Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ziegler-Mfm-3480 Manual-E1R0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 78

ZIEGLER mfm 3480

Digital Multifunction Instrument - Touch Screen Graphics LCD

© Ziegler Instruments Order No. Ziegler mfm 3480 User Manual-E1.R0-920716-41-2013-EN


www.ziegler-instruments.com User Manual

Version: 15001123 Rev.A - 08/2012


Single Phase
Single Phase Touch Screen Digital Multi-function Meter
Installation & Operating Instructions
Section Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.1.1 Change Password
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 Potential transformer Primary value
3.2.1.2 Potential transformer secondary value
3.2.1.3 Current transformer Primary value
3.2.1.4 Current transformer Secondary value
3.2.1.5 Demand integration time
3.2.1.6 Auto Scrolling
3.2.1.7 Low current noise cutoff
3.2.1.8 Energy on RS485
3.2.1.9 Energy Digit Reset Count
3.2.2 Communication Parameter selection screen
3.2.2.1 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection
15001123 Rev.A - 8/2012
1
3.2.3 Reset Parameter selection screen
3.2.3.1 Resetting Parameter
3.2.4 Output Option selection screen (menu)
3.2.4.1 Relay 1 output selection menu
3.2.4.1.1 Pulse output
3.2.4.1.1.1 Assignment of Energy to Pulse (Relay 1)
3.2.4.1.1.2 Pulse Duration Selection
3.2.4.1.1.3 Pulse Rate
3.2.4.1.2 Limit output
3.2.4.1.2.1 Assignment of Limit Output1 to Parameter
3.2.4.1.2.2 Limit Configuration
3.2.4.1.2.3 Trip point selection
3.2.4.1.2.4 Hysteresis selection
3.2.4.1.2.5 Energizing delay time
3.2.4.1.2.6 De-energizing delay time
3.2.4.2 Relay 2 output selection menu
3.2.4.3 Parameter setting for Analog Output-1
3.2.4.4 Parameter setting for Analog Output-2
3.2.5 Brightness & Contrast
4. Touch screen calibration.
5. Run - Hour.
6. On - Hour.
7. Number of Interruption
8. Analog Output
9. Relay Output
9.1 Pulse output
9.2 Limit switch
10. RS 485 (Modbus) output
10.1 User Assignable modbus Registers

2
11. Phaser Diagram
12. Installation
12.1 EMC Installation Requirements
12.2 Case Dimensions and Panel Cut-out
12.3 Wiring
12.4 Auxiliary Supply
12.5 Fusing
12.6 Earth / Ground Connections
13. Connection Diagram
14. Specification
15. Connection for Optional Pulse output / RS 485 /Analog Ouput
1. Introduction
This instrument is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the
measurement of important electrical parameters like AC voltage, AC Current, Frequency,
Power, Energy(Active / Reactive / Apparent) . The instrument integrates accurate
measurement of technology (All Voltage & Current measurements are True RMS upto 15th
Harmonic) with 320x240 Pixels touch screen TFT LCD display.
This instrument can be configured and programmed at site
for the following: PT Primary, PT Secondary, CT Primary and
CTMAIN
LINE-NEUTRAL
MAIN MENU
VOLTAGE
MENU
SECONDARY
CT Secondary (5A or1A).
1 AMPERE
VL2 0.000 V
VL2 0.000
5 AMPERE
SYSTEM VOLTAGE
V
CURRENT The front panel has a 3.5” Touch Screen through which the user can
VL2 0.000 V move across the available measurement readings, reset the energy,
OKVOLTAGE
MAIN ENERGY
POWER SETUP
Min/Max (System Voltage and System Current) and configure the
product settings.

3
TABLE 1:
Units of
Measured Parameters
Measurement
System Voltage Volts
System Current Amps
Frequency Hz
System Active Power Kwatts
System Reactive Power KVAr
System Apparent Power KVA
System Power Factor
System Phase Angle Degree
Active Import Energy (8 Digit resolution) kWh
Active Export Energy (8 Digit resolution) kWh
Reactive Import Energy (8 Digit resolution) kVArh
Reactive Export Energy (8 Digit resolution) kVArh
Apparent Energy (8 Digit resolution) kVAh
Ampere Hour (8 Digit resolution) KAh
Current Demand Amps
KVA Demand KVA
KW Import Demand KW
KW Export Demand KW
Max Current Demand Amps
Max kVA Demand KVA
Max KW Import Demand KW
Max KW Export Demand KW
Run Hour Hours
On Hour Hours

4
Units of
Measured Parameters
Measurement
Number of Interruptions Counts
System Voltage THD %
System Current THD %
Pictorial representation of Phaser Diagram
Pictorial representation of Voltage Waveform
Pictorial representation of Current Waveform
Pictorial representation of VA Waveform

2. Measurement Reading Screens


In normal operation the user is presented with one of the measurement reading screens out of
several screens. These screens from particular submenu may be scrolled through one at a time
in incremental order by touching the “ key” and in decremental order by touching “ key”
on that screen. Viewing of any individual parameter with large reading (eg. shown
of Line-Neutral Voltage in sub menu 2 screen 12) is also possible by touching that
particular parameter.
SUBMENU 1 : SYSTEM
Screen 1 : System Parameters Screen 2 : System Max. Screen 3 : System
(System Voltage, System Values (System Voltage, Min. Values (System Voltage,
Current, System Active Power) System Current) System Current)
V x1000

SYSTEM PARAMETERS
LINE-NEUTRAL VOLTAGE SYSTEM Max.VOLTAGE
LINE-NEUTRAL VALUES SYSTEM Min.VOLTAGE
LINE-NEUTRAL VALUES

VL2 0.000 V
239.6 0.000 0.000
239.9 V KVA
Min
KVAh
Ph Y 239.2 V
VL2 0.000 A
5.001 VL2 0.000 V %THD 0.000 V KW
VBR
x1000
P.F.
5.005 A 4.998 A
VL2 0.000 KW
3.592 AngleKWh Angle KWh
0.000
Max Ph B Max Ph B
MAIN VOLTAGE
SYSTEM Demand MAIN VOLTAGE
SYSTEM Demand MAIN VOLTAGE
SYSTEM

5
Screen 4 : Screen 5 : Screen 6 :
Phaser Diagram System Run Hour System ON Hour

0
90 V/Div
Capacitive Inductive 124.5
-P,+Q +P,+Q 1.500 A/Div SYSTEM RUNVOLTAGE
LINE-NEUTRAL HOUR SYSTEM ON VOLTAGE
LINE-NEUTRAL HOUR
VL1 0.000 V
IL1 0.000 A
1 0.000
VL2 0.000 V
180
0
0
0 000001.19 000005.18
VL2 0.000 VL2 0.000 V
hrs hrs
VL2 0.000
-P,-Q
Inductive
270
0
+P,-Q
Capacitive 0.000 VL2 0.000 V
MAIN SYSTEM
VOLTAGE MAIN VOLTAGE
SYSTEM MAIN VOLTAGE
SYSTEM

Screen 7 : Screen 8 : Screen 9 :


System Interruptions System Frequency System Power Factor

SYSTEM INTERRUPTIONS
LINE-NEUTRAL VOLTAGE SYSTEM FREQUENCY
LINE-NEUTRAL VOLTAGE SYSTEM POWER
LINE-NEUTRAL FACTOR
VOLTAGE

VL2 0.000 V VL2 0.000 V VL2 0.000 V


1.000
VL200000012
0.000 V VL2
0.000
0.000 Hz
V VL2 0.000 V
VL2 0.000 V VL2 0.000 V VL2 0.000 V
MAIN VOLTAGE
SYSTEM MAIN VOLTAGE
SYSTEM MAIN VOLTAGE
SYSTEM

Screen 10 : Screen 11 :
System Power
SUBMENU 2 : VOLTAGE
System % THD Screen 12 : Line-Neutral Voltage

SYSTEM % THD
LINE-NEUTRAL VOLTAGE SYSTEM POWER
LINE-NEUTRAL VOLTAGE LINE-NEUTRAL
LINE-NEUTRAL VOLTAGE
VOLTAGE

VL2
0.000
0.000 kVAr
V VL2 0.000 V
VL2
V 0.000 %
V
VL2
0.000
0.000 kVA
V VL2239.6
0.000 V
VL2
A 0.000 V
%
VL2 0.000 V 0.000
VL2 0.000 kWV VL2 0.000 V
MAIN SYSTEM
VOLTAGE MAIN VOLTAGE
SYSTEM MAIN VOLTAGE

6
Line-Neutral Voltage Screen 13 : Screen 14 : Pictorial representation
(Displayed after touching any where Phase Voltage % THD of Voltage Waveform (Only accessed
in the row shown in screen 12) through voltage submenu list)

LINE-NEUTRAL
LINE-NEUTRAL VOLTAGE PHASE VOLTAGE
LINE-NEUTRAL % THD
VOLTAGE LINE-NEUTRAL VOLTAGE
VOLTAGE WAVEFORM
VOLTAGE
VL2 0.000 V 116.5
Vrms

239.6 VL20.000
0.000 V
%
49.94

V
BACK
VL2 0.000 V
62.25
Hz

MAIN VOLTAGE MAIN VOLTAGE


2.500
V/Div ms/Div

SUBMENU 3 : CURRENT Screen 16: Screen 17 : Pictorial representation


of Current Waveform
Screen 15 : Line Current Line Current %THD
(Only accessed through
current submenu list)

LINE CURRENT
LINE-NEUTRAL VOLTAGE LINE CURRENT
LINE-NEUTRAL % THD
VOLTAGE CURRENT WAVEFORM
LINE-NEUTRAL VOLTAGE

VL2 0.000 V VL2 0.000 V 42.43


Arms

VL20.000
0.000 V
A VL2 0.000
0.000 V
% 49.94

VL2 0.000 V VL2 0.000 V Hz

30.00 2.500
MAIN CURRENT
VOLTAGE MAIN VOLTAGE
CURRENT A/Div MAIN CURRENT ms/Div

SUBMENU 4 : POWER Screen 19 : Phase Apparent Screen 20 : Phase Active


Screen 18 : Phase Reactive Power Power
Power

PHASE REACTIVE
LINE-NEUTRAL POWER
VOLTAGE PHASE APPARENT
LINE-NEUTRAL POWER
VOLTAGE PHASE ACTIVE
LINE-NEUTRAL POWER
VOLTAGE

VL2 0.000 V VL2 0.000 V VL2 0.000 V


VL2 0.000 kVAr
0.000 V VL2
0.000
0.000 kVA
V VL2 0.000 kW
0.000 V
VL2 0.000 V VL2 0.000 V VL2 0.000 V
MAIN VOLTAGE
POWER MAIN VOLTAGE
POWER MAIN VOLTAGE
POWER

7
Screen 21 : Phase Angle Screen 22 : Phase Power Screen 23 :
Factor Current Demand

PHASE ANGLE
LINE-NEUTRAL VOLTAGE PHASE POWER
LINE-NEUTRAL FACTOR
VOLTAGE CURRENT DEMAND
LINE-NEUTRAL VOLTAGE

VL2 0.000 V VL2 0.000 V VL2 0.000 V


0.000
Demand A
0.000
VL2 0.000 DEG
V 1.000
VL2 0.000 V VL2
Max0.000 V
0.000
Demand A
VL2 0.000 V VL2 0.000 V VL2 0.000 V
MAIN VOLTAGE
POWER MAIN VOLTAGE
POWER MAIN VOLTAGE
POWER

Screen 24 : Screen 25 : Screen 26 :


