M 385 Content
M 385 Content
M 385 Content
2020
CONTENTS:
I. INTRODUCTION
II. FANS AND BLOWERS
1. Centrifugal Fans
2. Axial Fans
3. Fans Application
4. Centrifugal Fan Types
5. Axial Fan Types
6. Special Fan Types
7. Fan Power Capacity
8. Total Pressure
9. Fan Inlet Pressure Drop
10. Pressure Drop, Velocity and Velocity Pressure Relation
11. Pressure Head
12. Converting Head to Pressure
13. Coefficient of Entry
14. Hood Static Pressure
15. Rate Velocity Measurements
16. Air Density Correction Factors
17. Fan Average Capacities
18. Fan Laws
19. Fan Basic Characteristics
20. Pressure Correction Factors
21. NTP – Normal Temperature and Pressure
22. V-Belt Drives
23. Fan Drive Arrangements
24. Fans or Blowers Standard Positions
25. Vibration
IX. REFERENCES
I. INTRODUCTION:
According to Occupational Safety & Health Administration (OSHA), industrial ventilation is one of the
most important engineering controls available for improving or maintaining the quality of the air in the
occupational work environment.
Broadly defined, ventilation is a method of controlling the environment with air flow.
The quality of indoor air inside workplaces is important not only for workers' comfort but also for their
health. Specific diseases have been linked to specific air contaminants due poor indoor air quality like
asthma, lungs cancer, headaches, fatigue, trouble concentrating and irritation of the eyes, noses, throat
and several other symptoms.
The main scope of this manual is the practical industrial ventilation concepts application and equipment
calculation avoiding as possible, the tiresome extensive theory.
Centrifugal fans are the most used ventilation equipment, commonly applied in systems to control
environment temperatures and in material handling applications to control room moisture or the
air particulate content.
Centrifugal fans use a rotating impeller to increase the velocity of an airstream. As the air is
sucked in direction to the blades, it gains kinetic energy.
The kinetic energy is then converted to a static pressure increase as the air slows before
entering the discharge.
Axial fans move an airstream along the axis of the fan. The air is pressurized by aerodynamic fan
blades, much like a propeller and an airplane wing frequently used in exhaust applications
where air particulate sizes are small, such as dust streams, smoke and steam and applications
that require reverse airflow.
The reverse flow characteristic is useful when an environment may require contaminated air to
be exhausted or in reverse flow, fresh air to be supplied.
Fans are usually selected from a manufacturer range of models and sizes, rather than designed
specifically for a particular application.
Fan selection is based on calculating the airflow and pressure requirements of a system, then finding
a fan of the right design and materials to meet these requirements.
Noise reduction can be accomplished by insulating the duct, mounting the fan on rubber pads or spring
isolators to limit the transmitted vibration energy, or installing sound damping material and baffles to
absorb the noise energy.
a) Forward-Curved Blades. This fan type, shown below, are typically used in applications that require
low to medium air volumes at low pressure, well suited for HVAC applications, but, limited for cleaning
systems. This type has low efficiency between 55% and 65% and can operate at relatively low speeds,
with low levels of noise, commonly selected because of their small size comparing to other fan types.
b) Radial-Blade. This fan type, shown below, is commonly used in applications with low to medium
airflow rates at high pressures. The flat blades, coated with protective compounds to improve erosion and
corrosion resistance, are capable of handling high-particulate airstreams, including dust, wood chips, and
metal scrap.
c) Radial-Tip. This fan type, shown below, is well-suited for use with airstreams that have small
particulates at moderate concentrations and airstreams with high moisture contents. Radial-tip fans have
low angle of attack between the blades which promotes low turbulence. Radial-tip fans can have
efficiencies up to 75%.
d) Backward-Inclined Fans. These fans types, shown below, have three different blade shapes: flat,
curved, and airfoil.
Flat blade types are more robust, curved-blade fans are efficient but the airfoil-type blades are the most
efficient of all and capable of achieving efficiencies exceeding 85%, commonly selected for forced -draft
service to relatively clean airstream systems.
a) Propeller Fans. This fan type, shown below, generates high airflow rates but, creates low pressures
so, is very limited to extensive ductwork application. Propeller fans tend to be comparatively noisy
reflecting inefficient operation, then, are often used in rooftop ventilation applications.
b) Tube Axial Fans. This fan type, shown below, is used in medium-pressure and high airflow rate
applications and is well-suited for ducted HVAC installations and also frequently used in exhaust
applications because they create sufficient pressure to overcome duct losses accompanied by moderate
airflow noise.
c) Vane Axial Fans. This fan type, shown below, is typically used in medium-to high-pressure
applications, such as induced draft service for a boiler exhaust and ventilation applications where quick
air removal or supply is required. Like other axial fans, vane axial fans can generate flow in reverse
direction, which is also helpful in ventilation applications.
a) Inline Flow Centrifugal Fans. This type of fan, shown below, has backward-curved blades and a
special housing to permit a straight line duct installation. The wheel is very similar to that of the airfoil, but
space requirements are similar to a vane axial fan.
b) Power Roof Ventilators. This type of fan, shown below, has a special housing to permit a straight line
roof installation to produce a high-volume flow at low pressure and can be centrifugal or axial type.
