Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Indoor Error
03 Remote controller error Between Indoor and Remote controller communication poorly
05 Communcation error between in and out Between Indoor and Outdoor communication poorly
1
Outdoor Error
2
Display
Title Cause of error Check point & Normal condition
code
• Open / Short
Indoor air sensor • Soldered poorly Normal resistor : 10KΩ/ at 25°C (Unplugged)
01
• Internal circuit error Normal voltage : DC 2.5V / at 25°C (plugged)
• Open / Short
Normal resistor : 5KΩ/ at 25°C (Unplugged)
02 Indoor inlet pipe sensor • Soldered poorly
Normal voltage : DC 2.5V / at 25°C (plugged)
• Internal circuit error
• Open / Short
Normal resistor : 5KΩ/ at 25°C (Unplugged)
06 Indoor outlet pipe sensor • Soldered poorly
Normal voltage : DC 2.5V / at 25°C (plugged)
• Internal circuit error
10k 2.5Vdc
Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor.
3. If the resistance of the sensor is 10KΩ/ 5KΩ at 25°C, then sensor is normal.
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. ¡ Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ¡ Repair or Change the PCB.
3
Display
Title Cause of error Check point & Normal condition
code
• Connection of wire
Communication • Open / Short • Main PCB Volt. DC12V
03
Wired R/C • Wrong connection • Noise interference
12Vdc 12Vdc
V V
Check Point
1. Check the wire connection. (Open / Short) ¡ Repair the connection
2. Check the soldering state of connector. (Soldered poorly) ¡ Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V) ¡ Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) ¡ Adjust the state of installation
4
Display
Title Cause of error Check point & Normal condition
code
• The connection of wire(Drain pump/ Float switch)
Drain pump • Float switch Open. • Drain pump power input. (230V)
04
/ Float switch (Normal : short) • Drain tube installation.
• Indoor unit installation. (Inclination)
CN Float
Check Point
1. Check the wire connection. (Open, Soldered poorly) ¡ Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) ¡ Check the float switch.
3. Check the level of water
4. Check the volt. Of Drain pump power supply. (AC 230V) ¡ Repair or Change the main PCB.
5
Display
Title Cause of error Check point & Normal condition
code
Check Point
1. Check another indoor model operation mode
2. Operating the same mode with the first operated indoor unit
3. Clearing the "CH07"
Press the on/off button or mode change button and matching the indoor unit mode same as the first operated
indoor unit
6
Display
Title Cause of error Check point & Normal condition
code
Check Point
1. Check the EEPROM Direction
2. If the EEPROM value & the Program value are not matched, the Code is Displayed
3. After Checking the connection and Insertion, replace the PCB or Option PCB
7
Display
Title Cause of error Check point & Normal condition
code
Yellow White
Blue Black Red
Fan motor
connector
Tester
Check Point
Check the PCB during the Power on
1. Check the Voltage Red line to Black line
¡ The Voltage is about [input voltage x 1.414]
¡ if the Voltage does not come with the above Voltage,
¡ Check the power input
¡ Replace the PCB & Motor
2. Check the Voltage Black line to White
¡ the Voltage is DC 15V
¡ Check the Power input
¡ Replace the motor
Check the Motor
1. Check the shaft
¡ if the shaft is not turn smoothly, the Motor Power IC is defected
¡ replace the motor
2. Check the motor resistance(if the shaft is turn smoothly, check the resistance)
¡ Check Red line to Black line, Blue line to Black line
¡ The resistance should infinite
¡ replace the motor
8
Display
Title Cause of error Check point & Normal condition
code
• Compressor blocked
• Check compressor constraint
• Disconnection/shortcircuit
• Check compressor wire open/short
inside compressor
DC Peak • Check compressor insulation damage
21 • Over load operation
(IPM Fault) • Check outdoor fan constraint / screened / flow
(Outdoor fan constraint,
structure
screened, blocked)
• Check if IPM burned
• Burned parts inside PCB
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
Yes
Yes
9
Display
Title Cause of error Check point & Normal condition
code
• Input voltage error(low
voltage) • Check input voltage
CT 2 • Over load operation • Check outdoor fan canstraint / screened / flow
22
(Max CT) (Outdoor fan constraint, structure
screened, blocked) • Check PCB current sensor parts
• Burned parts inside PCB
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
10
Display
Title Cause of error Check point & Normal condition
code
• DC Link Voltage is above
420Vdc • Check Input Voltage
23 DC Link High / Low Volt
• DC Link Voltage is below • Check PCB DC Link voltage sensor parts
140Vdc
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
11
Display
Title Cause of error Check point & Normal condition
code
Yes
Yes
Yes
Is high pressure
more than 4200kPa No
or low pressure less than 30kPa Replace PCB
at manifold gauge?