VA Demand Import Active Demand Export Active Demand

VA DEMAND
LINE-NEUTRAL VOLTAGE IMPORT ACTIVE
LINE-NEUTRAL DEMAND
VOLTAGE EXPORT ACTIVE
LINE-NEUTRAL DEMAND
VOLTAGE

VL2 0.000 V VL2 0.000 V


Demand 0.000 kVA Demand 0.000 kW Demand 0.000 kW
VL2
Max 0.000 V VL2
Max 0.000 V Max
Demand 0.000 kVA Demand 0.000 kW Demand 0.000 kW
VL2 0.000 V VL2 0.000 V
MAIN VOLTAGE
POWER MAIN VOLTAGE
POWER MAIN VOLTAGE
POWER

Screen 27 : Pictorial representation SUBMENU 5 : ENERGY


Of Phase Waveform Screen 28 : Screen 29 :
(only accessed through power submenu list) Active Energy Import Active Energy Export

PHASE WAVEFORM
LINE-NEUTRAL VOLTAGE ACTIVE ENERGY
LINE-NEUTRAL IMPORT
VOLTAGE ACTIVE ENERGY
LINE-NEUTRAL EXPORT
VOLTAGE

210.4
DEG
VL2 0.000 V VL2 0.000 V
49.94
0.0000000 0.0000000
Hz
VL2 0.000 V VL2 0.000 V
116.5
V kWh kWh
42.43
A
VL2 0.000 V VL2 0.000 V
62.25
MAIN POWER
2.500
MAIN ENERGY
VOLTAGE MAIN ENERGY
VOLTAGE
V/Div ms/Div

8
Screen 35 : Screen 36 : Screen 37 :
Reactive Energy Import Reactive Energy Export Apparent Energy

REACTIVE ENERGY
LINE-NEUTRAL IMPORT
VOLTAGE REACTIVE ENERGY
LINE-NEUTRAL EXPORT
VOLTAGE APPARENT ENERGY
LINE-NEUTRAL VOLTAGE

VL2 0.000 V VL2 0.000 V 0.000


0.0000000 0.0000000 0.0000000
VL2 0.000 V VL2 0.000 V 0.000
kVArh kVArh kVAh
VL2 0.000 V VL2 0.000 V VL2 0.000
MAIN ENERGY
VOLTAGE MAIN ENERGY
VOLTAGE MAIN ENERGY
VOLTAGE

Screen 38 :
Ampere Hour

AMPERE HOUR
LINE-NEUTRAL VOLTAGE

VL2 0.000 V
0.0000000
VL2 0.000 V
kAh
VL2 0.000 V
MAIN ENERGY
VOLTAGE

9
Parameter Screens
MAIN MENU

A
A
SYSTEM
COMMUNICATION
VOLTAGE
PARAMETERS
RESET
CURRENT POWER
OPTIONS
(Sec 3.2.4)
CHANGE
ENERGY
PASSWORD
(Sec 3.1)
A

B
A

SYSTEM
SYSTEM TYPE Line to Neutral PHASE REACTIVE ACTIVE ENERGY
(Sec 3.2.1.1)
PARAMETERS VOLTAGE Line Current POWER IMPORT

Max.
PT VOLTAGE
PRIMARY
PHASE APPARENT ACTIVE ENERGY
And(Sec
CURRENT
3.2.1.2) PHASE VOLTAGE LINE CURRENT POWER EXPORT
%(SecTHD
3.2.2.3)
% THD

Min. VOLTAGE
PT SECONDARY CURRENT PHASE ACTIVE REACTIVE ENERGY
And(Sec 3.2.1.3)
CURRENT WAVEFORM
(Sec 3.2.2.3) WAVEFORM POWER IMPORT

PHASER
CT PRIMARY PHASE REACTIVE ENERGY
DIAGRAM
(Sec 3.2.1.4)
ANGLE EXPORT

RUN(Sec HOUR
CT SECONDARY
3.2.1.5)
PHASE APPARENT
POWER FACTOR ENERGY

DEMAND POWER FACTOR


CT SECONDARY
(Sec 3.2.1.5)

ON HOUR
INTEGRATION
TIME
CURRENT AMPERE
DEMAND HOUR
DEMAND
THD.VOLTAGE
INTEGRATION
No.SCROLL
OF AND TIME
CURRENT
AUTO
(Sec 3.2.1.7)
INTERRUPTIONS
APPARENT
DEMAND
SYSTEM
AUTO SCROLL
(Sec 3.2.1.7)
SYSTEM
LOW CURR.
NOISE CUTOFF
POWER IMPORT
FREQUENCY
ACTIVE DEMAND
B
LOW CURR.
A
NOISE CUTOFF

EXPORT
ACTIVE DEMAND

PHASE
WAVEFORM

10
Setup Parameter Screens PASSWORD
(Sec 3.1)
ENTER

SYSTEM
SYSTEM COMMUNICATION RESET OUTPUT CHANGE BRIGHTNESS
PARAMETERS
PARAMETERS
PARAMETERS PARAMETERS PARAMETERS OPTIONS & CONTRAST
PASSWORD
(Sec
(Sec 3.2.1)
3.2.1) (Sec 3.2.2) (Sec 3.2.3) (Sec 3.2.4) (Sec 3.2.5)
(Sec 3.1.1)

PT PRIMARY Rs485 ADDRESS RESET ALL


(Sec 3.2.1.1) RESET DEMAND PARAMETERS
RELAY
(Sec 3.2.2.1)
RESET ALL ENERGIES OUTPUT 1
PT SECONDARY RS485 RESET MAX VOLTAGE & CURRENT (Sec 3.2.4.1) PULSE LIMIT
(Sec 3.2.1.2) BAUD RATE OUTPUT
(Sec 3.2.2.2) RESET MIN VOLTAGE & CURRENT OUTPUT
RELAY (Sec 3.2.4.1.1) (Sec 3.2.4.1.2)
CT PRIMARY RESET RUN-HOUR,ON-HOUR
(Sec 3.2.1.3) RS485 PARITY OUTPUT 2 PARAMETER
(Sec 3.2.2.3) RESET AUX INTERRUPT COUNT SELECTION
(Sec 3.2.4.2) PARAMETER (Acc. To Table 2)
Select any option by (Sec 3.2.4.1.2.1)

11
CT SECONDARY SELECTION
(Sec 3.2.1.4) touching on it.
(Sec 3.2.4.1.1.1)
CONFIGURATION
DEMAND ANALOG OUTPUT 1 SELECTION
INTEGRATION (Sec 3.2.4.1.2.2)
TIME (Analog 1 parameter
(Sec 3.2.1.5)
selection) PULSE TRIP POINT
AUTO SCROLL (Acc. To Table 2) DURATION 10% to 100%/120%
(Sec 3.2.1.6) (Sec 3.2.4.3) (Sec 3.2.4.1.2.3)
60,100,200
(Sec 3.2.4.1.1.2) HYSTERESIS
LOW CURR. 0.5% to 50%
NOISE CUTOFF
(Sec 3.2.4.1.2.4)
(Sec 3.2.1.7) ANALOG OUTPUT 2
(Analog 2 parameter PULSE RATE ENERGIZING
ENERGY ON selection) DELAY
RS485 (Pulse DivisorRRate) 1s to 10s
(Sec 3.2.1.8) (Acc. To Table 2) (Sec 3.2.4.1.2.5)
1, 10, 100, 1000
(Sec 3.2.4.4)
ENERGY DIGIT (Sec 3.2.4.1.1.3) DE-ENERGIZING
RESET COUNT DELAY
(Sec 3.2.1.9) 1 s to 10s
(Sec 3.2.4.1.2.6)
3. Programming
The following sections comprise step by step procedures for configuring the instrument for
individual user requirements.
To access the set-up screens touch on the “ SETUP ” icon in Main Menu. This will take the
User into the Password Protection Entry Stage(Section 3.1).

3.1. Password Protection


Password protection can be enabled to prevent unauthorised access to set-up screens, by default
password is “0000”.
Password protection is enabled by selecting any four digit number.

After touching “ SETUP” icon Password protection screen is


SETUP
displayed. Screen consists of 0 to 9 digit input keypad for entering
ENTER PASSWORD
1 2 3 DEL the password very similar to any calculator in touchscreen mobile.
4 5 6
ENTER “Enter Password” is displayed on screen at start so that user can enter
7 8 9
0 BACK password using displayed keypad.

Touching “ 1 key” will display 1 in display area, similarly user can


SETUP
enter remaining 3 digits.
1
1 2 3 DEL For deleting any digit while entering password, user can touch
4 5 6
7 8 9
ENTER “ DEL key”.
0 BACK

12
After entering the complete password user needs to confirm password
SETUP

1234 by touching “ key”.


ENTER
1 2 3 DEL
4 5 6
ENTER
7 8 9
0 BACK

Password confirmed.
SETUP

PASSWORD ACCEPTED
If Entered password is correct then “Password Accepted” is displayed
1 2 3 DEL
on screen & user will enter into setup menu.
4 5 6
ENTER
7 8 9
0 BACK

Password Incorrect.
SETUP

PASSWORD REJECTED.
If Entered password is wrong then “Password Rejected” is displayed
1 2 3 DEL
on screen & user need to re-enter the password
4 5 6
ENTER
7 8 9
0 BACK

PASSWORD

PRESS ENTER TO TRY AGAIN


1 2 3 DEL After wrong password is entered, user needs to touch “ ENTER
key” for
4 5 6
7 8 9
ENTER trying another password.
0 BACK

13
3.1.1 Change Password
Change Password Option is the second last option in list of “SETUP”
PASSWORD submenu, so can be accessed by a simple touch anywhere in “ Change
ENTER CURRENT PASSWORD
Password” row.
1 2 3 DEL
4 5 6 In this screen user first needs to enter the current password.
ENTER
7 8 9
0 BACK

After input of correct password,“PASSWORD ACCEPTED”is displayed


PASSWORD & now user can enter the new 4 digit password.
ENTER NEW PASSWORD
1 2 3 DEL
4 5 6
ENTER
7 8 9
0 BACK

New Password confirmed.


PASSWORD
After entering new password user needs to touch “ ENTER
key” to
PASSWORD CHANGED
1 2 3 DEL
confirm.
4 5 6
ENTER
7 8 9 After confirming “PASSWORD CHANGED” is displayed on screen,
0 BACK
which ensures successful changing of the password.

3.2 Menu selection.


After entering in the SUBMENU 6 - SETUP, user will be asked to enter password & after input of
correct password list of following parameters will be displayed on screen :-
3.2.1 SYSTEM PARAMETERS
3.2.2 COMMUNICATION PARAMETERS
14
3.2.3 RESET PARAMETERS
3.2.4 OUTPUT OPTIONS
3.2.5 BRIGHTNESS & CONTRAST
Touching on SYSTEM PARAMETER will open the system parameters list screen.Then these
screens from particular parameter may be scrolled through one at a time in incremental order by
touching the “ key” and in decremental order by touching “ key” on given touch screen.

