Final Setting Test: 1. Relay Details
Final Setting Test: 1. Relay Details
Final Setting Test: 1. Relay Details
TEST DESCRIPTION
MAIN-1
PANEL:415RA
MANDOLA-3 LINE
CUSTOMER:PGCIL
DATE:06/08/2012
1. RELAY DETAILS:
Make
: Siemens
Relay Type
: 7SA522
Panel Ref
: 415RA
MLFB
: 7SA522-6CB90-4QB4/0S
Relay Sl.No
: BF-1101072724
Rated current
: 1A
Aux Supply
: 220V DC
P-Set
: V04.70.07
DISCRIPTION
CHECKED
1.
Yes
------
2.
Yes
------
3.
Yes
------
4.
Yes
------
5.
Yes
------
6.
Yes
------
7.
Yes
------
TESTED BY
M/s SIEMENS
WITNESSED BY PGCIL
DATE
06.08.2012
Phase Ref
Applied
Value (V)
VT Ratio Applied
Displayed Primary
Value (KV)
VAB
11030
400KV/110V
400
VBC
110270
400KV/110V
400
VCA
110150
400KV/110V
400
VAN
63.510.0
400KV/110V
231
VBN
63.51240
400KV/110V
231
VCN
63.51120
400KV/110V
231
INPUT
INJECTION VALUE
EXPECTED
VALUE
DISPLAYED
VALUE
Frequency
50 HZ
50 Hz
50 Hz
P (GW)
VA=63.510
1385.64MW
1.38 GW
Q (GVAR)
VB=63.51240
0.00 MVAR
0.0 GVAR
S (GVA)
VC=63.51120
1385.64MVA
1.38 GVA
1.00
1.00
IA=1.00.0
PF
IB=1.0240
IC=1.0120
WITNESSED BY PGCIL
DATE
06.08.2012
23.30ms
322.10ms
326.80ms
322.80ms
6. FAULT LOCATOR
Reactance = 0.1817/KM
Line Length=102KM
Total line reactance = 18.5334 , 86
% of Line length
100
50
L1-E
102.
3
52.5
L2-E
102.2
52.1
L1-L2-L3
102.0
51.2
WITNESSED BY PGCIL
06.08.2012
Meas.Time
Pickup Current (A)
(S)
R-N
2.515
23.20
2.550
Y-N
2.520
18.10
2.550
B-N
2.515
31.10
2.550
*Inject directly 2.51A and Measure the trip time.
Phase Ref.
Meas.Time (S)
22.60
22.00
31.10
Pickup (V)
70.04
70.04
69.97
Drop-Off (V)
68.62
68.68
68.63
DO/PU Ratio
97.97%
98.05%
98.08%
Time (S)
2.033
2.034
2.033
DO/PU Ratio
97.97%
97.96%
98.06%
Time (ms)
133.30
133.20
133.50
Pickup (V)
95.04
95.07
94.96
Drop-Off (V)
93.12
93.14
93.12
Ph-ph
Setting (V)
121.00
121.00
121.00
TESTED BY
M/s SIEMENS
Pickup (V)
Drop-Off (V)
DO/PU Ratio
Time (S)
121.070
121.035
121.053
118.610
118.680
118.818
97.96%
98.05%
98.15%
2.033
2.034
2.033
WITNESSED BY PGCIL
DATE
06.08.2012
Ph-ph
Setting (V)
165.00
165.00
165.00
Pickup (V)
Drop-Off (V)
DO/PU Ratio
Time (ms)
165.064
165.029
164.990
161.756
161.770
161.738
97.99%
98.02%
98.02%
132.60
134.00
133.30
1 VT Fuse fail
3 VT Fuse fail
Pick-up Uo
Applied
Phase Ref
Pick-up (V)
(V)
Current(A)
R-N
29.95
4.99
1.00
Y-N
30.03
4.99
1.00
B-N
29.95
4.99
1.00
*For 3 VT fuse fail, Reduced the 3 voltage less than the set value immediately.
TESTED BY
M/s SIEMENS
WITNESSED BY PGCIL
DATE
06.08.2012
I>Set (A)
1.50
1.50
1.50
Pick-up (A)
1.495
1.498
1.498
Time (ms)
37.40
37.40
37.40
Applied
Current (A)
0.20
0.20
0.20
Pickup (V)
Time (S)
57.07
57.08
57.01
2.0319
2.0320
2.0326
Applied
Current (A)
0.20
0.20
0.20
TESTED BY
M/s SIEMENS
Pickup (V)
Time (ms)
31.99
32.04
32.01
132.90
132.20
132.90
WITNESSED BY PGCIL
DATE
06.08.2012
Applied
Current (A)
0.20
0.20
0.20
Pickup Voltage
(V)
99.055
99.107
99.038
Time (S)
2.031
2.032
2.033
Applied
Current (A)
0.20
0.20
0.20
Pickup Voltage
(V)
55.06
55.06
55.06
Time (ms)
132.10
133.10
132.70
IR
STATE-1
63.510
63.51240
63.51120
0.000
IY
0.00240
IB
0.00120
Time
20ms
VB
VC
STATE-2
53.510
53.51240
53.51120
0.2500
0.250240
0.250120
20ms
TESTED BY
M/s SIEMENS
STATE-3
45.510
45.51240
45.51120
0.500
STATE-4
35.510
35.51240
35.51120
1.00
STATE-5
25.510
25.51240
25.51120
1.500
0.50240
1.0240
1.50240
2.00240
0.50120
1.0120
1.50120
2.00120
20ms
20ms
20ms
20ms
WITNESSED BY PGCIL
STATE-6
15.510
15.51240
15.51120
2.000
DATE
06.08.2012
14. DT SEND:
DT Send for: Over Voltage Protection
Directional Earth fault Protection
DT Send checked: OK
15. DT RECEIVED:
Activate the binary Input No: 4 (J4 - J5) by Jumpering the terminal of XPLCC: 1 & 5 in 415RA
Panel.
Lockout Relay Operation Checked: OK
16. AUTO RECLOSER: (Through BCU)
Auto Recloser Operating Conditions
Fault Type
Z1-R Phase
Z1-Y Phase
Z1-B Phase
CR+Z1B R Ph
CR+Z1B Y Ph
CR+Z1B B Ph
% of Fault
Applied
Main CB Status
Tie-CB Status
50
Reclosed
Reclosed
100
Reclosed
Reclosed
Main CB Status
Tie-CB Status
Not Reclosed
Not Reclosed
Not Reclosed
Not Reclosed
Line Length
Measured (KM)
52.40
52.10
52.20
105.0
105.7
104.9
% of Fault
Applied
100
50
100
WITNESSED BY PGCIL
Line Length
Measured (KM)
102.0
53.00
48.90
105.60
DATE
06.08.2012
CR+Z1B 3Phase
Reclaim Time Fault
102.00
52.40
AR PRIORITY CLOSING
Main CB AR
ON
OFF
ON
OFF
Tie CB AR
ON
ON
OFF
OFF
Remarks
Main CB & TIE CB Reclosed
Priority Close of TIE CB
Main CB Reclosed & TIE CB Locked out
Main & Tie Locked Out
REMARKS:
Relay found healthy and fit for service
TESTED BY
M/s SIEMENS
WITNESSED BY PGCIL
DATE
06.08.2012