Site Acceptance Test (SAT)

SITE ACCEPTANCE TEST (SAT)

CUSTOMER : Chilime Jalavidhyut Company Limited


PROJECT : Chilime Hydro Electric Project,2x11.28MW
DOCUMENT NAME : 11KV Breaker Panel
DOCUMENT NO. : NICPL-137-01

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 1 of 31
Site Acceptance Test (SAT)

Introduction
This document describes the Generator Relay Metering Panel item to be tested on a SAT period. The SAT
will demonstrate the operation and integration of the UCB, Governor, SCADA, SYN system and verify the
hardware being supplied.

References
The following documents will be available as references during the SAT.

Ref Document Reference Description


1 AMB/2485/L01 Wiring drawings

Manufacturer/Model Number Serial Number Cal Cert Ref Cal Exp Date
Relay tester / ISA DRTS 33 2119/48617

Digital Multi meter / Fluke 46311178WS

Health and Safety

The tests to be conducted involve test and measurement operations with hazardous voltages present. All
tests must be performed by skilled persons taking due care and attention to avoid electrical shocks. The
tests are to be performed in the stated sequence to avoid danger. All faults during electrical testing must
be rectified or deemed by a qualified and competent person not to compromise safety before further
testing can proceed.

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 2 of 31
Site Acceptance Test (SAT)

11kV Switchgear Specification

Description
Make ABB
Type VD4
Standard IEC6227-100
Rated voltage 12KV
Rated insulation Voltage 12kV
Withstand Voltage 50HZ 28kV
Impulse Withstand Voltage 75kV
Rated frequency 50-60HZ
Rated Breaking Capacity 31.5kA
Rated Short time withstand Current 3(s) 31.5kA for 3 Sec
Closing coil operating Voltage 110V DC
Tripping coil Operating Voltage 110V DC

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 3 of 31
Site Acceptance Test (SAT)

Generator Incomer-1
Ammeter

Specification

Nomenclature AMMETER
Make Secure DPM I300
Aux. Volts 110VAC
Nominal Current 1/5A
Serial Number 80195331
CT Ratio 800/1A
Accuracy Class 0.5

SL .No Applied Current ( A) Measured current (A)


1 400A 401A
2 300A 301A
3 200A 199A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 4 of 31
Site Acceptance Test (SAT)

Current Transformer

Specification

Nomenclature Current transformer


Make AE
CT Ratio 800/1-1A
Core-1 Class: 0.5 Burden:30VA
Core-2 Class: PS, knee point Voltage:vk>=100V Imag<=30mA, vk/2,RCt =2 ohm
Fault current 31.5kA for 3 sec

Core: 1
SL .No Applied Current ( A) Secondary Measured current
1 400A 0.49A
2 300A 0.37A
3 200A 0.24A

Core: 2
SL .No Applied Current ( A) Secondary Measured current
1 400A 0.5A
2 300A 0.38A
3 200A 0.24A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 5 of 31
Site Acceptance Test (SAT)

Current Transformer for 11kV Bus Duct side

Specification

Nomenclature Current transformer


Make AE
CT Ratio 800/1A
Core-1 Class: PS, knee point Voltage:vk>=300V Imag<=30mA, vk/2,RCt =2 ohm
Fault current 31.5kA for 3 sec

Core: 1
SL .No Applied Current ( A) Secondary Measured current
1 400A 0.49A
2 300A 0.38A
3 200A 0.25A

Remarks Found Ok

Generator Breaker Functional Check


21901333
SL.no Description Remarks
1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 6 of 31
Site Acceptance Test (SAT)

Generator Incomer-2
Ammeter

Specification

Nomenclature AMMETER
Make Secure DPM I300
Aux. Volts 110VAC
Nominal Current 1/5A
Serial Number 80195322
CT Ratio 800/1A
Accuracy Class 0.5

SL .No Applied Current ( A) Measured current (A)


1 400A 399A
2 300A 299A
3 200A 200A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 7 of 31
Site Acceptance Test (SAT)

Current Transformer

Specification

Nomenclature Current transformer


Make AE
CT Ratio 800/1-1A
Core-1 Class: 0.5 Burden:30VA
Core-2 Class: PS, knee point Voltage:vk>=100V Imag<=30mA, vk/2,RCt =2 ohm
Fault current 31.5kA for 3 sec

Core: 1
SL .No Applied Current ( A) Secondary Measured current
1 400A 0.49A
2 300A 0.37A
3 200A 0.24A

Core: 2
SL .No Applied Current ( A) Secondary Measured current
1 400A 0.5A
2 300A 0.38A
3 200A 0.24A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 8 of 31
Site Acceptance Test (SAT)

