List of Contents
1. Introduction 02
1.1. Operating Principle 02
1.2. Applications 02
1.3. Safety Instructions 02
1.4. Unpacking the flowmeter 02
2. Installation 03
2.1. Remote or Compact? 03
2.2. Sensor Installation 03
2.3. Dry Liner 04
2.4. Installation of the Transmitter 05
2.5. Module Installation 06
2.6. Cables connections 07
2.7. Potting the remote sensor terminal box 08
3. MAGX2 Transmitter Unit 09
3.1. Main Screen 09
3.2. Flowmeter Menu 10
3.3. Info Menu 10
3.4. Display Menu 11
3.5. User Settings Menu 12
3.6. Service Settings Menu 23
3.7. Factory Settings Menu 24
3.8. Authorize Menu 25
4. Modules 26
4.1 Power Supply Module 26
4.2 Datalogger 27
4.3 Module Positioning 27
4.4 USB Module 28
4.5 RS485 Module 29
4.6 RS232 Module 30
4.7 Current Loop Output Module 31
4.8 V-Out Module 32
4.9 TCP/IP 33
4.10 BLUETOOTH Module 34
4.11 GPRS Module 35
5. Liner and Electrode Selection 36
6. Flowmeter Dimensions 37
7. How to order your MAGX2 39
8. MAGX2 Error Code Table 40
9. Appendix 41
Liquid flows through a tube in the direction of the magnetic field. Liquid with a certain
minimum electrical conductivity induces a voltage which is detected by two
electrodes located in a 90 degree angle from the magnetic field and the flow
direction. B
1.2. Applications
Keep this manual for future reference. Arkon Flow Systems, s.r.o will not be liable for any damage caused by
improper use of the product or its accessories.
The MAGX2 flow converter - flow-meter must not be mounted in explosive hazardous areas.
o Flowmeter
o Cables
o CD ROM+ Manual
o Mounting kit
The cable type used for the connection between sensor and transmitter for remote versions: UNITRONIC®
LiYCY (TP) 0035 830, 2x2x0,5
The MAGX2 is equipped with an electronic board located inside the sensor neck. This board sends a digital
signal to the transmitter, unlike traditional flowmeters, which send an analogue signal. This allows the
MAGX2 to carry its signal over much longer distances than conventional flowmeters; up to 500m is possible.
Sensor
installation
requirements:
Flowmeters with a Hard Rubber liner can show incorrect readings during the first 2-3 days after installation.
This is due to the fact that the time needed for transport and the time before installation is long enough for the
liner to dry out, and thus it changes shape/size. This change, in effect, affects reading accuracy. Simply be
keeping the meter wet, this problem solve itself within 2-3 days and no other action is required at all.
In case of a compact flowmeter version, the transmitter will need no further installation, and should be ready
for use.
In case of a remote version, the following 4 steps are necessary.
Wall mounting:
DIN-rail mounting:
Panel mounting:
Connect the transmitter to the signal cable from the sensor. To do this, first open the transmitter housing by
disconnecting the two parts of the transmitter housing with the metal “key” that is provided with the meter
After the meter is opened, pull the signal cable through the cable gland on the bottom of the transmitter
housing (see page 3).Connect the connector at the end of the signal cable from the sensor to the transmitter
circuit board.
Electrical installation should only be done by a qualified person. Standard safety regulations for
hazardous electrical installations have to be respected.
The customer is assumed to supply its own network power supply cable (90-250VAC, 24VDC or 12VDC,
depending on the type of power supply ordered with the flowmeter). Before connecting to network power, the
cable needs to be properly connected to the transmitter.
First pull the cable end through one of the cable glands (ideally the first on the left looking at the transmitter
housing from the back-side) on the bottom of the transmitter.
3x1mm recommended cable.
After connecting the power cable, close the housing and connect the cable to network power. This will make
the flowmeter switch on.
Here are
examples of
incorrect
installations
The RS232 Module is
placed in the incorrect
slot, and with the
bevelled corner in the
wrong direction.
Any connection or disconnection of any module has to be done with network power to the meter
switched off.
The following diagrams show the connections of the cables between sensor and transmitter.
