Diesel Generator Set: QSB7 Series Engine 125-200 KW at 60 HZ EPA Tier 3 Emissions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Specification sheet

Diesel
generator set
QSB7 series engine
125-200 kW @ 60 Hz
EPA Tier 3 emissions

Description
Cummins® generator sets are fully integrated Cooling system - Standard cooling package
power generation systems providing optimum provides reliable running at up to 50 °C
performance, reliability and versatility for (122 °F) ambient temperature.
stationary Standby applications.
Enclosures - The aesthetically appealing
Features enclosure incorporates special designs that
deliver one of the quietest generators of its kind.
Heavy duty engine - Rugged 4-cycle industrial Aluminium material plus durable powder coat
diesel delivers reliable power and fast response paint provides the best anti-corrosion
to load changes. performance. The generator set enclosure has
been evaluated to withstand 180 MPH wind
Alternator - Several alternator sizes offer
loads in accordance with ASCE7 -10. The
selectable motor starting capability with low
design has hinged doors to provide easy access
reactance 2/3 pitch windings, low waveform
for service and maintenance.
distortion with non-linear loads and fault clearing
short-circuit capability. Fuel tanks - Dual wall sub-base fuel tanks are
offered as optional features, providing
Control system - The PowerCommand®
1.1
economical and flexible solutions to meet
electronic control is standard equipment and
extensive code requirements on diesel fuel
provides total generator set system integration
tanks.
including automatic remote starting/stopping,
precise frequency and voltage regulation, alarm NFPA - The generator set accepts full rated load
and status message display, output metering, in a single step in accordance with NFPA 110 for
auto-shutdown at fault detection and NFPA 110 Level 1 systems.
Level 1 compliance.
Warranty and service - Backed by a
comprehensive warranty and worldwide
distributor network.

Standby Prime
60 Hz 60 Hz
Model kW kVA kW kVA Data sheets
C125D6D 125 156 113 141 NAD-6371-EN
C150D6D 150 188 135 169 NAD-6372-EN
C175D6D 175 219 158 197 NAD-6373-EN
C200D6D 200 250 180 225 NAD-6374-EN

power.cummins.com
©2019 Cummins Inc. | NAS-6370-EN.DOCX (04/19) A061Y585
Generator set specifications
Governor regulation class ISO8528 Part 1 Class G3
Voltage regulation, no load to full load ± 1.0%
Random voltage variation ± 1.0%
Frequency regulation Isochronous
Random frequency variation ± 0.50%
Radio frequency emissions compliance FCC code title 47 part 15 class A and B

Engine specifications
Design Turbocharged and charge air cooled
Bore 107 mm (4.21 in.)
Stroke 124 mm (4.88 in.)
Displacement 6.7 L (408 in3)
Cylinder block Cast iron, in-line 6 cylinder
Battery capacity 2 x 850 amps per battery at ambient temperature of 0 °C (32 °F)
Battery charging alternator 100 amps
Starting voltage 2 x 12 volt in parallel, negative ground
Lube oil filter type(s) Spin-on with relief valve
Standard cooling system High ambient radiator
Rated speed 1800 rpm

Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator 2/3 pitch
Rotor Direct coupled, flexible disc
Insulation system Class H per NEMA MG1-1.65
Standard temperature rise 120 ºC (248 °F) Standby
Exciter type Torque match (shunt) with PMG as option
Alternator cooling Direct drive centrifugal blower
AC waveform Total Harmonic Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic
Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) < 3%

Available voltages
1-phase 3-phase
• 120/240 • 120/208 • 120/240 • 277/480 • 347/600 • 127/220