Horsepower (HP). The equations, below, to determine the required horsepower to drive fans or blowers
do not compensate for temperature, density or airflow characteristics. HP is the power required to move a
given volume against a given pressure.
Or:
Or:
For purpose of estimating, the efficiency of a fan or blower may be assumed to be 0.65.
Notes:
Brake Horsepower (BHP): Is the actual horsepower required to drive the fan, includes other
inefficiencies plus bearing losses. To calculate the BHP use the following formula:
Obs.: Once the BHP is known, the RPM of the fan can be measured. The motor BHP and fan RPM can
then be matched on the fan performance curve to approximate airflow.
The total pressure (TP) represents all energy requirements for moving air through the ventilation system.
TP = TP outlet - TP inlet;
TP = SPout - VP out - SPin - VP in;
TP = SPout – Spin.
The operation of is often expressed in the terms of Total Pressure, Air Flow and Velocity Pressure:
TP = SP + DP = constant ;
TP = SP + VP.
VP = (V / 4005) 2
V = 4005 (VP) 0.5
Q=VxA
V = Q/V
Where:
The Dynamic Pressure (DP), measured between the fan air inlet and the fan air outlet, can also be
expressed:
DP = ρ V 2
2
Where:
Examples:
1) Find the Fan Total Pressure (TP) given that the SP (inlet) = -5.0 in WG, SP (outlet) = +0.40 in. WG.
2) Calculate de Air Velocity (V) and the Velocity Pressure (VP) for the below data:
Fan Air Flow Rate, Q = 4000 CFM; Duct Size: 10” x 36”;
Outlet Duct Cross-Sectional Area, A = 10 x 36/144 = 2.5 ft2.
The pressure drop occurs at the fan inlet of a Cooling Tower fan stack unless the shape of the fan inlet
is elliptical and no obstruction, in case of induced draft fan arrangement.
The following fan table below could be applied to a Cooling Tower fan as a guide line in choosing the
pressure drop coefficient or the ventilation constant (K).
Or:
Then:
Where:
And,
Pd = Pressure Drop ;
K = Pressure Drop Coefficient/Ventilation Constant ;
ρ = Air Density, lb/ft³;
V = Air Velocity, ft/min.
The constant of 4008.7 was obtained to convert the unit of pressure drop to inch WG. Therefore
relation for Velocity and Velocity Pressure became:
VP = (V / 4005) 2
and
Term used in fluid mechanics to represent the internal energy of a fluid due to the pressure exerted on its
container. It may also be called static pressure head or simply static head.
The head as a function of air flow volume is, in general, presented in diagrams as shown below:
The red lines are the pressure head as a function of the air flow and the speed of the fan.
The green lines marked - l - are the throttle lines.
The blue lines are the power consumption of the fan.
Since pressure gauges often are calibrated in pressure - psi or bar, it may be necessary a conversion to
head - feet or meter, commonly used in pump curves.
Pump curves in feet of head can be converted to pressure - psi - by the expression:
p = 0.434 h SG (1)
Where:
p = Pressure (psi);
h = Head (ft);
SG = Specific Gravity.
Pump curves in meter of head can be converted to pressure - bar - by the expression:
p = 0.0981 h SG (2)
Where:
h = Head (m);
p = Pressure (bar).
h = p 2.31 / SG (3)
Where:
h = Head (ft);
p = Pressure (psi).
h = p 10.197 / SG (4)
Where:
h = Head (m);
p = Pressure (bar).
Example:
1) Converting Pump Head - feet - to Pressure – psi. The pressure - psi - of a water pump operating with
head 120 ft can be expressed as:
The Coefficient of Entry (Ce), a factor usually ranging between 0.6 and 0.98, indicates the relationship
between the actual hood turbulence losses, and that of a "perfect" hood with no turbulence losses
(coefficient of entry is the ratio of actual flow and theoretical flow).
Using the Static Pressure (SP) and Velocity Pressure (VP), a fairly accurate estimation of flow rate of
an exhaust opening can be determined, with Coefficient of Entry (Ce).
Hood shapes can vary widely, but most have hood openings of between 70% and 100% of the
corresponding duct area.
