Wind Load Calculation

This document calculates wind loads on various structural members according to MS 1553 based on site conditions and member geometry. It determines: 1) The design wind speed of 38.525 m/s based on the site wind pressure and various adjustment factors. 2) The wind pressure of 0.363 kN/m on UC members with dimensions of 3125mm x 356mm. 3) The wind pressure of 0.465 kN/m on UB members with the same dimensions as the UC members.

Uploaded by

WangTF
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
386 views

Wind Load Calculation

This document calculates wind loads on various structural members according to MS 1553 based on site conditions and member geometry. It determines: 1) The design wind speed of 38.525 m/s based on the site wind pressure and various adjustment factors. 2) The wind pressure of 0.363 kN/m on UC members with dimensions of 3125mm x 356mm. 3) The wind pressure of 0.465 kN/m on UB members with the same dimensions as the UC members.

Uploaded by

WangTF
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

SMHB Sdn. Bhd.

Job number :
Jurutera Perunding Calculation Sheet no
Job name : Drawings nos.
Calculations by : Date :
Structure : Checked by : Date :
Section : Reviewed by Date :
MS 1553 Wind Load Calculation

Figure 3.1 Zone : Zone I


site wind pressure Vs = 33.5
Md = 1
terrain/ height multiplier Mz,cat = 1 ( Table 4.1 )
hill shape multiplier Mh = 1 ( Table 4.4 )
shielding multiplier Ms = 1 ( Table 4.3 )
Site Wind Speed Vsit = Vs (Md) ( Mz,cat) (Ms) (Mn)
33.5 m/s

Importance factor I= 1.15 ( Table3.2 )


design wind speed Vdes = Vsit x I
= 38.525 m/s

design wind pressure p = (0.5 rair ) [Vdes]2 Cfig C dyn


0.5 rair = 0.613

dynamic response factor Cdyn = 1 (greater than 1 Hertz)

UC member
aerodynamic shape factor Cfig = Kar Ki Cd (Appendix E, E1)
length of member l = 3125 mm
breadth of member b = 356 mm
aspect ratio l/b = 9
correction factor Kar = 0.7 (Table E1)
ki = 1 ( wind is normal to member )
drag force coefficient Cd = 1.6 ( Table E5, UC section )

UC: 0.613 x (38.525) 2 x 1.12 x 1 x 0.356 = 0.363 kN/m

UB member
aerodynamic shape factor Cfig = Kar Ki Cd (Appendix E, E1)
length of member l = 3125 mm
breadth of member b = 356 mm
aspect ratio l/b = 9
correction factor Kar = 0.7 (Table E1)
ki = 1 ( wind is normal to member )
drag force coefficient Cd = 2.05 ( Table E5, UB section )

UB: 0.613 x (38.525) 2 x 1.435 x 1 x 0.356 = 0.465 kN/m

SHS member
aerodynamic shape factor Cfig = Kar Ki Cd (Appendix E, E1)
length of member l = 6000 mm
breadth of member b = 250 mm
aspect ratio l/b = 24
correction factor Kar = 0.8 (Table E1)
ki = 1 ( wind is normal to member )
drag force coefficient Cd = 2.2 ( Table E4 , SHS or RHS )
RHS/SHS: 0.613 x (38.525) 2 x 1.76 x 1 x 0.25 = 0.400 kN/m

SMHB Sdn. Bhd. Job number :


Jurutera Perunding Calculation Sheet no
Job name : Drawings nos.
Calculations by : Date :
Structure : Checked by : Date :
Section : Reviewed by Date :
MS 1553 Wind Load Calculation

CHS / Pipe member


aerodynamic shape factor Cfig = Kar Ki Cd (Appendix E, E1)
length of member l = 85000 mm
breadth of member b = 1300 mm
aspect ratio l/b = 65
correction factor Kar = 1 (Table E1) 1.419kN/m
ki = 1 ( wind is normal to member )
drag force coefficient Cd = 1.2 ( Table E4 , SHS or RHS ) 800 mm

You might also like