3.2.1 System Parameters Selection


After entering in the “SYSTEM PARAMETERS”, List of following parameters will be displayed :-
3.2.1.1 PT PRIMARY(L-L)
3.2.1.2 PT SECONDARY(L-L)
3.2.1.3 CT PRIMARY
3.2.1.4 CT SECONDARY
3.2.1.5 DEMAND INTEGRATION TIME
3.2.1.6 AUTO SCROLL
3.2.1.7 LOW CURRENT NOISE CUTOFF
3.2.1.8 ENERGY ON RS485
3.2.1.9 ENERGY DIGIT RESET COUNT

3.2.1.1 Potential Transformer Primary Value


The nominal full scale voltage will be displayed as Line to Line Voltage.
This screen can be accessed only from system parameters list menu.
LINE-NEUTRAL
PT PRIMARY
VOLTAGE
Here again 0 to 9 digit input keypad is provided to set value of PT
ENTER PT PRIMARY VALUE(L-L) Primary, & user can confirm this value with a simple touch “
1 2 3 DEL ENTER
4 5 6
ENTER
key”. “ K key” is used to multiply value by 1000.
7 8 9
. 0 K BACK
In case presently displayed Potential Transformer Primary value together
with the Current Transformer Primary value, previously set, would result
in a maximum power of greater than 666.6 MVA per phase,”Invalid
value” will be displayed. Then the valid range will be displayed.

15
Valid range of PT primary setting value is from
LINE-NEUTRAL
PT PRIMARY
VOLTAGE 100 VL-L to 692.8 KVL-L.
INVALID VALUE
1 2 3 DEL
If value outside the range is entered, It will display “INVALID VALUE”
4 5 6
ENTER
followed by correct range of parameter.
7 8 9
. 0 K BACK

3.2.1.2 Potential Transformer secondary Value


The value must be set to the nominal full scale secondary voltage which will be obtained from the
the Transformer when the potential transformer(PT)primary is supplied with the voltage defined
in 3.2.1.1 potential transformer primary voltage. The ratio of full scale primary to full scale
secondary is defined as the transformer ratio.
This screen can be accessed only from system parameters list menu.
LINE-NEUTRAL
PT SECONDARY
VOLTAGE

ENTER PT SECONDARY VALUE(L-N)


Here again 0 to 9 digit input keypad is provided to set value of PT
1 2 3 DEL Secondary, & user can confirm this value with a simple touch on
4 5 6
7 8 9
ENTER
“ key”.
. ENTER
0 K BACK

LINE-NEUTRAL
PT SECONDARY
VOLTAGE Valid range of PT secondary setting value is from 241.0 to 480.0.
INVALID VALUE
1 2 3 DEL
for 415 VL-L. Please refer the table bellow for different ranges.
4 5 6
7 8 9
ENTER If value outside the range is entered, It will display “INVALID VALUE”
. 0 K BACK followed by correct range of parameter.

Potential Transformer secondary ranges for various Input Voltages


63.5V L-N 57.73V - 69.28V L-N
133.0V L-N 69.86V - 138.56V L-N
239.6V L-N 139.14V - 277.12V L-N

16
3.2.1.3 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen
enables the user to display the Line currents inclusive of any transformer ratios, the values
displayed represent the Current in Amps.
This screen can be accessed only from system parameters list menu.
LINE-NEUTRAL
CT PRIMARY
VOLTAGE

ENTER CT PRIMARY VALUE Here again 0 to 9 digit input keypad is provided to set value of CT
1 2 3 DEL
4 5 6
Primary & user can confirm this value with a simple touch on “
ENTER ENTER
7 8 9 key”. “ K key” is used to multiply value by 1000.
. 0 K BACK

In case presently displayed Current Transformer Primary Value


together with the Potential Transformer Primary Value results in a
maximum power of greater than 666.6 MVA, “invalid value” will be displayed. Example:
If primary value of PT is set as 692.8kV L-L (max value) then primary value of Current is
restricted to 1157A.
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and
120% of nominal voltage, i.e, 462.96 MVA nominal power per phase.
Valid range of CT primary setting value is from 1 to 9999. If value
LINE-NEUTRAL
CT PRIMARY
VOLTAGE outside the range is entered, It will display “INVALID VALUE”
INVALID VALUE followed by correct range of parameter.
1 2 3 DEL
4 5 6
ENTER
7 8 9
. 0 K BACK

17
3.2.1.4 Current Transformer Secondary Value
This screen is used to set the secondary value for Current Transformer.
CT
CTSECONDARY
LINE-NEUTRAL VOLTAGE
SECONDARY Two options: 1 AMPERE & 5 AMPERE are displayed on screen.
1 AMPERE
VL2
1 AMPERE
0.000 V Touching radio button in front of particular option will select that option.
VL2 0.000
5 AMPERE
5 AMPERE V Touch on “ OK key” will confirm the setting. Touching the
OK
MAIN BACK
“ BACK key” will keep the old selected setting and will return
to previous menu.

3.2.1.5 Demand Integration Time


This screen is used to set the period over which current and power
DEMAND INTEGRATION
LINE-NEUTRAL VOLTAGETIME
CT SECONDARY readings are to be integrated.
8 MINUTES 20 MINUTES
1 AMPERE
VL2 0.000 Four options: 8, 15, 20, 30 Minutes are displayed on screen. Touching
VL2 0.000
15 MINUTES
5 AMPERE 30 MINUTES
radio button in front of particular option will select that option.
OK
MAIN BACK Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will
return to previous menu.
3.2.1.6 Auto Scrolling
This screen allows user to enable screen scrolling. Seven options :
AUTO - SCROLL
LINE-NEUTRAL VOLTAGE
CT SECONDARY
ALL, SYSTEM, VOLTAGE, CURRENT
1 AMPERE
VL2
ALL 0.000 V
SYSTEM
POWER, ENERGY & NONE are displayed on screen. Touching radio
VOLTAGE
POWER
CURRENT
ENERGY
button in front of particular option will select that option. Selecting
VL2 0.000
NONE V particular option means, only screens which are under that submenu
OK
MAIN BACK
will be scrolled automatically. Selecting NONE will disable Auto-Scroll.
Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will return to previous menu.

18
While in Auto-scrolling mode, touch sense for entire screen will be disabled except for the
top right most corner where “A” symbol would be displayed stating that meter is in Auto-
scroll mode.
Touching on “A” will show two options “ON” and “OFF”. Touching on “ON” will continue
auto scrolling & touching on “OFF” will stop auto-scrolling & return to normal mode.

3.2.1.7 Low Current noise cutoff.


This screen allows the user to set Low noise current cutoff in mA.
Two options, 0 MILLI-AMPERE & 30 MILLI-AMPERE are displayed on
LOW CURRENT
LINE-NEUTRAL NOISE CUTOFF
VOLTAGE
CT SECONDARY screen. Touching radio button in front of particular option will
0 MILLI-AMPERE
1 AMPERE
VL2 select that option.
VL2
30 MILLI-AMPERE
5 AMPERE

Touch on “ OK key” will confirm the setting.


OK
MAIN BACK Touching the “ BACK key” will keep the old selected setting
and will return to previous menu.

3.2.1.8 ENERGY ON RS485.


This screen enable user to set energy in terms of Wh / kWh / MWh on Rs485 Output
depending as per the user’s requirement .This setting is applicable for all types of energy.
Three options: WATT, KILO-WATT & MEGA-WATT are displayed on
LINE-NEUTRAL VOLTAGE
CT SECONDARY
ENERGY ON RS485 screen. Touching radio button in front of particular option will
WATT (W)
1 AMPERE
VL2 select that option.
VL2
KILO-WATT
5 AMPERE (KW)

MEGA-WATT (MW) Touch on “ OK key” will confirm the setting.


OK
MAIN BACK Touching the “ BACK key” will keep the old selected setting
and will return to previous menu.

Note : Default value is set to ‘WATT’ i.e. Energy on Modbus will be in


terms of Wh/VArh/VAh/Ah respectively.

19
3.2.1.9 ENERGY DIGIT RESET COUNT (ROLLOVER COUNT)
This screen enables the user for setting maximum energy count after which energy will
rollover to zero depending on the setting of Wh, kWh & Mwh in Energy on RS485 option.
If Energy on RS485 is in WATT then rollover count can be from
7 to 14 DIGITS.
ENERGY
CTDIGIT
LINE-NEUTRAL RESET COUNT
VOLTAGE
SECONDARY
If Energy on RS485 is in KILO-WATT then rollover count can be from
7 DIGITS 8 DIGITS
1 AMPERE
VL2
9 DIGITS 10 DIGITS
7 to 12 DIGITS.
VL2
5 AMPERE
11 DIGITS 12 DIGITS If Energy on RS485 is in MEGA-WATT then rollover count can be from
13 DIGITS 14 DIGITS
7 to 9 DIGITS.
OK
MAIN BACK
Touching radio button in front of particular option will select that option.
Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will return to previous menu.
Note : 1) Default value of energy digit reset count is set to “14” i.e if energy crosses the
14 digit count it will rollover to zero.
2) If Energy on RS485 is set to kW & energy digit reset count is set to 12, Energy screen
on display will show “-------” i.e energy overflow when energy crosses the 11 digit count.
3) If Energy on RS485 is set to MW & energy digit reset count is set to 9, Energy screen
on display will show “-------” i.e energy overflow when energy crosses the 8 digit count.
3.2.2 Communication Parameter Selection :
After entering in the “COMMUNICATION PARAMETERS” list of following parameters
will be displayed
3.2.2.1 RS485 ADDRESS
3.2.2.2 Rs485 BAUD RATE
3.2.2.3 Rs485 PARITY

20
3.2.2.1 Rs485 Address Setting
This screen applies to the RS 485 output only. This screen allows
LINE-NEUTRAL VOLTAGE
RS485 ADDRESS
the user to set RS485 address parameter for the instrument.
ENTER RS485 ADDRESS
1 2 3 DEL This screen can be accessed only from Communication
4 5 6
7 8 9
ENTER Parameters List menu.
0 BACK Here again 0 to 9 digit input keypad is provided to set RS485 address &
user can confirm this value with a simple touch on “ key”.
ENTER

LINE-NEUTRAL VOLTAGE
RS485 ADDRESS

INVALID VALUE
The range of allowable address is 1 to 247.
1 2 3 DEL If value outside the range is entered, it will display “INVALID VALUE”
4 5 6
7 8 9
ENTER
followed by the correct range of parameter.
0 BACK

3.2.2.2 RS 485 Baud Rate


This screen allows the user to set Baud Rate of RS 485 port.
RS485 BAUD
LINE-NEUTRAL RATE
VOLTAGE
CT SECONDARY
Four options: 2400, 4800, 9600, 19200 Bauds are displayed on
2400
1 AMPERE 9600
screen. Touching radio button in front of particular option will
VL2 0.000
4800 0.000
VL2
5 AMPERE 19200 select that option.
VL2 0.000 V Touch on “ OK key” will confirm the setting.
OK
MAIN BACK
Touching the “ BACK key” will keep the old selected setting
and will Return to previous menu.

21
3.2.2.3 RS 485 Parity & Stop bit Selection
This screen allows the user to set Parity & number of stop bits.
RS485 PARITYVOLTAGE
LINE-NEUTRAL & STOP BITS Four options: ODD PARITY WITH ONE STOP BIT, NO PARITY
ODD PARITY WITH ONE STOP BIT
1 AMPERE
VL2 WITH ONE STOP BIT, NO PARITY WITH TWO STOP BITS,
NO PARITY WITH ONE STOP BIT
VL2
5 AMPERE
NO PARITY WITH TWO STOP BIT EVEN PARITY WITH ONE STOP BIT are displayed on screen.
EVEN PARITY WITH ONE STOP BIT
VL2 Touching radio buttion in front of particular option will select that option.
OK
MAIN BACK
Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and
will return to previous menu.
3.2.3 Reset Parameter Selection
3.2.3.1 Resetting Parameter
These screens allow the users to reset all the parameters
RESET PARAMETERS
LINE-NEUTRAL VOLTAGE eg:- Energy, Min, Max, Demand, Run hour, On hour, No. of Interrupts.
RESET ALL
VL2 0.000
RESET DEMAND PARAMETERS V Touching “ down” key scrolls list in upward direction.
VL2 0.000
RESET ALL ENERGIES V
VL2 0.000
RESET MAX VOLTAGE & CURRENT V
MAIN VOLTAGE
SETUP

This screen is displayed after repeatedly touching “ down” key.


