the insulation supporting the
electrodes is pollution degree 3. (IEC 60335-2-98)
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Compliance is checked by inspection and P
measurements as specified
29.2.1 Creepage distances of basic insulation not less than P
specified in table 17
For pollution degree 1, creepage distance not less N/A
than the minimum specified for the clearance in table
16, if the clearance has been checked according to
the test of clause 14
29.2.2 Creepage distances of supplementary insulation at P
least as specified for basic insulation in table 17
29.2.3 Creepage distances of reinforced insulation at least P
double as specified for basic insulation in table 17
29.2.4 Creepage distances of functional insulation not less N/A
than specified in table 18
Creepage distances may be reduced if the appliance Between PCB tracks of SELV P
complies with clause 19 with the functional insulation circuit
short-circuited
29.3 Supplementary and reinforced insulation having P
adequate thickness, or a sufficient number of layers,
to withstand the electrical stresses
Compliance checked by: -
- measurement, in accordance with 29.3.1, or P
- an electric strength test in accordance with 29.3.2, N/A
or
- an assessment of the thermal quality of the material N/A
combined with an electric strength test, in
accordance with 29.3.3
29.3.1 Supplementary insulation having a thickness of at P
least 1 mm
Reinforced insulation having a thickness of at least 2 P
mm
29.3.2 Each layer of material withstand the electric strength N/A
test of 16.3 for supplementary insulation
Supplementary insulation consisting of at least 2 N/A
layers
Reinforced insulation consisting of at least 3 layers N/A
29.3.3 The insulation is subjected to the dry heat test Bb of N/A
IEC 60068-2-2, followed by
the electric strength test of 16.3 N/A
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
If the temperature rise during the tests of Clause 19 N/A
does not exceed the value specified in Table 3, the
test of IEC 60068-2-2 is not carried out
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Parts for which the glow-wire test cannot be carried N/A
out meet the requirements in ISO9772 for category
HBF material
30.2.3 Appliances operated while unattended, tested as P
specified in 30.2.3.1 and 30.2.3.2
Tests not applicable to conditions as specified P
30.2.3.1 Parts of insulating material supporting connections P
carrying a current exceeding 0.2A during normal
operation, and
parts of non-metallic material within a distance of P
3mm,
subjected to the glow-wire test of IEC 60695-2-11 P
with a test severity of 850°C
Glow-wire test not carried out on parts of material N/A
classified as having a glow-wire flammability index of
at least 850°C according to IEC 60695-2-12
Glow-wire test not carried out on small parts that N/A
comply with the needle-flame test of Annex E or on
small parts of material classified as V-0 or V-1
according to IEC 60695-11-10
Test as specified for an interposed shielding material P
30.2.3.2 Parts of non-metallic material supporting current- P
carrying connections, and
parts of non-metallic material within a distance of P
3mm,
subjected to glow-wire test of IEC 60695-2-11 P
Test not carried out on material having a glow-wire N/A
ignition temperature according to IEC 60695-2-13 of
at least:
-775C, for connections carrying a current exceeding N/A
0,2A during normal operation
-675C, for other connections N/A
When the glow-wire test of IEC 60695-2-11 is carried out, the temperatures are: -
-750C, for connections carrying a current exceeding P
0,2A during normal operation
-650C, for other connections P
Parts that during the test produce a flame persisting P
longer than 2 s, tested as specified
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
If a flame persists longer than 2 s during the test, P
parts above the connection, as specified, subjected
to the needle-flame test of annex E, unless
the material is classified as V-0 or V-1 according to N/A
IEC 60695-11-10
30.2.4 Base material of printed circuit boards subjected to P
needle-flame test of annex E
Test not applicable to conditions as specified P
31 RESISTANCE TO RUSTING -
Relevant ferrous parts adequately protected against P
rusting
A ANNEX A (INFORMATIVE) -
ROUTINE TESTS
Description of routine tests to be carried out by the N/A
manufacturer
B ANNEX B (NORMATIVE) _
APPLIANCES POWERED BY RECHARGEABLE BATTERIES
The following modifications to this standard are N/A
applicable for appliances powered by batteries that
are recharged in the appliance
This annex does not apply to battery chargers N/A
3.1.9 Appliance operated under the following conditions: -
-the appliance, supplied by its fully charged battery, N/A
operated as specified in relevant part 2
-the battery is charged, the battery being initially N/A
discharged to such an extent that the appliance
cannot operate
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
-if possible, the appliance is supplied from the supply N/A
mains through its battery charger, the battery being
initially discharged to such an extent that the
appliance cannot operate. The appliance is operated
as specified in relevant part 2
If the appliance incorporates inductive coupling N/A
between two parts that are detachable from each
other, the appliance is supplied from the supply
mains with the detachable part removed
3.6.2 Part to be removed in order to discard the battery is N/A
not considered to be detachable
5.101 Appliances supplied from the supply mains tested as N/A