The Coefficient of Entry can also be estimated using the following formula:
Ce = (1 / 1+K) 0.5
Or:
Where:
Some typical coefficients of entry, Ce, and entry loss, K, are as follows:
Note: In calculations using the Velocity Pressure, the hood entry loss for chipping and grinding
operations, as an example, is 0.25 VP.
For calculation of velocity pressures at velocities other than those listed below:
VP = (V / 4005)2 =
V = 4005 √VP =
Q = 4005 Ce A √ SPh =
Or:
Where:
Examples:
1) A fan will be designed for a Cooling Tower with an impeller diameter 28 ft and a hub diameter 88
inch (7.33 ft). The fan inlet shape is rounded R/D = 0.10. The airflow volume of the Cooling Tower at the
drift eliminator is 1,019,716.3 ft³/min. Estimate the pressure drop at the fan inlet with the following data:
Air density and specific volume at 97°F and 100% RH is 0.0696 lb/ft³;
Air standard density is 0.075 lb/ft³.
Q=VxA=
For a fan inlet shape R/D = 0.10, K total factor is = 0.18 (see fan table). Then the pressure drop is:
2) Calculate the hood SP, when the Velocity Pressure is 3.2 in. WG and the Coefficient of Entry is 0.96.
Where:
Ce = Coefficient of Entry;
VP = Velocity Pressure;
SP = Static Pressure.
3) If the Static Pressure is 2.56 in. WG and the Coefficient of Entry is 0.92, calculate the VP.
Solution:
4) The Velocity Pressure in the duct is 3.15 in. WG. Calculate is the Velocity in the duct.
Solution:
Where:
V = Velocity in fpm;
VP = Velocity Pressure in inches of water (WG).
5) The Velocity in a duct is 4000 fpm and the area of the duct is 1.5 m², what is the flow rate?
Solution:
Q=A*V=
Where:
Q = Flow rate,;
A = Cross-sectional area (1.5 m² = 16.145 ft²);
V = Velocity.
6) The rate of flow in a pipe is 350 m³/s and the area of the pipe is 25 ft², calculate the flow Velocity.
Solution:
7) Calculate the Velocity in m/s, when the Velocity Pressure in a hood is 2.20 cm of water.
Solution:
Where:
V = Velocity in fpm;
VP = Velocity Pressure in inch of water (2.20 cm WG = 0.866 in. WG).
8) Air flows in a 3 ft diameter circular duct. At the end of a long straight run the centerline Velocity is
measured to be 20m/s. Estimate the average Velocity and mass flow rate of the air.
Solution:
Vaverage:
9) The transport Velocity is 4500 fpm and the duct is diameter 2 ft. What air flow is needed?
Solution:
Smoke is useful for measuring rate velocity (see below) because it is visible. Nothing convinces more
quickly that the ventilation is not functioning properly than to show smoke drifting away from the hood,
escaping the hood, or traveling into the worker's breathing zone.
Velocity = Distance/Time =
V=D=
t
If the air stream temperature is greater than 100°F and/or if the altitude is greater than 1,000 feet, add
a density correction factor to the above equation:
Where:
ρ = Relative Density of air.
Obs.: Commonly the density correction is not needed if the temperature is between 40°F to 100°F and
elevations are between 100 ft. to 1000 ft.
Examples:
1) A fan is selected to deliver 7500 CFM at 1.5 inch SP at an altitude of 6000 ft above sea level and an
operating temperature of 200° F. At Air Standard conditions and ambient temperature the fan is 3.53
BHP at 976 RPM.
Solution:
From the table above, Air Density Factors for Altitude and Temperature, the air density correction
factor is 1.56. Using the fan’s operating altitude and temperature the correction is:
At Air Standard conditions and temperature the fan is required to be 3.53 BHP. This should be
corrected to new altitude condition that is 6000 ft above sea level:
2) A centrifugal fan with 20 inches impeller diameter is required to deliver 5,000 CFM at 3.0 in. WG,
Static Pressure (SP). Elevation is 0 (sea level). At Air Standard conditions and temperature between
40°F and 100°F, the fan will require 6.76 BHP. What is the operating BHP at 600 F?
Solution:
As a rule of thumb, the following table gives average capacities for various sizes of fans and the
corresponding horse-power of electric motor for fans of the blower type having curved blades when run at
a speed corresponding to 1/2 ounce pressure at the discharge outlet.
Centrifugal Fan - flow within the fan is mainly Axial Fan - flow within the fan is mainly parallel to
radial to the shaft. the shaft.
The fans operate under a predictable set of laws concerning speed, power and pressure. A change in
speed (revolutions per minute or RPM) of any fan will predictably change the pressure rise and power
necessary to operate it at the new RPM.