RESET PARAMETERS
LINE-NEUTRAL VOLTAGE
Touching “ Up” key scrolls list in downward direction.
RESET MAX VOLTAGE & CURRENT
VL2 0.000 V For resetting specific parameter user can touch on that parameter.
RESET MIN VOLTAGE & CURRENT
VL2 0.000
RESET RUN-HOUR, ON-HOUR
V
VL2 0.000
RESET AUX INTERRUPT COUNT V
MAIN VOLTAGE
SETUP

22
Touching on any parameter will display the confirmation dialog, now
RESET PARAMETERS
LINE-NEUTRAL VOLTAGE
a touch on “ YES key” will confirm the resetting of that particular
RESET ALL
VL2 0.000
RESET
RESET ALL ENERGIES
DEMAND
ARE YOU PARAMETERS
SURE YOU
V
WANT TO RESET ALL
Parameter.
VL2 0.000
YES NO
V
THE STORED ENERGIES
Touching on “ NO key” will move back to Reset parameters menu
VL2 0.000
RESET MAX VOLTAGE & CURRENT
V For example resetting All Energies will display a confirmation
MAIN VOLTAGE
SETUP
dialog as shown in the screen beside.
User can reset other parameters in similar manner.
3.2.4. Output Option selection menu
After entering in the “OUTPUT OPTIONS”, List of following parameters will be displayed :-
3.2.4.1 RELAY-1
3.2.4.2 RELAY-2
3.2.4.3 ANALOG-1
3.2.4.4 ANALOG-2

3.2.4.1 Relay1 output Selection menu


This screen applies to the Relay1 Output option Selection .
CTRELAY-1
LINE-NEUTRAL VOLTAGE
SECONDARY Two options : PULSE OUTPUT & LIMIT OUTPUT displayed on
1 AMPERE
VL2
PULSE0.000
OUTPUT screen. Touching any option will open screens of parameters
VL2
LIMIT0.000
OUTPUT V
5 AMPERE related to that option.
0.000 V Touch on “ OUTPUT OPTIONS key” will take back to Output
OK
OUTPUT OPTIONS
Options screen.

3.2.4.1.1 Pulse output


After entering in the “PULSE OUTPUT”, List of following parameters will be displayed :-
3.2.4.1.1.1 ENERGY
3.2.4.1.1.2 PULSE DURATION
3.2.4.1.1.3 PULSE RATE
These settings are used to assign Relay1 in Pulse output mode.
23
3.2.4.1.1.1 Assignment of Energy to pulse output (Relay 1) :
This screen allows the user to assign energy to pulse output (for Relay 1)
Following six options are displayed:-
RELAY-1 ENERGYVOLTAGE
LINE-NEUTRAL ASSIGNMENT
Apparent Energy Import Energy ( Active )
1APPARENT
AMPERE ENERGY Export Energy ( Active ) Import Energy (Reactive)
VL2
IMPORT ENERGY(ACTIVE)
5 AMPERE
EXPORT ENERGY(ACTIVE)
VL2
Export Energy (Reactive) Ampere Hour
IMPORT ENERGY(REACTIVE)
EXPORT ENERGY(REACTIVE)
VL2
AMPERE HOUR
Touching radio button in front of any particular option will select that option.
OK
MAIN BACK Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and
will return to previous menu.
3.2.4.1.1.2 Pulse Duration Selection:
This screen applies only to the Pulsed output mode of both the relays.
This screen allows the user to set Relay energisation time in milliseconds.
RELAY-1 PULSE
LINE-NEUTRAL DURATION
VOLTAGE
CT SECONDARY Three options: 60, 100, 200 ms are displayed on screen. Touching
60 MILLI-SECONDS
1 AMPERE
VL2 radio button in front of particular option will select that option.
100 MILLI-SECONDS
VL2
5 AMPERE
200 MILLI-SECONDS Touch on “ OK key” will confirm the setting.
OK
MAIN BACK
Touching the “ BACK key” will keep the old selected setting
and will return to previous menu.
3.2.4.1.1.3 Pulse Rate
This screen applies only to the Pulsed output mode of both the relays.
The screen allows user to set the energy pulse rate divisor.
RELAY-1
CTPULSE
LINE-NEUTRAL RATE DIVISOR
VOLTAGE
SECONDARY Divisor values can be selected through 1,10, 100,1000.Touching
1
1 AMPERE
VL2 0.000 100
V radio button in front of particular value will select that value.
VL2 0.000 V
10
5 AMPERE 1000 Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting
OK
MAIN BACK
and will return to previous menu.
Pulse rate divisor is set to 1, when Energy on Rs485 is set to kWh
or MWh.
24
3.2.4.1.2 Limit output
This screen is for Limit output mode selection. It allows the user to set Limit output
corresponding measured value. After entering in Limit Output first time(was disabled previously),
only “PARAMETER:” is displayed on screen. Now a simple touch on “PARAMETER:” will open
list of parameters, Refer Table 2 “Parameter for Analog & Limit output” for assignment.
Now after assignment of any parameter, list of following setting parameters will be displayed:-
3.2.4.1.2.1 PARAMETER
3.2.4.1.2.2 CONFIG
3.2.4.1.2.3 TRIP POINT
3.2.4.1.2.4 HYSTERESIS POINT
3.2.4.1.2.5 ENERGIZING DELAY
3.2.4.1.2.6 DE-ENERGIZING DELAY
3.2.4.1.2.1 Limit Parameter selection
This option allows the user to set Relay\-1 limit to corresponding measured parameter. A simple
touch on “PARAMETER” row will open screen having list of parameters. (Refer Table 2
“Parameters for Analog & limit output”) Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will return to previous menu.
3.2.4.1.1.2.2 Limit1 Configuration select
This screen is used to set the Limit1 Configuration, four different types of configuration can be selected
HIGH ALARM & ENERGIZED RELAY
LINE-NEUTRAL
RELAY-1 VOLTAGE
CT SECONDARY
CONFIGURATION
HIGH ALARM & DE-ENERGIZED RELAY
1 AMPERE
LOW ALARM & ENERGIZED RELAY
VL2
HIGH ALARM & ENERGIZED RELAY

HIGH ALARM & DE-ENERGIZED RELAY LOW ALARM & DE-ENERGIZED RELAY
VL2
5 AMPERE
LOW ALARM & ENERGIZED RELAY

VL2
LOW ALARM & DE-ENERGIZED RELAY
(For detail refer to section 9.2)
OK
MAIN BACK
Touching radio button in front of particular type will select that type.
Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will return to previous menu.

25
3.2.4.1.2.3 Trip point selection
This screen applies to the Trip point selection.
This screen allows the user to set Trip point for instrument in %.
RELAY-1 TRIP
LINE-NEUTRAL POINT
VOLTAGE This screen can be accessed only from Limit Output settings list menu.
ENTER TRIP POINT IN %
Here a 0 to 9 digit input keypad is provided to set value of Trip Point,
1 2 3 DEL
4 5 6
ENTER
& user can confirm this value with a simple touch on “ key.”
ENTER
7 8 9
0 BACK
“ BACK key” is used to go back to Limit Output list menu.

The allowable range is from 10% to 120% for High Alarm & is from
RELAY-1 TRIP
LINE-NEUTRAL POINT
VOLTAGE 10% to 100% for Low Alarm.
INVALID VALUE
1 2 3 DEL
If value outside this range is entered, it will display “INVALID VALUE”
4 5 6
ENTER
followed by correct range of parameter.
7 8 9
0 BACK

3.2.4.1.2.4 Hysteresis selection


This screen applies to the Hysteresis selection.
This screen allows the user to set Hysteresis in % for relay1.
RELAY-1 HYSTERESIS
LINE-NEUTRAL VOLTAGE
This screen can be accessed only from Limit Output settings list menu.
SET HYSTERESIS IN % Here a 0 to 9 digit input keypad is provided to set value of Hysteresis,
1 2 3
4 5 6
DEL
& user can confirm this value with a simple touch on “ key”.
ENTER ENTER
7 8 9
. 0 K BACK
“ BACK key” is used to go back to Limit Output list menu.

26
The allowable range is 0.5% to 50 % of Trip point .
RELAY-1 HYSTERESIS
LINE-NEUTRAL VOLTAGE
If value outside this range is entered, it will display “INVALID VALUE”
INVALID VALUE
1 2 3 DEL
followed by correct range of parameter.
4 5 6
ENTER
7 8 9
. 0 K BACK

3.2.4.1.2.5 Energizing Delay time.


This screen allows the user to set Energizing Delay time for Relay 1 Limit Assigned Parameters .
This screen can be accessed only from Limit Output settings list menu.
RELAY-1 ENERGIZING
LINE-NEUTRAL VOLTAGEDELAY Here a 0 to 9 digit input keypad is provided to set value of Delay, &
ENTER ENERGIZING DELAY IN SEC
user can confirm this value with a simple touch on “ key.”
1 2 3 DEL ENTER
4 5 6
ENTER
7 8 9
0 BACK
“ BACK key” is used to go back to Limit Output list menu.

The allowable range is from 1 to 10 sec.


RELAY-1 ENERGIZING
LINE-NEUTRAL VOLTAGEDELAY If value outside this range is entered, it will display “INVALID VALUE”
VALID RANGE IS : 1 - 10 Secs
followed by correct range of parameter.
1 2 3 DEL
4 5 6
ENTER
7 8 9
0 BACK

27
3.2.4.1.2.6 De-Energizing Delay time
This screen allows the user to set De-Energizing Delay time for Relay 1 Limit Assigned Parameters .
This screen can be accessed only from Limit Output settings
RELAY-1 DE-ENERGIZING
LINE-NEUTRAL VOLTAGE DELAY list menu.
ENTER DE-ENERGIZING DELAY IN SEC Here a 0 to 9 digit input keypad is provided to set value of Delay, &
1 2 3 DEL
4 5 6 user can confirm this value with a simple touch on “ key.”
ENTER ENTER
7 8 9
0 BACK
“ BACK key” is used to go back to Limit Output list menu.

The allowable range is from 1 to 10 sec.


RELAY-1 DE-ENERGIZING
LINE-NEUTRAL VOLTAGE DELAY If value outside this range is entered, It will display “INVALID VALUE”
VALID RANGE IS : 1 - 10 Secs followed by correct range of parameter.
1 2 3 DEL
4 5 6
ENTER
7 8 9
0 BACK

3.2.4.2 Relay 2 Output Selection


Configuration of Relay 2 for Pulse or Limit Output is same as Relay 1. If you Select the
Pulse output option for Relay 1 same setting will be applicable for Relay 2 except
assignment of energy to Pulse output (i.e. Energy assignment of both relay can be different.)

3.2.4.3 Parameter setting for Analog Output 1 ( Optional )


This option allows the user to set analog output 1 to corresponding measured parameter. A
simple touch on “ANALOG-1”row will open screen having list of parameters.( Refer table2
“ Parameter for Analog & Limit output ”)
Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will return to previous menu.

28
3.2.4.4 Parameter setting for Analog Output 2 ( Optional )
This option allows the user to set analog output 2 to corresponding measured parameter. A
simple touch on “ANALOG-2”row will open screen having list of parameters.( Refer table2
“ Parameter for Analog & Limit output ”)
Touch on “ OK key” will confirm the setting.
Touching the “ BACK key” will keep the old selected setting and will return to previous menu.

