This document calculates the number of earth pits required for a site in Mhow, India based on soil resistivity test results and formulas from IS 3043-2018. It determines that 26 earth pits are needed, each with a 50mm copper-plated pipe 3m in length buried in the ground. It also calculates the resistance values of the pipe electrodes and interconnecting strips in the grounding grid, and selects conductor sizes of 25x6mm copper for the neutral grounding and 40x10mm GI for the body grounding based on a maximum fault current of 15,000A.
This document calculates the number of earth pits required for a site in Mhow, India based on soil resistivity test results and formulas from IS 3043-2018. It determines that 26 earth pits are needed, each with a 50mm copper-plated pipe 3m in length buried in the ground. It also calculates the resistance values of the pipe electrodes and interconnecting strips in the grounding grid, and selects conductor sizes of 25x6mm copper for the neutral grounding and 40x10mm GI for the body grounding based on a maximum fault current of 15,000A.
This document calculates the number of earth pits required for a site in Mhow, India based on soil resistivity test results and formulas from IS 3043-2018. It determines that 26 earth pits are needed, each with a 50mm copper-plated pipe 3m in length buried in the ground. It also calculates the resistance values of the pipe electrodes and interconnecting strips in the grounding grid, and selects conductor sizes of 25x6mm copper for the neutral grounding and 40x10mm GI for the body grounding based on a maximum fault current of 15,000A.
This document calculates the number of earth pits required for a site in Mhow, India based on soil resistivity test results and formulas from IS 3043-2018. It determines that 26 earth pits are needed, each with a 50mm copper-plated pipe 3m in length buried in the ground. It also calculates the resistance values of the pipe electrodes and interconnecting strips in the grounding grid, and selects conductor sizes of 25x6mm copper for the neutral grounding and 40x10mm GI for the body grounding based on a maximum fault current of 15,000A.
Download as XLSX, PDF, TXT or read online from Scribd
Download as xlsx, pdf, or txt
You are on page 1of 1
CALCULATION OF NO OF EARTH PITS AS PER IS 3043-2018
Site Location- ATC Mhow
Average Soil resistivity( ρ). as per test report ρ= Based on Soil resistivity document , 280.00 Ohm-mtr Refer document "Soil Test Report- MHOW Indore" time(t) 1 Sec
Maintenance free with 250 microns Cu plated 50 mm pipe
Diameter of Pipe d= 0.1 mtr Resistivity of compound ρc= 0.12 Ohm-mtr length of Pipe L= 3 mtr Surface area S= 0.9426 Sqmtr Electrode resistance Rb =1/2∏L{(ρ-ρc)[log(8L/d)-1]+ρc[log(8L/d)-1] as per IS3043-2018 section 14.2.5 Resistance of an Electrode Encased 66.5912 Ohms in Low Resistivity Material No of pits proposed 26 No's
Resistance achieved by Interconnecting strips & other burried strips
Conductor size 50mm (interconnecting strips) 150 m Conductor size 40mm (Cu for Transformer Neutral) burried length 49 m Conductor size 25mm (Cu and GI) 77 m Average Width of strip 4.1 cm Length of grid strip in m l= 27600 cm Resistivity of interconnection strip and other burried strips 1.647 R=100ρ/2∏l(log(4l/d)
Cummilative resistance at site
Cumulative Resistance of Pipe electrodes.(Resistance of one Pipe 2.56 Ohm electrode / No.of Pipe electrodes considered) Cumulative Resistance of Interconnecting & other strips (only strips 1.65 Ohm burried in soil) Effective Resistance with Earth electrodes and strips in ground 1.0 Ohm
Conductor size calculation based on maximum fault current
if I= 15000 A t= 1 Sec K= 80 For steel conductor K= For Cu 205 conductor
Then the cross section of the grid
electrode is give by the equation S= I x Sqroot(t)/K Neutral Grounding Thus Conductor size S = 73.2 mm2 Conductor selected 25 x 6 - Cu Body Grounding Thus Conductor size S = 187.5 mm2 Conductor selected 40 x 10 - GI