Hall Level-Piping

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

LEGEND

B.O.D. Bottom of duct


B.O.C. Bottom of cutout
AHU Air handling unit
ATG Air transfer grill
FCU Fan coil unit 3D 07.7 9B' 10E
TFA Treated fresh air
Acoustic Insulation 1.1 2.9 04.1 05.7 07.1 9A' 10C 12.6
Thermal Insulation
Exhaust air duct
Supply air duct
SYMBOLS
Return air duct
Fresh air duct
Continuous grill
Jet diffuser
Hydronic Hi- wall Drawn By: Checked By: Aproved By:
Dx type Hi - wall Narinder kumar Harendra P. Bhatnagar
Axial fan
Circular inline fan Dated: Scale: Per size
Propeller fan 31.08.20 N.T.S A1
Chilled water S/R pipe M'9 Dwg. Number:- Revision No.
Refnet pipes
Drain line R-6
Control damper L4.9 M1-103A_CPS_SGM-R06
AUDI 2 AUDI 3 AUDI 4
M
Motorize dmaper
AUDI 8
Access door MACRO XE
Cut out AUDI 1

Cassette unit Drawing Title


NOTES :- HALL LEVEL
1) All dimensions are in mm unless otherwise specified HVAC PIPING LAYOUT
2) All Supply, Return & Exhaust grills/diffusers shall have VCD. PurPose Of Release
3) Volume control dampers shall be installed in each branch of 2 Nos. Cassette unit
the return air duct 100 mm above grill inside all the Audi's
FOR ADVANCE G.F.C.
0.85 Tr. / 300 cfm
where it is easier for a person to operate it.
Ø65 CHWS/R
4) All the Fresh/Exhaust air duct shall have wiremesh/birdscreen (57.24 GPM)
or louver sized with velocity not greater than 2.5 m/sec Ø50 CHWS/R
considering its free area.Gravity louvers shall be provided (31.44 GPM)
wherever specified 2Nos.DX type Hi - wall unit

BFV
3# DX type Hi - wall unit (Stand-by)

BFV
(Stand-by) 1.0 Tr. / 400 cfm Ø50 mm drain ENGINEERING CONSULTANT
(ODU on terrace) Ø20 2.0 Tr. / 800 cfm each
5) Thermal Insulation (ODU on terrace)
5.1) 25 mm thick Supply,Return & TFA ducts exposed to Ø32 TECHFOUR ENGINEERING SOLUTIONS PVT. LTD.
sun/Ambient as per detailed BOQ specification . Cassette unit Cassette unit
2.95 Tr. / 1200 cfm Ø25 0.85 Tr. / 300 cfm
5.2) 13 mm thick Supply,Return & TFA ducts inside false ceiling UNIT- 121 & 122,
DX type Hi - wall unit (Stand-by) US COMPLEX, JASOLA
5.3) 9 mm thick Return air ducts exposed to air conditioning 2# Cassette unit Ø32 Ø40 1.5 Tr. /600 cfm each ENGINEERING . TECHNOLOGY
area inside Audi's upto false ceiling level +0.5 Mtrs above Ø20 CHWS/R NEW DELHI-110076
2.95 Tr. / 1200 cfm each (ODU on terrace)
Ø32 mm drain Ø25 mm drain (2.04 GPM) Tel. +91-11-26397250
False ceiling level shall be Nitrile Rubber (Black in colour) .
There should be an overlap of 0.5 Mtrs.
J1.9 www.techfoursolutions.com
Ø50 CHWS/R Ø32 CHWS/R
6) Acoustic Insulation (21.24 GPM) (8.16 GPM)
BOP @2500lvl. Cassette unit Ø20 mm drain Ø20 mm drain
6.1) Acoustic Insulation for Audi's - In supply air duct 0.85 Tr. / 300 cfm
(Complete plenum + Exposed ducts on terrace+SA Cassette unit Ø25 mm Cassette unit Ø25 mm drain Ø32 mm drain
duct up to Audi's entrance.) J1.3 VIP 3 0.85 Tr. / 300 cfm 0.85 Tr. / 300 cfm
6.2) Acoustic Insulation for lobby - In supply air duct Ø80 CHWS/R

BFV

BFV
(Complete plenum + 3 Mtrs of Supply duct ) J1.1 Ø20 mm drain Ø25 CHWS/R Ø20 mm drain Ø32 CHWS/R (87.0 GPM)
form projection lvl. (4.08 GPM) (10.2 GPM) FM - AHU
7) All smoke Extraction / Makeup air ducts shall have 45° BOP @2500lvl. 32 Tr. / 10000 cfm
Cassette unit Ø80 CHWS/R
cowl with birdscreen / wiremesh on terrace. (76.8 GPM) Size: 2650x2200x1525H
J'1 0.85 Tr. / 300 cfm Ø40 mm drain
8) All chilled water supply, return and drain pipes shall
be insulated as per specification.

9) All Branches in supply air ducts shall have guide vanes.

10) Projector fans shall be silent type -


Acoustic cabinet fans with noise range 25-32 Db max. or
equivalent. Ø32 CHWS/R
(6.12 GPM)
11) All Audi's AHU rooms shall have acoustic insulation as per
I.4
specification in BOQ.
Cassette unit
12) All Audi's AHU fresh air duct should have installation with 0.85 Tr. / 300 cfm
control dampers and 45°cowl with wiremesh.
VIP 2

Ø20 mm drain
form projection lvl.

Ø25 CHWS/R
(4.08 GPM)
G1.7
Cassette unit
0.85 Tr. / 300 cfm
AUDI 5 AUDI 6 AUDI 7
VIP 1
450 cfm
200x250
G'1
1000 cfm
400x250
6000 cfm
750x600

Ø20 mm drain
Ø20 CHWS/R form projection lvl.
(2.04 GPM)
Ø40 mm drain
F'1

Cassette unit
0.85 Tr. / 300 cfm
Ø50 mm drain
pipe vertical

CINEPOLIS 7 + 1 MXE. + 3 VIP


SOBHA GLOBAL MALL

BANGALORE, KARNATAKA, INDIA

HALL LEVEL
HALL LEVEL