Please note that wrong connection of the cables between sensor and transmitter could cause
permanent damage to the flowmeter.
To guarantee IP68 protection of the sensor, it is necessary to pot the sensor terminal box properly. The
proper way to do this is described below:
Plug the connectors into the sensor (white and green wire adjacent).
Screw the small terminal box to the sensor neck (4 screws).
Fill the terminal box completely with silicone, by squeezing it through the opening on top of the box.
Close the small terminal box with the sealing screw.
The MAGX2 Transmitter unit is the main part of the flowmeter. It consists of the MAGX2 motherboard, a
graphical display, touch-button controls and a transmitter housing.
Through the display and with help of the push buttons, you can go through the various menu’s for data
reading, configuration and setup of your flowmeter.
The following symbols are used in this manual and on the flowmeter display.
ENTER UP
Esc LEFT
Back Menu
DOWN
Selection menu
RIGHT
Total Volume
This is the total volume counter; the sum of all historical flows for a particular
flowmeter. The user is not able to zero this counter without use of the service
password. Direction of flow is ignored for this counter (negative flow is calculated the
same way as positive flow).
Positive Volume
This counter is only credited when the measured medium is flowing in the chosen
positive direction. In case the flow is 0, or if it is flowing in the opposite (negative)
direction, the number on the counter remains the same.
Negative Volume
This counter works the same way as the positive volume counter, yet in the opposite
direction. In case the flow is 0, or flowing in the designated positive direction, the
number on this counter will remain the same.
Auxiliary Volume
nd
This is a 2 total volume counter. It works the same as the Total Volume positive
counter, yet with the only difference being that it can be reset to 0 at any time, with
User Settings password.
After pressing the enter button you get to into the root-menu.
From here, you can chose any of the sub-menu’s displayed in
the picture on the right.
Date This item shows the current date according to the transmitter’s setup if the Real-Time
Clock module is installed. It can be changed in the User Settings menu.
Unit No. Displays the serial number of the motherboard. This number is allocated during
production by the manufacturer.
Sensor Unit No. Displays the serial number of the sensor. This number is allocated during production by
the manufacturer.
Error (min) The number of minutes the device was not measuring because of errors.
OK (min) The number of minutes that the device measured correctly.
This item shows the nominal sensor diameter that is currently configured for the given
Diameter flowmeter.
Flow Qn Here, the flowmeter displays the predicted flow-range limits. Values can be changed
under User Settings.
Firmware No. This shows the current firmware version.
Power frequency Identifies the network power supply frequency.
SD card present Shows if the SD card is inserted in the flowmeter.
GPRS MODULE Shows if the GPRS module is inserted in the flowmeter.
present
GPRS MODULE Displays IP address of GPRS module.
address
Unit Flow
Setup of the displayed measurement unit for current
flow.
UKG / UK gallon per minute
min
USG / US gallon per minute
min
m3 / h Cubic meters per hour
l / min Litres per minute
l/s Litres per second
(item selection confirm , selection identification back
)
Unit volume
Setup of the displayed measurement unit for total flow.
UKG UK gallon
USG US gallon
m3 Cubic meter
l Litre
Unit temperature
Setup of the displayed measurement unit of
temperature indication.
C Degrees Celsius
F Degrees Fahrenheit
Language
Setup of the language for flowmeter menu
ENG English
SPA Spanish
Contrast
Contrast of the display setup.
Possible range: 0 – 100 %
Back with no change
Selection of digit position
Value setting
Confirmation of setup and saving to memory.
To enter the User Settings menu, it is necessary to enter the user password. The default factory setting is
1111. See page 24 for user password settings.
Measurement
This option allows selecting flow measurement to be on or off.
RUN The device is measuring, the totalisers are active.
Datalogger Interval
This option allows select how often will be totalizers saved on
SD card
OFF Totalizer is not used (SD card not necessary)
Air detector:
This option allows selecting empty pipe check (air detector)
to be on or off.
ON The detector is active
OFF The detector is switched off
Air Constant
Constant value to determine the Empty Pipe detection limit.
Possible range: 0.000 – 0.999
Back with no change
Selection of digit position
Value setting
Confirmation of setup and saving to memory.
