Site Acceptance Test (SAT)

SITE ACCEPTANCE TEST (SAT)

CUSTOMER : Chilime Jalavidhyut Company Limited


PROJECT : Chilime Hydro Electric Project, 2x11.28MW
DOCUMENT NAME : 66KV Line Relay Metering Panel
DOCUMENT NO. : NICPL-137-01

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 1 of 16
Site Acceptance Test (SAT)

Introduction
This document describes the Line Relay Metering Panel item to be tested on a SAT period. The SAT will
demonstrate the operation and integration of the LRMP system and verify the hardware being supplied.

References
The following documents will be available as references during the SAT.

Ref Document Reference Description


1 NICPL-137-06-101 Wiring drawings

Manufacturer/Model Number Serial Number Cal Cert Ref Cal Exp Date
Relay tester / ISA DRTS 33 2119/48617

Digital Multimeter / Fluke 46311178WS

Health and Safety

The tests to be conducted involve test and measurement operations with hazardous voltages present. All
tests must be performed by skilled persons taking due care and attention to avoid electrical shocks. The
tests are to be performed in the stated sequence to avoid danger. All faults during electrical testing must
be rectified or deemed by a qualified and competent person not to compromise safety before further
testing can proceed.

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 2 of 16
Site Acceptance Test (SAT)

Line Specification
Line
Chilime – Trishuli 66KV Line
Line Lenghth 39.5KM
Chilime – Trishuli 35km (Protected Line)
Trishuli-Debighat 4.5km ( Shortest Line)
Conductor Wolf
CT Ratio 300/1
PT Ratio 66000/110
R` 0.213 ohm/kM
X` 0.412 ohm/kM
B` 0.4788 US/kM
Ro` 0.6417 ohm/kM
Xo` 1.1457 ohm/kM
Bo` 0.3894 US/kM
Zone-1 80% Of Protected Line ( Trishuli Line)
Zone-1 Time 0.05 sec
Zone-2 100% Of Protected Line ( Trishuli Line) +
20% Of Shortest Line (Debighat Line)
Zone-2 Time 0.40 sec
Zone-3 100% Of Protected Line ( Trishuli Line) +
100% Of Shortest Line (Debighat Line)
Zone-3 Time 1 sec

Line Protection Relay (P3L30)-Main Protection Relay

RELAY TEST REPORT

Nomenclature Line Protection Relay Settings:


Relay Type P3L30-CGGGG-AAFNA- CT rated primary current(HV Side) 300A
BBAAA
Sr.N. EB200320022 CT rated secondary current 1A
Make Schneider Electric
Aux. Volts 110VDC
Nominal Current 5A Rated primary voltage (L-L) 66kV
Nominal Voltage 110-250VDC Rated secondary voltage 110V
110-240VAC

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 3 of 16
Site Acceptance Test (SAT)

Protection Functions

Over Current I-Stage:(IDMT)

S.NO. Pick Up Value Applied Current Trip Time with Status


TMS=0.200

CS TMS 2x Iset 4x Iset 2x Iset 4x Iset

1 0.87A 0.200 1.745A 3.382A 2.051Sec 1.02 Sec OK

Over Current II-Stage:(INSTANTANEOUS)

S.NO. CS Applied Current Operational Delay Trip Time Status


(DMT)

1 4A 4.1A 0.2 Sec 0.209 Sec OK

Earth Fault

S.NO. CS Applied Current Operational Trip Time Status


Delay

TMS=0.2

1 0.157A 0.315A 0.2 2.0045Sec OK

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 4 of 16
Site Acceptance Test (SAT)

Bus Differential

S.NO. CS Applied Current Operational Trip Time Status


Delay

1 0.10A 0.11A 0.50 0.504Sec OK

Cable Differential

S.NO. CS Applied Current Operational Trip Time Status


Delay

1 0.10A 0.11A 0.50 Sec 0.503 Sec OK

Over Voltage – 1st Stage

S.NO. Voltage Setting Applied Voltage Operational Delay Trip Time Status

1 110% 70V 5.00 Sec 5.006 Sec OK

Over Voltage – 2nd Stage

S.NO. Voltage Setting Applied Voltage Operational Delay Trip Time Status

1 125% 78V 0.10 Sec 0.1031 OK


Sec

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 5 of 16
Site Acceptance Test (SAT)

Zone-1

Phase Setting Applied Setting Operational Delay Trip Time Status

R-Y X=5.247(ohm) 0.05 Sec 0.0593 OK


Sec

R=2.058(ohm)

Y-B X=5.479(ohm) 0.0625 OK

X=5.78(ohm) R=2.145(ohm)

B-R R=2.95(ohm) X=4.551(ohm) 0.0645 OK

R=1.681(ohm)

RYB X=5.16(ohm) 0.0573 OK

R=2.609(ohm)

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 6 of 16
Site Acceptance Test (SAT)

Zone-2

Phase Setting Applied Setting Operational Delay Trip Time Status

R-Y X=7.16(ohm) 0.40 Sec 0.4109 OK


Sec

R=2.725(ohm)

Y-B X=7.131(ohm) 0.4087 OK

X=7.41(ohm) R=2.725(ohm)

B-R R=3.78(ohm) X=7.247(ohm) 0.4107 OK

R=2.754(ohm)

RYB X=7.102(ohm) 0.4107 OK

R=3.275(ohm)

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 7 of 16
Site Acceptance Test (SAT)