Current Transformer for 11kV Bus Duct side

Specification

Nomenclature Current transformer


Make AE
CT Ratio 800/1A
Core-1 Class: PS, knee point Voltage:vk>=300V Imag<=30mA, vk/2,RCt =2 ohm
Fault current 31.5kA for 3 sec

Core: 1
SL .No Applied Current ( A) Secondary Measured current
1 400A 0.49A
2 300A 0.38A
3 200A 0.25A

Remarks Found Ok

Generator Breaker Functional Check


Sl.no:21901338
SL.no Description Remarks
1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 9 of 31
Site Acceptance Test (SAT)

Bus Coupler-1

Master Trip Relay

Specification

Nomenclature Master Trip Relay


Make Alstom
Aux. Volts 110VDC
Serial Number 34870974/08/19

Master trip Relay Functional Check


Sl.no:34870974/08/19
SL.no Description Remarks
1 Manually relay operated Found ok
2 Master trip Relay out put contact function Found ok
check
3 Electrical reset function check Found ok
4 Master Trip relay operated .Breaker also Found ok
tripping function check

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 10 of 31
Site Acceptance Test (SAT)

Trip circuit supervision Relay

Specification

Nomenclature TCS
Make ABB
Aux. Volts 110VDC
Serial Number 41903094/41903087

TCS Functional Check


Sl.no:41903094/41903087
SL.no Description Remarks
1 Pre Close function check Found ok
2 Post Close function check Found ok
3 TCS Relay Output contact function check Found ok
4 TCS-1 & 2 indication function check Found ok

Voltmeter

Specification

Nomenclature Voltmeter
Make Secure/DPM300
Aux. Volts 110VAC
Serial Number 80147751

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 11 of 31
Site Acceptance Test (SAT)

Bus coupler -1Breaker Functional Check


Sl.no:21901342
SL.no Description Remarks
1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 12 of 31
Site Acceptance Test (SAT)

Bus Coupler-2

Master Trip Relay

Specification

Nomenclature Master Trip Relay


Make Alstom
Aux. Volts 110VDC
Serial Number 34900457/10/19

Master trip Relay Functional Check


Sl.no: 34900457/10/19
SL.no Description Remarks
1 Manually relay operated Found ok
2 Master trip Relay out put contact function Found ok
check
3 Electrical reset function check Found ok
4 Master Trip relay operated .Breaker also Found ok
tripping function check

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 13 of 31
Site Acceptance Test (SAT)

Trip circuit supervision Relay

Specification

Nomenclature TCS
Make ABB
Aux. Volts 110VDC
Serial Number 31919930/31919172

TCS Functional Check


Sl.no:41903094/41903087
SL.no Description Remarks
1 Pre Close function check Found ok
2 Post Close function check Found ok
3 TCS Relay Output contact function check Found ok
4 TCS-1 & 2 indication function check Found ok

Voltmeter

Specification

Nomenclature Voltmeter
Make Secure/DPM300
Aux. Volts 110VAC
Serial Number 80147872

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 14 of 31
Site Acceptance Test (SAT)

Bus coupler -2 Breaker Functional Check


Sl.no:21901328
SL.no Description Remarks
1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Ammeter

Specification

Nomenclature Voltmeter
Make Secure/DPM300
Aux. Volts 110VAC
Serial Number 80147751

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 15 of 31
Site Acceptance Test (SAT)

Station Auxiliary transformer-1

Master Trip Relay

Specification

Nomenclature Master Trip Relay


Make Alstom
Aux. Volts 110VDC
Serial Number 34861812/08/19

Master trip Relay Functional Check


Sl.no: 34861812/08/19
SL.no Description Remarks
1 Manually relay operated Found ok
2 Master trip Relay output contact function Found ok
check
3 Electrical reset function check Found ok
4 Master Trip relay operated .Breaker also Found ok
tripping function check

Trip circuit supervision Relay

Specification

Nomenclature TCS
Make ABB
Aux. Volts 110VDC
Serial Number 31919931

TCS Functional Check


Sl.no:41903094/41903087
SL.no Description Remarks
1 Pre Close function check Found ok
2 Post Close function check Found ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 16 of 31
Site Acceptance Test (SAT)

3 TCS Relay Output contact function check Found ok


4 TCS-1 & 2 indication function check Found ok

Remarks Found Ok

Multi-function Meter

Specification

Nomenclature Multi-function Meter


Make Secure Elite 440-446
Aux. Volts 110VDC
Nominal Current 1/5A
Nominal Voltage 110-250VDC
110-240VAC