Start Delay
Time delay for the flowmeter where it, after switching on, will
not request measurement data from the sensor.
Possible range: 0 – 120 s
Back with no change
Selection of digit position
Value setting
Confirmation of setup and saving to memory.
Flow Qn
This function serves to setup the expected flow-rate.
Possible range: 0 – 10000 l/s
Back with no change
Selection of digit position
Value setting
Confirmation of setup and saving to memory.
Invert Flow
This function serves to change the definition of flow direction.
Back with no change
Choice selection
Confirmation of setup and saving to memory.
Settings Signal
This function serves to select which signal the output should
be giving.
Back with no change
Choice selection
Confirmation of setup and saving to
memory.
Flow + Output: 10mA for any positive flow.
Flow - Output: 10mA for any negative flow.
Error Output: 10mA, for any error identified by
the device. The signal can be cancelled by
pressing any push button on the
flowmeter.
Air Detect Output: 10mA, during air detection (empty
pipe).
Fixed Output: fixed output of 10mA
Direct Driving Output: Direct Driving – setup is below
OFF Output: fixed output of 4mA
Direct Driving
This function serves to set flow values in relation to current
output. Possible range: 0.000 – 10000 l/s, 4 – 20mA
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
Calibration Setup of calibration point 1, 2. First point must be less than second point.
point 1,2
Calibration Setup of calibration constant for first and for second calibration point.
constant 1,2
Current
Formula for calibration constant calculation: before
Expected value: 6 mA, Measured value: 6.1 mA after
Calibration point one: 6mA
Calibration constant one = 6 = 0.9836 max
6.1
Expected value: 18 mA, Measured value: 17.9 mA
Calibration point two: 18mA min
18
Calibration constant two = = 1.0056
17.9
min max
Flow
Voltage Output
Settings Signal
Direct Driving
Back with no change
Item selection
Confirmation of setup and saving to
memory.
Settings Signal
This function serves to select which signal the output should
be giving.
Back with no change
Item selection
Confirmation of setup and saving to
memory.
Flow + Output: 5V for any positive flow.
Flow - Output: 5V for any negative flow.
Error Output: 5V, for any error identified by the
device. The signal can be cancelled by
pressing any push button on the
flowmeter.
Direct Driving
This function serves to set flow values in relation to voltage
output. Possible range: 0.000 – 10000 l/s, 0 – 10V
Back with no change
Selection of digit position
Change of value
Pulse Output
RE1 & RE2
RE3 & RE4
Frequency Output
Back with no change
Item selection
Confirmation of setup and saving to
memory.
OF
F
F1 F 1 + H1 F 2 – H2 F2
On Out:
ON
OFF
F 1 F 1 + H1 F 2 – H2 F 2
ON
On > F1:
OFF
F1 F 1 + H1
On < F1: ON
OFF
F1 F 1 + H1
Comparator Settings
Possible range: 0.000 – 10000 l/s, 0.000 – 10000 l/s
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
Flow 1, 2 This function serves to configure the flow-range for the Comparator Mode. Flow 1 < Flow 2.
Hysteresis Setup of hysteresis for the Comparator Mode.
Frequency output
Frequency function
Direct Driving
Duty cycle
Back with no change
Item selection
Confirmation of setup and saving to memory.
Frequency function
This function serves to select which signal the output should
be giving.
Back with no change
Item selection
Confirmation of setup and saving to memory.
Direct Driving
This function serves to set flow values in relation to frequency
output. Possible range:
0.000 – 10000 l/s, 0 – 1000 Hz
Back with no change
Change of value
Selection of digit position
min
Flow
min max
Duty Cycle
Function to set duty cycle of the Frequency output.
Percentage of high level.
Possible range: 1 – 99 %
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
Date Setting
Function to set date.
Back with no change
Change of value
Selection of digit position
Confirmation of setup and saving to memory.
Date DD\MM\YY
format.
Password Setup
This function serves to setup the flowmeter user password.
Possible range: 0000 – 9999
Back with no change
Change of value
Selection of digit position
Confirmation of setup and saving to memory.