3.2.5 Brightness & Contrast


The brightness & contrast of the TFT LCD screen can be varied by
LINE-NEUTRAL
BRIGHTNESS &VOLTAGE
CONTRAST the user by sliding the sliders. Touching the “ OK key” will
VL2 0.000 V confirm the current brightness contrast setting.
VL2BRIGHTNESS V Touching the DEFAULT key will set brightness and contrast as per
0.000 V
VL2 CONTRAST
DEFAULT
MAIN OKVOLTAGE
DEFAULT BACK
factory settings. Touching the BACK key will move back to the
setup menu without making any changes.

4 Touch screen calibration


This instrument is able to perform calibration to ensure the proper operation of the units
touch screen functionalities. The calibration procedure will correct the problem of out of
tolerance touch screen malfunction. Note that errors corrected by this calibration
procedure are specific only to touch screen operation.

For starting touch screen calibration, touch the screen any where
LINE-NEUTRAL
CT VOLTAGE
SECONDARY
IMPORTANT.
for 1 sec at system reset. After that touch screen calibration will
Performing touch
1 AMPERE
VL2 0.000 V
screen calibration. start & the message shown besides will be displayed. Touch the
Press & hold the center
VL2 0.000 V
of the filled circle
5 AMPERE
screen to continue.
0.000
VL2Touch screen to V
continue.
MAIN OKVOLTAGE

29
LINE-NEUTRAL VOLTAGE
CT SECONDARY LINE-NEUTRAL VOLTAGE
CT SECONDARY LINE-NEUTRAL VOLTAGE
CT SECONDARY

VL2 Press
1 AMPERE
0.000 V Hold V
1 AMPERE
VL2 0.000 Hold
VL2 Release
1 AMPERE
0.000 V Hold

VL2on 0.000
the filledV
5 AMPERE
VL2 the filled V
0.000
5 AMPERE the filled
circle VL2the filled V
0.000
5 AMPERE the filled
circle

VL2 circle
0.000 V circle V
VL2 0.000 circle V
VL2 0.000
MAIN OKVOLTAGE MAIN OKVOLTAGE MAIN OKVOLTAGE

Follow the instructions displayed. Press & hold the center of the filled red circle for at least
2 seconds. Release when message for release is being displayed. For accurate results try
to touch the center of the filled circle.

Repeat the same After successful


LINE-NEUTRAL VOLTAGE
CT SECONDARY procedure for the LINE-NEUTRAL
HoldCT VOLTAGE
SECONDARY
screen for 1 sec
calibration, the
VL2 Press
1 AMPERE
0.000 V remaining 3 1after
VL2AMPEREsystem reset to message shown
REPEAT0.000 V
the calibration
on the
VL2 filledV
0.000
5 AMPERE corner circles. VL2 0.000 V
procedure.
5 AMPERE
besides would be
VL2 circle
0.000 V 0.000
VL2Touch screen toV displayed. Touch the
MAIN OKVOLTAGE
continue.
MAIN OKVOLTAGE
screen to continue.

LINE-NEUTRAL VOLTAGE
CT SECONDARY
If the touch screen was not calibrated properly, “Error in
1 AMPERE
calibration”message would be shown & the user will be asked to
VL2 0.000
Error in V
calibration
Touch
VL2 screen toV
0.000
5 AMPERE recalibrate the touch screen. In such case the meter will retain the
re-calibrate.
VL2 0.000 V previously stored touch - screen calibration values unless a
MAIN OKVOLTAGE successful calibration is being performed.

30
5. Run Hour
This Screen shows the total no. of hours the load is connected
Even if the Auxiliary supply is interrupted count of Run hour will be
SYSTEM RUN
LINE-NEUTRAL HOUR
VOLTAGE
maintained in internal memory & displayed in the format “hours. min”.
VL2 0.000 V For example if Displayed count is 000001.19 hrs it indicates
000001.19
VL2 0.000 V
hrs 1 hors & 19 minutes.
VL2 0.000 V
MAIN VOLTAGE
SYSTEM After 999999.59 run hours display will restart from zero.
To reset run hour manually see section Resetting Parameter 3.2.3.1

6. On Hour
This Screen shows the total no. of hours the Axillary Supply is ON.
SYSTEM ON VOLTAGE
LINE-NEUTRAL HOUR Even if the Auxiliary supply is interrupted count of On hour will be
VL2 0.000 V maintained in internal memory & displayed in the format “hours. min”.
000005.18
VL2 0.000 V For example if Displayed count is 000005.18 hrs it indicates
hrs
VL2 0.000 V 15 hours & 18 minutes.
MAIN VOLTAGE
SYSTEM
After 999999.59 On hours display will restart from zero.
To reset On hour manually see section Resetting Parameter 3.2.3.1

7. Number of Interruption
This Screen Displays the total no. of times the Auxilliary Supply was
SYSTEM INTERRUPTIONS
LINE-NEUTRAL VOLTAGE Interrupted. Even if the Auxiliary supply is interrupted count will be
VL2 0.000 V maintained in internal memory
VL200000012
0.000 V To reset No of Interruption manually see section Resetting
VL2 0.000 V Parameter 3.2.3.1
MAIN VOLTAGE
SYSTEM

31
8. Analog Output ( optional ) :
This module provides two d.c. isolated outputs .There are two output options

1) Two 0 - 1mA outputs , internally powered .


2) Two 4 - 20mA outputs , internally powered .

The 0 -1mA output module has an 0V return on each end of the 4 way connector
( Please refer section 15 for connection details )

On both modules the output signals are present on pins A1(Analog Output 1) &
A2 (Analog Output 2)
These outputs can be individually assigned to represent any one of the measured and
displayed Parameters.

All settlings are user configurable via the user interface screen. See Analog o/p selection
( section 3.2.4.3 & section 3.2.4.4 ) for details .

* Note : Refer diagrams 1 & 2 00 (12 mA)

Diagram 1 : ( 4 -20 mA )

0
270 (8 mA)
900 (16 mA)

0
181 (4 mA)

0
180 (20 mA)
32
Diagram 2 : ( 0 - 1 mA ) 0
0 (0.5 mA)

0 0
270 (0.25 mA) 90 (0.75 mA)

0
181 (0 mA)

0
180 (1 mA)
TABLE 2 : Parameter for Analog & Limit output
Range
Parameter Parameter
No. Analog Output Limit Output
0 None – –
1 INPUT VOLTAGE 0 - 100 % 10 - 120 %
4 INPUT CURRENT 0 - 100 % 10 - 120 %
7 ACTIVE POWER 0 - 120 % 10 - 120 %
10 APPARENT POWER 0 - 120 % 10 - 120 %
13 REACTIVE POWER 0 - 120 % 10 - 120 %
180 / 0 / -180 1800 / 0 / -180
0 0 0
16 POWER FACTOR
0 0
19 PHASE ANGLE 180 / 0 / -180 1800 / 0 / -1800
(1)
36 FREQUENCY 45 to 66 Hz 10 - 100 %
43 WATT DEMAND IMPORT 0 - 120 % 10 - 120 %
44 WATT MAX DEMAND IMP. 0 - 120 % 10 - 120 %

33
Range
Parameter Parameter
No. Analog Output Limit Output
45 WATT DEMAND EXPORT 0 - 120 % 10 - 120 %
46 WATT MAX DEMAND EXP. 0 - 120 % 10 - 120 %
51 VA DEMAND 0 - 120 % 10 - 120 %
52 VA MAX DEMAND 0 - 120 % 10 - 120 %
53 CURRENT DEMAND 0 - 100 % 10 - 120 %
54 CURRENT MAX DEMAND 0 - 100 % 10 - 120 %
Note : For Frequency 0% corresponds to 40 Hz & 100% corresponds to 70 Hz.

9. Relay output (Optional) :


This instrument is provided with either 1 or 2 relay for pulse output as well as for limit switch
9.1 Pulse Output :
Pulse output is the potential free, very fast acting relay contact which can be used to drive
an external mechanical counter for energy measurement.
This instrument’s pulse output can be configured to any of the following parameter
through setup parameter screen

1) Active Energy (Import)


2) Active Energy (Export)
3)Reactive Energy (Import)
4)Reactive Energy (Export)
5)Apparent Energy
6)Ampere hour

34
TABLE 3 : Energy Pulse Rate Divisor
1.For Energy Output in Wh 2. For Energy Output in Kwh
Pulse rate
Pulse rate
Divisor Pulse System Power*
Divisor Pulse System Power*
1 1per Wh Up to 3600W
1per kWh Up to 3600kW 1 1 per kWh Up to 3600W
1per Mwh Above 3600kW 1 per 1000kWh Up to 3600kW
10 1per 10Wh Up to 3600W 1 per 1000MWh Above 3600kW
1per 10kWh Up to 3600kW
1per 10MWh Above 3600kW
100 1per 100Wh Up to 3600W 3. For Energy Output in Mwh
1per 100kWh Up to 3600kW
1per 100MWh Above 3600kW
Pulse rate
Divisor Pulse System Power*
1000 1 per 1000Wh Up to 3600W
1 per 1000kWh Up to 3600kW 1 1 per Mwh Up to 3600W
1per 1000MWh Above 3600kW 1 per 1000Mwh Up to 3600kW
Pulse Duration 60 ms,100 ms or 200 ms
1 per 1000Gwh Above 3600kW

Above options are also applicable for Apparent and Reactive Energy.
* System power = 3 x CT(Primary) x PT(Primary)L-N for 3 Phase 4 Wire
System power = Root3 x CT(Primary) x PT(Primary)L-L for 3 Phase 3 Wire
Ampere Hour:
Divisor 1(Default)
CT secondary = 1A Max pulse rate 3600 pulses per Ah **
CT secondary = 5A Max pulse rate 720 pulses per Ah **

Divisors 10
CT secondary = 1A Max pulse rate 3600 pulses per 10Ah **
CT secondary = 5A Max pulse rate 720 pulses per 10Ah **
35
Divisors 100
CT secondary = 1A Max pulse rate 3600 pulses per 100Ah **
CT secondary = 5A Max pulse rate 720 pulses per 100Ah **

Divisors 1000
CT secondary = 1A Max pulse rate 3600 pulses per 1000Ah **
CT secondary = 5A Max pulse rate 720 pulses per 1000Ah **

Pulse duration 60 ms, 100 ms or 200 ms


**No. of Pulses per Ampere hour = Maximum Pulses / CT Ratio Where, CT Ratio =
(CT primary/ CT Secondary)

9.2 Limit Switch :


Limit switch can be used to monitor the measured parameter ( Ref.Table:2 )in relation
with to a set limit.
The limit switch can be configured in one of the four mode given below:-
1) Hi alarm & Relay Energized Relay..
2) Hi alarm & De-Energized Relay.
3) Lo alarm & Energized Relay.
4) Lo alarm & De-Energized Relay.
Limit switch has user selectable Trip point, Hysteresis, Energizing Delay & De-Energizing delay.
Hi Alarm:
If Hi-Alarm Energized or Hi Alarm De-Energized option is selected then relay will get
energized or De-energized,if selected parameter is greater than or equal to trip point.
Lo Alarm:
If Lo-Alarm Energized or Lo Alarm De-Energized option is selected then relay will get
energized or De-energized,if selected parameter is less than or equal to trip point.