specified for motor-operated appliances
7.1 Battery compartment for batteries intended to be N/A
replaced by the user, marked with battery voltage
and polarity of the terminals
7.12 The instructions for appliances incorporating N/A
batteries intended to be replaced by the user
includes required information
Details about how to remove batteries containing N/A
materials hazardous to the environment given
7.15 Markings placed on the part of the appliance N/A
connected to the supply mains
8.2 Appliances having batteries that according to the N/A
instruction may be replaced by the user need only
have basic insulation between live parts and the
inner surface of the battery compartment
If the appliance can be operated without batteries, N/A
double or reinforced insulation required
11.7 The battery is charged for the period described N/A
19.1 Appliances subjected to tests of 19.101, 19.102 and N/A
19.103
19.101 Appliances supplied at rated voltage for 168 h, the N/A
battery being continually charged
19.102 Short-circuiting of the terminals of the battery, being N/A
fully charged, for appliances having batteries that
can be removed without the aid of a tool
19.103 Appliances having batteries replaceable by the user N/A
supplied at rated voltage under normal operation
with the battery removed or in any position allowed
by the construction
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
21.101 Appliances having pins for insertion into socket- N/A
outlets have adequate mechanical strength, checked
according to procedure 2 of IEC 68-2-32
Part of the appliance incorporating the pins subjected to the free fall test, procedure 2, -
of IEC 60068-2-32, the number of falls being:
- 100, the mass of part does not exceed 250 g N/A
- 50, the mass of part exceeds 250 g N/A
After the test, the requirements of 8.1, 15.1.1, 16.3 N/A
and clause 29 are met
22.3 Appliances having pins for insertion into socket- N/A
outlets tested as fully assembled as possible
25.13 An additional lining or bushing not required for N/A
interconnection cords operating at safety extra-low
voltage
30.2 For parts of the appliance connected to the supply N/A
mains during the charging period, 30.2.3 applies
For other parts, 30.2.2 applies N/A
C ANNEX C (NORMATIVE) -
AGEING TEST ON MOTORS
Tests, as described, carried out when doubt with N/A
regard to the temperature classification of the
insulation of a motor winding
D ANNEX D (NORMATIVE) -
THERMAL MOTOR PROTECTORS
Applicable to appliances having motors that N/A
incorporate thermal motor protectors
E ANNEX E (NORMATIVE) -
NEEDLE-FLAME TEST
Needle-flame test carried out in accordance with P
IEC 60695-11-5, with the following modifications:
7 Severities -
The duration of application of the test flame is P
30 s ± 1 s
9 Test procedure -
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
9.1 The specimen so arranged that the flame can be P
applied to a vertical or horizontal edge as shown in
the examples of figure 1
9.2 The first paragraph does not apply P
If possible, the flame is applied at least 10 mm from P
a corner
9.3 The test is carried out on one specimen P
If the specimen does not withstand the test, the test P
may be repeated on two additional specimens, both
withstanding the test
11 Evaluation of test results -
The duration of burning not exceeding 30 s P
However, for printed circuit boards, the duration of P
burning not exceeding 15 s
F ANNEX F (NORMATIVE) -
CAPACITORS
Capacitors likely to be permanently subjected to the N/A
supply voltage, and used for radio interference
suppression or voltage dividing, comply with the
following clauses of IEC 60384-14, with the following
modifications:
1.5 Terminology -
1.5.3 Class X capacitors tested according to subclass X2 N/A
1.5.4 This subclause is applicable N/A
1.6 Marking -
Items a) and b) are applicable N/A
3.4 Approval testing -
3.4.3.2 Table II is applicable as described N/A
4.1 Visual examination and check of dimensions -
This subclause is applicable N/A
4.2 Electrical tests -
4.2.1 This subclause is applicable N/A
4.2.5 This subclause is applicable N/A
4.2.5.2 Only table IX is applicable N/A
Values for test A apply N/A
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
However, for capacitors in heating appliances the N/A
values for test B or C apply
4.12 Damp heat, steady state -
This subclause is applicable N/A
Only insulation resistance and voltage proof are N/A
checked
4.13 Impulse voltage -
This subclause is applicable N/A
4.14 Endurance -
Subclauses 4.14.1, 4.14.3, 4.14.4 and 4.14.7 N/A
applicable
4.14.7 Only insulation resistance and voltage proof are N/A
checked
Visual examination, no visible damage N/A
4.17 Passive flammability test -
This subclause is applicable N/A
4.18 Active flammability test -
This subclause is applicable N/A
G ANNEX G (NORMATIVE) -
SAFETY ISOLATING TRANSFORMERS
The following modifications to this standard are P
applicable for safety isolating transformers:
7 Marking and instructions -
7.1 Transformers for specific use marked with: -
-name, trademark or identification mark of the Ten Pao P
manufacturer or responsible vendor
-model or type reference TM41246F0 P
17 Overload protection of transformers and associated circuits -
Fail-safe transformers comply with subclause 15.5 of P
IEC 61558-1
22 Construction -
Subclauses 19.1 and 19.1.2 of IEC 61558-2-6 are P
applicable
29 Clearances, creepage distances and solid insulation -
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