Modbus
Slave Address
Baud Rate
Parity
Interframe Spacing
Response Delay
Back with no change
Item selection
Confirmation
Slave Address
Modbus device address (Factory settings: 1)
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
Baud Rate
Setup communication speed (Factory settings: 9600)
Back with no change
Value setting
Confirmation of setup and saving to memory.
Parity
Setup communication parameters (Factory settings: Even, 1
stopbit)
Back with no change
Value setting
Confirmation of setup and saving to memory.
Response Delay
The minimum time from when a slave receives a request
and until it returns a response. This makes it possible to
send data to slow masters without overwhelming its
receiver. (Factory setting: 50) Possible range: 0 – 255 ms
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
Electrode Cleaning
Power
Clean Time
Start Now
Back with no change
Item selection
Confirmation
Power
Setup automatic electrodes cleaning
Back with no change
Value setting
Confirmation of setup and saving to memory.
Clean Time
Setup clean time for automatic electrode cleaning
(Factory setting: 500) Possible range: 1 – 9999 s
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
Start Now
Start automatic electrode cleaning now
Back with no change
Loads default settings
Error delete:
This option serves to zero the totaliser for number of minutes
the flowmeter signalised an error.
Item selection
No change
Resets error minute totaliser
OK delete
This option serves to zero the totaliser for number of minutes
of operation.
Item selection
No change
Resets error minute totaliser
Delete volume –
Option to zero the totaliser for negative flow.
Item selection
Confirmation
Back without change
Delete volume +
Option to zero the totaliser for positive flow.
Item selection
Confirmation
Back without change
Flow Simulation
Switching on/off the flow simulation status
ON Flow Simulatin status is ON
OFF Flow Simulatin status is OFF
Item selection
Confirmation
Simulated Flow
Simulation flow percentage of Flow Qn
(Factory setting: 50) Possible range: 0 – 100 %
Back with no change
Selection of digit position
Change of value
Confirmation of setup and saving to memory.
To enter this part of the menu, it is necessary to enter the Factory Password.
This function is only available to Arkon staff in the Arkon workshop
To enter this part of the menu, it is necessary to enter the Autorize Password.
This function is only available to Arkon staff in the Arkon workshop.
Electrical Specifications
Input Voltages ±5% / AC90 - 250V / max. 100mA
possible current DC24 / max. 600mA
consumption DC12 / max. 1050mA
Output Voltages 3,3V / 2A
23.6V/300mA
Frequency Outputs 50-60Hz
Temp. Range -20 – 70°C
Dimensions: R = 50mm
H(230V) = 58mm
H(12,24V) = 58mm
Weight 300g
Connection of the flowmeter is to be done via a switch or circuit breaker for safety purposes. The
device does not have a network power switch. For any electrical work it is necessary to disconnect
the device from the network power, and this has to be done via a switch.
Size:
11mm x 15mm x 1.0mm
Durability:
10,000 insertion/removal cycles
Weight:
0.4g
APPLICATIONS:
Any System Requiring, USB Communications, Peripheral - PC and Terminal, Data-loggers. USB 1.1 and USB
2.0 compatible
Any connection or disconnection of any module has to be done with the network power to the meter
switched off.
APPLICATIONS:
Industrial Automation, Industrial Process Control, Peripheral - PC and Terminal, Data-loggers
Electrical Specifications
VCC to Ground 3,3 VDC
Baud rate Max. 115200 baud/s
For computers that do not have an RS485 port, we can provide an RS485 to RS232 or an RS485 to USB
convertor. Please contact the Arkon sales office for details.
Terminator Rt with resistance 100Ω Ω should be connect to the end of line RS-485.
APPLICATIONS:
Industrial Automation, Industrial Process Control, Peripheral - PC and Terminal, Data-loggers
Electrical Specifications
VCC to Ground 3,3 VDC
Baud rate Max. 115200 baud/s
APPLICATIONS:
Industrial Automation, Industrial Process Control, Test Systems, Smart Transmitter
Electrical Specifications:
12-bit DAC
Maximum Resolution 3,9 uA.