Yes
12
Display
Title Cause of error Check point & Normal condition
code
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
Check
No R~S/S~T/T~R phase voltage is 220V 10%
Is input voltage normal?
→ Check connection condition and wiring if power is
abnormal
Yes
Is main
No Check connection between main PCB assembly and bridge
PCB assembly power
diode(misconnection, disconnection)
connection normal?
→ wiring again if abnormality found
Yes
No
Monitoring PCB LED Replace main PCB assembly.
display error
Yes
13
Display
Title Cause of error Check point & Normal condition
code
• Compressor Locking
• Check compressor locking
• Overload operation
• Compressor wire open/short
(Outdoor fan constraint,
• Check compressor insulation damage
DC Compressor Position screened, blocked)
26 • Check outdoor fan constraint / screened / flow
Error • Burned parts inside
structure
PCB(IPM)
• Check if IMP burned (refer to CH21)
• Burned PCB phase current
• Check on-PCB current sensing circuit parts
sensing circuit parts
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
14
Display
Title Cause of error Check point & Normal condition
code
1. Overload operation (Pipe clogging/Covering/EEV
• Overload operation
defect/Ref. overcharge)
(Outdoor fan constraint,
2. Compressor damage (Insulation damage/Motor
screened, blocked)
damage)
27 PSC/PFC Fault Error • Wrong application of
3. Input voltage abnormal (L,N)
Reactor Spec.
4. Power line assemble condition abnormal
• Burned PCB internal
5. Inverter PCB assembly Damage (input current
parts (PSC Module)
sensing part)
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
No Check
Is input voltage normal? L~N phase voltage is 230V ± 15%
→ Check connection condition and wiring if power is abnormal
Yes
Yes
Yes
Yes
15
Display
Title Cause of error Check point & Normal condition
code
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref. over-
charge)
Inverter compressor over Inverter compressor input
29 2. Compressor damage(Insulation damage/Motor
current current is over 30A
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
Is compressor No 2. Check wire disconnection and wiring
Wire connection
3. Check compressor terminal connection condition
condition normal?
(bad contact)
→ Reassemble if abnormality found
Yes
Check
No L~N phase is 230V±15%
Is input voltage normal? → Check connection condition and wiring if power is
abnormal
Yes
Yes
16
Display
Title Cause of error Check point & Normal condition
code
• Overload operation
(Outdoor fan constraint,
screened, blocked) • Check outdoor fan constraint/ screened/ flow
• Refrigerant leakage structure
32 D-Pipe High (insufficient) • Check refrigerant leakage
• Poor INV Comp • Check if the sensor is normal
Discharge sensor • Check the status of EEV assembly
• LEV connector displaced
/ poor LEV assembly
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
CN- DISCHARGE
Yes
17
Display
Title Cause of error Check point & Normal condition
code
• Defective low pressure sensor
• Defective outdoor/indoor unit fan
• Refrigerant shortage/leakage
• Deformation because of damage of refrigerant pipe
• Defective indoor / outdoor unit EEV
Excessive decrease of low
35 Low Presser Error • Covering / clogging (outdoor unit covering during
pressure
the cooling mode / indoor unit filter clogging dur-
ing heating mode)
• SVC valve clogging
• Defective outdoor unit PCB
• Defective indoor unit pipe sensor
Is service valve No
Open service valve
opened?