Fans basic calculations and their characteristics are summarized in the tables below:
Fan Type Wheel Type Static Impeller Air Flow Break Horse
Pressure Diameter (cubic feet per Power
(inches WG) (inches) minute) (bhp)
Backward
0 - 12 10 - 75 500 - 125, 000 1/3 - 200
Inclined
Centrifugal
Backward
0 - 14 20 - 120 1, 500 - 450, 000 1/3 - 1500
Inclined Airfoil
Propeller Axial Direct Drive 0-1 10 - 50 50 - 50, 000 1/6 - 10
Tube Axial Direct Drive 0-1 20 - 50 2, 500 - 50, 000 1/3 - 15
Vane Axial Direct Drive 0-5 20 - 60 1, 200 - 150, 000 1/3 - 150
When the measured inlet suction pressure exceeds 10 in WG (270 mm WG) the change in air density
should be compensated by increasing the suction pressures with a correction factor.
ScP = Ps x f =
Where:
Example:
1) For a measured suction pressure Ps = -14 in. WG. The correction factor from table above is 1.04.
For proper fan selection the suction pressure should be corrected to:
NTP - Normal Temperature and Pressure – is commonly used as a standard condition for testing and
documentation of fan capacities. The standard conditions are:
Most fan drive systems are based on the standard "V" drive belt which is relatively efficient and readily
available and easily selected through a combination of AC motor RPM and drive pulley ratios. Calculate
the approximate belt length using the following formula:
The fans and blowers drive arrangements are standardized by AMCA (Air Movement and Control
Association) may be belt or direct electric motor driven:
1) Centers should not exceed 2.5 to 3 times the sum of the sheave diameters or be less than the
diameter of the larger sheave.
2) The arc of contact on the smaller sheave should be not less than 120º.
3) Sheave diameter ratios should not exceed 8:1.
4) Belt speed should not exceed 5000 ft/min, or be less than 1000 ft/min, anyway, 4000 ft/min is the
best practice.
5) Sheaves should be dynamically balanced for impeller speeds above 5000 ft/min.
The fan blowers positions depends entirely on application design. The standard positions are:
25.) Vibration:
The natural frequency of a system is the frequency at which the system prefers to vibrate. It can be
calculated by the following equation:
The static deflection corresponding to this natural frequency can be calculated by the following equation:
Sd = (188/fn)2 (inches) =
By adding vibration isolation, the transmission of vibration can be minimized. A common rule of thumb
for selection of vibration isolation is as follows:
The term “ductwork” denotes all the equipment between capture devices of particulates and the control
devices, including: straight ducts, fittings (elbows and tees), flow control devices (dampers) and duct
supports. The design of the ductworks in ventilation systems are often done by using:
A=Q/V=
Where:
The proper velocity depends on the application. The table below indicates common velocity limits:
Main ducts 800~1400 ft/min (4 ~ 7 m/s) 1600~1400 ft/min (8 ~ 12 m/s) 2000~3500 ft/min (10 ~ 18 m/s)
Main branch ducts 600~1000 ft/min (3 ~ 5 m/s) 1000~1600 ft/min (5 ~ 8 m/s) 1200~2400 ft/min (6 ~ 12 m/s)
Branch ducts 200~600 ft/min (1 ~ 3 m/s) 600~1000 ft/min (3 ~ 5 m/s) 1000~1600 ft/min (5 ~ 8 m/s)
Note.: Be aware that high velocities close to outlets and inlets may generate unacceptable noise.
©2011 Jurandir Primo Page 23 of 47
www.PDHcenter.com PDH Course M385 www.PDHonline.org
Chart friction loss or head loss (k) in standard air ducts are indicated in the diagram below:
Example:
In a 20 inches duct diameter with air flow 4000 cfm and air velocity approximately 2000 fpm, the
friction loss is approximately 0.25 inches water per 100 feet duct as shown in the diagram above.
The diagram is based on standard air 0.075 lb/ft3 in clean round galvanized metal ducts.
1 inch water = 249 N/m2 (Pa) = 0.036 lb/in2 (psi) = 25.4 kg/m2 = 0.0739 in mercury;
1 ft3/min (CFM) = 1.7 m3/h = 0.47 l/s;
1 ft/min (FPM) = 0.00508 m/s.
2.1) Equivalent diameters for rectangular and circular ducts - Air flows between 100 - 50,000 cfm:
The table below is based on the ducts friction loss formula, adapted to the equal friction loss method of
sizing ventilation duct systems. An approximate friction loss of 0.8 inches WG per 100 ft duct is used.
