EMERS-5888-EN Specification Sheet PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Specification sheet

Diesel
generator set
QSZ13 series
engine
409 kVA - 500 kVA 50 Hz
364 kW - 440 kW 60 Hz

Description
This Cummins® commercial generator set is a Cooling system - Standard integral set-
fully integrated power generation system, mounted radiator system, designed and tested
providing optimum performance, reliability, and for rated ambient temperatures, simplifies
versatility for stationary Standby and Prime facility design requirements for rejected heat.
Power.
Control system - Standard PowerCommand®
Features electronic control is standard equipment and
provides total genset system integration,
Cummins heavy-duty engine - Rugged 4-
including auto remote start/stop, precise
cycle industrial diesel delivers reliable power,
frequency and voltage regulation, alarm and
low emissions and fast response to load
status message display, AmpSentryTM
changes.
protection and output metering.
Optional Permanent Magnet Generator
Enclosures - Optional weather-protective and
(PMG) - Offers enhanced motor starting and
sound-attenuated enclosures.
fault clearing short circuit capability.
Warranty and service - Backed by a
Alternator - Low reactance 2/3 pitch windings;
comprehensive warranty and worldwide
low waveform distortion with non-linear loads,
distributor network.
fault clearing short-circuits capability, and class
H insulation.

Emissions
Standby rating Prime rating compliance
50 Hz 60 Hz 50 Hz 60 Hz EU Stage/EPA Controller
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) Tier Std/Opt Data sheet
C400 D5eB 400 (320) 364 (291) EU Stage IIIa 2.2/3.3 EMERD-6301
C450 D5eB 450 (360) 409 (327) EU Stage IIIa 2.2/3.3 EMERD-5934
C500 D5 500 (400) 455 (364) EU Stage II 2.2/3.3 EMERD-5935
C350 D6e 350 (440) 320 (400) EPA Tier 3 2.2/3.3 EMERD-6302
C400 D6e 400 (500) 364 (455) EPA Tier 3 2.2/3.3 EMERD-5936
C440 D6 440 (550) 400 (500) EPA Tier 2 2.2/3.3 EMERD-5937
power.cummins.com
©2017 Cummins Inc. | EMERS-5888-EN.DOCX (01/18)
Generator set specifications
Governor regulation class ISO 8528 G3
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
Radio frequency emissions compliance BS EN61000-6-2:2005 / BS EN61000-6-3:2007 +A1:2001

Engine specifications
Design 4 cycle, in-line, turbocharged and charge air-cooled
Bore 130 mm (5.12 in)
Stroke 163 mm (6.42 in)
Displacement 13 liter (793 in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 100 AH
Battery charging alternator 80 amps
Starting voltage 24 volts, negative ground
Fuel system XPI
Fuel filter Spin on fuel filters with water separator
Air cleaner type Dry replaceable element with restriction indicator
Lube oil filter type(s) Spin on full flow filter
Standard cooling system 122 ºF (50 ºC) ambient radiator

Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation system Class H
Standard temperature rise Standby 125-163 ºC
Exciter type Self excited (PMG optional)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) < 50% per NEMA MG1
Telephone Harmonic Factor (THF) < 2%

Available voltages
50 Hz Line – Neutral/Line - Line 60 Hz Line – Neutral/Line - Line
 110/190  220/380  110/190  220/380

 115/200  230/400  115/200  230/400

 120/208  240/416  120/208  240/416

 127/220  255/440  127/220  255/440

 139/240  277/480

Generator set options


Engine Circuit breaker Control panel
 Heavy duty air cleaner  3 or 4 pole main circuit breaker  PowerCommand 3.3
 Water jacket heater 240 V  Motorised 3 or 4 pole circuit breaker  PowerCommand 3.3 MLD
 Aux contacts and trip alarm  AC output bargraph
Enclosure
 Shunt trip – 24 VDC  Shutdown audible alarm
 Sound attenuated canopy  Earth fault shutdown
Fuel Tank
Alternator  Control cabinet heater
 Low fuel level warning or shutdown
 Alternator heater  High fuel level warning
 Exciter voltage regulator (PMG)  Electric fuel transfer pump
 High alternator temp shutdown

power.cummins.com
©2017 Cummins Inc. | EMERS-5888-EN.DOCX (01/18)
Generator set options (continued)
Warranty Silencer Battery charger
 2 years for Prime application  9 dB attenuation critical silencer  Set mounted
 5 years for Standby application  25 dB attenuation residential silencer  Standalone
 10 years for major components  5 A or 10 A
*Note: Some options may not be available on all models - consult factory for availability.