Generator set options


Fuel system Control Cooling system
• Basic fuel tanks • AC output analog meters • Shutdown – low coolant level
• Regional fuel tanks • Stop switch – emergency • Warning – low coolant level
Engine • Auxiliary output relays (2) • Extension – coolant drain
• Engine air cleaner – normal or heavy • Auxiliary configurable signal • Coolant heater options:
duty inputs (8) and relay outputs (8) - <4 °C (40 °F) – cold weather
• Shut down – low oil pressure Electrical - <-18 °C (0 °F) – extreme cold
• Extension – oil drain • One, two or three circuit breaker Exhaust system
• Engine oil heater configurations • Exhaust connector NPT
Alternator • 80% rated circuit breakers • Exhaust muffler mounted
• 120 °C temperature rise alternator • 80% or 100% rated LSI circuit Generator set application
breakers
• 105 °C temperature rise alternator • Base barrier – elevated genset
• Battery charger
• PMG excitation • Radiator outlet duct adapter
• Alternator heater, 120 V Enclosure
Warranty
• Reconnectable full 1 phase output • Aluminium enclosure Sound Level 1 or • Base warranty – 2 year/1000 hours,
alternator upto 175 kWe Level 2, green color
Standby
• Aluminium weather protective enclosure
• Base warranty – 1 year/unlimited
with muffler installed, green color hours, Prime
• 3 & 5 year Standby warranty options
power.cummins.com
©2019 Cummins Inc. | NAS-6370-EN.DOCX (04/19) A061F585
Generator set accessories
• Coolant heater • Remote monitoring device – • Alternator PMG excitation
• Battery heater kit PowerCommand 500/550 • Alternator heater
• Engine oil heater • Battery charger – stand-alone, 12 V • Improved PC1.1 display readability
• Remote control displays • Circuit breakers • Top conduit entry access
• Auxiliary output relays (2) • Enclosure Sound Level 1 to Sound
• Auxiliary configurable signal Level 2 upgrade kit
inputs (8) and relay outputs (8) • Base barrier – elevated generator
• Annunciator – RS485 set
• Audible alarm • Mufflers – industrial, residential or
critical

Control system PowerCommand 1.1


• Low coolant level warning or shutdown
• Low coolant temperature warning
• High, low and weak battery voltage warning
• Fail to start (overcrank) shutdown
• Fail to crank shutdown
• Redundant start disconnect
• Cranking lockout
• Sensor failure indication
PowerCommand control is an integrated generator set • Low fuel level warning or shutdown
control system providing voltage regulation, engine protection,
Alternator data
operator interface and isochronous governing (optional). Major
features include: • Line-to-Line and Line-to-neutral AC volts
• Battery monitoring and testing features and smart starting • 3-phase AC current
control system. • Frequency
• Standard PCCNet interface to devices such as remote • Total kVa
annunciator for NFPA 110 applications. Engine data
• Control boards potted for environmental protection. • DC voltage
• Control suitable for operation in ambient temperatures from • Lube oil pressure
-40 °C to +70 °C (-40 °F to +158 °F) and altitudes to 5000 • Coolant temperature
meters (13,000 feet).
• Engine speed
• Prototype tested; UL, CSA, and CE compliant.
Other data
• InPower™ PC-based service tool available for detailed
diagnostics. • Generator set model data
Operator/display panel • Start attempts, starts, running hours
• Manual off switch • Fault history
• Alpha-numeric display with pushbutton access for viewing • RS485 Modbus® interface
engine and alternator data and providing setup, controls and • Data logging and fault simulation (requires
adjustments (English or international symbols) InPower service tool)
• LED lamps indicating generator set running, not in auto, Digital governing (optional)
common warning, common shutdown, manual run mode and • Integrated digital electronic isochronous governor
remote start • Temperature dynamic governing
• Suitable for operation in ambient temperatures from Digital voltage regulation
-40 °C to +70 °C
• Integrated digital electronic voltage regulator
• Bargraph display (optional)
• 2-phase Line-to-Line sensing
AC protection
• Configurable torque matching
• Over current warning and shutdown
Control functions
• Over and under voltage shutdown
• Time delay start and cooldown
• Over and under frequency shutdown
• Cycle cranking
• Over excitation (loss of sensing) fault
• PCCNet interface
• Field overload
• (2) Configurable inputs
Engine protection
• (2) Configurable outputs
• Overspeed shutdown
• Remote emergency stop
• Low oil pressure warning and shutdown
• Automatic Transfer Switch (ATS) control
• High coolant temperature warning and shutdown
• Generator set exercise, field adjustable