29.1, 29.2 The distances specified in items 2a, 2c and 3 in table Between primary to iron core : P
and 29.3 13 of IEC 61558-1 apply cr = 5.8mm , cl = 5.8mm
Between secondary to iron
core : cr = 3.8mm, cl = 3.8mm
Between primary to secondary
: cr = 9.5mm , cl = 9.5mm
Bobbin DTI = 2.4mm
Between adjacent output circuit
: 13.8mm
H ANNEX H (NORMATIVE) -
SWITCHES
Switches comply with the following clauses of IEC 61058-1, as modified: -
-The tests of IEC 61058-1 carried out under the N/A
conditions occurring in the appliance
-Before being tested, switches are operated 20 times N/A
without load
8 Marking and documentation -
Switches are not required to be marked N/A
However, switches that can be tested separately N/A
from the appliance marked with the manufacturer’s
name or trade mark and the type reference
13 Mechanism -
The tests may be carried out on a separate sample N/A
15 Insulation resistance and dielectric strength -
15.1 Not applicable N/A
15.2 Not applicable N/A
15.3 Applicable for full disconnection and micro- N/A
disconnection
17 Endurance -
Compliance is checked on three separate appliances N/A
or switches
For 17.2.4.4, the number of cycles is 10 000, unless N/A
otherwise specified in 24.1.3 of the relevant part 2 of
IEC 60335
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Switches for operation under no load and which can N/A
be operated only by a tool and switches operated by
hand that are interlocked so that they cannot be
operated under load, are not subjected to the tests
Subclauses 17.2.2 and 17.2.5.2 not applicable N/A
The ambient temperature during the test is that N/A
occurring in the appliance during the test of Clause
11 in IEC 60335-1
Temperature rise of the terminals not more than 30 K N/A
above the temperature rise measured in clause 11 of
IEC 60335-1
20 Clearances, creepage distances, solid insulation and coatings of rigid printed board -
assemblies
This clause is applicable to clearances and creepage N/A
distances for functional insulation, across full
disconnection and micro-disconnection, as stated in
table 24
I ANNEX I (NORMATIVE) -
MOTORS HAVING BASIC INSULATION THAT IS INADEQUATE FOR THE RATED
VOLTAGE OF THE APPLIANCE
The following modifications to this standard are N/A
applicable for motors having basic insulation that is
inadequate for the rated voltage of the appliance:
8 Protection against access to live parts -
8.1 Metal parts of the motor are considered to be bare N/A
live parts
11 Heating -
11.3 Temperature rise of the body of the motor is N/A
determined instead of the temperature rise of the
windings
11.8 Temperature rise of the body of the motor, where in N/A
contact with insulating material, not exceeding
values in table 3 for the relevant insulating material
16 Leakage current and electric strength -
16.3 Insulation between live parts of the motor and its N/A
other metal parts not subjected to the test
19 Abnormal operation -
19.1 The tests of 19.7 to 19.9 not carried out N/A
19.101 Appliance operated at rated voltage with each of the following fault conditions: -
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
- short circuit of the terminals of the motor, including N/A
any capacitor incorporated in the motor circuit
- short circuit of each diode of the rectifier N/A
- open circuit of the supply to the motor N/A
- open circuit of any parallel resistor, the motor being N/A
in operation
Only one fault simulated at a time, the tests carried N/A
out consecutively
22 Construction -
22.101 For class I appliances incorporating a motor supplied N/A
by a rectifier circuit, the d.c. circuit being insulated
from accessible parts of the appliance by double or
reinforced insulation
Compliance checked by the tests specified for N/A
double and reinforced insulation
J ANNEX J (NORMATIVE) -
COATED PRINTED CIRCUIT BOARDS
Testing of protective coatings of printed circuit N/A
boards carried out in accordance with IEC 60664-3
with the following modifications:
5.7 Conditioning of the test specimens -
When production samples are used, three samples N/A
of the printed circuit board are tested
5.7.1 Cold -
The test is carried out at -25C N/A
5.7.3 Rapid change of temperature -
Severity 1 is specified N/A
5.9 Additional tests -
This subclause is not applicable N/A
K ANNEX K (NORMATIVE) -
OVERVOLTAGE CATEGORIES
The information on overvoltage categories is P
extracted from IEC 60664-1
Overvoltage category is a numeral defining a P
transient overvoltage condition
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Equipment of overvoltage category IV is for use at N/A
the origin of the installation
Equipment of overvoltage category III is equipment N/A
in fixed installations and for cases where the
reliability and the availability of the equipment is
subject to special requirements
Equipment of overvoltage category II is energy P
consuming equipment to be supplied from the fixed
installation
If such equipment is subjected to special N/A
requirements with regard to reliability and availability,
overvoltage category III applies
Equipment of overvoltage category I is equipment for N/A
connection to circuits in which measures are taken to
limit transient overvoltages to an appropriate low
level
L ANNEX L (INFORMATIVE) -
GUIDANCE FOR THE MEASUREMENT OF CLEARANCES AND CREEPAGE
DISTANCES
Sequences for the determination of clearances and P
creepage distances
M ANNEX M (NORMATIVE) -
POLLUTION DEGREE
The information on pollution degrees is extracted P
from IEC 60664-1
Pollution -