36
Trip point:
Trip point can be set in the range of 10% to 120 % of nominal value for Hi-Alarm &
10% to 100 % of nominal value for Lo-Alarm.
Hysteresis:
Hysteresis can be set in the range of 0.5% to 50 % of set trip point .
If Hi-alarm Energized or Hi-alarm De-energized is selected then relay will get
De-energized or Energized respectively, if set parameter value is less than Hysteresis
Similarly if Lo-alarm Energized or Lo-alarm De-Energized.
Energizing Delay:
The energizing delay can be set in the range from1 to 10 sec.

De-Energizing Delay:
The De-energizing delay can be set in the range from1 to 10 sec.

Note : In case of lo alarm if trip point is set at 100% then maximum 20%
Hysterisis can be set..

Hysterisis point

37
10. RS 485 ( ModBus ) Output :
This instrument supports MODBUS (RS485) RTU protocol( 2-wire ) .
Connection should be made using twisted pair shielded cable. All "A" and "B" connections
are daisy chained together. The screens should also be connected to the “Gnd” terminal.
To avoid the possibility of loop currents, an Earth connection should be made at one point
on the network.Loop (ring) topology does not require any termination load. Line topology
may or may not require terminating loads depending on the type and length of cable used.
The impedance of the termination load should match the impedance of the cable and be at
bothends of the line. The cable should be terminated at each end with a 120 ohm
(1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32
instruments can be connected in Rs485 network.The permissible address range for the
instrument is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.
The maximum latency time for the instrument is 200ms i.e. this is the amount of time that
can pass before the first response character is output.
After sending any query through software ( of the Master) , it must allow 200ms of time to
elapse before assuming that the instrument is not going to respond. If slave does not
respond within 200 ms, Master can ignore the previous query and can issue fresh query
to the slave.
38
The each byte in RTU mode has following format:
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of
the message

Format of Data Bytes 4 bytes (32 bits) per parameter.


Floating point format ( to IEEE 754)
Most significant byte first (Alternative least significant byte first)

Error Checking Bytes 2 byte Cyclical Redundancy Check (CRC)

Byte format 1 start bit,


8 data bits, least significant bit sent first
1 bit for even/odd parity
1 stop bit if parity is used; 1 or 2 bits if no parity

Communication Baud Rate is user selectable from the front panel between 2400, 4800,
9600, 19200 bps.
Function code :

03 Read Holding Registers Read content of read /write location ( 4X )

04 Read input Registers Read content of read only location ( 3X )

16 Presets Multiple Registers Set the content of read / write locations ( 4X )

Exception Cases : An exception code will be generated when the instrument receives
ModBus query with valid parity & error check but which contains some other error
( e.g. Attempt to set floating point variable to an invalid value ) The response generated
will be “Function code” Ored with HEX (80H ). The exception codes are listed below

39
01 Illegal function This function code is not supported by the instrument.

02 Illegal Data Attempt to access an invalid address or an attempt to read


Address or write part of a floating point value
03 Illegal Data Attempt to set a floating point variable to an invalid value
Value

Accessing 3 X register for reading measured values:


Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses
of 3X registers (Parameters measured by the instruments).
Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.

Example :
To read parameter ,
Volts 3 : Start address= 04 (Hex) Number of registers = 02

Note : Number of registers = Number of parameters x 2


Each Query for reading the data must be restricted to 20 parameters or less. Exceeding
the 20 parameter limit will cause a ModBus exception code to be returned.

Query :

01 (Hex) 04 (Hex) 00 (Hex) 04(Hex) 00 (Hex) 02(Hex) 30 (Hex) 0A (Hex)

Device Function Start Address Start Address Number of Number of CRC CRC
Address Code High Low Registers Hi Registers Lo Low High
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.

40
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)

Response: Volt3 (219.25V)

01 (Hex) 04 (Hex) 04 (Hex) 43 (Hex) 5B (Hex) 41 (Hex) 21 (Hex) 6F (Hex) 9B (Hex)

Device Function Byte Data Register1 Data Register1 Data Register2 Data Register2 CRC CRC
Address Code Count High Byte Low Byte High Byte Low Byte Low High

Byte Count : Total number of data bytes received.


Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)

Table 4 : 3 X register addresses (measured parameters)


Address Parameter Parameter Modbus Start Address Hex
(Register) No. High Byte Low Byte
30001 1 Voltage 00 0
30007 4 Current 00 6
30013 7 Active Power 00 C
30019 10 VA1 00 12
30025 13 VAR1 00 18
30031 16 PF1 00 1E
30037 19 Phase Angle 1 00 24

41
Address Parameter Parameter Modbus Start Address Hex
(Register) No. High Byte Low Byte
30071 36 Freq 00 46
30073 37 Wh Import 00 48
30075 38 Wh Export 00 4A
30077 39 VARh Import 00 4C
30079 40 VARh Export 00 4E
30081 41 VAh 00 50
30083 42 Ah 00 52
30085 43 W Demand (Import) 00 54
30087 44 W Max Demand (Import) 00 56
30089 45 W Demand (Export) 00 58
30091 46 W Max Demand (Export) 00 5A
30101 51 VA Demand 00 64
30103 52 VA Max Demand 00 66
30105 53 A Demand 00 68
30107 54 A Max Demand 00 6A
30133 67 Volts Ave Max 00 84
30135 68 Volts Ave Min 00 86
30141 71 Current Ave Max 00 8C
30143 72 Current Ave Min 00 8E
30219 110 Voltage THD( % ) 00 DA
30221 111 Current THD( % ) 00 DC
30225 113 I neutral 00 E0
30227 114 Run Hour 00 E2
30229 115 On Hour 00 E4
30231 116 No. Of Interrupts 00 E6

42
Accessing 4 X register for Reading & Writing :
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting
and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register addresses.

Example : Reading CT Secondary


System type : Start address= 2A (Hex) Number of registers = 02

Note :Number of registers = Number of Parameters x 2

Query :

Device Address 01 (Hex)


Function Code 03 (Hex)
Start Address High 00 (Hex)
Start Address Low 2A (Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02 (Hex)

CRC Low E5 (Hex)


CRC High C3 (Hex)

Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)

43
Response:
Device Address 01 (Hex)
Function Code 03 (Hex)

Byte Count 04 (Hex)


Data Register1 High Byte 3F (Hex)
Data Register1Low Byte 80 (Hex)
Data Register2 High Byte 00 (Hex)

Data Register2 Low Byte 00(Hex)


CRC Low F7 (Hex)
CRC High CF (Hex)

Byte Count : Total number of data bytes received.


Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Example : Writing CT Secondary to 1 A

System type : Start address= 2A (Hex) Number of registers = 02

Query:
Device Address 01 (Hex)
Function Code 10 (Hex)

44
Starting Address Hi 00 (Hex)
Starting Address Lo 2A(Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02(Hex)
Byte Count 04 (Hex)
Data Register-1High Byte 3F (Hex)
Data Register-1 Low Byte 80(Hex)
Data Register-2 High Byte 00(Hex)
Data Register-2 Low Byte 00(Hex)
CRC Low 7C(Hex)

CRC High 34(Hex)

Byte Count : Total number of data bytes received.


Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Response:
Device Address 01 (Hex)
Function Code 10 (Hex)
Start Address High 00 (Hex)

Start Address Low 2A(Hex)

45
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02(Hex)
CRC Low 60 (Hex)
CRC High 00 (Hex)
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Table 5 : 4 X register addresses
Address Parameter Parameter Read / Write Modbus Start Address Hex
(Register) No. High Byte Low Byte
40001 1 Demand Reset R/Wp 00 00
40003 2 Demand Period R
R/Wp 00 02
40005 3 Energy on RS485 R/Wp 00 04
40007 4 Sys Voltage R 00 06
40009 5 Sys Current R 00 08
40013 7 Pulse Width R/Wp 00 0C
40015 8 Energy Reset Wp
W 00 0E
40017 9 Run/On Hour & Interruption Reset Wp 00 10
40019 10 RS 485 Set-up Code R/Wp 00 12
40021 11 .Node Address. R/Wp 00 14
40023 12 Pulse Divisor R/Wp 00 16
40025 13 Min Reset Wp 00 18
40027 14 Max Reset Wp 00 1A

46
Address Parameter Parameter Read / Write Modbus Start Address Hex
(Register) No. High Byte Low Byte
40029 15 Analog Out 1- Para Sel R/Wp 00 1C
40031 16 Analog Out 2- Para Sel R/Wp 00 1E
40033 17 PT Primary R/Wp 00 20
40035 18 CT Primary R/Wp 00 22
40037 19 System Power R 00 24
40039 20 Energy- digit reset count R/Wp 00 26
40041 21 Register Order/Word Order R/Wp 00 28
40043 22 CT Secondary R/Wp 00 2A
40045 23 PT Secondary R/Wp 00 2C
40047 24 Relay1 output select R/Wp 00 2E
40049 25 Pulse1/Limit1 Parameter select R/Wp 00 30
40051 26 Limit1 Trip point R/Wp 00 32
40053 27 Hysteresis(Limit1) R/Wp 00 34
40055 28 Limit1 delay(On) R/Wp 00 36
40057 29 Limit1 delay(Off) R/Wp 00 38
40059 30 Relay2 output select R/Wp 00 3A
40061 31 Pulse2/Limit2 Parameter select R/Wp 00 3C
40063 32 Limit2 Trip point R/Wp 00 3E
40065 33 Hysteresis(Limit2) R/Wp 00 40
40067 34 Limit2 Delay(On) R/Wp 00 42
40069 35 Limit2 Delay(Off) R/Wp 00 44
40071 36 Password R/W 00 46
40073 37 Limit1 Configuration select R/Wp 00 48
40075 38 Limit2 Configuration select R/Wp 00 4A
40077 39 - - - -
40079 40 30mA Noise Current Elimination R/Wp 00 4E
47
Explanation for 4 X register :

Address Parameter Description


40001 Demand Reset Demand Reset is used to reset the Demand parameter. A value
of zero must be Written to this register to reset the Demand
period. Writing any other value will return an error.

40003 Demand Period Demand period represents demand time in minutes. The
applicable values are 8,15,20 or 30. Writing any other value will
return an error.
This address is used to set energy display on MODBUS in Wh,
40005 Energy display KWh & Mwh. Write one of the following value to this address.
on Modbus 1 = Energy in Wh. 2 = Energy in KWh.
3 = Energy in MWh.
40007 System Voltage This address is read only and displays System Voltage
40009 System Current This address is read only and displays System Current
40013 Pulse Width This address is used to set pulse width of the Pulse output.
of Relay Write one of the following values to this address:
60 : 60 ms
100 : 100 ms
200 : 200 ms
Writing any other value will return error .
40015 Reset Energy This address is used to reset the Energy Counter.
Counter Write zero value to this register to reset the energy counter.
Writing any other value will return an error.

40017 Run/On Hour & This address is used to reset the Run/On hour & number
Interruption of Interruption . Write zero value to this register to reset
reset the Run/On hour & number of Interruption.
Writing any other value will return an error.

48
Address Parameter Description
40019 Rs485 Set-up This address is used to set the baud rate, Parity, Number of
Code stop bits. Refer to Table 6 for details.
40021 Node This register address is used to set Device address
Address between 1 to 247 .
40023 Pulse Divisor This address is used to set pulse divisor of the Pulse output.
Write one of the following values to this address:
1: Divisor 1
10 : Divisor 10
100 : Divisor 100
1000 : Divisor 1000
Writing any other value will return an error.
Pulse rate divisor is set to 1, when Energy on Rs485 is set
to kWh or MWh.
40025 Min - Reset This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters.
Writing any other value will return an error.

