Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Mks Series 10

Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

DATA SHEET KP111E3G COOLING UNITS SERIES 10 SLIM



Quick mounting.
No condensation


Filter is optional for severe environments.
ALUZINC structure: rust free for more
WALL MOUNTED MODEL 1100 W
 Quick and simple maintenance than 600 hours in saline fog.
 Designed for working with no filter.  Extra Slim(76mm) - High Power.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP1111TEI 1~ 230V 50/60Hz 1+I

MKP1111REI 2~ 400V 50/60Hz 1+I

MKP1116TEI 1~ 230V 50/60Hz 6+I

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


Versions:
(V) 1 = Electromechanical thermostat + alarm signal.
(V) 2 = Electromechanical thermostat + alarm signal + door open checking device.
(V) 3 = Electronic thermostat + display + alarm signal + door open checking device.
(V) 4 = Electronic thermostat + display + alarm signal.
(V) 6 = Electromechanical thermostat + alarm signal + remote control.
(V) I = Recessed mounting.

Filter kit See reference sheet


Available Spare filter set See reference sheet
accessories Dissipator of condensation
432

10
22
I rated I start-up Protection = =
Voltage 50/60 Hz 50/60 Hz fuse
MCA

90
Operating voltage 1~ 230V 3,8/4,0 A 14,8/17 A T6 A
±10%
2~ 400V 2,2/2,3 A 8,5/10,5 A T6 A Ø6

350
Technical data Frequency 50/60 Hz
A35-A35 1,1 / 1,2 kW [ 3754 / 4095 Btu/h ]
Cooling power

350
A50-A35 0,85 / 0,9 kW [ 2900 / 3071 Btu/h ]

1580
= =
A35-A35 0,87 / 0,92 kW
Absorbed electrical power
A50-A35 0,99 / 1,1 kW 350

Energy efficiecy EER A35-A35 1,3 / 1,3


ext. cabinet 860 / 900 m3/h
Fan flow rate
int. cabinet 570 / 620 m3/h
350

Cooling gas R134a


Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20÷55 / 20÷50 °C [68÷131 / 68÷122 F]
setting 35°C [95 F] int. cabinet 20÷50 / 20÷45 °C [68÷122 / 68÷113 F] 300 10
= =
Noise level 67 dB(A) 450
= =
Weight 42 kg [ 92,6 lb ]
Continuous duty 100% 76
20
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions WxHxD 495x1640x162 mm [ 19,49x64,57x6,38 in ] 76
Installation environment Indoor
1570

1800 1800
1285
1265

Ti [ C ] Ti [ C ]

1600 1600
50
1400 50 1400 45
742
655
Pf [ W ]

Pf [ W ]

45 40
1200 40 1200
35
35
30
1000 1000
30
25
25
800 800 20
20 21 141
600 600 495 162
400 400
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS s.r.l. - Società unipersonale - Ver.: 10/03/2009


Via Vernea, 143 — 10042 Nichelino(TO) — ITALIA
 +39— 011 — 68.98.511  +39 — 011 — 68.98.501
info@mksclima.com www.mksclima.com
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP271L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2700 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP2717T*$ 1~ 230V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified.
(*) U = cURus certified.

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control
I rated I start-up Protection
Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 6,4/7,4 A 24,2/28,2 A T16 A 9,7 A

Technical data Frequency 50/60 Hz


A35-A35 2,7 / 2,9 kW [ 9213 / 9895 Btu/h ]
Cooling power
A50-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
A35-A35 1,2 / 1,4 kW
Absorbed electrical power
A50-A35 1,4 / 1,7 kW
Energy efficiecy EER A35-A35 2,3 / 2,1
ext. cabinet 1200 / 1340 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 57 kg [ 125,7 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

4400 4400

4000 Ti [ C 4000 Ti [ C

3600 3600 50
50
45
3200 45 3200
Pf [ W ]

40
40
2800 2800 35
35
2400 30 30
2400
25 25 Version = O S I
2000
20
2000
20
A(Inside enclosure) = 29 mm 81 141
1600 B(Outside enclosure) = 133 mm 81 21
1600
1200
1200
20 25 30 35 40 45 50 55
20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz
Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP271M2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2700 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
3~ 400V 50 Hz cURus
MKP2717C*$ 7
3~ 460V 60 Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