The microenvironment determines the effect of P
pollution on the insulation, taking into account the
microenvironment
Means may be provided to reduce pollution at the P
insulation by effective enclosures or similar
Minimum clearances specified where pollution may P
be present in the microenvironment
Degrees of pollution in the microenvironment -
For evaluating creepage distances, the following degrees of pollution in the -
microenvironment are established:
- pollution degree 1: no pollution or only dry, non- N/A
conductive pollution occurs. The pollution has no
influence
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
- pollution degree 2: only non-conductive pollution P
occurs, except that occasionally a temporary
conductivity caused by condensation is to be
expected
- pollution degree 3: conductive pollution occurs or N/A
dry non-conductive pollution occurs that becomes
conductive due to condensation that is to be
expected
- pollution degree 4: the pollution generates N/A
persistent conductivity caused by conductive dust or
by rain or snow
N ANNEX N (NORMATIVE) -
PROOF TRACKING TEST
The proof tracking test is carried out in accordance N/A
with IEC 60112 with the following modifications:
7 Test apparatus -
7.3 Test solutions -
Test solution A is used N/A
10 Determination of proof tracking index (PTI) -
10.1 Procedure -
The proof voltage is 100V, 175V, 400V or 600V .....: N/A
The last paragraph of Clause 3 applies N/A
The test is carried out on five specimens N/A
In case of doubt, additional test with proof voltage N/A
reduced by 25V, the number of drops increased to
100
10.2 Report -
The report stating if the PTI value was based on a N/A
test using 100 drops with a test voltage of (PTI-25) V
O ANNEX O (INFORMATIVE) -
SELECTION AND SEQUENCE OF THE TESTS OF CLAUSE 30
Description of tests for determination of resistance to P
heat and fire
P ANNEX P (INFORMATIVE) -
GUIDANCE FOR THE APPLICATION OF THIS STANDARD TO APPLIANCES
USED IN WARM DAMP EQUABLE CLIMATES
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
Modifications applicable for class 0 and 01 appliances having a rated voltage -
exceeding 150V, intended to be used in countries having a warm damp equable
climate and that are marked WdaE
Modifications may also be applied to class 1 appliances having a rated voltage -
exceeding 150V, intended to be used in countries having a warm damp equable
climate and that are marked WdaE, if liable to be connected to a supply mains that
excludes the protective earthing conductor
5 General conditions for the tests -
5.7 The ambient temperature for the tests of Clauses 11 N/A
and 13 is 40 +3/0
7 Marking and instructions -
7.1 The appliance marked with the letters WdaE N/A
7.12 The instructions state that the appliance is to be N/A
supplied through a RCD having a rated residual
operating current not exceeding 30 mA
The instructions state that the appliance is N/A
considered to be suitable for use in countries having
a warm damp equable climate, but may also be used
in other countries
11 Heating -
11.8 The values of Table 3 are reduced by 15 K N/A
13 Leakage current and electric strength at operating temperature N/A
13.2 The leakage current for class I appliances not N/A
exceeding 0,5 mA
15 Moisture resistance -
15.3 The value of t is 37 C N/A
16 Leakage current and electric strength -
16.2 The leakage current for class I appliances not N/A
exceeding 0,5 mA
19 Abnormal operation N/A
19.13 The leakage current test of 16.2 is applied in addition N/A
to the electric strength test of 16.3
Q ANNEX Q (INFORMATIVE) -
SEQUENCE OF TESTS FOR THE EVALUATION OF ELECTRONIC CIRCUITS
Description of tests for appliances incorporating electronic circuits P
IEC/EN 60335-2-98
Clause Requirement + Test Result - Remark Verdict
R ANNEX R (NORMATIVE) -
SOFTWARE EVALUATION
Software evaluated in accordance with the following clauses of Annex H of IEC -
60730-1, as modified
H.2 Definitions -
Only definitions H.2.16 to H.2.20 applicable N/A
H.7 Information -
Only footnotes 12) to 18) of Table 7.2, as modified, N/A
applicable
H.11.12 Controls using software -
All the subclauses of H.11.12, as modified, except N/A
H.11.12.6 and H.11.12.6.1, applicable
H.11.12.7 Delete text N/A
H.11.12.7.1 For appliances using software class C having a N/A
single channel with self-test and monitoring
structure, the manufacturer provides the measures
necessary to address the fault/errors in safety
related segments and data
H.11.12.8 Software fault/error detection occurs before N/A
compliance with 19.13 of IEC 60335-1 is impaired
H.11.12.8.1 Replace text N/A
H.11.12.13 Software and safety related hardware under its N/A
control initializes and terminates before compliance
with 19.13 of IEC 60335-1 is impaired
ANNEX EMF
supplementary information:
supplementary information:
supplementary information:
Capacitor for fan Epcos (Anhui) CBB65A-1 30uF, 450V EN60252-1 VDE
motor
P2
(alternative)
Capacitor for Ducati Energia 16.33.4660 25uF, 425-500V EN-60252-1 VDE, IMQ, UL
Seeley (Able)
motor P2
Capacitor for fan Epcos (Anhui) CBB65A-1 25uF, 450V EN60252-1 VDE
motor
P2
(alternative)
Fan Motor Seeley 6095V4A001 230V/50Hz, 950W, EN60355-1 Tested in
(TBA550-X, International P/L 5.5A, class H appliance
LCB550-X,
CPL1100X-X)
Fan Motor Seeley 6056V4A001 230V/50Hz, 560W, EN60355-1 Tested in
(TBA450-X, International P/L 3.6A class F appliance
LCB450-X)
Fan Motor Seeley (Able) AVAC 600 220/240V, 50Hz, EN60355-1 Tested in
(CPL850-X, 600W, 4.6A,class F appliance
BM900-X,
TBA450-X alt.,
LCB450-X alt.)
