SS27 CPGK DC50
SS27 CPGK DC50
SS27 CPGK DC50
Diesel
Generator set
QSK78 series
engine
2500 kVA - 2750 kVA 50 Hz
Data Center Continuous
Description
Cummins Power Generation commercial Alternator - Several alternator sizes offer
generator sets are fully integrated power selectable motor starting capability with low
generation systems providing optimum reactance 2/3 pitch windings; low waveform
performance, reliability and versatility for Data distortion with non-linear loads, fault clearing
Center applications. short-circuits capability, and class F or H
insulation.
Features
Control system - Standard PowerCommand®
Data Center Continuous® (DCC) - Applicable electronic control provides total system
for supplying power continuously to a constant integration including remote start/stop, precise
or varying electrical load for unlimited hours in frequency and voltage regulation, alarm and
a data center application. status message display, AmpSentry protection,
output metering, auto-shutdown.
Uptime Compliant - Meets the requirement of
NFPA - The genset accepts full rated load in a
a Tier III and IV data center site by being rated
to run for unlimited hours of operation when single step in accordance with NFPA 110 for
loaded to 'N' demand for the engine generator Level 1 systems.
set.
Cooling system - Optional remote mounted
Cummins® heavy-duty engine - Rugged 4- horizontal cooling system, designed and tested
cycle industrial diesel delivers reliable power, for rated ambient temperatures, offers maximum
low emissions and fast response to load flexibility for facility design requirements.
changes.
Warranty and service - Backed by a
Permanent magnet generator (PMG) - Offers comprehensive warranty and worldwide
enhanced motor starting and fault clearing distributor network.
short circuit capability.
50 Hz Emissions Compliance
Model kVA (kW) TA LUFT and EPA Controller Data sheets
C2750 D5 2500 (2000) 4g TA LUFT 3.3 DS352-CPGK-DC
C3000 D5 2750 (2200) 4g TA LUFT 3.3 DS335-CPGK-DC
power.cummins.com
©2016 Cummins Power Generation Inc. | SS27c-CPGK-DC50 (3/16)
Generator set specifications
Transient Performance ISO 8528-5 compliant
Steady state voltage regulation, no load to full load ± 0.25%
Steady state frequency variation ± 0.25%
Frequency regulation Isochronous
Radiated emissions to BS EN 61000-6.3
EMC compatibility
Conducted immunity to BS EN 61000-6.2
Engine specifications
Design 4 cycle, V, turbo charged and low temperature after-cooled
Bore 170
Stroke 190
Displacement 77.6 L (4735 in3)
Cylinder block Cast iron, 18 cylinder
Battery capacity 2200 amps
Battery charging alternator 55 amps
Starting voltage 24-volt, negative ground
Direct injection: number 2 diesel fuel, fuel filter, automatic electric fuel
Fuel system
shutoff
Fuel filter Triple element, 10 micron filtration, spin on fuel filter with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Six spin-on, combination full flow and bypass filters
Cooling system 104 ºF (40 ºC) ambient
Alternator specifications
Design Brushless, 4 pole, drip-proof revolving field
Stator 2/3 pitch
Rotor 2 bearing, flexible coupling
Insulation system Class H on low and medium voltage, Class F on high voltage
Standard temperature rise 150 °C standby
Exciter type PMG (Permanent magnet generator)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion No load <1.5%. Non distorting balanced linear load <3%
Telephone influence factor (TIF) < 50% per NEMA MG1-22.43
Telephone harmonic factor (THF) < 2%
Available voltages
50 Hz line – neutral / line - line
220/380 1905/3300
230/400 3810/6600
240/416 6350/11000
255/440
Note: Some options may not be available on all models - consult factory for availability. Data Center options are available through RFQ with the Custom
Applications Group and could result in additional leadtimes. Please consult with the Engineering to Order group to understand feasibility.
power.cummins.com
©2016 Cummins Power Generation Inc. | SS27c-CPGK-DC50 (3/16)
PowerCommand® 3.3 control system
Engine data
DC voltage
Engine speed
Lube oil pressure and temperature
Coolant temperature
Comprehensive FAE data (where applicable)
Other data
Genset model data
Start attempts, starts, running hours, kW hours
Control system Load profile (operating hours at % load in 5%
increments)
The PowerCommand® control system is an Fault history
integrated microprocessor based generator set Data logging and fault simulation (requires
control system providing voltage regulation, engine InPower)
protection, alternator protection, operator interface
and isochronous governing.
AmpSentry – Includes integral AmpSentry protection,
Standard control functions
which provides a full range of alternator protection
Digital governing (optional)
functions that are matched to the alternator
provided. Integrated digital electronic isochronous governor
Power management – Control function provides Temperature dynamic governing
battery monitoring and testing features and smart Digital voltage regulation
starting control system. Integrated digital electronic voltage regulator
Advanced control methodology – Three phase 3-phase, 4-wire line-to-line sensing
sensing, full wave rectified voltage regulation, with a Configurable torque matching
PWM output for stable operation with all load types.
Communications interface – Control comes standard AmpSentry AC protection
with PCCNet and Modbus interface. AmpSentry protective relay
Regulation compliant – Prototype tested: UL, CSA Over current and short circuit shutdown
and CE compliant. Over current warning
Service - InPower™ PC-based service tool available Single and three phase fault regulation
for detailed diagnostics, setup, data logging and fault Over and under voltage shutdown
simulation. Over and under frequency shutdown
Reliable design – The control system is designed for Overload warning with alarm contact
reliable operation in harsh environment. Reverse power and reverse var shutdown
Multi-language support Field overload
Engine protection
Operator panel features Battery voltage monitoring, protection and testing
Over speed shutdown
Operator panel features – The operator panel, in Low oil pressure warning and shutdown
addition to the alternator, displays the Utility/AC Bus High coolant temperature warning and shutdown
data. Low coolant level warning or shutdown
Operator/display functions Low coolant temperature warning
Fail to start (over crank) shutdown
320 x 240 pixels graphic LED backlight LCD Fail to crank shutdown
Auto, manual, start, stop, fault reset and lamp Cranking lockout
test/panel lamp switches Sensor failure indication
Alpha-numeric display with pushbuttons Low fuel level warning or shutdown
LED lamps indicating genset running, remote start, Fuel-in-rupture-basin warning or shutdown
not in auto, common shutdown, common warning, Full authority electronic engine protection
manual run mode, auto mode and stop
Control functions
Paralleling control functions
Time delay start and cool down
Digital frequency synchronization and voltage Real time clock for fault and event time stamping
matching Exerciser clock and time of day start/stop
Isochronous kW and kvar load sharing controls Data logging
Droop kW and kvar control Cycle cranking
Sync check Load shed
Extended paralleling (Peak Shave/Base Load) Configurable inputs and outputs (4)
Digital power transfer control (AMF) provides load Remote emergency stop
transfer operation in open or closed transition or
soft (ramping) transfer mode Options
Alternator data Auxiliary output relays (2)
Line-to-neutral and line-to-line AC volts
3-phase AC current
Frequency
kW, kvar, power factor kVA (three phase and total)
power.cummins.com
©2016 Cummins Power Generation Inc. | SS27c-CPGK-DC50 (3/16)
C
A B
This outline drawing is to provide representative configuration details for Model series only.
See respective model data sheet for specific model outline drawing number.
Open set
Dim “A” Dim “B” Dim “C” Set Weight* Set Weight*
Model mm mm mm dry kg wet kg
C2750 D5 5691 2305 2798 18549 19145
C3000 D5 5691 2305 2798 18964 19560
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.