Voltage I rated I start-up Protection MCA


Operating voltage
±10% 3~ 400V 50 Hz 3A 9A T8 A
3~ 460V 60 Hz 3,5 A 10,6 A T8 A 4,8 A

Technical data Frequency 50/60 Hz


A35-A35 2,7 / 2,9 kW [ 9213 / 9895 Btu/h ]
Cooling power
A50-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
A35-A35 1,7 / 2,0 kW
Absorbed electrical power
A50-A35 2,0 / 2,3 kW
Energy efficiecy EER A35-A35 1,6 / 1,5
ext. cabinet 1200 / 1340 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 60 kg [ 132,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

4400 4400

4000 Ti [ C 4000 Ti [ C

3600 3600 50
50
45
3200 45 3200
Pf [ W ]

40
40
2800 2800 35
35
2400 30 2400
30 Version = O S I
2000
25 25 A(Inside enclosure) = 29 mm 81 141
2000
20 20 B(Outside enclosure) = 133 mm 81 21
1600
1600
1200
1200
20 25 30 35 40 45 50 55
20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz
Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP271L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2700 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP2717T*$ 1~ 230V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified.
(*) U = cURus certified.

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control
I rated I start-up Protection
Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 6,4/7,4 A 24,2/28,2 A T16 A 9,7 A

Technical data Frequency 50/60 Hz


A35-A35 2,7 / 2,9 kW [ 9213 / 9895 Btu/h ]
Cooling power
A50-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
A35-A35 1,2 / 1,4 kW
Absorbed electrical power
A50-A35 1,4 / 1,7 kW
Energy efficiecy EER A35-A35 2,3 / 2,1
ext. cabinet 1200 / 1340 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 57 kg [ 125,7 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

4400 4400

4000 Ti [ C 4000 Ti [ C

3600 3600 50
50
45
3200 45 3200
Pf [ W ]

40
40
2800 2800 35
35
2400 30 30
2400
25 25 Version = O S I
2000
20
2000
20
A(Inside enclosure) = 29 mm 81 141
1600 B(Outside enclosure) = 133 mm 81 21
1600
1200
1200
20 25 30 35 40 45 50 55
20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz
Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP191M2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2200 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.
Voltage Version Certification
Models Compliance
Frequency (V) on demand
3~ 400V 50 Hz cURus
MKP2017C*$ 7
3~ 460V 60 Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

Protection
Voltage I rated I start-up
fuse
MCA
Operating voltage
±10% 3~ 400V 50 Hz 2,6 A 7,9 A T8 A
3~ 460V 60 Hz 3,2 A 9,5 A T8 A 4,5 A

Technical data Frequency 50/60 Hz


A35-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
Cooling power
A50-A35 1,8 / 2,0 kW [ 6142 / 6824 Btu/h ]
A35-A35 1,5 / 1,8 kW
Absorbed electrical power
A50-A35 1,8 / 2,1 kW
Energy efficiecy EER A35-A35 1,5 / 1,3
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 54 kg [ 119 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

3400 3400
Ti [ C Ti [ C

3000 3000 50
50
45
2600 45 2600
Pf [ W ]

40
40
35
[

2200 35 2200
30
30 Version = O S I
1800 1800 25
25 A(Inside enclosure) = 29 mm 81 141
20 20 B(Outside enclosure) = 133 mm 81 21
1400 1400

1000 1000
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP191L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2200 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP2017T*$ 1~ 230V 50/60Hz 7 cURus
MKP2017P*$ 1~ 115V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified.
(*) U = cURus certified.

Filter kit / Spare filter set See reference sheet

Available Kit Display


accessories Dissipator of condensation
Kit Remote Control

I rated I start-up Protection


Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 5,8/6,9 A 22,2/26,2 A T16 A 9,1 A
1~ 115V 11,6/13,8 A 44,4/52,4 A T25 A 18,2 A

Technical data Frequency 50/60 Hz


A35-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
Cooling power
A50-A35 1,8 / 2,0 kW [ 6142 / 6824 Btu/h ]
A35-A35 1,1 / 1,3 kW
Absorbed electrical power
A50-A35 1,3 / 1,5 kW
Energy efficiecy EER A35-A35 2,0 / 1,8
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 50 kg [ 110,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

3400 3400
Ti [ C Ti [ C

3000 3000 50
50
45
2600 45 2600
Pf [ W ]