Air flow - Q Rectangular Duct Sizes Equivalent Diameter Velocity - V Friction Loss
(ft³/min, cfm) (Inches) Round Duct Sizes (ft/min) (Inch WG
(m3/s) (Inches) (m/s) per 100 ft duct)
200 (0.09) (3 x 7) – (4 x 5) 4.9 1527 (7.8) 0.88
300 (0.14) (4 x 7) – (5 x 6) 5.7 ~ 6.0 1635 (8.3) 0.82
400 (0.19) (4 x 9) – (5 x 7) – (6 x 6) 6.4 ~ 6.6 1736 (8.8) 0.80
500 (0.24) (6 x 7) 7.1 1819 (9.2) 0.78
750 (0.35) (5 x 12) – (6 x 10) – (7 x 8) 8.3 ~ 8.4 1996 (10.1) 0.77
1000 (0.47) (7 x 10) – (8 x 9) 9.1 ~ 9.3 2166 (11) 0.79
1250 (0.59) (8 x 10) – (9 x 9) 9.8 2386 (12.1) 0.88
1500 (0.71) (8 x 12) – (10 x 10) 10.7 ~ 10.9 2358 (11.9) 0.77
2000 (0.94) (8 x 15) – (10 x 12) 11.8 ~ 12.0 2589 (13.2) 0.81
2500 (1.2) (10 x 14) – (12 x 12) 12.9 ~ 13.1 2712 (13.8) 0.8
3000 (1.4) (12 x 14) 14.1 2767 (14.1) 0.75
3500 (1.7) (12 x 15) 14.6 3010 (15.3) 0.84
4000 (1.9) (10 x 22) – (14 x 15) 15.9 ~ 15.8 2938 (14.9) 0.73
4500 (2.1) (12 x 19) – (14 x 16) 16.4 3068 (15.6) 0.76
5000 (2.4) (10 x 25)-(12 x 20)-(15 x 16) 16.9 3248 (16.5) 0.82
6000 (2.8) (14 x 20) – (15 x 18) 17.9 ~18.2 3358 (17.1) 0.8
7000 (3.3) (12 x 26) – (16 x 20) 19.0 ~ 19.5 3482 (17.7) 0.8
8000 (3.8) (12 x 30) – (14 x 25) 20.2 3595 (18.3) 0.8
9000 (4.3) (12 x 34) – (15 x 25) 21.4 ~ 21.0 3671 (18.6) 0.78
10000 (4.7) (12 x 36)–(16 x 25)-(20 x 20) 21.9 ~ 21.9 3858 (19.6) 0.83
15000 (7.1) (16 x 36)-(18 x 30)-(23 x 25) 24.7 ~ 26.2 4331 (22) 0.87
17500 (8.3) (16 x 40)-(20 x 32)-(25 x 25) 27.0 ~ 27.5 4337 (22) 0.79
20000 (9.4) (20 x 35) – (25 x 28) 28.6 ~ 28.9 4483 (22.8) 0.79
25000 (11.8) (16 x 55)-(20 x 43)-(25 x 38) 31.0 ~ 33.5 4709 (23.9) 0.78
30000 (14.2) (20 x 50) – (30 x 32) 33.7 ~ 33.9 4815 (24.5) 0.74
35000 (16.5) (20 x 55) – (30 x 35) 35.2 ~ 35.4 5179 (26.3) 0.81
40000 (18.9) (25 x 48) – (30 x 40) 37.4 ~ 37.8 5243 (26.6) 0.77
45000 (21.2) (32 x 40) 39.1 5397 (27.4) 0.77
50000 (23.6) (32 x 45) – (35 x 40) 40.9 ~ 41.3 5222 (26.5) 0.66
Examples:
a) Air flows in a 0.6 m diameter circular duct. At the end of a long straight run the centerline velocity is
measured to be 9 m/sec. Estimate the average velocity and mass flow rate of the air assuming
standard conditions for the air.
Assuming a parabolic velocity distribution inside the duct, average velocity is 2/3 of centerline velocity.
Solution:
c) Assume duct diameter 54.33 inches, length 100 feet, velocity 4000 fpm and that air is flowing
through a black iron duct. Calculate the friction factor using Wright's and Darcy-Weisbach equations.
Where:
h = 12 x (f / D) * L x VP =
Where:
D = 35 microns ; D= 10 microns;
Specific gravity = 0.80; Specific gravity = 1.8.
Solution:
V = 0.0052 x SG x D² =
Where:
V = Velocity in fpm;
SG = Specific gravity;
D = Diameter in microns.
e) Determine the scfm of an air stream measured at 7000 cfm and 300°F.
Solution:
SCFM = ACFM x Ts / Ta =
Where:
Ductwork is fabricated from either metal or plastic, according to application, structural considerations,
purchase and installation costs, aesthetics, and other factors. Metals used include carbon steel (bare or
galvanized), stainless steel, and aluminum according to SMACNA (Sheet Metal and Air Conditioning
Contractors’ National Association) Standards.
