A Grid-Friendly Plant: by Mahesh Morjaria, Dmitriy Anichkov, Vladimir Chadliev, and Sachin Soni
A Grid-Friendly Plant: by Mahesh Morjaria, Dmitriy Anichkov, Vladimir Chadliev, and Sachin Soni
A Grid-Friendly Plant: by Mahesh Morjaria, Dmitriy Anichkov, Vladimir Chadliev, and Sachin Soni
Plant
By Mahesh Morjaria, Dmitriy Anichkov,
Vladimir Chadliev, and Sachin Soni
The Role of
Utility-Scale
Photovoltaic Plants
in Grid Stability
and Reliability
A
A Recent rapid Photovoltaic (PV)
price reduction has significantly increased the
competitiveness of PV-generated electricity, which
has now reached grid parity in many markets,
plant—© fotosearch, background—image licensed by ingram publishing
A task force under the aegis of the North American Electric In this article, we describe our design of a grid-friendly
Reliability Corporation (NERC) has made several recommen- PV plant, including the development of a plant controller
dations on specific requirements that such variable generation that complies with these requirements, resulting in a PV
plants must meet to provide their share of grid support. These plant that actively contributes to the reliability and stabil-
recommendations address grid requirements such as voltage ity of electrical transmission and distribution system. Field
control and regulation, voltage and frequency fault ride-through, data from First Solar-developed utility-scale PV plants are
reactive and real power control, and frequency response criteria used to illustrate the concepts. The grid-friendly PV plant
in the context of the technical characteristics and physical capa- also includes the ability to ride through specific low and high
bilities of variable-generation equipment. voltages or low- and high-frequency ranges.
POI Voltage,
Current, and Frequency
SCADA HMI
Plant Controller
Substation RTU
Set Points Set Points
Plant Network
Inverter Commands
PCS 1 PCS n
DAS/PLC DAS/PLC
Power Plant Controller Architecture the real and reactive power necessary to meet the desired
A key component of a grid-friendly PV power plant is a settings at the POI.
plant-level controller. It is designed to regulate real and The plant operator can set an active power curtailment
reactive power output from the PV plant, such that it command to the controller. In this case, the controller calcu-
behaves as a single large generator. While the plant is com- lates and distributes active power curtailment to individual
posed of individual small generators (or, more specifically, inverters. In general, the inverters can be throttled back only
inverters), with each generator performing its own energy to a certain specified level of active power and not any lower
production based on local solar array conditions, the func- without causing the dc voltage to rise beyond its operating
tion of the plant controller is to coordinate the power output range. Therefore, the plant controller dynamically stops and
to provide typical large power-plant features such as active starts inverters as needed to manage the specified active power
power control and voltage regulation (through reactive
power regulation).
The plant controller provides the following plant-level Automatic Voltage Regulation (AVR)
control functions:
✔✔ dynamic voltage and/or power factor regulation of the AVR Control Mode
solar plant at the point of interconnection (POI)
On
✔✔ real power output curtailment of the solar plant
when required so that it does not exceed an operator- Off
specified limit
✔✔ ramp-rate controls to ensure that the plant output does Mode Current Setpoint New Setpoint
not ramp up or down faster than a specified ramp-rate Voltage Control 528.0 kV 528.0 kV
limit, to the extent possible
Power Factor Mode 0.98 0.98
✔✔ frequency control to lower plant output in case of over-
frequency situation or increase plant output (if pos- Var Mode 0.2 MVar 0.2 MVar
sible) in case of under-frequency
✔✔ start-up and shut-down control. Confirm Cancel
The plant controller implements plant-level logic and Changes Changes
closed-loop control schemes with real-time commands to
the inverters to achieve fast and reliable regulation. It relies
figure 2. An HMI screen on AVR modes.