40
40
35
[

2200 35 2200
30 Version = O S I
30
1800 25 A(Inside enclosure) = 29 mm 81 141
25 1800
20
B(Outside enclosure) = 133 mm 81 21
20
1400 1400

1000 1000
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP191M2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2200 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.
Voltage Version Certification
Models Compliance
Frequency (V) on demand
3~ 400V 50 Hz cURus
MKP2017C*$ 7
3~ 460V 60 Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

Protection
Voltage I rated I start-up
fuse
MCA
Operating voltage
±10% 3~ 400V 50 Hz 2,6 A 7,9 A T8 A
3~ 460V 60 Hz 3,2 A 9,5 A T8 A 4,5 A

Technical data Frequency 50/60 Hz


A35-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
Cooling power
A50-A35 1,8 / 2,0 kW [ 6142 / 6824 Btu/h ]
A35-A35 1,5 / 1,8 kW
Absorbed electrical power
A50-A35 1,8 / 2,1 kW
Energy efficiecy EER A35-A35 1,5 / 1,3
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 54 kg [ 119 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

3400 3400
Ti [ C Ti [ C

3000 3000 50
50
45
2600 45 2600
Pf [ W ]

40
40
35
[

2200 35 2200
30
30 Version = O S I
1800 1800 25
25 A(Inside enclosure) = 29 mm 81 141
20 20 B(Outside enclosure) = 133 mm 81 21
1400 1400

1000 1000
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP191L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2200 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP2017T*$ 1~ 230V 50/60Hz 7 cURus
MKP2017P*$ 1~ 115V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified.
(*) U = cURus certified.

Filter kit / Spare filter set See reference sheet

Available Kit Display


accessories Dissipator of condensation
Kit Remote Control

I rated I start-up Protection


Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 5,8/6,9 A 22,2/26,2 A T16 A 9,1 A
1~ 115V 11,6/13,8 A 44,4/52,4 A T25 A 18,2 A

Technical data Frequency 50/60 Hz


A35-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
Cooling power
A50-A35 1,8 / 2,0 kW [ 6142 / 6824 Btu/h ]
A35-A35 1,1 / 1,3 kW
Absorbed electrical power
A50-A35 1,3 / 1,5 kW
Energy efficiecy EER A35-A35 2,0 / 1,8
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 50 kg [ 110,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

3400 3400
Ti [ C Ti [ C

3000 3000 50
50
45
2600 45 2600
Pf [ W ]

40
40
35
[

2200 35 2200
30 Version = O S I
30
1800 25 A(Inside enclosure) = 29 mm 81 141
25 1800
20
B(Outside enclosure) = 133 mm 81 21
20
1400 1400

1000 1000
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP151M1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1500 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
3~ 400V 50Hz cURus
MKP1517C*$ 7
3~460V 60Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet

Available Kit Display


accessories
Dissipator of condensation
Kit Remote Control
Protection
Voltage I rated I start-up
fuse
MCA
Operating voltage
±10% 3~ 400V 50Hz 2,4 A 7,2 A T8 A
3~ 460V 60Hz 3,0 A 9,0 A T8 A 4,2 A

Technical data Frequency 50/60 Hz


A35-A35 1,5 / 1,6 kW [ 5118 / 5459 Btu/h ]
Cooling power
A50-A35 1,2 / 1,3 kW [ 4094 / 4435 Btu/h ]
A35-A35 1,3 / 1,5 kW
Absorbed electrical power
A50-A35 1,5 / 1,8 kW
Energy efficiecy EER A35-A35 1,2 / 1,1
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 860 / 900 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 50 kg [ 110,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

2200 Ti [ C 2200 Ti [ C ]

50
50
1800 1800 45
45
Pf [ W ]

40
40
35
35
1400 1400 30
30
25 25 Version = O S I
1000 20 1000 20 A(Inside enclosure) = 29 mm 81 141
B(Outside enclosure) = 133 mm 81 21
600 600
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP151L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1500 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP1517T*$ 1~ 230V 50/60Hz 7 cURus

MKP1517P*$ 1~ 115V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control
I rated I start-up Protection
Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 4,4/5,1 A 16,7/19,2 A T12 A 6,8 A

