The combination of cost-effective design, power
density and reliability makes the Flatpack2 a
product family that truly stands outs and
provides unparalleled network availability.
FLATPACK2 48/2000
RECTIFIER MODULE
Doc 241115.100.DS3 – v12
POWER UTILITIES
• SCADA
FLATPACK2 SYSTEM IN TYPE3 OUTDOOR CABINET FLATPACK2 2U 150A SYSTEM
Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com
FLATPACK2 48/2000
RECTIFIER MODULE
INPUT DATA
Voltage (nominal) 185 - 275 VAC
Voltage (operating range) 85 - 300 VAC1)
Frequency 44 - 66 Hz
Current (maximum) @ nominal input, full load 12.5 ARMS
Power Factor > 0.99 above 50% load
Protection Fuse in L & N, Varistors, Disconnect above 290 VAC
OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.5 - 57.6 VDC
Power maximum (@ nominal input) 2000 W
Power maximum (@ 85 VAC input) 850 W
Current (maximum) @ nominal input, full load 41.7 A (@ 48 VDC)
Current sharing (10 - 100% load) ±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) ±0.5%
Dynamic Voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time, 1500 W output power >20ms; output voltage > 43.5 VDC
Ripple and noise < 100 mV peak to peak, 30 MHz bandwidth, < 0.96 mVRMS psophometric noise
Protection ORing diode, Short circuit proof, High temperature protection, Overvoltage shutdown
OTHER SPECIFICATIONS
Efficiency @ nominal input Up to 92.5%
Isolation 3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth
Alarms: Red LED Low and high input voltage shutdown, High and low temperature shutdown, Rectifier
Failure, Overvoltage shutdown on output, Fan failure, Low output voltage alarm at
43.5VDC, CAN bus failure
Warnings: Yellow LED Rectifier in power de-rate mode, Remote output current limit activated, Input voltage out
of range, flashing at overvoltage, Loss of CAN communication with controller
Normal operation: Green LED
Cooling Single fan (front to back airflow, temperature and load regulated speed) 2)
Acoustic noise < 55dBA at nominal input and full load (Tambient < 30°C)
MTBF (Telcordia SR-332 Issue I method III (a)) >350 000 (@ Tambient : 25 °C)
Operating temperature -40 to + 75°C [-40 to +167°F] humidity 5 - 95% RH non-condensing
Maximum output power derates above temp / to 45°C [113°F] / 1350 W @ 75°C [+167°F]
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.9 kg (4.2 lbs)
DESIGN STANDARDS
Electrical safety UL 60950-1:2007, IEC 60950-1:2005 + A1:2009
EN 60950-1: 2006 + A11:2009 + A1:2010 + A12:2011
EMC EN 61000-6-1:2007, -6-2:2005, - 6-3:2007 + A1:2011, - 6-4:2007 + A1:2011
ETSI EN 300 386 V.1.6.1, Telcordia NEBS GR1089 CORE
Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ETSI EN 300 132-2, Telcordia NEBS GR63 CORE Zone 4
RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant
1) also certified for 140 - 250 VDC, but will have de-rate maximum power 850 - 1900W
2) from HW revision 4. Two fans for HW revisions < 4