REGISTER ADDRESS REGISTER NAME RANGE UNIT FORMAT R/W SWAP Remark
1 0 Wh RESET - - F001 W -
101 100 rWh RESET - - F001 W -
201 200 VARh RESET - - F001 W -
301 300 rVARh RESET - - F001 W -
401 400 VAH RESET - - F001 W -
501 500 MAX V THD RESET - - F001 W -
601 600 MAX A RESET - - F001 W -
701 700 MAX A THD RESET - - F001 W -
801 800 MAX W RESET - - F001 W -
901 900 MAX VAR RESET - - F001 W -
1001 1000 MAX VA RESET - - F001 W -
1101 1100 MAX DEMAND W RESET - - F001 W -
1201 1200 MAX DEMAND A RESET - - F001 W -
1301 1300 DEMAND A RESET - - F001 W -
1401 1400 DEMAND W RESET - - F001 W -
1501 1500 DI1 COUNTER RESET - - F001 W -
1511 1510 DI2 COUNTER RESET - - F001 W -
2001 2000 ALL DATA RESET - - F001 W -
5555 5554 ALL ERROR COUNTER RESET - - F001 W -
REGISTER ADDRESS REGISTER NAME RANGE UNIT FORMAT R/W Default Value Remark
40001 0 Manufacturer Name - - STRING R "LSELECTRIC"
40017 16 Modbus Map Identifier - - STRING R "GIMAC1000"
40033 32 Modbus Map Version - - STRING R "01.00.00"
40038 37 Product Name - - STRING R "GIMAC1000"
40054 53 Manufacturing number - - STRING R -
40065 64 Product code - - STRING R -
40071 70 Hardware Version - - STRING R "01.00.00"
40076 75 Software Version - - STRING R "01.00.00"
41001 1000 Product Option Specification - - F224 R 0(Normal,5A,60Hz,RS485 OFF, ETH OFF)
41002 1001 Wiring Connection 1:1P2W, 2:1P3W, 3:3P3W(D),4:3P3W(Y),5:3P4W - F219 R 5(3P4W)
41003 1002 Demand Time 1,2,3,4,5,6,10,15,20,30,60 min F038 R 15(min)
41004 1003 The constant part of PT Ratio (PT Ratio High) 1~1400 - F038 R 1 NAK reply if the value is outside
41005 1004 The decimal part of PT Ratio (PT Ratio Low) 0~9999 - F038 R 0 the range of 1 ~ 1400
41006 1005 CT Ratio ( High Word ) 0 - F038 R 0 don’t care
41007 1006 CT Ratio ( Low Word ) 1~2000 - F038 R 1
41008 1007 RS485 Address/ Tx delay time High(Address):1~247/Low(Delay Time):10~200(ms) - F217 R High(Address):1,Low(Delay Time):20(ms)
41009 1008 RS485 Comm Speed / Swap High(SWAP):1~2/Low(Speed):1~3 - F218 R High(SWAP):1(NO),Low(Speed):3(38400bps)
41010 1009 DI Debounce Time 5~200 ms F222 R High(DI1):5,Low(DI2):5
41011 1010 RS485 Comm Termination Resistance 1(OFF),2(ON) - F223 R 1(OFF)
41012 1011 MAC Address 00-0B-29-00-00-00 ~ 00-0B-29-FF-FF-FF - F040 R 00-0B-29-00-00-00
41015 1014 IP Address 01-00-00-00 ~ DF-FF-FF-FF - F041 R 192.168.0.100
41017 1016 Subnet Mask 00-00-00-00 ~ FF-FF-FF-FF - F041 R 255.255.255.0
41019 1018 Gateway Address 01-00-00-00 ~ DF-FF-FF-FF - F041 R 192.168.0.1
41021 1020 Idle Time 0x000A ~ 0x003C ms F038 R 0x000A
REGISTER ADDRESS REGISTER NAME RANGE UNIT FORMAT R/W SWAP Remark
41022 1021 Ethernet Module Swap 0x0000 : On, 0x5555 : off - F038 R 0x0000
41023 1022 Ethernet Module Software Version - F038 R 0x000A 0x000A = 10 ( Means 1.0 )
* Address 40000 does not apply SWAP
Format Detail
F001
F038 type
Only ON (0xFF00) can be input to data
F004
IEEE754 32bit short float form
F037
32bit Unsigned Integer type
F038
16Bit Unsigned Integer type
F040
48bit Mac address
In the form (00-0B-29-hh-hh-hh), h has a value from 0 to f.
Ex) Write : 85 10 08 34 00 03 06 00 0b 29 00 00 01 crc-h crc-l
Read : 85 03 08 34 00 03 crc-h crc-l
F041
32bit IP/SUB NET/G,W address
In the form (hh.hh.hh.hh), h has a value from 0 to f.
F217
F038 type
High Byte Low Byte
F218
F038 type
High Byte Low Byte
F221
F038 type
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
DI 02 DI 01
- - - - - - - - - - - - - -
Status Status
※ 0:Open, 1:Close
F222
F038 type
High Byte Low Byte
Ex) If Debounce data is 05 06, DI1 Debounce time is 5ms, DI2 Debounce time is 6ms.
F223
F038 type
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
- - - - - - - - - - - - - - ON OFF
Ex) If the Comm. terminal resistance status data is 00 01, the function is OFF. If it is 00 02, the function is ON.
F224
F038 type
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
Rated
Etherne RS485 Freque Functi
- - - - - - - - - - - curren
t Y/N Y/N ncy on
t
1) Function : 0 -> NO, 1 -> EX
2) Rated frequency : 0 -> 60Hz, 1-> 50Hz
3) Rated current : 0 -> 5A Type, 1-> 1A Type
4) RS485 : 0 -> No Comm, 1-> M485
5) ETHERNET : 0 -> No ETHERNET, 1-> ETHERNET
< Exception Codes >
Ex) If Master tries to READ the 30501 Register under the condition where 30501
Register is not defined at the register map,
Slave device responses to it with ILLEGAL DATA ADDRESS(02).
Request Response
Field Name (Hex) Field Name (Hex)
Slave Address 01 Slave Address 01
Function 04 Function 84
Starting Address Hi 01 Exception Code 02
Starting Address Lo F4 CRC Lo -
Quantity of Inputs Hi 00 CRC Hi -
Quantity of Inputs Lo 01
CRC Lo -
CRC Hi -