1~ 115V 8,8/10,2 A 33,4/38,4 A T20 A 13,6 A

Technical data Frequency 50/60 Hz


A35-A35 1,5 / 1,6 kW [ 5118 / 5459 Btu/h ]
Cooling power
A50-A35 1,2 / 1,3 kW [ 4094 / 4435 Btu/h ]
A35-A35 0,83 / 0,95 Kw
Absorbed electrical power
A50-A35 0,95 / 1,1 kW
Energy efficiecy EER A35-A35 1,9 / 1,8
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 860 / 900 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 49 kg [ 108 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

2200 Ti [ C 2200 Ti [ C ]

50
50
1800 1800 45
45
Pf [ W ]

40
40
35
35
1400 1400 30
30
25 25 Version = O S I
1000 20 1000 20 A(Inside enclosure) = 29 mm 81 141
B(Outside enclosure) = 133 mm 81 21
600 600
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP151M1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1500 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
3~ 400V 50Hz cURus
MKP1517C*$ 7
3~460V 60Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting.
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet

Available Kit Display


accessories
Dissipator of condensation
Kit Remote Control
Protection
Voltage I rated I start-up
fuse
MCA
Operating voltage
±10% 3~ 400V 50Hz 2,4 A 7,2 A T8 A
3~ 460V 60Hz 3,0 A 9,0 A T8 A 4,2 A

Technical data Frequency 50/60 Hz


A35-A35 1,5 / 1,6 kW [ 5118 / 5459 Btu/h ]
Cooling power
A50-A35 1,2 / 1,3 kW [ 4094 / 4435 Btu/h ]
A35-A35 1,3 / 1,5 kW
Absorbed electrical power
A50-A35 1,5 / 1,8 kW
Energy efficiecy EER A35-A35 1,2 / 1,1
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 860 / 900 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 50 kg [ 110,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

2200 Ti [ C 2200 Ti [ C ]

50
50
1800 1800 45
45
Pf [ W ]

40
40
35
35
1400 1400 30
30
25 25 Version = O S I
1000 20 1000 20 A(Inside enclosure) = 29 mm 81 141
B(Outside enclosure) = 133 mm 81 21
600 600
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP151L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1500 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP1517T*$ 1~ 230V 50/60Hz 7 cURus

MKP1517P*$ 1~ 115V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control
I rated I start-up Protection
Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 4,4/5,1 A 16,7/19,2 A T12 A 6,8 A

1~ 115V 8,8/10,2 A 33,4/38,4 A T20 A 13,6 A

Technical data Frequency 50/60 Hz


A35-A35 1,5 / 1,6 kW [ 5118 / 5459 Btu/h ]
Cooling power
A50-A35 1,2 / 1,3 kW [ 4094 / 4435 Btu/h ]
A35-A35 0,83 / 0,95 Kw
Absorbed electrical power
A50-A35 0,95 / 1,1 kW
Energy efficiecy EER A35-A35 1,9 / 1,8
ext. cabinet 885 / 990 m3/h
Fan flow rate
int. cabinet 860 / 900 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 49 kg [ 108 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

2200 Ti [ C 2200 Ti [ C ]

50
50
1800 1800 45
45
Pf [ W ]

40
40
35
35
1400 1400 30
30
25 25 Version = O S I
1000 20 1000 20 A(Inside enclosure) = 29 mm 81 141
B(Outside enclosure) = 133 mm 81 21
600 600
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP111M2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1100 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
cURus
3~ 400V 50 Hz
MKP1117C*$ 7
3~ 460V 60 Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

Voltage I rated I start-up Protection MCA


Operating voltage
±10% 3~ 400V 50 Hz 2,3 A 6,9 A T8 A
3~ 460V 60 Hz 2,9 A 8,5 A T8 A 4A

Technical data Frequency 50/60 Hz


A35-A35 1,1 / 1,2 kW [ 3754 / 4095 Btu/h ]
Cooling power
A50-A35 0,85 / 0,9 Kw [ 2900 / 3071 Btu/h ]
A35-A35 1,2 / 1,4 kW
Absorbed electrical power
A50-A35 1,4 / 1,7 kW
Energy efficiecy EER A35-A35 0,9 / 0,8
ext. cabinet 860 / 900 m3/h
Fan flow rate
int. cabinet 570 / 620 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 50 kg [ 110,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

1800 1800
Ti [ C ] Ti [ C ]
1600 1600
50
1400 50 1400 45
Pf [ W ]

