FUNCTIONAL SPECIFICATION
FOR
ROTAMETERS
TOTAL
PREPARED / REVIEWED REV.
APPROVED BY No. OF DATE
REVISED BY BY No.
PAGES
VS SRS GRP 6 18.02.2008 3
ET RS GRP 9 28.03.2007 2
ET MC RK 9 23.06.2005 1
ET MC AC 9 10.03.2003 0
FORMAT No. Ref. PROCEDURE No. ISSUE No. REV. No. REV. DATE:
DD/SOF/004A/B DD/SOP/008 TO 015 02 01 01/08/2006
Design Division Spec # 3206
Engineering Services Functional Specifications Rev # 3
11 - High, Mumbai ROTAMETERS Discipline Instt.
ISO 9001: 2000 Page # 2 of 6
CONTENTS
FORMAT No. Ref. PROCEDURE No. ISSUE No. REV. No. REV. DATE:
DD/SOF/004A/B DD/SOP/008 TO 015 02 01 01/08/2006
Design Division Spec # 3206
Engineering Services Functional Specifications Rev # 3
11 - High, Mumbai ROTAMETERS Discipline Instt.
ISO 9001: 2000 Page # 3 of 6
FORMAT No. Ref. PROCEDURE No. ISSUE No. REV. No. REV. DATE:
DD/SOF/004A/B DD/SOP/008 TO 015 02 01 01/08/2006
Design Division Spec # 3206
Engineering Services Functional Specifications Rev # 3
11 - High, Mumbai ROTAMETERS Discipline Instt.
ISO 9001: 2000 Page # 4 of 6
4.3.1 The material requirements for Rotameter shall in general be according to clause
3.6.4.5 of Instrumentation Design Criteria and the material selection chart provided
in Annexure I of this specification.
4.3.2 The Rotameter tube, float and end fittings shall in general be SS 316, unless
otherwise mentioned.
4.3.3 The Contractor shall ensure that all wetted parts are compatible with the process
conditions.
4.4 Range:
4.4.1 The range of the Rotameter shall be selected such that the normal flow rate is
between 50% and 100% of the instrument range.
4.5 Reading Scales:
4.5.1 Scales for Rotameters shall be direct reading, marked for 10-100% of flow.
4.5.2 The flow rate shall be indicated by the vertical position of the float or magnetically
coupled pointer.
4.6 Accuracy:
4.6.1 Rotameter shall have an accuracy of +/- 2% or better.
4.7 Transmitter:
4.7.1 Wherever transmitters are to be provided, they shall be 2-wire magnetic type. The
transmitter shall operate on 24 V DC and shall give an output of 4 – 20 mA. The
transmitter shall be intrinsically safe with the enclosure class for Rotameter being
Weather proof to IP 65 or better
4.8 Miscellaneous
4.8.1 Rotameters shall be installed vertically with the outlet connection at the top and the
inlet connection at the bottom.
4.8.2 Rotameters shall be installed as received. A level plumb shall be used to check for
proper installation.
4.8.3 The Rotameter location shall be free from vibration.
4.8.4 The Rotameter shall be located with sufficient clearance for maintenance purposes,
including float removal, without dismantling the meter body from the pipeline.
4.8.5 Elbows, valves & other fittings shall not be closer than 5 pipe diameters upstream.
4.8.6 The meters shall be provided with two full-bore isolating valves and by-pass valve
for maintenance.
4.8.7 A check valve shall be installed downstream, where backflow may be expected in
gas service, or where there is the possibility of liquid hammer.
4.8.8 Rotameters shall be checked and tested after installation both at yard and at
offshore site to confirm that shipping stops have been removed.
4.8.9 The transmitting mechanism of the Rotameters shall be checked by mechanically
raising and lowering the float and then checking the output.
4.8.10 Rotameter calibration curve shall also be furnished along with the purchase
specification.
FORMAT No. Ref. PROCEDURE No. ISSUE No. REV. No. REV. DATE:
DD/SOF/004A/B DD/SOP/008 TO 015 02 01 01/08/2006
Design Division Spec # 3206
Engineering Services Functional Specifications Rev # 3
11 - High, Mumbai ROTAMETERS Discipline Instt.
ISO 9001: 2000 Page # 5 of 6
ANNEXURE – I
Rotameter
S. No. Piping Class
Body End Fitt. Float
A1, B1, D1, E1, F1, XF1, F1, PA1, PB1,
PD1, PE1, PXF1, PF1, A2, B2, D2, E2,
1 XG1, A1H, A3, B3, A8 SS 316 SS 316
(EXCEPT WAT. INJ. SERVICE)
4 A5 MONEL MONEL
5 A7 TITANIUM TITANIUM
FORMAT No. Ref. PROCEDURE No. ISSUE No. REV. No. REV. DATE:
DD/SOF/004A/B DD/SOP/008 TO 015 02 01 01/08/2006
Design Division Spec # 3206
Engineering Services Functional Specifications Rev # 3
11 - High, Mumbai ROTAMETERS Discipline Instt.
ISO 9001: 2000 Page # 6 of 6
NOTE:-
FORMAT No. Ref. PROCEDURE No. ISSUE No. REV. No. REV. DATE:
DD/SOF/004A/B DD/SOP/008 TO 015 02 01 01/08/2006