Diesel Generator Set QSB7 Series Engine: 160 kVA - 220 kVA 50 HZ 135 KW - 200 KW 60 HZ
Diesel Generator Set QSB7 Series Engine: 160 kVA - 220 kVA 50 HZ 135 KW - 200 KW 60 HZ
Diesel Generator Set QSB7 Series Engine: 160 kVA - 220 kVA 50 HZ 135 KW - 200 KW 60 HZ
Diesel
generator set
QSB7 series
engine
160 kVA - 220 kVA 50 Hz
135 kW - 200 kW 60 Hz
Description
This Cummins® Power Generation commercial Cooling system - Standard integral set-
generator set is a fully integrated power mounted radiator system, designed and tested
generation system, providing optimum for rated ambient temperatures, simplifies
performance, reliability, and versatility for facility design requirements for rejected heat.
stationary standby, prime power and Control system – The PowerCommand®
continuous duty applications. electronic control is standard equipment and
provides total genset system integration,
Features
including auto remote start/stop, alarm and
Cummins® heavy-duty engine - Rugged status message display.
4-cycle industrial diesel delivers reliable power,
Enclosures - Optional weather-protective and
low emissions and fast response to load
sound-attenuated enclosures are available.
changes.
Warranty and service - Backed by a
Optional permanent magnet generator
comprehensive warranty and worldwide
(PMG) - Offers enhanced motor starting and
distributor network.
fault clearing short circuit capability.
Alternator - Low reactance 2/3 pitch
windings; low waveform distortion with non-
linear loads, fault clearing short-circuits
capability, and class H insulation.
C200 D5e QSB7G5 200 (160) 182 (146) PC1.2 EU SIIIA DS330-CPGK
C220 D5e QSB7G5 220 (176) 200 (160) PC1.2 EU SIIIA DS331-CPGK
C150 D6e QSB7G5 150 (188) 135 (169) PC1.2 EPA T3 DS332-CPGK
C175 D6e QSB7G5 175 (219) 160 (200) PC1.2 EPA T3 DS333-CPGK
C200 D6e QSB7G5 200 (250) 180 (225) PC1.2 EPA T3 DS334-CPGK
power.cummins.com
©2015 Cummins Power Generation Inc. | SS22b-CPGK (9/15)
Generator set specifications
Governor regulation class ISO 8528 G3
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMS compatibility In compliance with BS 800 and VDE levels G and N
Engine specifications
Design 4 cycle, in-line, turbo-charged
Bore 107 mm
Stroke 124 mm
Displacement 6.69 liter (408.0 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100 AH
Battery charging alternator 70 amps
Starting voltage 12 volt, negative ground
Fuel system Direct injection
Fuel filter Strata pore fuel filter
Air cleaner type Heavy duty air cleaner
Lube oil filter type(s) Strata pore lube oil filter
Standard cooling system 122 ºF (50 ºC) ambient radiator
Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Standard temperature rise Standby 125-163 ºC
Exciter type Separately excited by PMG
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load <1.5%. Non distorting balanced linear load <5%
Telephone influence factor (TIF) < 50% per NEMA MG1-22.43
Telephone harmonic factor (THF) <2%
Available voltages
50 Hz line – neutral / line - line 60 Hz line – neutral / line - line
· 110/190 · 127/220 · 120/208 · 240/416
· 115/200 · 230/400 · 127/220 · 254/440
· 120/208 · 240/415 · 132/230 · 266/460
· 139/240 · 277/480
· 220/380*
*Derate may be applicable at this voltage. Please consult factory for details.
power.cummins.com
©2015 Cummins Power Generation Inc. | SS22b-CPGK (9/15)
Control system Service adjustments – The HMI includes provisions for
adjustment of generator set control functions. Adjustments
PowerCommand® 1.2 – The PowerCommand® control are protected by a password. Functions include:
system is a microprocessor- based generator set monitoring, · Engine speed governor adjustments.
metering and control system designed to meet the demands · Voltage regulation adjustments.
of today’s engine driven generator sets. The integration of all · Cycle cranking.
control functions into a single control system provides · Configurable fault set up.
enhanced reliability and performance compared to · Configurable output set up.
conventional generator set control systems. These control · Meter calibration.
systems have been designed and tested to meet the harsh · Units of measurement.
environment in which gensets are typically applied.