The ductwork system consists of straight ducts, fittings, flow control devices, and supports. The “fittings”
change the direction of the ducted gas stream, modify the stream velocity, tie it to another duct(s),
facilitate the connection of two or more components, or provide for expansion/contraction when thermal
stresses arise using Expansion Joints.
b) Typical Fiitings:
4.) Insulation:
Serves to reduce heat loss/gain, saves energy and prevents noise and condensation. The insulation
layer is typically 1-inch, although 2- and 3-inch thicknesses, available for more extreme applications.
The thermal conductivities of these thicknesses are 0.27, 0.13, and 0.09 Btu/hr-ft²-ºF, respectively.
The bellows expansion joint, consists of a piece of flexible metal welded to connect two duct ends, to
allow the ductwork to expand or contract in response to temperature variation and thermal stresses.
For instance, silicone fiberglass and aramid fiber cloth can be used for duct temperatures of up to
500ºF, while coated fiberglass cloth is needed to accommodate temperatures of 1000ºF.
The last component to consider is the ductwork support system. The SMACNA - HVAC Duct
Construction Standards manual recommends the selection of a hanging system should not be taken
lightly, because the erection of an inadequate hanging system can be disastrous.
As a rule, a support should be provided for every 8 to 10 feet of duct run. Ductwork can be
suspended from a ceiling or other overhead structure via hangers or supported from below by girders,
pillars, or other supports.
When air or gas enters a hood, there is mechanical energy loss due to friction. This friction loss is
calculated using the equations described below:
The Static Gauge Pressure, SPh is the reference pressure at one atmosphere. The hood is under a
vacuum created by a fan downstream and should be always calculated considering the standard
pressure and temperature. The empirical equations to estimate the pressure loss factors (K) are:
K = (SPh) / VP) – 1 =
K = (Sph) – VP) / VP =
The hood loss factor (K) varies according to the hood shape. It can range from 0.04 to 1.78 for various
slotted hoods. The parameter related to the hood loss factor is the Coefficient of Entry, Ce defined as:
Ce = (1 / 1 + K) 0.5
(or) Ce = (VP / SP) 0.5
Example:
a) In some duct the transport velocity (V) is 3,500 ft/min and the Static Gauge Pressure, (SPh) is 1.75 in.
WG. Calculate the loss factor (K) and Coefficient of Entry (Ce) considering standard temperature.
VP = (V / 4005)2
VP = (3500 / 4005)2 = 0.76” in WG.
K = (SPh / VP) – 1
K = (1.75) / 0.76) – 1 = 1.30 (unitless).
Ce = (1 / 1 + K)0.5 =
Ce = (1 / 1 + 1.30)0.5 = 0.66 (unitless).
The face velocity is the average velocity of the air passing through the hood inlet (face). A similar
parameter is the slot velocity, which is the average air velocity through the hood slot openings, whose
areas is only a fraction of the entire hood face area. The parameters are in tne table below:
A simple sizing method for estimating purposes to determine the volumetric flow rate (Q) through the
hood and ductwork, the following equation below can be used:
Q = 1.4.P.X.Vs =
Where:
Example:
a) A circular canopy hood is being used to capture emissions from a Chromium Electroplating Tank, 8-
foot diameter. The hood face is 6 feet above the tank, 40% bigger than the tank diameter. The capture
velocity is 200 ft/min. At air standard conditions, calculate the required volumetric flow rate, the hood
face area, and the hood face velocity.
Solution:
Q = 1.4.P.X.Vs =
The hood diameter is 40% greater than the tank diameter. Then, the hood face area is:
Vs = Q / A =
Can be fabricated of steel, brick, or plastic (fiberglass-reinforced plastic, or FRP), installed after control
devices to disperse the exhaust gases above ground level and surrounding buildings.
For study purposes, the only two stack design parameters that need to be determined are the stack
diameter and the stack height. The other variables (wall thickness) are incorporated into the equipment.
The stack diameter (Ds) can be calculated via the duct diameter formula:
Ds = 1.128 (Q / Vs)0.5 =
Height should be dimensioned according to application. Short stacks are no taller than 120 feet. Tall
stacks can be up to 1,000 feet high.
Example:
a) A fabric filter handling 16,500 ft³/min of cocoa dust must be dispersed through a stack. Calculate the
diameter of the stack knowing that the minimum transport velocity is 3000 ft/min.
Ds = 1.128 (Q / Vs)0.5 =
b) Assume a 4 inch duct diameter 0.087 ft² using a bench grinder hood Ce = 0.78 and velocity 4000
fpm. Calculate Velocity Pressure, Static Pressure and Flow Rate.
Q=VxA=
Q = 348 cfm.
