Test-Lamp - T-229-4P v5

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

1

Test Lamp T-229/4P for UV, IR and


UV/IR Flame detectors

 Installation instructions
 User Guide
 Specifications Optional carrying
case
This document is available in 18 other languages on www.testlamp.com
Description:
®
The Sense-WARE T-229/4P flame detector test lamp activates UV, IR and UV/IR flame detectors which detect in
the 185-235 nm UV and 4.4 µ IR frequency ranges. For UV only detectors the maximum distance is up to 8 meters
(26 ft) in the continuous mode. The test range for IR and UV/IR detectors is up to 4 meters (13 ft).
Most IR Flame detectors have an extra alarm criterion; analyzing the flicker frequency of a fire. In order to simulate
the flame flicker, the lamp needs to be pulse operated. For this, the test lamp T-229/4P can be put into the pulse
mode by means of a selection switch on the left side of the test lamp. The lamp then emits pulsed light with a
frequency of approx. 2 Hz. After the alarm delay time the IR or UV/IR flame detector will activate.

Specifications:
Adapter (charger) 100-240 Vac, 500 mA switching with plugs for US, EU, GB and AU
Test range UV flame detectors up to 8 m (26 ft) in continue mode, up to 4 m (13 ft) in pulse mode
Test range IR and UV/IR flame detectors up to 4 m (13 ft)
Battery sealed Lead Acid battery, 12 Vdc / 2.7 Ah
Lamp H3, 12 Vdc / 100 W
Use 10-15 minutes under optimal conditions and continuous use
Housing ABS (plastic) black
Shipping dimensions (box) 310 x 220 x 210 mm (12 5/8 x 9 x 8 5/8 “ )
Shipping weight 2.1 kg (4.62 lbs)
Ingress protection rating IP30 / NEMA 1
0 0
Temperature range +4 to +40 C (+39 to +104 F)
Country of Origin/Intrastatistic Number EU, 8531 10 30
Optional carrying case
Material Case: polypropylene, inlay polyurethane
Shipping dimensions (box) 440 x 340 x 280 mm (17 3/8 x 13 3/8 x 11 “ )
Shipping weight incl. test lamp 5.0 kg (11.1 lbs)

Operation:
Before a test is carried out make sure the flame detector is switched on and the alarm outputs are in override. Please
avoid unwanted alarm signals as a result of your test.

The test lamp will turn on/off by pressing/releasing the trigger.

1. Point at the flame detector within the test distance and on the central axis
of the cone of vision of the detector.
2. Press the trigger and wait until the Flame detector is activated.
3. Verify that the switch on the left of the test lamp is in the continuous
mode (see figure on the RHS of this page). For the For IR or UV/IR continuous mode pulse mode
detectors the switch on the left of the test lamp should be in the pulse
mode. In this mode the test lamp emits light with a pulse frequency of approx. 2 Hz.
4. Operate the test lamp for at least the selected delay time of the detector. Most flame detectors will respond within
30 seconds when the test criteria have been met.
5. Do not use the test lamp in intermittent operation or in continuous mode for longer than 1 minute.
6. Wait at least 30 seconds after each test before performing the next test.

SW_IN_UV-IR_test-lamp_T-229-4P_v5_EN
2
First use:

1. Remove the cover of the battery compartment (on the top of the test lamp).
2. Take the battery.
3. Place the battery back into the battery compartment in such a way that the terminals of
the 12 Vdc battery are making contact with the terminals of the lamp.
4. Place the cover of the battery compartment in the original position.
5. Charge the battery for at least 4 hours (6 hours max.).
Remark:
The battery is already charged when leaving the factory. However, the unit should be charged immediately after
purchase

Charging:
1. Plug in the charger and apply the charger cable to the Test Lamp. The charge time for a completely discharged
battery is +/- 4 hours. Do not charge for more than 6 hours.
2. The Test Lamp must be fully charged when stored immediately after use, before the test lamp is stored.
3. Every 3 months the unit should be recharged when stored without using.
4. During charging the red LED on the left of the test lamp is on. However, when the test lamp is completely
discharged, during the first hours the red LED may be off.

Please read the following instructions carefully:


1. The life time of the battery is negatively influenced if you use the test lamp continuously longer than 10 minutes
and in one go.
2. The T-229/4P test lamp has a protective grate which should not be removed.
3. Do not stick objects through the grate.
4. Store the test lamp clean and dry. A dirty reflector will reduce the test range.
5. Do not use the test lamp in wet conditions.
6. Keep away from children.
7. Do not point directly at eyes from a short distance. Do not look directly into the light.
8. The test lamp should not be used when damaged.
®
9. Do not open the lamp, send it back for repair. Contact Sense-WARE for details.
10. Do not throw the unit in a fire. The battery could explode when exposed to intense heat.
11. Warning, after use the grate may be hot.
12. The sealed lead battery has a lifetime of several years. Please ask your local city official how to dispose the unit.
13. Not suitable for IR/IR- (dual IR), IR/IR/IR (IR3 or triple IR) flame detectors.
14. Make sure testing of the flame detectors does not activate unwanted alarm signals.
15. Only for use in safe areas.

Battery replacement
1. The battery can be ordered locally by means of the battery information in the specification.
2. Remove the cover from the battery compartment.
3. Slide the new battery in the battery compartment. Make sure that the poles are heading in the direction of the
terminals of the test lamp.
4. Place the cover of the battery compartment in the original position.
5. Charge the new battery charged immediately for at least 4 hours (6 hours max.). -
+
Battery specifications:
Battery type sealed rechargeable lead acid battery
Battery voltage and capacity 12 Vdc/ 2.7 Ah
Terminal type spade 103

Terminal position see drawing “battery terminal position”


Dimernsions l x w x h 103 x 70 x 46 mm 46
Type BATT4P 70
Battery terminal position

Please check the latest version of this instruction (several languages) on www.testlamp.com.

Due to the policy of continued product development Sense-WARE® Fire and Gas Detection BV reserves the right to alter or amend
information in their publications without prior notice and no responsibility can be accepted for errors or omissions.

SW_IN_UV-IR_test-lamp_T-229-4P_v5_EN