Fan Motor Seeley (Able) AVAC 430 220/240V, 50Hz, EN60355-1 Tested in
(CPL700-X, 430W, 3.4A,class F appliance
BM750-X,
TBA350-X alt.,
LCB350-X alt.)
Fan Motor Seeley (Able) AVAC 340 220/240V, 50Hz, EN60355-1 Tested in
(CPL450-X, 340W, 2.9A,class F appliance
BM500-X,
TBA250-X alt.,
LCB250-X alt.)
1)
An asterisk indicates a mark which assures the agreed level of surveillance
1250 and 1600 8,4 12,6 18,0 25,0 32,0 36,0 40,0
1600 and 2000 5,6 8,0 11,0 16,0 20,0 22,0 25,0
1600 and 2000 5,6 8,0 11,0 16,0 20,0 22,0 25,0
1600 and 2000 11,2 16,0 22,0 32,0 40,0 44,0 50,0
2000 and 2500 7,5 10,0 14,0 20,0 25, 0 28,0 32,0
2000 and 2500 7,5 10,0 14,0 20,0 25, 0 28,0 32,0
2000 and 2500 15,0 20,0 28,0 40,0 50,0 56,0 64,0
2500 and 3200 10,0 12,5 18,0 25,0 32,0 36,0 40,0
2500 and 3200 10,0 12,5 18,0 25,0 32,0 36,0 40,0
>2500 and 3200 20,0 25,0 36,0 50,0 64,0 72,0 80,0
3200 and 4000 12,5 16,0 22,0 32,0 40,0 45,0 50,0
3200 and 4000 12,5 16,0 22,0 32,0 40,0 45,0 50,0
3200 and 4000 25,0 32,0 44,0 64,0 80,0 90,0 100,0
4000 and 5000 16,0 20,0 28,0 40,0 50,0 56,0 63,0
4000 and 5000 16,0 20,0 28,0 40,0 50,0 56,0 63,0
4000 and 5000 32,0 40,0 56,0 80,0 100,0 112,0 126,0
5000 and 6300 20,0 25,0 36,0 50,0 63,0 71,0 80,0
5000 and 6300 20,0 25,0 36,0 50,0 63,0 71,0 80,0
5000 and 6300 40,0 50,0 72,0 100,0 126,0 142,0 160,0
6300 and 8000 25,0 32,0 45,0 63,0 80,0 90,0 100,0
6300 and 8000 25,0 32,0 45,0 63,0 80,0 90,0 100,0
6300 and 8000 50,0 64,0 90,0 126,0 160,0 180,0 200,0
8000 and 10000 32,0 40,0 56,0 80,0 100,0 110,0 125,0
8000 and 10000 32,0 40,0 56,0 80,0 100,0 110,0 125,0
8000 and 10000 64,0 80,0 112,0 160,0 200,0 220,0 250,0
10000 and 12500 40,0 50,0 71,0 100,0 125,0 140,0 160,0
10000 and 12500 40,0 50,0 71,0 100,0 125,0 140,0 160,0
10000 and 12500 80,0 100,0 142,0 200,0 250,0 280,0 320,0
)
* , B=Basic, S=Supplementary and R=Reinforced
Measured on control PCB
The following parts were subjected to the appropriate glow-wire/needle flame tests specified in
IEC60335-1:2002 inc. Amdts 1 & 2 .