Zone-3

Phase Setting Applied Setting Operational Delay Trip Time Status

R-Y X=7.943(ohm) 1 Sec 1.0149 OK


Sec

R=3.044(ohm)

Y-B X=7.943(ohm) 1.0149 OK

X=8.16(ohm) R=3.073(ohm)

B-R R=4.16(ohm) X=7.943(ohm) 1.0157 OK

R=3.102(ohm)

RYB X=7.885(ohm) 1.0151 OK

R=3.71(ohm)

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 8 of 16
Site Acceptance Test (SAT)

Line Protection Relay (REL 670)-Main 2 Protection Relay

RELAY TEST REPORT

Nomenclature Line Protection Relay Settings:


Relay Type REL 670 CT rated primary current(HV Side) 300A
Sr.N. IO915003 CT rated secondary current 1A
Make ABB
Aux. Volts 110VDC
Nominal Current 5A Rated primary voltage (L-L) 66kV
Nominal Voltage 110-250VDC Rated secondary voltage 110V
110-240VAC

Protection Functions

Over Current I-Stage:(IDMT)

S.NO. Pick Up Value Applied Current Trip Time with Status


TMS=0.200

CS TMS 2x Iset 4x Iset 2x Iset 4x Iset

1 0.87A 0.200 1.745A 3.382A 2.048Sec 1.09 Sec OK

Over Current II-Stage:(INSTANTANEOUS)

S.NO. CS Applied Current Operational Delay Trip Time Status


(DMT)

1 4A 4.1A 0.2 Sec 0.204 Sec OK

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 9 of 16
Site Acceptance Test (SAT)

Earth Fault

S.NO. CS Applied Current Operational Trip Time Status


Delay

TMS=0.2

1 0.157A 0.315A 0.2 2.0039Sec OK

Zone-1

Phase Setting Applied Setting Operational Delay Trip Time Status

R-Y X=10.544(ohm) 0.05 Sec 0.0594 OK


Sec

R=5.684(ohm)

Y-B X=6.85(ohm) 0.0563 OK


X=11.54(ohm)

R=5.97(ohm)
R=3.979(ohm)

B-R X=4.86(ohm) 0.0591 OK

R=2.842(ohm)

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 10 of 16
Site Acceptance Test (SAT)

Zone-2

Phase Setting Applied Setting Operational Delay Trip Time Status

R-Y X=13.955(ohm) 0.40 Sec 0.4104 OK


Sec

R=7.106(ohm)

Y-B X=13.102(ohm) 0.4107 OK


X=14.78(ohm)

R=7.65(ohm)
R=7.106(ohm)

B-R X=13.387(ohm) 0.4106 OK

R=7.39(ohm)

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 11 of 16
Site Acceptance Test (SAT)

Zone-3

Phase Setting Applied Setting Operational Delay Trip Time Status

R-Y X=15.66(ohm) 1 Sec 1.0142 OK


Sec

R=8.242(ohm)

Y-B X=15.66(ohm) 1.0148 OK


X=16.27(ohm)

R=8.41(ohm)
R=8.242(ohm)

B-R X=15.66(ohm) 1.0147 OK

R=8.527(ohm)

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 12 of 16
Site Acceptance Test (SAT)

Multi function Meter

Specification

Nomenclature Multi function Meter


Make Secure Elite 440-446
Aux. Volts 110VDC
Nominal Current 1/5A
Nominal Voltage 110-250VDC
110-240VAC

S.NO. CT Ratio Applied Current Applied Current Injected Status


with
0.5A 1A secondary
injection
kit

1 0.499A 0.99A ISA DRTS OK


33

SL .No MFT Serial Number Remarks

1 X1285294 Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 13 of 16
Site Acceptance Test (SAT)

Energy Meter

Specification

Nomenclature Energy Meter


Make Secure Premier 300
Aux. Volts 110VAC
Nominal Current 1/5A

SL .No EM Serial Number Remarks

1 X1296009 Found Ok

Master Trip Relay

Specification

Nomenclature Master Trip Relay


Make Alstom
Aux. Volts 110 –125 V DC
Nominal Current 25A
Nominal Voltage VX 110-125 VDC

SL .No MT Serial Number Remarks

1 34972229/01/20 (MTR-1) Functional Checked Found Ok

2 34390424/01/20 (MTR-2) Functional Checked Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 14 of 16
Site Acceptance Test (SAT)

Trip Circuit Supervision Relay

Specification

Nomenclature Trip Circuit Supervision Relay


Make Alstom
Aux. Volts 110 –125 V DC
Nominal Voltage VX 110-125 VDC

SL .No TCSR Serial Number Remarks

1 34982117/01/20 Found Ok

2 34982121/01/20 Found Ok

Annunciator

Specification

Nomenclature 24W Annunciator


Make SECO
Aux. Volts 75 –275 V AC/DC

SL .No ANN Serial Number Remarks

1 20-01-4951 Found Ok

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 15 of 16
Site Acceptance Test (SAT)

Nelumbo Chilime Electrical Engineer Chilime Project Manager

Chilime Consultant

Doc Type Site Acceptance Test report NICPL Doc No NICPL-137-01


Title: 66kV Line Relay Metering Panel Project Title: Chilime Hydro Electric Project 2X11.28MW
Nelumbo Icona Controls Pvt Ltd
Noida India - 201301 Sheet: 16 of 16