Volume 5 Earthing Calculations Report-REV-01
Volume 5 Earthing Calculations Report-REV-01
Volume 5 Earthing Calculations Report-REV-01
I t
A = 82.66 10 % corrosion tolerance 90.93 (mm2)
K
where :-
A cross section area of the main earthing conductor (mm2)
I fault current (ampere) 15000
t duration of fault current (seconds) 1.00
K material coefficient of the main earth conductor (A.sqrt(sec.)/mm2)
SELECTED CROSS SECTION AREA FOR THE MAIN COPPER CONDUCTOR (mm2) = 95.00 (mm2)
NOTE: Metal α β
Copper 226 234.5
POWER EARTHING RESISTANCE CALCULATIONS FOR OPEN MARKET
According to BS 7430
1 - CALCULATION OF SINGLE EARTHING ROD RESISTANCE
According to BS 7430:2011 + A1:2015 Equation 9.5.3
8L
Rr ln 1 ohm
2L d
27.73
where :-
ρ Rho Specific Resistivity of the Soil (ohm. m) after adding bentonite 100.00
L length of the earth rod (m) 3.60
d diameter of the earth rod (m) 0.020
Re = 0.92 ohm
where :-
4- THE COMBINED EARTH RESISTANCE OF THE RODS & CONDUCTOR (LOOP) AS FOLLOWS