PowerCommand 2.2 control system Other data


The PowerCommand control  Genset model data.
system is an integrated  Start attempts, starts, running hours, kW hours.
microprocessor based  Load profile (operating hours at % load in 5%
generator set control system increments).
providing voltage regulation,
 Fault history.
engine protection, alternator
protection, operator interface  Data logging and fault simulation (requires InPower)
and isochronous governing. Standard control functions
Refer to document S-1568 for
Digital governing
more detailed information on the control.
 Integrated digital electronic isochronous governor
Major Features  Temperature dynamic governing
AmpSentry – Includes integral AmpSentry protection Digital voltage regulation
which provides a full range of alternator protection
 Integrated digital electronic voltage regulator.
functions that are matched to the alternator provided.
 3-phase, 4-wire Line-to-Line sensing.
Power management – Control function provides battery
monitoring and testing features and smart starting control  Configurable torque matching.
system. AmpSentry AC protection
Advanced control methodology – Three phase  AmpSentry protective relay.
sensing, full wave rectified voltage regulation, with a  Over current and short circuit shutdown.
PWM output for stable operation with all load types.
 Over current warning.
Communications interface – Control comes standard
with PCCNet and Modbus interface.  Single and three phase fault regulation.
Regulation compliant – Prototype tested: CE, UL and  Over and under voltage shutdown.
CSA compliant.  Over and under frequency shutdown.
Service – InPower™ PC-based service tool available for  Overload warning with alarm contact.
detailed diagnostics, setup, data logging and fault  Reverse power and reverse var shutdown.
simulation.
 Field overload.
Easily upgradeable – PowerCommand controls are
Engine protection
designed with common control interfaces.
 Battery voltage monitoring, protection and testing.
Reliable design – The control system is designed for
reliable operation in harsh environment.  Overspeed shutdown.
Multi-language support  Low oil pressure warning and shutdown.
Operator panel features  High/low coolant temperature warning or shutdown.
 128 x 128 pixels graphic LED backlight LCD  Low coolant level warning or shutdown.
 Auto, manual, start, stop, fault reset and lamp  Fail to start (overcrank) shutdown.
test/panel lamp switches.  Fail to crank shutdown.
 Alpha-numeric display with pushbuttons.  Cranking lockout.
 LED lamps indicating genset running, remote start, not  Sensor failure indication.
in auto, common shutdown, common warning, manual  Low fuel level warning or shutdown (optional).
run mode, auto mode and stop mode.
 Fuel-in-rupture-basin warning or shutdown (optional).
Alternator data
 Full authority electronic engine protection
 Line-to-Neutral and Line-to-Line AC volts.
Control functions
 3-phase AC current.
 Time delay start and cool down.
 Frequency.
 Real time clock for fault and event time stamping.
 kW, kVAr, power factor kVA (three phase and total).
 Exerciser clock and time of day start/stop.
Engine data
 Data logging.
 DC voltage.
 Cycle cranking.
 Engine speed.
 Load shed.
 Lube oil pressure and temperature.
 Configurable inputs and outputs (4).
 Coolant temperature.
 Remote emergency stop.
 Comprehensive FAE data (where applicable).

power.cummins.com
©2017 Cummins Inc. | EMERS-5888-EN.DOCX (01/18)
PowerCommand 3.3 control system Paralleling control functions
(MLD)  First Start Sensor System selects first genset to close to
bus.
The PowerCommand 3.3 has
the following additional features  Phase Lock Loop Synchronizer with voltage matching.
and benefits over the  Sync check relay.
PowerCommand 2.2. Refer to  Isochronous kW and kVAr load sharing.
document S-1570 for more  Load govern control for utility paralleling.
detailed information on the
control.  Extended Paralleling (baseload/peak shave) Mode.
Operator panel features  Digital power transfer control, for use with a breaker pair
to provide open transition, closed transition, ramping
 320 x 240 pixels graphic LED backlight LCD.
closed transition, peaking and base load functions.
 In addition to the 2.2 functions, the operator panel Masterless Load Demand (MLD)
displays paralleling breaker status and provides for direct
control of the paralleling breaker.  Load dependant start/stop of multi-gen system
 Predictive load input
 Run hour equalization
Ratings definitions
Emergency Standby Power (ESP): OPEN
Applicable for supplying power to varying electrical load for
the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with
ISO 8528. Fuel Stop power in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical load
for limited hours. Limited-Time Running Power (LTP) is in
accordance with ISO 8528.
Prime Power (PRP): ENCLOSED
Applicable for supplying power to varying electrical load for
unlimited hours. Prime Power (PRP) is in accordance with
ISO 8528. Ten percent overload capability is available in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant
electrical load for unlimited hours. Continuous Power (COP)
This outline drawing is to provide representative configuration
in accordance with ISO 8528, ISO 3046, AS 2789, details for Model series only.
DIN 6271 and BS 5514. See respective model data sheet for specific model outline
drawing number.
Do not use for installation design
Open Enclosed
Dim “A” Dim “B” Dim “C” Dry wt.* Wet wt.* Dim “A” Dim “B” Dim “C” Dry wt.* Wet wt.*
Model mm mm mm kg kg mm mm mm kg kg
C400 D5eB 3376 1500 2192 3884 4669 5093 1564 2446 4966 5751
C450 D5eB 3376 1500 2192 3884 4669 5093 1564 2446 4966 5751
C500 D5 3376 1500 2192 3879 4679 5093 1564 2446 4961 5761
C350 D6e 3376 1500 2192 3884 4669 5093 1564 2446 4966 5751
C400 D6e 3376 1500 2192 3884 4669 5093 1564 2446 4966 5751
C440 D6 3376 1500 2192 3879 4679 5093 1564 2446 4961 5761
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
Codes and standards
This generator set is designed in
This generator set conforms to former EU
facilities certified to ISO 9001 and Emissions
Stage II emission levels (50 Hz) and EPA
manufactured in facilities certified to compliance Tier 2 (60 Hz) emissions regulations.
ISO 9001 or ISO 9002.

This generator set is available with CE This generator set has been designed to
certification. ISO 8528 comply with ISO 8528 regulation.

For more information contact your local Cummins distributor


or visit power.cummins.com

©2018 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
EMERS-5888-EN.DOCX (01/18)