S.NO. CT Ratio Applied Current Measured current Injected with Status


secondary
injection kit

1 50/5A 5A 5.01A ISA DRTS 33 OK

2 50/5A 2.5A 2.49A ISA DRTS 33 OK

SL .No MFT Serial Number Remarks

1 X1085633 Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 17 of 31
Site Acceptance Test (SAT)

Station Auxiliary transformer-1 Breaker Functional Check

SL.no Description Remarks


1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Ammeter

Specification

Nomenclature AMMETER
Make Secure DPM I300
Aux. Volts 110VAC
Nominal Current 1/5A
Serial Number 80195331
CT Ratio 50/5A
Accuracy Class 0.5

SL .No Applied Current ( A) ( Primary Measured current (A)


injection)
1 50A 49.5A
2 25A 24.9A
3 10A 11A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 18 of 31
Site Acceptance Test (SAT)

RELAY TEST REPORT

Nomenclature Feeder Protection Relay Settings:


Relay Type P3U30-5AAA2BCAA CT rated primary current 50A
Sr.N. WX195010003 CT rated secondary current 5A
Make Schneider Electric
Aux. Volts 110VDC
Nominal Current 1/5A Rated primary voltage (L-L) 11kV
Nominal Voltage 110-250VDC Rated secondary voltage 110V
110-240VAC

Protection Functions
Over Current I-Stage:(IDMT)

S.NO. Pick Up Value Applied Current Trip Time with Status


TMS=0.300
CS TMS 2x Iset 4x Iset 2x Iset 4x Iset
1 0.85 1.0 1.7A 3.4A 3.0524Sec 1.52 Sec OK

Over Current II-Stage: (INSTANTANEOUS)


S.NO. CS Applied Current Operational Delay Trip Time Status
(DMT)
1 5.58A 5.6A 0.04 Sec 0.0403Sec OK

1.1.1.7 Earth Fault: Stage-1st

S.NO. CS Applied Current Operational Trip Time Status


Delay
TMS=0.3
1 0.1A 0.21A 0.5 3.032Sec OK

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 19 of 31
Site Acceptance Test (SAT)

Earth Fault: Stage-2nd

S.NO. CS Applied Current Operational Trip Time Status


Delay

1 0.50A 0.52A 0.04 0.0423Sec OK

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 20 of 31
Site Acceptance Test (SAT)

Station Auxiliary transformer2

Master Trip Relay

Specification

Nomenclature Master Trip Relay


Make Alstom
Aux. Volts 110VDC
Serial Number 34390417/03/18

Master trip Relay Functional Check


Sl.no: 34390417/03/18
SL.no Description Remarks
1 Manually relay operated Found ok
2 Master trip Relay out put contact function Found ok
check
3 Electrical reset function check Found ok
4 Master Trip relay operated .Breaker also Found ok
tripping function check

Trip circuit supervision Relay

Specification

Nomenclature TCS
Make ABB
Aux. Volts 110VDC
Serial Number 31920055

TCS Functional Check


Sl.no:31920055
SL.no Description Remarks
1 Pre Close function check Found ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 21 of 31
Site Acceptance Test (SAT)

2 Post Close function check Found ok


3 TCS Relay Output contact function check Found ok
4 TCS-1 & 2 indication function check Found ok

Remarks Found Ok

Multi-function Meter

Specification

Nomenclature Multi-function Meter


Make Secure Elite 440-446
Aux. Volts 110VDC
Nominal Current 1/5A
Nominal Voltage 110-250VDC
110-240VAC

S.NO. CT Ratio Applied Current Measured current Injected with Status


secondary
injection kit

1 50/5A 5A 5.01A ISA DRTS 33 OK

2 50/5A 2.5A 2.49A ISA DRTS 33 OK

SL .No MFM Serial Number Remarks

1 X1085632 Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 22 of 31
Site Acceptance Test (SAT)

Station Auxiliary transformer-2 Breaker Functional Check

SL.no Description Remarks


1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Ammeter

Specification

Nomenclature AMMETER
Make Secure DPM I300
Aux. Volts 110VAC
Nominal Current 1/5A
Serial Number 80056618
CT Ratio 50/5A
Accuracy Class 0.5

SL .No Applied Current ( A)primary Measured current (A)


injection
1 50A 51A
2 25A 24.5A
3 10A 11A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 23 of 31
Site Acceptance Test (SAT)

RELAY TEST REPORT

Nomenclature Feeder Protection Relay Settings:


Relay Type P3U30-5AA2BCAA CT rated primary current 50A
Sr.N. WX194450016 CT rated secondary current 5A
Make Schneider Electric
Aux. Volts 110VDC
Nominal Current 1/5A Rated primary voltage (L-L) 11kV
Nominal Voltage 110-250VDC Rated secondary voltage 110V
110-240VAC

Protection Functions
Over Current I-Stage:(IDMT)

S.NO. Pick Up Value Applied Current Trip Time with Status


TMS=0.300
CS TMS 2x Iset 4x Iset 2x Iset 4x Iset
1 0.85 1.0 1.7A 3.4A 3.0524Sec 1.52 Sec OK