40027 Max - Reset This address is used to reset the Max parameters value.
Write Zero value to this register to reset the Max parameters.
Writing any other value will return an error.
40029 Analog Out 1- This address is used to set the parameter for Analog Output 1.
Para Set Write one of the parameter no. As per the options given in
Table 2 for Analog & Limit Output Parameters.
Writing any other value will return an error.

49
Address Parameter Description

40031 Analog Out 2- This address is used to set the parameter for Analog Output 2..
Para Set Write one of the parameter no. As per the options given in
Table 2 for Analog & Limit Output Parameters.
Writing any other value will return an error.
40033 PT Primary This address allows the user to set PT Primary value.
The maximum settable value is 692.8kV L-L
depends on the per phase 666.6MVA Restriction of power
combined with CT primary
40035 CT Pimary This address allows the user to set CT Primary value.
The maximum settable value is 9999 & also depends on the per
phase 666.6MVA Restriction of power combined with PT primary
40037 Sys Power System Power (Read Only) is the Nominal system power based on
the values of Nominal system volts and Nominal system current.
40039 Energy digit This address is used to set the rollover count for energy. If
Reset Count Energy on Rs485 is in Wh rollover count can be from 7 to 14.
If it is in KWh then rollover count can be from 7 to 12 & for MWh
rollover count can be from 7 to 9.
40041 Word Order Word Order controls the order in which the instrument receives
or sends floating - point numbers:- normal or reversed register
order.In normal mode, the two registers that make up a floating
point numbers are sent most significant bytes first.
In reversed register mode , the two registers that make up
a floating point numbers are sent least significant bytes first.
To set the mode, write the value ‘2141.0’ into this register-
the instrument will detect the order used to send this value and
set that order for all ModBus transaction involving floating point
numbers.
50
Address Parameter Description

40043 CT secondary This address is used to read and write the CT secondary value
write one of the following values to this address.
1=1A CT secondary
5=5A CT secondary
writing any other value will return an error.
40045 PT secondary This address is used to read and write the PT secondary value.
Ref Table for the range of PT secondary settable values in
Section 3.2.1.2
40047 Relay1 output This address is used to select the Relay 1 operation as pulse or
select Limit.
write one of the following values to this address.
0 = Pulse output on Relay 1
128 (Decimal) = Limit output on Relay 1
writing any other value will return an error.
40049 Pulse 1 /Limit 1 This address is used to assign the Parameter to Relay1
parameter If Limit option is selected refer table 2 for parameter number
select & if Pulse option is selected then refer table 7.
40051 Limit1 This address is used to set the trip point in %. Any value between
Trip Point 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm can be written to
this address. Writing any other value will return an error.
40053 Hysteresis This address is used to set the hysteresis between
(Limit 1) 0.5 to 50 . Writting any other value will return an error.

40055 Limit1 This address is used to set the Energizing delay between
Energizing 1 to 10 . Writting any other value will return an error.
Delay
40057 Limit1 de- This address is used to set the De-Energizing delay between
energizing Delay 1 to 10 . Writting any other value will return an error.

51
Address Parameter Description
40059 Relay 2 This address is used to select the Relay 2 operation as
output select pulse or Limit.
write one of the following values to this address.
0 = Pulse output on Relay 2
128 (decimal) = Limit output on Relay 2
writing any other value will return an error.
40061 Pulse 2/Limit 2 This address is used to assign the Parameter to Relay2
Parameter If Limit option is selected refer table 2 for parameter number
select & if Pulse option is selected then refer table 7.
40063 Limit 2 This address is used to set the trip point in %. Any value between
Trip point 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm can be written to
this address. Writing any other value will return an error.
40065 Hysteresis This address is used to set the hysteresis between
(Limit 2) 0.5 to 50 . Writting any other value will return an error.
40067 Limit 2 This address is used to set the Energizing delay between
Energizing 1 to 10 . Writting any other value will return an error.
delay
40069 Limit 2 This address is used to set the De-Energizing delay between
De-Energizing 1 to 10 . Writting any other value will return an error.
delay
40071 Password This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999 .
1) If password lock is present & if this location is read it will
return zero.
2) If Password lock is absent & if this location is read it will
return One.

52
Address Parameter Description
3) If password lock is present & to disable this lock
first send valid password to this location then write “0000”
to this location
4) If password lock is present & to modify 4X parameter
first send valid password to this location so that 4X parameter
will be accessible for modification.
5) If for in any of the above case invalid password is send then
meter will return exceptional error 2.

40073 Limit1 This address is used to set the Configuration for relay 1
Configuration see table 8 . Writting any other value will return an error.
Select
40075 Limit2 This address is used to set the Configuration for relay 2
Configuration see table 8 . Writting any other value will return an error.
Select
30mA Noise This address is used to activate or de-activatethe 30 mA noise
40079
current current elimination write
Elimination 0-Deactivate
30 (Decimal)-Activate
Writing any other value will return an error.

Table 6 : RS 485 Set-up Code


Baud Rate Parity Stop Bit Decimal value

19200 NONE 01 12
19200 NONE 02 13
19200 EVEN 01 14

53
Baud Rate Parity Stop Bit Decimal value

19200 ODD 01 15
9600 NONE 01 08
9600 NONE 02 09
9600 EVEN 01 10
9600 ODD 01 11
4800 NONE 01 04
4800 NONE 02 05
4800 EVEN 01 06
4800 ODD 01 07
2400 NONE 01 00
2400 NONE 02 01
2400 EVEN 01 02
2400 ODD 01 03
NOTE :
Codes not listed in the table above may give rise to unpredictable results including loss of
communication. Excise caution when attempting to change mode via direct Modbus writes.

Table 7 : Pulse1 & Pulse2 Configuration select


Code Configuration
0 Import Active Energy
1 Export Active Energy
2 Import Reactive Energy
3 Export Reactive Energy
4 Apparent Energy

54
Table 8 :Limit1 & Limit2 Configuration select

Code Configuration
0 Hi- alarm & Energized relay
1 Hi- alarm & De-energized relay
2 Lo- alarm & Energized relay
3 Lo- alarm & De-energized relay

10.1 User Assignable Modbus Registers:


This instrument contains the 20 user assignable registers in the address range of 0x200
(30513) to 0x226 (30551) (see Table 9).
Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the
instrument can be mapped to these 20 user assignable registers.
Parameters (3X registers addresses ) that resides in different locations may be accessed
by the single request by re-mapping them to adjacent address in the user assignable
registers area.
The actual address of the parameters ( 3X registers addresses) which are to be assessed
via address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 10).

Table 9 : User Assignable 3X Data Registers


Address Parameter Modbus Start Address (Hex)
(Register) Number. Assignable Register High Byte Low Byte
30513 257 Assignable Reg 1 02 00
30515 258 Assignable Reg 2 02 02
30517 259 Assignable Reg 3 02 04
30519 260 Assignable Reg 4 02 06
30521 261 Assignable Reg 5 02 08
30523 262 Assignable Reg 6 02 0A

55
Address Parameter Modbus Start Address (Hex)
(Register) Number. Assignable Register High Byte Low Byte
30525 263 Assignable Reg 7 02 0C
30527 264 Assignable Reg 8 02 0E
30529 265 Assignable Reg 9 02 10
30531 266 Assignable Reg 10 02 12
30533 267 Assignable Reg 11 02 14
30535 268 Assignable Reg 12 02 16
30537 269 Assignable Reg 13 02 18
30539 270 Assignable Reg 14 02 1A
30541 271 Assignable Reg 15 02 1C
30543 272 Assignable Reg 16 02 1E
30545 273 Assignable Reg 17 02 20
30547 274 Assignable Reg 18 02 22
30549 275 Assignable Reg 19 02 24
30551 276 Assignable Reg 20 02 26

Table 10 : User Assignable mapping register ( 4X registers)


Address Parameter Modbus Start Address (Hex)
(Register) Number. Mapping Register High Byte Low Byte
40513 257 Mapped Add for register #0x0200 02 00
40514 258 Mapped Add for register #0x0202 02 01
40515 259 Mapped Add for register #0x0204 02 02
40516 260 Mapped Add for register #0x0206 02 03
40517 261 Mapped Add for register #0x0208 02 04
40518 262 Mapped Add for register #0x020A 02 05
40519 263 Mapped Add for register #0x020C 02 06
40520 264 Mapped Add for register #0x020E 02 07

56
Address Parameter Modbus Start Address (Hex)
(Register) Number. Mapping Register High Byte Low Byte
40521 265 Mapped Add for register #0x0210 02 08
40522 266 Mapped Add for register #0x0212 02 09
40523 267 Mapped Add for register #0x0214 02 0A
40524 268 Mapped Add for register #0x0216 02 0B
40525 269 Mapped Add for register #0x0218 02 0C
40526 270 Mapped Add for register #0x021A 02 0D
40527 271 Mapped Add for register #0x021C 02 0E
40528 272 Mapped Add for register #0x021E 02 0F
40529 273 Mapped Add for register #0x0220 02 10
40530 274 Mapped Add for register #0x0222 02 11
40531 275 Mapped Add for register #0x0224 02 12
40532 276 Mapped Add for register #0x0226 02 13

Example :
Assigning parameter to user assignable registers
To access the voltage (3X address 0x0000) and Power Factor (3X address 0x001E)
through user assignable register assign these addresses to 4x register (Table 10 ) 0x0200
and 0x0201 respectively .
Assigning Query:
Device Address 01 (Hex)
Function Code 10 (Hex)
Starting Address Hi 02 (Hex)
Starting Address Lo 00 (Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02(Hex)

57
Byte Count 04 (Hex)
Data Register-1High Byte
Data Register-1 Low Byte
00 (Hex)
00 (Hex)
}Voltage
(3X Address 0x0000)
Data Register-2 High Byte
Data Register-2 Low Byte
00 (Hex)
1E (Hex)
}Power Factor
(3X Address 0x001E)
CRC lOW 6A (Hex)
CRC High C7 (Hex)

Response :
Device Address 01 (Hex)
Function Code 10 (Hex)
Start Address High 02 (Hex)
Start Address Low 00 (Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02 (Hex)
CRC Low 40 (Hex)
CRC High 70 (Hex)

Reading Parameter data through User Assignable Registers:

In assigning query Voltage and Power Factor parameters were assigned to 0x 200 and
0x201(Table10) which will point to user assignable 3xregisters 0x200 and 0x202 (table9).
So to read Voltage and PowerFactor data reading query should be as below.

