AHD-SAS 15 M12 / AHD-SAS 15 RJ45

Data station for 15 inputs for analog and binary sensors

• Flexible acquisition of measured values


and adaptation of the most common
sensor types with freely combinable
plug-in modules
• Processing of non-linear sensors and
tank curves with configurable Wide-ranging parameterization options allow the use
characteristic curves of any characteristic curve, so applications with tank
content measurements or other non-linear systems can
• Safe CAN bus communication (redun- be set up successfully.
dantly on request) allows decentralized
installation close to the sensor The following operating modes can be selected:
• Passive Mode:
• Useable as a stand-alone system In passive mode, AHD-SAS 15 operates without a
configuration stored in itself and sends only raw
sensor values to the system over the CAN bus.
The data stasion AHD-SAS 15 is used in decentralized
alarm and monitoring systems on ships and in This mode should be preferred for all projects that
industrial installations for recording, monitoring and include a data station AHD DPU 9 or a Panel PC.
processing binary and analog sensors. All common In this case, the raw data are processed by the
types of sensors can be directly connected and higher-level data stations. From the raw data
monitored. physical measured values are calculated, configured
limit values are monitored and alarms are generated
AHD-SAS 15 is usually connected over the CAN bus to
if the limits are exceeded. In addition, freely
other components of an AMS/AMCS system to which
configurable events can be processed with logical
the acquired data are provided for further processing
functions, which makes it easy to set up complex
or visualization. Two CAN busses are available for
PLC controls.
redundant communication. Two versions of the
• Active Mode:
physical CAN connections are available:
In active mode, AHD-SAS 15 operates as a stand-
alone device. This application is only useful for
• AHD-SAS 15 M12 with 2 x DeviceNet connectors
smaller monitoring systems implemented without
for the two CAN buses (item no. 11663V02)
an AHD-DPU 9 or a Panel PC. In this case, serial
• AHD-SAS 15 RJ45 with 2 x RJ45 connectors for
devices (e.g. AHD-PS 15, AHD-R101 or AHD-SW I/II)
each of the two CAN buses (item no. 16800)
can be connected directly to AHD-SAS 15 as
extensions.
For the acquisition of the different measurement types,
15 pluggable input modules are available, which are
installed according to the project-specific
configuration in slots provided for this purpose (see
the table below). AHD-SAS 15 can therefore very
flexibly be integrated into a specified or existing sensor
system.
Wiring diagram

Images and Dimensions

AHD-SAS 15 RJ45
Version with 2x2
RJ45 connections
(Item no.: 11663V02)
AHD-SAS 15 M12
Version with 2
DeviceNet connections
(Item no.: 16800)

Dimensions in mm

Table of input module types (I)