45 40
1200 40 1200
35
35
30
1000 1000
30
25 Version = O S I
25
800 800 20 A(Inside enclosure) = 29 mm 81 141
20
600 600
B(Outside enclosure) = 133 mm 81 21

400 400
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP111L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1100 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP1117T*$ 1~ 230V 50/60Hz 7 cURus

MKP1117P*$ 1~ 115V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

I rated I start-up Protection


Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 2,9/3,5 A 11/13,5 A T8 A 4,8 A
1~ 115V 5,8/7 A 22/27 A T16 A 9,6 A

Technical data Frequency 50/60 Hz


A35-A35 1,1 / 1,2 kW [ 3754 / 4095 Btu/h ]
Cooling power
A50-A35 0,85 / 0,9 kW [ 2900 / 3071 Btu/h ]
A35-A35 0,6 / 0,71 KW
Absorbed electrical power
A50-A35 0,71 / 0,85 kW
Energy efficiecy EER A35-A35 1,8 / 1,7
ext. cabinet 860 / 900 m3/h
Fan flow rate
int. cabinet 570 / 620 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 46 kg [ 101,4 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

1800 1800
Ti [ C ] Ti [ C ]
1600 1600
50
1400 50 1400 45
Pf [ W ]

45 40
1200 40 1200
35
35
1000 1000 30 Version = O S I
30
25
25 A(Inside enclosure) = 29 mm 81 141
800 800 20
20 B(Outside enclosure) = 133 mm 81 21
600 600

400 400
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP111M2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1100 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
cURus
3~ 400V 50 Hz
MKP1117C*$ 7
3~ 460V 60 Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

Voltage I rated I start-up Protection MCA


Operating voltage
±10% 3~ 400V 50 Hz 2,3 A 6,9 A T8 A
3~ 460V 60 Hz 2,9 A 8,5 A T8 A 4A

Technical data Frequency 50/60 Hz


A35-A35 1,1 / 1,2 kW [ 3754 / 4095 Btu/h ]
Cooling power
A50-A35 0,85 / 0,9 Kw [ 2900 / 3071 Btu/h ]
A35-A35 1,2 / 1,4 kW
Absorbed electrical power
A50-A35 1,4 / 1,7 kW
Energy efficiecy EER A35-A35 0,9 / 0,8
ext. cabinet 860 / 900 m3/h
Fan flow rate
int. cabinet 570 / 620 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 50 kg [ 110,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

1800 1800
Ti [ C ] Ti [ C ]
1600 1600
50
1400 50 1400 45
Pf [ W ]

45 40
1200 40 1200
35
35
30
1000 1000
30
25 Version = O S I
25
800 800 20 A(Inside enclosure) = 29 mm 81 141
20
600 600
B(Outside enclosure) = 133 mm 81 21

400 400
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP111L2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 1100 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
MKP1117T*$ 1~ 230V 50/60Hz 7 cURus

MKP1117P*$ 1~ 115V 50/60Hz 7 cURus

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


(V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

I rated I start-up Protection


Voltage 50/60 Hz 50/60 Hz fuse
MCA
Operating voltage
±10% 1~ 230V 2,9/3,5 A 11/13,5 A T8 A 4,8 A
1~ 115V 5,8/7 A 22/27 A T16 A 9,6 A

Technical data Frequency 50/60 Hz


A35-A35 1,1 / 1,2 kW [ 3754 / 4095 Btu/h ]
Cooling power
A50-A35 0,85 / 0,9 kW [ 2900 / 3071 Btu/h ]
A35-A35 0,6 / 0,71 KW
Absorbed electrical power
A50-A35 0,71 / 0,85 kW
Energy efficiecy EER A35-A35 1,8 / 1,7
ext. cabinet 860 / 900 m3/h
Fan flow rate
int. cabinet 570 / 620 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 67 dB(A)
Weight 46 kg [ 101,4 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

1800 1800
Ti [ C ] Ti [ C ]
1600 1600
50
1400 50 1400 45
Pf [ W ]

45 40
1200 40 1200
35
35
1000 1000 30 Version = O S I
30
25
25 A(Inside enclosure) = 29 mm 81 141
800 800 20
20 B(Outside enclosure) = 133 mm 81 21
600 600

400 400
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP11-27-10E1G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Totally external mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL TOTAL EXTERNAL
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Version Certification
Models Compliance
(V) on demand
cURus
MKP (11-27) 17T*$ 7
cURus
MKP (11-27) 17P*$ 7
cURus
MKP (11-27) 17C*$ 7

FOR THECNICAL DATA SEE DATA SHEETS OF DIFFERENT MODEL.

