Earthing Calculation
Earthing Calculation
Earthing Calculation
X / R Transformer
%Xt=(Z(X/R)) / √((X/R)²+1)
%Xt = 4.9694 0.0497 Ω
%Rt = 0.5522 0.0055 Ω
Fault X1
Icc Secondary Transformer
Icc 3Ø = FLA/(%Z/100*0,9) (*+10% tolerance Z%) Icc Primary
Icc 3Ø Tr= 66823 A 2789.1 A
W/ motor Contribution* 74040 A 3090.4 A
Fault X2
Icc SWG Input
L=Lenght cable TrxSwg (ft)
n=number conductor/phase
C= Constant table 3
M = 1/(1+f) 0.87195
f=(1,732*L*IccTr)/C*n*EL-L 0.14685
Icc 3ØSWG = Icc 3ØTr*M 58267 A
W/ motor Contribution* 65484 A
Fault X3
Icc MCC Input
M = 1/(1+f) 0.84664
f=(1,732*L*IccSWG)/C*n*EL-L 0.18114
Icc 3ØMCC = Icc 3ØSWG*M 49331 A
W/ motor Contribution* 56548 A
Mesh Voltage
Em=(p*Km*Ki*IG)/Lm Em= 116653.4943 V
n=2*Lc/Lp n= 4
Kii=1/((2*n)^(2/n)) Kii= 0.35
Kh=√(1+(h/h0)) Kh= 1.265
Km=(1/(2pi))*(ln(((d^2)/16*h*d)+(((D+(2*h))^2)/
(8*D*d)-(h/(4*d)))+((Kii/Kh)*ln(8/(pi*(2*n-1))) Km= 1.4733007578
Ki=0,644+0,148*n Ki= 1.236
107mm2
TABLE 2
TABLE 3
TABLE 4
TABLE 7