APPLICATIONS:
Industrial Automation, Industrial Process Control, Test Systems, Smart Transmitter
Electrical Specifications
12-bit DAC
Maximum Resolution 2,44 mV
MAGX2 TCP/IP
“MAGX2 TCP/IP Communication Module”
Module
APPLICATIONS:
You can make any electronic product a smart device with embedded network intelligence, enabling it to
deliver innovative applications such as:
• Remote Diagnostics and Upgrades
• Asset Tracking and Replenishment
• Automation and Control
• Power Management
• Remote Collaboration
• Personalized Content Delivery
Electrical Specifications
VCC to Ground 3.14V to 3.46V
Power Sup. Current 120 – 267mA
Ethernet 10/100Mbit
Temp. Range -40-75°C
APPLICATIONS:
Wireless control of and communication between transmitter and PC or PLC systems
Any System Requiring BlueTooth Communications
Electrical Specifications
VCC to Ground 3.3 VDC
Power Sup. Current 120mA
Baud Rate Max. 460.8 Kbaud/s
Carrier Frequency 2.402 – 2.480 GHz
Range 100m (class 1)
Temp. Range –10 - +70°C
Warning!: There is a condition that must be fulfilled for the Bluetooth module to be able to operate
correctly: line speed of the communication protocol MODBUS must be set up on 19200Bd,
Parity none, 1 stop bit. If there is a different setting the communication will not work. You can find
the setting in the following MAGX2 flow meter menu: "Menu / User settings / Modbus / Baud rate"
and "Menu / User settings / Modbus / Parity". See BLUETOOTH installation manual.
MAGX2 GPRS
“MAGX2 GPRS Communication Module”
Module
APPLICATIONS:
Wireless control of and communication between transmitter and PC or PLC systems
Any System Requiring GPRS Communications
Electrical Specifications
VCC to Ground 3,3 VDC
Power Sup. Current RMS 400mA, MAX 1500mA
Baud Rate 19200 baud/s
Operating Systems GSM 850 / GSM 900
DCS 1800 / PCS 1900
Multi-slot class 10 (4 Rx / 2 Tx / 5 Sum)
SIM Card 3.0 / 1.8 V
Temp. Range –20 - + 75 °C
Warning!: There is a condition that must be fulfilled for the GPRS module to be able to operate
correctly: line speed of the communication protocol MODBUS must be set up on 19200Bd,
Parity none, 1 stop bit. If there is a different setting the communication will not work. You can find
the setting in the following MAGX2 flow meter menu: "Menu / User settings / Modbus / Baud rate"
and "Menu / User settings / Modbus / Parity". See GPRS installation manual.
Any connection or disconnection of any module has to be done with the network power to the
meter switched off.
Liner Selection:
Electrode selection:
Remote version
Standard pressure:
DN 10 – DN 50 → PN 40 / 600 lbs.
DN 65 – DN 150 → PN 16 / 150 lbs
Position 0
Position 1
Position 15
MAGX2 can detect and show a number of errors in one error code value.
1 Overloaded
2 Excitation
6 SD open file
Errors on the display are indicated in hex format. This number must be converted to binary
format! The Hex converter can be downloaded from Arkon Flow Systems´ website
www.arkon.co.uk/en/support.html or you can use a calculator with hex converting function.
Once the error code has been converted to binary format, each position is related to a different error (see the
table above). Number 1 indicates error and number 0 indicates no error.
Example:
9.1. CE requirements
9.2. Warranty
The warranty conditions are covered by Arkon Flow Systems, s.r.o. Terms & Conditions of Sale and by Arkon
Flow Systems, s.r.o Return Regulations and Warranty Conditions. The Arkon Flow Systems, s.r.o Terms &
Conditions of Sale and the Arkon Flow Systems, s.r.o Return Regulations and Warranty Conditions are an
integral part of the Resellers contract and of any Order Confirmation. Please see your Resellers contract or
www.arkon.co.uk; Support section. The Warranty sheet is part of the Packing note of any new goods sent. For
the claim or return procedure, please consult our web site www.arkon.co.uk or call the Arkon Flow Systems,
s.r.o sales office.
9.3. Contact:
Office hours:
8:30 – 18:30 (GMT+1)