Control box
M1 Appliance inlet Thermo-plastic Black
M2 Appliance inlet (alternative) Thermo-plastic Black
M3 Appliance inlet (alternative) Thermo-plastic Black
M4 Circuit breaker Thermo-plastic Black
M5 Connector circuit breaker Thermo-plastic White
M6 Main switch Thermo-plastic Black
M7 Relay, K1 Thermo-plastic Black
M8 Relay, K2,K3,K4 Thermo-plastic Black
M9 Connector pump 3 pins Thermo-plastic White
M10 Connector fan motor 4 pins Thermo-plastic White
M11 Connector to motor capacitor 1pin Thermo-plastic White
M12 Capacitor motor Thermo-plastic White
M13 Capacitor motor (alternative) Thermo-plastic White
M14 Connector water solenoid 2 pins Thermo-plastic Clear
M15 Connector water solenoid 1 pin Thermo-plastic Clear
M16 Solenoid water inlet Thermo-plastic Black
M17 Capacitor X2,C2 Thermo-plastic Grey
M18 Capacitor X2,C2 (alternative) Thermo-plastic Grey
M19 Capacitor X2,C2 (alternative) Thermo-plastic Grey
M20 Capacitor X2,C3,C4 Thermo-plastic Grey
M21 Capacitor X2,C3,C4 (alternative) Thermo-plastic Grey
M22 Capacitor X2,C3,C4 (alternative) Thermo-plastic Grey
M23 Transformer bobbin, T1 Thermo-plastic Black
M24 Pump motor impregnation Thermo-plastic Cream
M25 Connector drain valve 3 pins Thermo-plastic Clear
M26 Connector wired remote (RJ11) Thermo-plastic Black
M27 Connector probe 4 pins Thermo-plastic Clear
M28 PCB Fibrous Green
Enclosure
E1 Control box enclosure Thermo-plastic White
E2 Fan motor frame Thermo-plastic White
E3 Pump motor enclosure Thermo-plastic White
E4 Water inlet enclosure Thermo-plastic Black
E5 Water drain enclosure Thermo-plastic Grey
E6 Appliance enclosure Thermo-plastic Brown
E7 Actuator main switch Thermo-plastic Grey
For results see the following tables
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M1 M1 M2 M2 M3 M3
CLAUSE
4 How tested
SA SA C C C C
o
6 Glow-wire tip temp ( C)
750 850 750 850 750 850
11(a) Time till ignition of specimen (s)
10 4 NI 2 NI 3
Time till ignition of the underlying
layer (tissue paper, pinewood NI NI NI NI NI NI
board etc.) (s)
11(b) Time from tip application till
30 30 NI 30 NI 38
flaming or glowing ceased (s)
11(c) Maximum flame height (mm)
30 15 NI 15 NI 15
11(d) Specimen distortion
Yes Yes Yes Yes Yes Yes
Depth of penetration (mm)
NM NM NM NM NM NM
11(e) Pinewood board scorching
No No No No No No
12(a) Flame or glowing
Flame Flame NI Flame NI Flame
12(b) Time of flames or glowing of
specimen, surroundings or layer
<1 <1 NI 1 NI 8
below after removal of tip
(maximum allowable: 30 s)
Ignition of surrounding parts or
No No NI No NI No
layer below (not permitted)
12 Ignition of wrapping tissue (not
No No NI No NI No
allowed)
12 RESULT
NF P P P P P
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M4 M4 M5 M5 M6 M6
CLAUSE
4 How tested
C C SA SA C C
o
6 Glow-wire tip temp ( C)
750 850 750 850 750 850
11(a) Time till ignition of specimen (s)
7 7 NI NI 1 1
Time till ignition of the underlying
layer (tissue paper, pinewood NI NI NI NI NI NI
board etc.) (s)
11(b) Time from tip application till
8 30 NI NI 8 30
flaming or glowing ceased (s)
11(c) Maximum flame height (mm)
25 8 NI NI 30 45
11(d) Specimen distortion
Yes Yes Yes Yes Yes Yes
Depth of penetration (mm)
NM NM NM NM NM NM
11(e) Pinewood board scorching
No No No No No No
12(a) Flame or glowing
Flame Flame NI NI Flame Flame
12(b) Time of flames or glowing of
specimen, surroundings or layer
0 <1 NI NI 0 <1
below after removal of tip
(maximum allowable: 30 s)
Ignition of surrounding parts or
No No NI NI No No
layer below (not permitted)
12 Ignition of wrapping tissue (not
No No NI NI No No
allowed)
12 RESULT
P P P P NF P
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M7 M7 M8 M8 M9 M9
CLAUSE
4 How tested C C C C SA SA
6 Glow-wire tip temp (oC) 750 850 750 850 750 850
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M10 M10 M11 M11 M12 M12
CLAUSE
4 How tested SA SA SA SA C C
6 Glow-wire tip temp (oC) 750 850 750 850 750 850
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M13 M13 M14 M14 M15 M15
CLAUSE
4 How tested C C SA SA SA SA
6 Glow-wire tip temp (oC) 750 850 750 850 750 850
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M16 M16 M17 M17 M18 M18
CLAUSE
4 How tested C C C C C C
6 Glow-wire tip temp (oC) 750 850 750 850 750 850
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M19 M19 M20 M20 M21 M21
CLAUSE
4 How tested C C C C C C
6 Glow-wire tip temp (oC) 750 850 750 850 750 850
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M22 M22 M23 M23 M24 M24
CLAUSE
4 How tested C C SA SA SA SA
6 Glow-wire tip temp (oC) 750 850 750 850 750 850
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER M25 M26 M27 E1 E2 E3
CLAUSE
4 How tested SA SA SA C C C
6 Glow-wire tip temp (oC) 650 650 650 550 550 550
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
Glow-wire tests
The specimens were tested with the test surfaces arranged vertically and the glow-wire tip applied at right-
angles for 30s at the temperature stated:
IEC 60695-
2-11 SPECIMEN NUMBER E4 E5 E6 E7
CLAUSE
4 How tested C C C C
* Either 12(a) or 12(b) has to comply. ”Yes” does not constitute a point of non-compliance with 12(a) if the
requirements of 12(b) are met.
The specimens were tested by application of the test flame for 30 s, not less than 10 mm from a corner.
IEC
60695.11.5 SPECIMEN NUMBER M28
Clause
6 How tested VC
Legend:
P-Pass; For clause 6:
F-Fail; V- Vertical without components
NA-Not Applicable; VC-Vertical with components
H- Horizontal without components
HC- Horizontal with components
For clause 5.4:
WT-Wooden board covered with wrapping tissue; For Clause 11:
SP-Surroung part/material situated underneath ME-Manually Extinguished;
the test speciment in normal use NI-No Ignition;
*Specimen satisfies requirements if either 11a) or 11b) complies. ”Yes” does not constitute a point of non-
compliance with 11a) if the requirements of 11b) are met.