Yes
No check communication
Are communication cable/
piping normal? / piping correction.
Yes
Is amount of
No Is there pipe crack No Adjust the amount of
refrigerant normal?
or trace of refrigerant refrigerant (Additive charge)
[refer refrigerant part]
leakage?
Yes
Is fan normal?
No Check and replace related parts
(in heating outdoor fan,
in cooling indoor fan) (error 105~108 reference)
Yes
No
Is strainer Ok?* Replace the strainer
Yes
Yes
* If the temperature difference between inlet and outlet of strainer
Check indoor / outdoor unit LEV is so large that frost or ice formation can be seen or confirmed
Check Indoor unit PCB then clogging of strainer should be checked
Check indoor / outdoor unit (Notice: it is not full ice forming of strainer, in case that there is
installation conditions not at inlet portion but at outlet portion)
18
Display
Title Cause of error Check point & Normal condition
code
Is PFC Micom No
& INV Micom S/W Program Upgrade Micom Program
normal?
Yes
Is Inverter PCB No
Replace inverter PCB assembly
assembly normal?
Yes
19
Display
Title Cause of error Check point & Normal condition
code
• PCB sensing circuit part • Check power input connector, Comp output
40 CT Sensor (Open/short)
burned current sensing circuit
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
• DC voltage measurement
Is the Comp phase at the measurement point in
Current sensor figure 2 at power-on
part normal? standby state -> measured
value : within 2.5V ± 0.2V
Recheck power
and installation condition
20
Display
Title Cause of error Check point & Normal condition
code
• Open / Short
41 D-pipe sensor (Inverter) • Soldered poorly • Normal resistor : 200KΩ / at 25°C (Unplugged)
• Internal circuit error
• Open / Short
44 Air sensor • Soldered poorly • Normal resistor : 10KΩ / at 25°C (Unplugged)
• Internal circuit error
• Open / Short
45 Condenser Mid-pipe sensor • Soldered poorly • Normal resistor : 5KΩ / at 25°C (Unplugged)
• Internal circuit error
• Open / Short
46 Suction Pipe sensor • Soldered poorly • Normal resistor : 5KΩ / at 25°C (Unplugged)
• Internal circuit error
• Open / Short
48 Condenser Out-pipe sensor • Soldered poorly • Normal resistor : 5KΩ / at 25°C (Unplugged)
• Internal circuit error
21
Display
Title Cause of error Check point & Normal condition
code
• Bad connection of connector PCB
• Bad connection high pressure connector
High Pressure Sensor Abnormal value of sensor
43 • Defect of high pressure connector (Open/Short)
Error (Open/Short)
• Defect of connector PCB (Open/Short)
• Defect of outdoor main PCB.
Is sensor connected No
Connect sensor to PCB correctly
to PCB correctly?
Yes
Afterreplacement of No
outdoor unit main PCB is the END
system also abnormal?
Yes
Replace corresponding
pressure sensor
22
Display
Title Cause of error Check point & Normal condition
code
Check Point
• CH 51
1. Check the indoor unit capacity.
2. Check the combination table.
23
Display
Title Cause of error Check point & Normal condition
code
Main controller of Master 1. Power cable or transmission cable is not
Signal Error
unit of Master unit canʼt connected
52 (Inverter PCB <-> Main
receive signal from 2. Defect of outdoor Main fuse/Noise Filter
PCB)
inverter controller 3. Defect of outdoor Main / inverter PCB
Is transmission
No Is noise filter or fuse No
LED (Yellow) of inverter Replace noise filter or fuse
compressor normal?
PCB on?