If air is used for cooling, the needed air flow rate may be expressed as:
Qc = Wc / ρ Cp (To - T r) =
Where:
If air is used for heating, the needed air flow rate may be expressed as:
Qh = Wh / ρ Cp (Ti - To) =
Where:
Example:
a) If the heat load is Wh = 400 W, supply temperature Ti = 30oC and the room temperature To = 22oC,
the air flow rate can be calculated as:
Qh = Wh / ρ Cp (Ti - To) =
The Industrial Ventilation Manual gives ranges for various processes as shown in the table below:
Some additional guidelines for the use of slot hoods are as follows:
Based upon the above criteria, tables have been constructed to provide guidelines for tank ventilation
with lateral (side slot) exhaust:
Required Min. CFM per Square Foot Tank Area to Maintain the Required Minimum Control
Control Velocity, Velocities at the Following Tank Width to Length Ratios (W/L)
fpm 0.00-0.09 0.10-0.24 0.25-0.49 0.50-0.99 1.00-2.00
For a hood along one side or two parallel sides of a tank when one hood is against a wall or baffle. Also
for a manifold along the tank centerline.
50 50 60 75 90 100
75 75 90 110 130 150
100 100 125 150 175 200
150 150 190 225 250 250
Hood along one side or two parallel sides of a free standing tank not against a wall or baffle.
50 75 90 100 110 125
75 110 130 150 170 190
100 150 175 200 225 250
150 225 250 250 250 250
Use W/2 as the tank width when the manifold is along the centerline or two parallel sides of the tank.
The equation for calculating flow for round or essentially square free hanging hoods is:
V(x) = Q / (10. X2 + A) =
Where:
The velocity of the air stream moving toward the hood is (approximately) inversely proportional to the
square of the distance from the slot or hood opening. This emphasizes how important hood location is.
Air volume and velocity ratios for some rectangular shapes may be represented as follows:
Air flow at the entrance and exit of a fan should be as smooth as possible to minimize the generation
of turbulence. The conditions that produce turbulent air flow usually result in greater noise generation
and increase Static Pressure Drop in the system. The design conditions are shown below:
Where:
Where:
The capacity of a chimney depends on the potential chimney draft - the pressure difference created by
the inside and outside air temperature difference and chimney height - and the chimney area.
The pressure difference in the chimney, pulls air and fuel gas from the boiler or fireplace through the
chimney and out of the building.
Where:
Dpc = 0.0465.dt.h =
Where:
The velocity of air and flue gas in a smaller furnace should not exceed 2 m/s. Design velocities of
larger furnaces should not exceed 10 m/s. Required chimney area can be calculated as:
A=Q/V=
Where:
a) Air Change Method: Involves calculating the necessary number of air changes necessary to give
the proper ventilation for a given space using the following equation:
b) Heat Removal Method: The average outside temperature, necessary inside temperature and
Btu/min are required for this method. This formula gives the amount of air to be passed through
the building to maintain desired inside temperature, using the following equation:
Commonly known as baghouses, fabric collectors use filtration to separate dust particulates from dusty
gases and can achieve a collection efficiency of more than 99% for very fine particulates.
The dusty-laden gases enter the baghouses and pass through fabric bags that act as filters. The bags
can be of woven or felted cotton, synthetic, or glass-fiber material in either a tube or envelope shape.
Dust concentration and particle size: For minerals processing operations, the dust concentration can
range from 0.1 to 5.0 grains per cubic feet of air (0.23 to 11.44 grams per standard cubic meter),
and the particle size can vary from 0.5 to 100 µm.
Characteristics of airstream: The characteristics of the airstream can have a significant impact on
collector selection. For example, cotton fabric filters cannot be used where air temperatures exceed
180°F (82°C). Also, condensation of steam or water vapor can blind bags.
The cleaning methods for baghouses, using the typical Air to Cloth ratio are:
The following method will estimate the fan size, air flow rate (cfm), using the surface area of the bags
and a typical Air to Cloth ratio.
The Air to Cloth ratio is the amount of air (ACFM) or process gas entering the baghouses.
Examples:
a) Calculate the main data for a bag diameter, 10 inches, length 8 ft, quantity 200 bag filters.
Determine the Filter Area of all the bags, using the bag length:
Calculate the Flow Rate, using the Filter Area and Air to Cloth ratio:
b) Calculate the Air to Cloth ratio for a 10’ bag with a 6” tube sheet hole (actual diameter 5.875”)
whose baghouses is handling 10,000 ACFM with 144 bags.