on the ability of the inverters to provide a rapid response to
commands from the plant controller. Typically there is one
controller per plant controlling the output at a single high-
voltage bus (referred to as POI). The commands to the plant 10 1.000
controller can be provided through the supervisory control 0
0.995
Power Factor
80
Ramp Rates Between
80 Active Power
Set Point Changes Management
75 Are Controlled 75
Through the SCADA HMI, the
70 70 controller can also be set to con-
0 2 4 6 8 10 12 14 16 18 20 trol the active power output of the
Time (min) plant. When the control system
detects that the active power at POI
figure 5. Power curtailment at different levels. exceeds the specified set point, it
Power
Plant
Output Limit
Curtailed
Block Time
Commanded (MW)
will turn off certain inverters to
Power (MW)
achieve this desired set point since 75 75
Inverters Are
the output of each inverter cannot 70 Started in 70
be lowered below a certain thresh- Inverters Are Sequence
Turned Off in
old without causing a high dc volt- 65
Sequence;
65
age operating condition. Ramp Rates
60 60
Figure 4 illustrates field data Are Controlled
Plant Start Command
from a PV plant operating at 55 55
around 90-MW power. The cur- 0 1 2 3 4 5 6 7 8 9 10
tailment limit is initially changed Time (min)
from 100 to 82.5 MW. The plant Source: Agua Caliete PV Plant in Yuma, Arizona, USA
controller turns down the invert- 13 March 2012 ~90 MW Online
ers (and turns off some of them if
required) to achieve the new set figure 7. Plant shut-down and start-up controls.
point. Note that the turndown of
power is gradual to meet the spec-
ified ramp-rate limit.
Frequency Droop Parameters
The curtailment limit is reduced
again to around 75 MW, and the MW
controller responds as expected.
When the limit is raised, the con-
troller adjusts the output of the Droop
inverters to increase the total plant Low
Deadband
High Limits Decrease Active
output. Finally, when the limit is Limits
Power in Case of
raised to 100 MW, the plant is no Hz
High Frequency
longer curtailed since the plant is Deadband
producing less than the limit. Droop
In all the control actions, the con-
troller’s command to each inverter is
unique, given the specific conditions
each inverter is experiencing. For
example, when the plant is under Frequency Deadband 0.036 Hz
curtailment, the plant controller Frequency Droop 5.0 %
can release the power limit of indi- High Limit 61.500 Hz
vidual inverters if the total output of
Low Limit 58.500 Hz
the plant starts falling below the set
point. So in case of a cloud passage, Active Power High Limit 290.0 MW
which results in a reduction of the Active Power Low Limit 10.0 MW
output of a part of the plant, the con-
troller can make the adjustment to
increase the output of other inverters
that are not impacted.
The plant-level control strategy figure 8. The frequency droop function.
results in a capture of energy from
inverters that would have been otherwise unnecessarily cur- that are not impacted by the cloud cover to dynamically increase
tailed. This concept is illustrated in Figure 5. The left side of their previously curtailed limit. Since the total potential power
the figure represents the reduction in power output of some of of the plant is greater than the specified plant output limit (as
the inverters (grouped in blocks for illustration purposes) due illustrated on the right-hand side of Figure 5), the plant is able to
to partial cloud cover. The controller commands other inverters output the total power all the way to the limit.
An illustration of an additional function related to active required ramp rate. As mentioned earlier, some inverters
power management is shown in Figure 6, which shows the are turned down while others are shut down. Note that the
reaction of the plant when it is shut down and started up. control is quite effective even with moderately varying irra-
The field data in this case illustrates when one block (30 diance conditions.
MW), which is under the control of the plant controller, Figure 7 also illustrates the plant start command resulting in
is commanded to shut down. The active power manage- the controller gradually increasing the plant output by adjusting
ment function reduces plant output while maintaining the the inverters’ output and turning on the inverters in sequence.
Ibranch 1 VcompFlag +
Vreg Vreg – (Rc + jXc) × Ibranch 1 – ∑ Qmax
0 1 + sTfltr
dbd emax
+ 1 Ki 1 + sTft
+ RefFlag Kp + Qext
Qbranch Kc ∑ S 1 + sTiv
0
1 – emin
∑ Freeze State If
1 + sTfltr Qmin Vreg < Vfrz
+
Qref
Plant_Pref Pmax
Freg_flag
+ femax 0
1 – Kig 1 Pref
Pbranch ∑ Kpg +
1 + sTp 0 S 1 + sTlag 1
+ femin
fdbd1, fdbd2 Ddn + Pmin
Freg ∑ ∑
–
+ Dup +
Freg_ref
0
3
1
1 2 4 5
12-MVar Cap Bank
90.0 89.75 89.58 89.54 89.54 89.54 89.54
1.000
1.000
34.62
1.003
short-term solar generation forecasts is facilitating continued can reduce the impact of cloud passage and increase over-
efficient and reliable system operations. By providing PV all yield. Plant-model validation against measured field data
plants that can support the forecasting needs of grid opera- demonstrates that the WECC-proposed model for a solar PV
tors, this variable resource can address the load-balancing plant is adequately capturing actual plant behavior.