power.cummins.com
©2019 Cummins Inc. | NAS-6370-EN.DOCX (04/19) A061F585
Options • AC output analog meters (bargraph)
• Auxiliary output relays (2) - Color-coded graphical display of:
• Remote annunciator with (3) configurable inputs and - 3-phase AC voltage
(4) configurable outputs - 3-phase current
• PMG alternator excitation - Frequency
• PowerCommand 500/550 for remote monitoring and - kVa
alarm notification (accessory) • Remote operator panel
• Auxiliary, configurable signal inputs (8) and • PowerCommand 2.3 control with AmpSentry protection
configurable relay outputs (8)

Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load
for the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power (LTP)
is in accordance with ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying electrical load
for unlimited hours. Prime Power (PRP) is in accordance
with ISO 8528. Ten percent overload capability is
available in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant This outline drawing is for reference only. See respective
electrical load for unlimited hours. Continuous Power model data sheet for specific model outline drawing
(COP) in accordance with ISO 8528, ISO 3046, AS 2789, number.
DIN 6271 and BS 5514.
Do not use for installation design

power.cummins.com
©2019 Cummins Inc. | NAS-6370-EN.DOCX (04/19) A061F585
Dim “A” Dim “B” Dim “C” Set weight*wet
Model mm (in.) mm (in.) mm (in.) kg (lbs.)
Open set
C125D6D 2867 (113) 1016 (40) 1415 (56) 1470 (3240)
C150D6D 2867 (113) 1016 (40) 1415 (56) 1470 (3240)
C175D6D 2867 (113) 1016 (40) 1415 (56) 1470 (3240)
C200D6D 2867 (113) 1016 (40) 1415 (56) 1470 (3240)
Weather protective enclosure
C125D6D 2867 (113) 1016 (40) 1836 (72) 1600 (3527)
C150D6D 2867 (113) 1016 (40) 1836 (72) 1600 (3527)
C175D6D 2867 (113) 1016 (40) 1836 (72) 1600 (3527)
C200D6D 2867 (113) 1016 (40) 1836 (72) 1600 (3527)
Sound attenuated enclosure Level 1
C125D6D 3621 (143) 1016 (40) 1836 (72) 1649 (3635)
C150D6D 3621 (143) 1016 (40) 1836 (72) 1649 (3635)
C175D6D 3621 (143) 1016 (40) 1836 (72) 1649 (3635)
C200D6D 3621 (143) 1016 (40) 1836 (72) 1649 (3635)
Sound attenuated enclosure Level 2
C125D6D 4061 (160) 1016 (40) 1836 (72) 1665 (3671)
C150D6D 4061 (160) 1016 (40) 1836 (72) 1665 (3671)
C175D6D 4061 (160) 1016 (40) 1836 (72) 1665 (3671)
C200D6D 4061 (160) 1016 (40) 1836 (72) 1665 (3671)

* Weights above are average. Actual weight varies with product configuration.

power.cummins.com
©2019 Cummins Inc. | NAS-6370-EN.DOCX (04/19) A061F585
Codes and standards
Codes or standards compliance may not be available with all model configurations – consult factory for availability.
This generator set is designed
in facilities certified to ISO 9001 The generator set is available
and manufactured in facilities Listed to UL 2200, Stationary
certified to ISO 9001 or Engine Generator Assemblies.
ISO 9002.
The Prototype Test Support
(PTS) program verifies the
performance integrity of the
Engine certified to U.S. EPA SI
generator set design. Cummins
products bearing the PTS U.S. EPA Stationary Emission Regulation
40 CFR, Part 60.
symbol meet the prototype test
requirements of NFPA 110 for
Level 1 systems.

All low voltage models are CSA International The generator set is certified to
certified to product class Building International Building Code (IBC)
4215-01. 2012.
Code

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s
electrical system except through an approved device or after building main switch is open.

For more information contact your local Cummins distributor or


visit power.cummins.com

©2019 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins
Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
NAS-6370-EN.DOCX (04/19) A061F585