Notes: 1. PCB specimens with an FV-0 classification in accordance with IEC 707, need not be
tested.
2. Boards are tested oriented in their normal position of use.
As a consequence of the glow-wire test, the following specimens were subjected to the needle-flame
test of IEC 60695.11.5 for 30 s. Also, at the Client’s request, parts indicated with an asterisk(*) were
subjected to a 30 s needle-flame test:
IEC 60695-
11-5 SPECIMEN NUMBER M1 M2 M3 M7
Clause
Flame impinged from specimen no. M1,M10 M10 M10 M1,M7
6 How tested SA C C C
Legend:
P-Pass; For clause 6:
F-Fail; CE-Complete Equipment;
NA-Not Applicable; SA-Sub-Assembly;
C-Component;
For clause 5.4:
WT-Wooden board covered with wrapping tissue; For Clause 11:
SP-Surrounding part/material situated ME-Manually Extinguished;
underneath the test specimen in normal use NI-No Ignition;
*Specimen satisfies requirements if either 11a) or 11b) complies. ”Yes” does not constitute a point of non-
compliance with 11a) if the requirements of 11b) are met.
As a consequence of the glow-wire test, the following specimens were subjected to the needle-flame
test of IEC 60695.11.5 for 30 s. Also, at the Client’s request, parts indicated with an asterisk(*) were
subjected to a 30 s needle-flame test:
IEC 60695-
11-5 SPECIMEN NUMBER M8 M20 M21 M22
Clause
M1,M7, M1,M6 M1,M6 M1,M6
Flame impinged from specimen no.
M8 ,M10 ,M10 ,M10
6 How tested C C C C
Legend:
P-Pass; For clause 6:
F-Fail; CE-Complete Equipment;
NA-Not Applicable; SA-Sub-Assembly;
C-Component;
For clause 5.4:
WT-Wooden board covered with wrapping tissue; For Clause 11:
SP-Surrounding part/material situated ME-Manually Extinguished;
underneath the test specimen in normal use NI-No Ignition;
*Specimen satisfies requirements if either 11a) or 11b) complies. ”Yes” does not constitute a point of non-
compliance with 11a) if the requirements of 11b) are met.
As a consequence of the glow-wire test, the following specimens were subjected to the needle-flame
test of IEC 60695.11.5 for 30 s. Also, at the Client’s request, parts indicated with an asterisk(*) were
subjected to a 30 s needle-flame test:
IEC 60695-
11-5 SPECIMEN NUMBER M6 M10 M17 M18
Clause
Flame impinged from specimen no. M6 M10 M10 M10
6 How tested C SA C C
Legend:
P-Pass; For clause 6:
F-Fail; CE-Complete Equipment;
NA-Not Applicable; SA-Sub-Assembly;
C-Component;
For clause 5.4:
WT-Wooden board covered with wrapping tissue; For Clause 11:
SP-Surrounding part/material situated ME-Manually Extinguished;
underneath the test specimen in normal use NI-No Ignition;
*Specimen satisfies requirements if either 11a) or 11b) complies. ”Yes” does not constitute a point of non-
compliance with 11a) if the requirements of 11b) are met.
As a consequence of the glow-wire test, the following specimens were subjected to the needle-flame
test of IEC 60695.11.5 for 30 s. Also, at the Client’s request, parts indicated with an asterisk(*) were
subjected to a 30 s needle-flame test:
IEC 60695-
11-5 SPECIMEN NUMBER M19 M12 M11 M15
Clause
Flame impinged from specimen no. M10 M12 M12 M15
6 How tested C C SA SA
Legend:
P-Pass; For clause 6:
F-Fail; CE-Complete Equipment;
NA-Not Applicable; SA-Sub-Assembly;
C-Component;
For clause 5.4:
WT-Wooden board covered with wrapping tissue; For Clause 11:
SP-Surrounding part/material situated ME-Manually Extinguished;
underneath the test specimen in normal use NI-No Ignition;
*Specimen satisfies requirements if either 11a) or 11b) complies. ”Yes” does not constitute a point of non-
compliance with 11a) if the requirements of 11b) are met.
As a consequence of the glow-wire test, the following specimens were subjected to the needle-flame
test of IEC 60695.11.5 for 30 s. Also, at the Client’s request, parts indicated with an asterisk(*) were
subjected to a 30 s needle-flame test:
IEC 60695-
11-5 SPECIMEN NUMBER M16 E1 E4 E7
Clause
M1,M6,
Flame impinged from specimen no. M15 M10,M9, M15 M6,M10
M12
6 How tested SA SA C C
Legend:
P-Pass; For clause 6:
F-Fail; CE-Complete Equipment;
NA-Not Applicable; SA-Sub-Assembly;
C-Component;
For clause 5.4:
WT-Wooden board covered with wrapping tissue; For Clause 11:
SP-Surrounding part/material situated ME-Manually Extinguished;
underneath the test specimen in normal use NI-No Ignition;
*Specimen satisfies requirements if either 11a) or 11b) complies. ”Yes” does not constitute a point of non-
compliance with 11a) if the requirements of 11b) are met.