needs of grid operators. An advantage of solar in many mar-
kets is that its peak generation coincides with higher load For Further Reading
demand, making it more a valuable generation resource. R. Binz. (2012. Apr.). Practicing risk aware electricity regu-
lation: What every state regulators need to know. A Ceres
Grid Flexibility and Power Report. [Online]. Available: http://www.ceres.org/resources/
Systems Resource Planning reports/practicing-risk-aware-electricity-regulation
As the proportion of variable generation increases in the M. G. Lauby, M. Ahlstorm, D. L. Brooks, S. Beuning, J.
overall generation portfolio, another integration concern is Caspray, W. Grant, B. Kirby, M. Milligan, M. O’Malley, M.
that greater grid flexibility is required to provide the neces- Patel, R. Piwko, P. Pourbeik, D. Shirmohammadi, and J. C.
sary power backup when the variable generation resource is Smith., “Balancing act,” IEEE Power Energy Mag., vol. 9,
not adequate to meet the demand. This dictates an increased no. 6, pp. 75–85, Nov./Dec. 2011.
use of conventional resources that are able to respond and Modeling and Validation Work Group/Technical Stud-
ramp up more quickly and a reduced use of inflexible gen- ies Subcommittee. (2011, Jan.). [Online]. Available: https://
eration resources. A recent analysis points out “that planning www.wecc.biz/committees/StandingCommittees/PCC/TSS/
the lowest-cost, lowest-risk investment route aligns with a MVWG/Shared%20Documents/MVWG%20Approved%20
low-carbon future. From a risk management standpoint, Do cu ment s/ W ECC%20PV%20Pla nt%20Power%20
diversifying utility portfolios today by expanding invest- Flow%20Modeling%20Guide.pdf
ment in clean energy and energy efficiency makes sense R. Piwko, A. Ellis, R Walling, B. Zavadil, D. Jacobson,
regardless of how and when carbon controls come into play. M. Patel, D. Brooks, B. Nelson, J. MacDowell, C. Barker,
Placing too many bets on the conventional basket of genera- E. V. Engeln, E Seymour, L. Casey, E. John, W. Peter, W. Lasher, C.
tion technologies is the highest risk route.” Loutan, L. Dangelmaier, E. Seymour, and M. Behnke. (2012,
Mar.). Special reliability assessment: Interconnection require-
Summary ments for variable generation. NERC. [Online]. Available:
We have described a utility-scale, grid-friendly PV power http://www.nerc.com/comm/PC/Integration%20of%20Vari-
plant that incorporates advanced capabilities essential to able%20Generation%20Task%20Force%20IVGT/Sub%20
supporting grid stability and reliability. It includes features Teams/Interconnection/NERC_IVGTF_1-3_DRAFT.pdf
such as voltage regulation, active power controls, ramp-rate WECC Renewable Energy Modeling Task Force. (2012,
controls, fault ride through, and frequency control. These Sept.). [Online]. Available: https://www.wecc.biz. https://
capabilities provide the intrinsic benefits of reliable plant www.wecc.biz/committees/StandingCommittees/PCC/TSS/
operation in the grid, which in turn results in additional MVWG/Shared%20Documents/MVWG%20Approved%20
plant yield and potential additional revenue. Such capa- Documents/WECC%20Solar%20PV%20Dynamic%20
bilities are essential for successful the deployment of large- Model%20Specification%20-%20September%202012.pdf
scale PV plants.
A key component of such a grid-friendly plant is a plant- Biographies
level controller specifically engineered to regulate real and Mahesh Morjaria is with First Solar, Tempe, Arizona.
reactive power output of the solar facility such that it behaves Dmitriy Anichkov is with First Solar, Tempe, Arizona.
as a single large conventional generator, although within Vladimir Chadliev is with First Solar, Tempe, Arizona.
the limits dictated by the intermittent nature of the solar Sachin Soni is with Arizona State University, Tempe,
resource. In cases where the plant output is constrained but Arizona.
p&e
the plant has additional generation capability, this controller