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.

(V) 7 = Electronic thermostat + alarm signal + door open checking device.


($) E = Total External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

CUT-OUT FOR
EXTERNAL MOUNTING
-E-
RECESSED MOUNTING
EXTERNAL MOUNTING - O - Outside
-E- - S - Semi 200
- I - Inside 57 = = 2xØ5.2 40

460 165 495 162

260
340
= =

300
1605 mm

1570

1635

200
1605

340
= =
655

B
DRAIN DRAIN A
40

Version = O S I Ø5.2
A (INside enclosure) 29 81 141

B (OUTside enclosure) 133 81 21


460
= =

1 mm = 0.03937 ''
1 '' = 25.4 mm

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 10/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.
DATA SHEET KP271M2G COOLING UNITS SERIES 10 SLIM


Quick mounting.
Semi-recessed and recessed mounting.


Designed for working with no filter.
Filter is optional for severe environments.
WALL MOUNTED MODEL 2700 W
 No condensation.  ALUZINC structure: rust free for more
 Quick and simple maintenance. than 600 hours in saline fog.

Voltage Version Certification


Models Compliance
Frequency (V) on demand
3~ 400V 50 Hz cURus
MKP2717C*$ 7
3~ 460V 60 Hz

On demand: Different voltage; Stainless steel(AISI304) cover; Special painting.


V) 7 = Electronic thermostat + alarm signal + door open checking device.
($) I = Recessed mounting
($) S = Semi-recessed mounting.
($) O = External mounting.
(*) H = not cURus certified
(*) U = cURus certified

Filter kit / Spare filter set See reference sheet


Available Kit Display
accessories Dissipator of condensation
Kit Remote Control

Voltage I rated I start-up Protection MCA


Operating voltage
±10% 3~ 400V 50 Hz 3A 9A T8 A
3~ 460V 60 Hz 3,5 A 10,6 A T8 A 4,8 A

Technical data Frequency 50/60 Hz


A35-A35 2,7 / 2,9 kW [ 9213 / 9895 Btu/h ]
Cooling power
A50-A35 2,2 / 2,4 kW [ 7507 / 8189 Btu/h ]
A35-A35 1,7 / 2,0 kW
Absorbed electrical power
A50-A35 2,0 / 2,3 kW
Energy efficiecy EER A35-A35 1,6 / 1,5
ext. cabinet 1200 / 1340 m3/h
Fan flow rate
int. cabinet 885 / 990 m3/h
Cooling gas R134a
Max pressure 2,4 MPa [ 348 psi ]
Temperature range: ext. cabinet 20 ÷ 55 °C [68 ÷ 131 F]
setting 35°C [95 F] int. cabinet 20 ÷ 50 °C [68 ÷ 122 F]
Noise level 69 dB(A)
Weight 60 kg [ 132,2 lb ]
Continuous duty 100%
ext. Cabinet IP 34
Protection standard
int. cabinet IP 55
Standard colour Embossed RAL 7035
Power connection Connector
Dimensions Recessed / Semi-
recessed and External WxHxD 495x1640x162 mm [19,49x64,57x6,38 in]
mounting
Installation environment Indoor

4400 4400

4000 Ti [ C 4000 Ti [ C

3600 3600 50
50
45
3200 45 3200
Pf [ W ]

40
40
2800 2800 35
35
2400 30 2400
30 Version = O S I
2000
25 25 A(Inside enclosure) = 29 mm 81 141
2000
20 20 B(Outside enclosure) = 133 mm 81 21
1600
1600
1200
1200
20 25 30 35 40 45 50 55
20 25 30 35 40 45 50 55
Te [ °C ] f = 50Hz
Te [ °C ] f = 60Hz

MKS S.r.l. - Società unipersonale - Tel.: +39 011 6898511 Ver.: 13/06/2011
E-mail: info@mksclima.com Web: www.mksclima.com
WE RESERVE THE RIGHT TO MAKE TECHNICAL MODIFICATIONS.