Yes
Yes
Is transmission cable No
connected correctly? Re-connect transmission cable
Yes
No
Is MAIN PCB normal? Replace MAIN PCB
Yes
Replace inverter
compressor PCB
Check Point
- Check the Transmission connector and LED (Main & Inverter)
24
Display
Title Cause of error Check point & Normal condition
code
• No power on indoor unit
• Indoor/outdoor unit • Check indoor unit power status
Power connection • Check indoor/outdoor unit
error/communication power/communication line disconnection
Signal Error
5 / 53 error caused by external • Check the status of indoor/outdoor unit ground
(Indoor £ Outdoor)
noise connections
• Indoor/outdoor unit com- • Check if outdoor unit communication parts are
munication circuit parts burned
burned
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
Recheck power
and installation condition
25
Display
Title Cause of error Check point & Normal condition
code
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
Yes
26
Display
Title Cause of error Check point & Normal condition
code
• Outdoor unit PCB
EEPROM Check Sum EEPROM misapplied
60 EEPROM assembly
Error • Outdoor unit PCB
EEPROM poor assmbly
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
Replace EEPROM
27
Display
Title Cause of error Check point & Normal condition
code
• Overload operation
(Outdoor fan constraint,
screened, blocked) • Check outdoor fan constraint / screened / flow
• Outdoor unit heat structure
61 Cond. Pipe Sensor High exchanger contaminated • Check if refrigerant overcharged
• EEV connector displaced • Check the status of EEV assembly
/ poor EEV assembly • Check the status of sensor assembly / burn
• Poor Cond. Pipe sensor
assembly / burned
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Yes
28
Display
Title Cause of error Check point & Normal condition
code
• ODU fan locking
• Heatsink assembly of INV PCB assemble condi-
Inverter PCB heatsink tem-
62 Heatsink Sensor High tion abnormal
perature is over 85°C
• Defect of temperature sensing circuit part defect
of INV PCB
Is assemble condition No Check assemble condition between INV PCB heatsink and
of INV PCB heatsink PFC & IPM module ’ Reassemble if abnormality found
normal ?
Yes
Yes
29
Display
Title Cause of error Check point & Normal condition
code
• ODU fan locking
• Heatsink assembly of INV PCB assemble
Inverter PCB heatsink sen-
65 Heatsink Sensor Error condition abnormal
sor is open or short
• Defect of temperature sensing circuit part defect
of INV PCB
Yes
Yes
30
Display
Title Cause of error Check point & Normal condition
code
• ODU fan locking
Fan RPM is 10RPM or less
• Heatsink assembly of INV PCB assemble condi-
for 5 sec. when ODU fan
67 Outdoor BLDC Fan Lock tion abnormal
starts or 40 RPM or less
• Defect of temperature sensing circuit part defect
after fan starting.
of INV PCB
No
Is ODU Fan Motor Assemble Check ODU Fan Motor assemble condition and fan locking
condition normal? → Reassemble or replace if abnormality found
Yes
Yes
Yes
Is connector PCB No
assembly normal? Replace connector PCB assembly
Yes
No
Is main PCB assembly Replace main PCB assembly
normal?
Yes
Check Point
1. Check voltage between 1pin and 4pin of Fan Mortor connector (Tester diode mode)
2. Voltage value should be in 1V ±0.2V.
31
Display
Title Cause of error Check point & Normal condition
code
1. Overload operation (Pipe clogging/Covering/EEV
defect/Ref.overcharge)
2. Compressor damage
Inverter PCB input power
(Insulation damage/Motor damage)
73 PFC Fault Error (S/W) current is over 48A(peak)
3. Input voltage abnormal (L, N)
for 2ms
4. Power line assemble condition abnormal
5. Inverter PCB assembly damage
(input current sensing part)
Yes
No Check
Is input voltage normal? L~N phase voltage is 230V ± 15%
→ Check connection condition and wiring if power is abnormal
Yes
Yes
Yes
32