EN 60335-1, EN 60335-2-98
Clause Requirement - Test Result - Remark Verdict
EN 60335-1, EN 60335-2-98
Clause Requirement - Test Result - Remark Verdict
29.3 Replace third dashed item by: N/A
- an assessment of thermal quality of material
combined with an electric strength test, in
accordance with clause 29.3.3, and for accessible
reinforced insulation consisting of a single layer,
measurement in accordance with clause 29.3.Z1
(EN 60335-1/A12)
29.3.Z1 Accessible reinforced insulation consisting of a P
single layer, thickness of layer complies with
table Z1; rated voltage (V); overvoltage category;
thickness (mm) (EN 60335-1/A12) ............................ :
EN 60335-1, EN 60335-2-98
Clause Requirement - Test Result - Remark Verdict
Appliances covered by a Part 2 of EN 60335, also N/A
plugs in accordance with Section 107-2-D1, ed.3,
1998, standard sheet C2b, C3b or C4 are allowed
Class II appliances: Section 107-2-D1, ed.3 1998, N/A
standard sheet C1b, C5, C6, DKA 2-1a and
DKA 2-1b
Stationary single-phase appliances, having a rated Fixed wiring N/A
current not exceeding 13 A, and provided with a
supply cord and a plug, the plug is in accordance
with the requirements above
Multi-phase appliances and single-phase appliances having a rated current exceeding N/A
13 A, and provided with a supply cord and a plug, plug is in accordance with
requirements below:
- Class I appliances: Section 107-2-D1, standard N/A
sheet DK 6-1a / EN 60309-2, standard sheet 2-II,
2-IV
- Class II appliances: Section 107-2-D1, standard N/A
sheet DK 6-1a / EN 60309-2, standard sheet 2-II,
2-IV, the earthing contact not being connected
Current for plug not exceeding values specified; N/A
standard sheet (no.); current (A)................................ :
EN 60335-1, EN 60335-2-98
Clause Requirement - Test Result - Remark Verdict
29.3 GERMANY: Third dashed item not applicable for N/A
appliances where the insulation is accessible.
Additional measures, such as multi-layered
insulation or adequate thickness, taken
(EN 60335-1/A1)
EN 60335-1, EN 60335-2-98
Clause Requirement - Test Result - Remark Verdict
EN 60335-1, EN 60335-2-98
Clause Requirement - Test Result - Remark Verdict
Attachment 2
Variations to IEC 60335-1 Ed 4.2 for application in Australia and New Zealand
6 CLASSIFICATION -
6.1 Protection against electric shock: Class I, II, III Class I P
22 CONSTRUCTION -
22.3 Compliance is checked by inserting the pins of the N/A
appliance into a socket-outlet capable of accepting a
plug complying with Figure 2.1(a) of AS/NZS 3112.
The socket-outlet has a horizontal pivot at a distance
of 8 mm behind the engagement face of the socket-
outlet and in the plane of the lower intersection of the
centre lines of the contact apertures.
Applied torque not exceeding 0.25 Nm N/A
A new sample of the appliance shall be subjected to N/A
and shall comply with the tests in 2.13.9.2 of AS/NZS
3112.
Each pin subjected to a torque of 0.4Nm; the pins N/A
are not rotating unless rotating does not impair
compliance with the standard
22.201 Void P
22.202 Appliances having integral pins for insertion into N/A
socket outlets shall comply with the appropriate
requirements of AS/NZS3112.
24 COMPONENTS
24.1 NOTE 201 The relevant IEC standard may be P
replaced with the relevant Australia/New Zealand
standard where applicable.
24.1.7 In Australia, telecommunication interface circuitry N/A
must comply with the Telecom Labelling Notice
issued under the Telecommunications Act instead of
IEC62151.
VARIATIONS TO IEC 60335-2-98 ED 2.2 FOR APPLICATION IN AUSTRALIA AND NEW ZEALAND
11 HEATING
11.8 After the existing first paragraph, insert the following P
variation:
In Australia, the temperature rise limits for
evaporative coolers intended to be used in Australia,
are reduced by 15 K.
1. Model LCB250-B
1. Model LCB250-B
1. Model LCB250-B
1. Model LCB250-B
1. Model LCB250-B
1. Model LCB250-B
2. Model LCB350-G
2. Model LCB350-G
2. Model LCB350-G
2. Model LCB350-G
2. Model LCB350-G
2. Model LCB350-G
3. Model LCB450-B
3. Model LCB450-B
3. Model LCB450-B
3. Model LCB450-B
3. Model LCB450-B
3. Model LCB450-B
4. Model LCB550-B
4. Model LCB550-B
4. Model LCB550-B
4. Model LCB550-B
4. Model LCB550-B
4. Model LCB550-B
5. Model CPL1100-B
5. Model CPL1100-B
5. Model CPL1100-B
5. Model CPL1100-B
5. Model CPL1100-B
5. Model CPL1100-B
8. Remote controller
8. Remote controller
9. Water pump
9. Water pump
9. Water pump
Fig. 12.b. For Australia and New Zealand (LCB, CPL & BM series)