Code ¹) Selection (DeviceConfig) Application Result ²) Remark
B B Module "4..20mA" Sensor with current output Current Sensor is supplied via AHD-SAS 15
(1..40mA, 2pole) (2-pole) [mA]
C C Module "4..20mA" Sensor with current output Current Sensor is supplied via separate wires
(1..40mA, 4pole) (4-pole) [mA]
E E Module "Binary" Sensor with switch contact or Binary value Switched plus (same potential as
(Contact Plus Switched) ³) push button (plus signal) [0 or 1] system)
F F Module "Binary" Sensor with switch contact or Binary value Potential-free contact, switched
(Contact Potential Free) ³) push button (potential-free) [0 or 1] minus (same potential as system)
G (Type 1) G Module "PT100" PT100 temperature sensor Temperature Without sensor-fault monitoring
(-80…+220°C) ⁴) (max. 220°C / 2-pole) [°C]
G (Type 2) G Module Type2 “PT100” PT100 temperature sensor Temperature With sensor-fault monitoring
(-80…+220°C incl. SF) ⁴) ⁵) (max. 220°C / 2-pole) [°C]
G (Type 3) G Module Type3 “Resistor” Resistance sensor with free Resistance Specify characteristic curve
(68...183 Ohm) characteristic curve (max. [Ohm]
183 Ohms)
H (Type 1) H Module "PT1000" PT1000 temperature sensor Temperature Without sensor-fault monitoring
(-80…+220°C) ⁴) (max. 220°C / 2-pole) [°C]
H (Type 2) H Module Type2 “PT1000” PT1000 temperature sensor Temperature With sensor-fault monitoring
(-80…+220°C incl. SF) ⁴) ⁵) (max. 220°C / 2-pole) [°C]
H (Type 3) H Module Type3 “Resistor” Resistance sensor with free Resistance Specify „Characteristic Curve“
(680...1830 Ohm) characteristic curve [Ohm]
(max. 1830 Ohms)
I I Module "NiCrNi" NiCrNi temperature sensor Temperature Define channel for compensation of
(0..950°C) ⁴) (max. 950°C) [°C] ambient temperature!
J J Module "0..5V" Sensor with voltage output Voltage Measurement against system ground
(0..6V) (max. 6 volts) [V]
K K Module "0..10V" Sensor with voltage output Voltage Measurement against system ground
(0..12V) (max. 12 volts) [V]
L L Module "0..30V" Sensor with voltage output Voltage (Not available in new systems,
(0..36V) (max. 36 volts) [V] replaced by T-module)
M M Module "Racor/Parker" Resistance sensor Raw Value ⁶) Water detection (recommended
(10..100kOhm) (Manufact. Racor / Parker) [0..4095] settings: Analogue, "Limit AL min" =
2000) ⁷)
Table of input module types (II)
Code ¹) Selection (DeviceConfig) Applicatio Result ²) Remark
N N Module "Frequency" (0..8000Hz) Sensor with Frequency signal Frequency Galvanically isolated input
(max. 8000 Hz) [Hz] (e.g. Speed Pick-Up)
O Module "Blank" Place holder Raw Value ⁶) Without function
(No function) (no sensor) [0..4095]
P P Module "4..20mA" (1..40mA, Sensor with current output Current Galvanically isolated input
2pol., Galv. Isol.) (2-pole) [mA]
R (Typ 1) R Module "PT100" PT100 temperature sensor Temperature Without sensor-fault monitoring
(-80..+650°C) ⁴) (max. 650°C / 2-pole) [°C]
R (Typ 2) R Modul Type2 “PT100” PT100 temperature sensor Temperature With sensor-fault monitoring
(-80..+650°C incl. SF) ⁴) ⁵) (max. 650°C / 2-pole) [°C]
R (Typ 3) R Modul Type3 “Resistor” Resistance sensor with free Resistance Specify characteristic curve
(68...330 Ohm) characteristic (max. 330 Ohm) [Ohm]
S (Typ 1) S Module "PT1000" PT1000 temperature sensor Temperature Without sensor-fault monitoring
(-80..+650°C) ⁴) (max. 650°C / 2-pole) [°C]
S (Typ 2) S Modul Type2 “PT1000” PT1000 temperature sensor Temperature With sensor-fault monitoring
(-80..+650°C incl. SF) ⁴) ⁵) (max. 650°C / 2-pole) [°C]
S (Typ 3) S Modul Type3 “Resistor” Resistance sensor via free Resistance Specify characteristic curve
(680...3300 Ohm) characteristic (max. 3300Ohm) [Ohm]
T T Module "0..44V" Sensor with voltage output Voltage Measurement to system ground
(0..44.9V) (max. 44.9 Volts) [V] (50 mA fuse recommended)
U U Module "15..200 Ohm" General resistance sensor (max. Resistance Galvanically isolated input
(0..400Ohm galv. isol.) 400 Ohm) [Ohm] (specified from 15 to 200 Ohm)
V V Module "8..44V" Sensor with voltage output Voltage Galvanically isolated input
(7..44.9V galv. isol.) (max. 44.9 Volts) [V] (min. voltage = 7 Volt)
¹) The typical sensor or measuring range is indicated. The values in brackets contain the maximum detection range and additional information, if applicable.
The modules "G", "H", "R" or "S" each allow 3 different measuring methods (Type1...Type3). AHD-SAS 15 in active mode can only use method "Type1"!
²) The output variable is calculated depending on the selected input module. All further processing steps (e.g. characteristic curve definition, range specifications or
limit value comparison) are based on this.
³) Function without wire break detection. If fault monitoring is required for binary sensors, this channel must be processed as analog.
⁴) The calculation of the temperature value is done automatically using internal characteristics. An additional specification under "Characteristic Curve" is not required.
⁵) Function with sensor fault detection (wire break and short circuit)
⁶) Output = internal raw value in mV
⁷) Limit value comparison with raw value: alarm is triggered at water detection (Rsens < 47kOhm)

Technical Data
Mechanical Data Inputs 15 x slot for binary and analog inputs,
Dimension W x H x D 209 x 125 x 76 mm free and individually configurable with
Min. installation Height 116 mm input modules according to project-
for CAN Cable (M12) specific configuration
Weight Appr. 0.7 kg 2 x serial (opto-coupler) from binary
Environmental Data data stations AHD-PS 15/30/47
Outputs 4 x potential-free relay contact,
Operating Temperature -30°C … +70°C
30 V DC / 2 A max: (freely
Storage Temperature -50°C … +85°C configurable)
Degree of Protection IP 20 2 x serial (opto-coupler) for
Required Distance to Standard magnetic compass: 0.40 m relay station AHD-R101 or
Compass Steering magnetic compass: 0.50 m Spill Warning module AHD SW I/II
Electrical Data Installation
Power Supply 24 V DC (+30% / -25%) Module carrier Installation directly on DIN rails
Current Consumption Max. 700 mA (24 V DC) housing TS 32 oder TS 35
Interfaces 2 x CAN-Bus on terminal strip Approvals
with DeviceNet connector (M12) Classification DNV, CRS, LR, RS
(item no. 11663V02) or Societies
RJ45 In/Out plugs Item Numbers
(item no. 16800) AHD-SAS 15 M12 11663V02
1 x RS232 (Sub-D9), internal use only AHD-SAS 15 RJ45 16800

Böning Automationstechnologie GmbH & Co. KG • Am Steenöver 4 • D-27777 Ganderkesee • E-Mail:info@boening.com • www.boening.com
PaB-1177 V18 Rev.: 2022-02-14, approved: 2021/09/07, HeA •
The manufacturer accepts no liability for possible errors contained in descriptions and diagrams.