Over Current II-Stage: (INSTANTANEOUS)


S.NO. CS Applied Current Operational Delay Trip Time Status
(DMT)
1 5.58A 5.6A 0.04 Sec 0.0403Sec OK

Earth Fault: Stage-1st

S.NO. CS Applied Current Operational Trip Time Status


Delay
TMS=0.3
1 0.1A 0.21A 0.5 3.032Sec OK

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 24 of 31
Site Acceptance Test (SAT)

Earth Fault: Stage-2nd

S.NO. CS Applied Current Operational Trip Time Status


Delay

1 0.50A 0.52A 0.04 0.0423Sec OK

Isolation transformer

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 25 of 31
Site Acceptance Test (SAT)

Master Trip Relay

Specification

Nomenclature Master Trip Relay


Make Alstom
Aux. Volts 110VDC
Serial Number 34870971/08/19

Master trip Relay Functional Check


Sl.no: 34390417/03/18
SL.no Description Remarks
1 Manually relay operated Found ok
2 Master trip Relay out put contact function Found ok
check
3 Electrical reset function check Found ok
4 Master Trip relay operated .Breaker also Found ok
tripping function check

Trip circuit supervision Relay

Specification

Nomenclature TCS
Make ABB
Aux. Volts 110VDC
Serial Number 3190030

TCS Functional Check


Sl.no:31920055
SL.no Description Remarks
1 Pre Close function check Found ok
2 Post Close function check Found ok
3 TCS Relay Output contact function check Found ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 26 of 31
Site Acceptance Test (SAT)

4 TCS-1 & 2 indication function check Found ok

Remarks Found Ok

Multi-function Meter

Specification

Nomenclature Multi-function Meter


Make Secure Elite 440-446
Aux. Volts 110VDC
Nominal Current 1/5A
Nominal Voltage 110-250VDC
110-240VAC

S.NO. CT Ratio Applied Current Measured current Injected with Status


secondary
injection kit

1 75/5A 5A 5.01A ISA DRTS 33 OK

2 75/5A 2.5A 2.48A ISA DRTS 33 OK

SL .No MFM Serial Number Remarks

1 X1169583 Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 27 of 31
Site Acceptance Test (SAT)

Isolation transformer Breaker Functional Check

SL.no Description Remarks


1 R,Y,B indication Found ok
2 Service position Limit switch & indication Found ok
3 Test position Limit switch & indication Found ok
4 Spring charge Motor operation & Indication Found ok
5 Spring charge Motor operation & Indication Found ok
6 Local mode Breaker Tripping & closing Found ok
Operation
7 Remote mode Breaker Tripping & closing Found ok
Operation

Ammeter

Specification

Nomenclature AMMETER
Make Secure DPM I300
Aux. Volts 110VAC
Nominal Current 1/5A
Serial Number 80195319
CT Ratio 75/5A
Accuracy Class 0.5

SL .No Applied Current ( A) Primary Measured current (A)


injection
1 75A 74.5A
2 50A 49.5A
3 10A 11A

Remarks Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 28 of 31
Site Acceptance Test (SAT)

RELAY TEST REPORT

Nomenclature Feeder Protection Relay Settings:


Relay Type P3U30-5AAA2BCAA CT rated primary current 75A
Sr.N. WX195050013 CT rated secondary current 5A
Make Schneider Electric
Aux. Volts 110VDC
Nominal Current 1/5A Rated primary voltage (L-L) 11kV
Nominal Voltage 110-250VDC Rated secondary voltage 110V
110-240VAC

Protection Functions
Over Current I-Stage:(IDMT)

S.NO. Pick Up Value Applied Current Trip Time with Status


TMS=0.300
CS TMS 2x Iset 4x Iset 2x Iset 4x Iset
1 0.85 1.0 1.7A 3.4A 3.0524Sec 1.52 Sec OK

Over Current II-Stage: (INSTANTANEOUS)


S.NO. CS Applied Current Operational Delay Trip Time Status
(DMT)
1 5.58A 5.6A 0.04 Sec 0.0403Sec OK

1.1.1.7 Earth Fault: Stage-1st

S.NO. CS Applied Current Operational Trip Time Status


Delay
TMS=0.3
1 0.1A 0.21A 0.5 3.032Sec OK

Earth Fault: Stage-2nd

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 29 of 31
Site Acceptance Test (SAT)

S.NO. CS Applied Current Operational Trip Time Status


Delay

1 0.50A 0.52A 0.04 0.0423Sec OK

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 30 of 31
Site Acceptance Test (SAT)

Nelumbo Chilime Electrical Engineer Chilime Project Manager

Chilime Consultant

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 11kV Breaker Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 31 of 31