Protective functions
Description Protective functions include:
The PowerCommand® generator set control is suitable for use · Battle short mode.
on a wide range of generator sets in non-paralleling · Configurable alarm and status inputs.
applications. The PowerCommand control is compatible with · Emergency stop.
shunt or PMG excitation style. It is suitable for use with · Hydro mechanical fuel system engine protection.
connectable or non reconnectable generators, and it can be · Overspeed shutdown.
configured for any frequency, voltage and power connection · Low lube oil pressure warning.
from 120-600 VAC line-to-line. · High lube oil temperature warning/shutdown.
Power for this control system is derived from the generator · High engine temperature warning/shutdown.
set starting batteries. The control functions over a voltage · Low coolant temperature warning.
range from 8 VDC to 30 VDC. · Sensor failure indication.
· Full authority electronic engine protection.
Major features · General engine protection.
· 128 x 128 pixels graphic LED backlight LCD. · Low and high battery voltage warning.
· Digital voltage regulation. Single phase full wave SCR type · Weak battery warning.
regulator compatible with either shunt or PMG systems. · Fail to start (overcrank) shutdown.
· Digital engine speed governing (where applicable). · Fail to crank.
· Generator set monitoring and protection. · Cranking lockout.
· Advanced over-current protection. Alternator protection
· Modbus® interface for interconnecting to customer · High AC voltage shutdown (59).
equipment. · Low AC voltage shutdown (27).
· 12 and 24 VDC battery operation. · Overcurrent warning/shutdown.
· Warranty and service. Backed by a comprehensive · Under frequency shutdown (81 u).
warranty and worldwide distributor service network. · Over frequency shutdown/warning (81 o).
· Certification. Suitable for use on generator sets that are · Loss of sensing voltage shutdown.
designed, manufactured, tested and certified to relevant · Field overload shutdown.
UL, NFPA, ISO, IEC Mil Std., CE and CSA standards.
Field control interface
Base control functions Input signals to the base control include:
HDMI capability. · Remote start.
Operator adjustments – The HMI includes provisions for · Local and emergency stop.
many set up and adjustment functions. · Configurable inputs: Control includes (4) input signals from
customer.
Data logs – Includes engine run time, controller on time,
number of start attempts. Output signals from the PowerCommand control
include:
Fault history – Provides a record of the most recent fault
· Configurable relay outputs: Control includes (2) relay output
conditions with control hours time stamp. Up to 10 events are
contacts rated at 2 A.
stored in the control non-volatile memory.
Alternator data
· Voltage (single or three phase line-to-line and line-to
neutral).
· Current (single or three phase).
· KVA (three phase and total). PowerCommand 1.2®
· Frequency. control operator /
display panel
Engine data
· Starting battery voltage.
· Engine speed.
· Engine temperature.
· Engine oil pressure.
· Partial Full Authority Engine (FAE) data (where applicable).
power.cummins.com
©2015 Cummins Power Generation Inc. | SS22b-CPGK (9/15)
Ratings definitions
OPEN
Emergency standby power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a reliable
utility source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-time running power (LTP):
Applicable for supplying power to a constant electrical ENCLOSED
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514. This outline drawing is to provide representative configuration
Base load (continuous) power (COP): details for Model series only.
Applicable for supplying power continuously to a
See respective model data sheet for specific model outline
constant electrical load for unlimited hours. Continuous drawing number.
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514. Do not use for installation design
Open Enclosed
Length Width Height Length Width Height
“A” “B” “C” Dry wt.* Wet wt.* “A” “B” “C” Dry wt.* Wet wt.*
Model mm mm mm kg kg mm mm mm kg kg
C175 D5e 2656 1100 1822 1546 1572 3904 1142 2276 2922 2948
C200 D5e 2656 1100 1822 1644 1670 3904 1142 2276 3018 3044
C220 D5e 2656 1100 1822 1644 1670 3904 1142 2276 3018 3044
C150 D6e 2656 1100 1822 1546 1572 3904 1142 2276 2922 2948
C175 D6e 2656 1100 1822 1644 1670 3904 1142 2276 3018 3044
C200 D6e 2656 1100 1822 1644 1670 3904 1142 2276 3018 3044
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.