Air to Cloth ratio = 10,000 ACFM / 144 x 15.38 ft = 10,000 / 2214 = 4.52 : 1
c) Calculate the number of bags required for an 8-compartment pulse-jet baghouses with a process
gas exhaust rate, Q =100,000 ft³/min and Air to Cloth (A/C) ratio = 4 (ft³/min)/ft², bag diameter = 6
inches (0.5 ft) x 12 ft height:
Solution:
Where:
Ab = π.D.h =
d) If the cloth area (Ac) is known to be 4,050 ft², how many bags would be used in a baghouses with the
bag area of 78.5 ft².?
Number of Bags = 52
Electrostatic precipitators, described here only for reference in ventilation systems, use electrostatic
forces to separate dust particles from exhaust gases. A number of high-voltage, direct-current discharge
electrodes are placed between grounded collecting electrodes.
Low-voltage, two-stage: Two-stage precipitators use a similar principle; however, the ionizing
section is followed by collection plates. The low-voltage, two-stage precipitator is generally used
for filtration in air-conditioning systems.
Pneumatic conveying can be used for particles ranging from fine powders to pellets and bulk densities of
1 to 200 lb/ft³ - (16 to 3200 kg/m 3). Most millwork plants deal with dry wood in the form of sawdust and
shavings. The bulk densities of these materials are in the range of 24 lb/ft³.
The pneumatic systems are defined as low pressure systems, up to 18 inches WG static pressure. A
15,000 cfm fan system could transport 22.5 lb material per minute. With this value of material loading,
the mixture of air and material can be treated as if the load were exclusively air.
Examples:
a) Conveying sawdust at a rate of 1800 lb/h through a 6” pipe with a material loading ratio of 1:2 will
result in an air velocity of:
Solution:
ACFM = 26,000;
Material Loading = 19,500 lb/h;
Air Inlet Density = 0.05 lb/ft².
Solution:
In general, materials up to approximately 50 lb/ft³ can be conveyed with an air velocity of 5000 fpm.
Once the calculations for the system have been performed and the appropriate pipe size has been
selected based on material being conveyed, the required flow rate of the fan is:
Note: SCFM (Standard Cubic Feet per Minute): a volume of air at 0.075 lbs/ft.³ standard density is used
at sea level, temperature at 70 ºF.
For displacement ventilation systems, designers normally assume that all pollutants follow the buoyant
air flow into an upper zone. The ventilation systems are designed with exhaust fans or blowers in line
with ducts and air cleaners exiting the clean air to atmosphere. A variety pollutant powder of organic or
inorganic bulky materials like stones, chalk, fertilizers, saw dust, wood chips, fumes and particles can be
exhausted to filter bags or any other pollution control equipment using canopies or plain openings, as
shown in the sketch below:
a) Chute to belt transfer and conveyor transfer for dusty materials as follows:
Note: From American Conference of Governmental Industrial Hygienists (ACGIH®) Industrial Ventilation:
rd
A Manual of Recommended Practice, 23 Edition.
Duct and fitting losses for some common shapes are given below as a fraction of the VP. These are often
converted to equivalent lengths of straight run duct for summing losses:
Use the Chart Friction Loss (see chapter III) to look up the pressure loss per 100 ft of duct.
Every air system or sub-system has a system constant (K). This constant (K) can be calculated as long as
you know one (CFM, Static Pressure) point. To calculate the system constant:
Once you have the system constant you can calculate the Static Pressure for any flow rate.
K
L/D
Degº 0 1 2 3 4 6 8 10 12 14 20 25 40
60 2.0 1.90 1.50 1.35 1.30 1.20 1.25 1.50 1.63 1.73 1.85 1.95 2.0
90 2.0 1.80 1.60 1.55 1.55 1.65 1.80 1.90 1.93 1.98 2.0 2.0 2.0
Now calculate Velocity, Velocity Pressure and Frictional Loss for each section.
Section 1:
Section 2:
Section 3:
Cyclonic separation is a method of removing particulates from air, gas or water stream, using cylindrical
or conical vessels called cyclones. Fans or blowers commonly suck the air in line after the cyclones. Air
flows in a spiral pattern, beginning at the wide top of the cyclone and ending at the narrow bottom end
before exiting the cyclone in a straight stream through the center of the cyclone and out the top.
Obs.: Larger or denser particles entering the rotating stream have much inertia to follow the tight curve of
the top outlet nozzle and when strike the outside wall, fall to the bottom of the cyclone to be removed.
In a conical system, as the rotating flow moves towards the narrow end of the cyclone the rotational
radius of the stream is reduced, separating smaller and smaller particles. The cyclone geometry, together
with flow rate, defines the cut point of the cyclone. This is the size of particle that will be removed from
the stream with 50% efficiency. Large scale cyclones are used in sawmills to remove sawdust, in oil
refineries to separate oils and gases and in the cement industry as components of kiln pre-heaters.
Analogous devices for separating particles or solids from liquids are called hydrocyclones, used to
separate solid waste from water in wastewater and sewage treatment.