58
Query:
Device Address 01 (Hex)
Function Code 04 (Hex)
Start Address High 02 (Hex)
Start Address Low 00 (Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 04 (Hex) **
CRC Low F0 (Hex)
CRC High 71 (Hex)
Start Address High : Most significant 8 bits of starting address of User assignable register.
Start Address low :Least significant 8 bits of starting address of User assignable register.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
**Note : Two consecutive 16 bit register represent one parameter.
Since two parameters are requested four registers are required
Response : (Voltage = 219.30 / Power Factor = 1.0)

Device Address 01 (Hex)


Function Code 04 (Hex)
Byte count 08 (Hex)
Data Register-1High Byte
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-2 Low Byte
43 (Hex)
5B (Hex)
4E (Hex)
04 (Hex)
} Voltage Data

59
Data Register-3 High Byte 3F (Hex)
Data Register-3 Low Byte
Data Register-4 High Byte
Data Register-4 Low Byte
CRC Low
80 (Hex)
00 (Hex)
00 (Hex)
79 (Hex)
} Power Factor 1Data

CRC High 3F (Hex)

User Assignable mapping Registers User Assignable Data Registers


(Starting ( 4X Registers Table10 ) (Starting ( 3X Registers Table 9 )
Address) Address)
0x200 Voltage (0x0000) 0x200 0x200 0x201
(16 bit) (16 bit)

0x201 Power Factor (0x001E) 0x202 0x202 0x203


(16 bit) (16 bit)

0x202 Wh Import (0x0048) 0x204 0x204


(16 bit)
0x205
(16 bit)

0x203 Frequency (0x0046) 0x206 0x206


(16 bit)
0x207
(16 bit)

0x212 Current (0x0006) 0x224 0x224


(16 bit)
0x225
(16 bit)

0x213 VAh (0x0050) 0x226 0x226 0x227


(16 bit) (16 bit)

60
To get the data through User assignable Register use following steps:
1) Assign starting addresses(Table3) of parameters of interest to a
“User assignable mapping registers” in a sequence in which they are to be accessed
(see section “Assigning parameter to user assignable registers”)

2) Once the parameters are mapped data can be acquired by using


“User assignable data register “ Starting address . i.e to access data of Voltage,
Power factor, Wh import, Frequency send query with starting address 0x200
with number of register 8 or individually parameters can be accessed
for example if current1 to be accessed use starting address 0x212.
(See section Reading Parameter data through User Assignable Registers)

11. Phaser Diagram :

Capacitive Inductive
90 degrees (0.000)
2
-
+

180 degrees (-1.000) 0 degrees (+1.000)

Capacitive
Inductive
4
+
-
270 degrees (0.000)

61
Sign of Sign of Sign of Inductive /
Connections Quadrant Active Reactive Power Capacitive
Power ( P ) Power ( Q ) Factor ( PF )
Import 1 +P +Q + L
Import 4 +P -Q + C
Export 2 -P +Q - C
Export 3 -P -Q - L

Inductive means Current lags Voltage


Capacitive means Current leads Voltage
When the instrument displays Active power ( P )with “ + ” ( positive sign ) ,
the connection is “ Import ” .

When the instrument displays Active power ( P )with “ - ” ( negative sign ) ,


the connection is “ Export ” .
SLIDE IN THIS DIRECTION
12. Installation PANEL AND LOCK
Mounting is by four side clamps, slide the side
clamps through side slot till side clamp gets firmly
locked in a groove (Refer fig.) Consideration should
be given to the space required behind the Meter
instrument to allow for bends in the connection cables.

62
As the front of the enclosure conforms to IP54 it is protected from water spray from all directions,
additional protection to the panel may be obtained by the use of an optional panel gasket.
The terminals at the rear of the product should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range
0
-10 to 55 C . Vibration should be kept to a minimum and the product should
not be mounted where it will be subjected to excessive direct sunlight.

Caution
1. In the interest of safety and functionality this product must be installed by
a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal
connections of this unit. Ensure that all supplies are de-energised before
attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must
be used to ensure safety under fault conditions.

12.1 EMC Installation Requirements


This product has been designed to meet the certification of the EU directives when installed to a
good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF suppression
components, such as ferrite absorbers, line filters etc., in the event that RF fields cause
problems.
Note: It is good practice to install sensitive electronic instruments that are performing critical
functions, in EMC enclosures that protect against electrical interference which could cause a
disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of
interference.
63
3. To protect the product against permanent damage, surge transients must be limited to
2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source.
The unit has been designed to automatically recover in the event of a high level of
transients. In extreme circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via
Current Transformers only, where one side is grounded.
4. ESD precautions must be taken at all times when handling this product.

12.2 Case Dimension and Panel Cut Out


3.78” 3.15” 3.62”
96mm 80mm 92mm

3.78” 3.62”
96mm FRONT DISPLAY PANEL CUTOUT 92mm
AREA

MAX PANEL THICKNESS 0.18”,5mm


12.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure.
Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
2
regulations. Terminal for both Current and Voltage inputs will accept upto 3mm x 2
diameter cables.
Note : It is recommended to use wire with lug for
connection with meter.
64
12.4 Auxiliary Supply
The instrument should ideally be powered from a dedicated supply, however it may be powered
from the signal source, provided the source remains within the limits of the chosen auxiliary voltage.

12.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuses.

12.6 Earth/Ground Connections


For safety reasons, CT secondary connections should be grounded in accordance with local
regulations.

13. Connection Diagrams


SINGLE PHASE
DIGITAL METERING SYSTEM
2 3

L N
AUX
SUPPLY
P1 S1 L
L O
A
N D

65
14. Specification :
Inputs
Nominal input voltage (AC RMS) Phase-Neutral 57.7 to 277 V L-N
Max continuous input voltage 120% of Rated Value
Max short duration input voltage 2 x Rated Value
(1s application repeated 10 times
at 10s intervals)
Nominal input voltage burden 0.2VA approx. per phase
Nominal input current 5A AC rms
Max continuous input current 1 2 0 % of Rated Value
Nominal input current burden 0 .6 VA approx. per phase

Max short duration current input 20 x Rated Value (1s application repeated
5 times at 5 min. intervals)
System CT primary values Std. Values from 1 to 9999A
(1 or 5 Amp secondaries)
Auxiliary
Standard nominal Auxillary 100 - 250V AC- DC (45-66Hz),
supply voltages & Frequency 12 - 48V DC
a.c. supply voltage tolerance +10 % / -10 % of Rated Value
d.c. supply voltage tolerance +10 % / -10 % of Rated Value
a.c. supply frequency range 4 5 to 66 Hz

66
a.c. supply burden 6.5 V A
d.c. supply burden 3W

Operating Measuring Ranges

Voltage 5 .. 120 % of Rated Value

Current 5 .. 120 % of Rated Value

Frequency 40 .. 70 Hz

Power Factor 0.5 Lag ... 1 ... 0.8 Lead

Accuracy
Accuracy 1:
Voltage ± 0.5 % of range
C urrent ± 0.5 % of range
Frequency 0.15% of mid frequency
Active Power ± 0.5 % of range
Re- Active Power ± 0.5 % of range
Apparent Power ± 0.5 % of range
Active Energy ± 1.0 % of range
Re - Active Energy ± 1.0 % of range
Apparant Energy ± 1.0 % of range
Power Factor ± 1 % of Unity

67
Angle ± 1 % of range
Analog Output ± 1 % of Output end value
Total Harmonic Distortion ±1%
Neutral Current ± 4 % of range.

Accuracy 0.5:
Voltage ± 0.5 % of range

C urrent ± 0.5 % of range


Frequency 0.15% of mid frequency

Active Power ± 0.5 % of range


Re- Active Power ± 0.5 % of range

Apparent Power ± 0.5 % of range


Active Energy ± 0.5 % of range
Re - Active Energy ± 0.5 % of range

Apparant Energy ± 0.5 % of range

Power Factor ± 1 % of Unity

Angle ± 1 % of range

Analog Output ± 1 % of Output end value

Total Harmonic Distortion ±1%


Neutral Current ± 4 % of range

68
Accuracy 0.2:
Voltage ± 0.2 % of range

C urrent ± 0.2 % of range


Frequency 0.15% of mid frequency

Active Power ± 0.2 % of range


Re- Active Power ± 0.2 % of range

Apparent Power ± 0.2 % of range


Active Energy ± 0.2 % of range
Re - Active Energy ± 0.2 % of range

Apparant Energy ± 0.2 % of range

Power Factor ± 1 % of Unity

Angle ± 1 % of range

Analog Output ± 1 % of Output end value

Total Harmonic Distortion ±1%

Neutral Current ± 4 % of range

Reference conditions for Accuracy :


Reference temperature 0
23 0C + 2 C

Input frequency 50 or 60Hz ± 2%


69
Input waveform Sinusoidal (distortion factor 0.005)

Auxiliary supply voltage Rated Value + 1 %

Auxiliary supply frequency Rated Value + 1 %


Voltage Range 50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
Current Range 10... 100% of Nominal Value.
20... 100% of Nominal Value for THD.
Power cosØ / sinØ = 1
For Active / Reactive Power & Energy
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.

Power Factor / Phase Angle 40... 100% of Nominal Current &


50... 100% of Nominal Voltage.

Nominal range of use of influence quantities for measurands

Voltage 50 .. 120 % of Rated Value

Current 10 .. 120 % of Rated Value

Input frequency Rated Value + 10 %

Temperature 0 to 50 0C

Auxiliary supply voltage Rated Value + 10 %

Auxiliary supply frequency Rated Value + 10 %

70
Temperature Coefficient 0.025% / 0C for Voltage (50..120% of Rated Value)
0
(For Rated value range of use 0.05% / C for Current ( 10..120% of Rated Value )
0
0... 50 C )
Error change due to variation of an 2 * Error allowed for the reference
influence quantity condition applied in the test.

Display
TFT LCD 3.5” Graphical LCD, resolution 320x240 pixels
Update Approx. 1 seconds

Controls
User Interface Resistive Touch screen

Standards
EMC Immunity IEC 61326
10V/m min-Level 3 industrial low level
electromagnetic radiation environment
IEC 61000-4-3.

Safety IEC 61010-1 , Year 2001


IP for water & dust IEC 60529

Isolation
Dielectric voltage withstand 2.2 kV RMS 50 Hz for 1 minute
test between circuits and between all electrical circuits
accessible surfaces

71
Environmental
0
Operating temperature -10 to 55 C
Storage temperature -20 to +65 0C
Relative humidity 0 .. 90 % RH
Warm up time 3 minute (minimum)
Shock 15g in 3 planes
Vibration 10 .. 55 Hz, 0.15mm amplitude
Enclosure ( front only ) IP 54 as per IEC 60529

Enclosure
Style 96mm x 96mm DIN Quadratic
Material Polycarbonate Housing ,
Self extinguish & non dripping as per UL 94 V-0
Terminals Screw-type terminals
Depth < 80 mm
Weight 0.620 kg Approx.

Pulse output Option ( 1 or 2 Relay ) :


Relay 1NO + 1NC
Switching Voltage & Current 240VDC , 5Amp.
Default Pulse rate Divisor 1 per Wh (up to 3600W),
1 per kWh (up to 3600kW),
1 per MWh (above 3600 kW)

72
Pulse rate Divisors Programmable on site
10 1 per 10Wh (up to 3600W),
1 per 10kWh (up to 3600kW),
1 per 10MWh (above 3600 kW)
100 1 per 100Wh (up to 3600W),
1 per 100kWh (up to 3600kW),
1 per 100MWh (above 3600 kW)
1000 1 per 1000Wh (up to 3600W),
1 per 1000kWh (up to 3600kW),
1 per 1000MWh (above 3600 kW)
Pulse Duration 60ms , 100ms or 200ms

Note : Above conditions are also applicable for Reactive & Apparent Energy .
Note : Pulse rate divisor is set to 1, when Energy on Rs485 is set to kWh or MWh.

ModBus ( RS 485 ) Option :


Protocol ModBus ( RS 485 )
Baud Rate 19200 , 9600 , 4800 or 2400
( Programmable )
Parity Odd or Even, with 1 stop bit,
Or None with 1 or 2 stop bits
Analog Output Option :
Linear 0 ... 1mA dc into 0 - 2 kohm
Uni-directional, internally powered .

4 ... 20mA dc into 0 - 500 ohm


Uni-directional, internally powered.
73
15. Connection for Optional Pulse Output / RS 485
/ Analog Output ( rear view of the instrument ) :
1. One Pulse Output (One Limit Output)

N/O N/C COM


Relay 1

2. Two Pulse Output ( Two Limit Output)

N/O N/C COM N/O N/C COM


Relay 1 Relay 2

3. RS 485 Output

B A Gnd
RS 485

4. Two Analog Output

Gnd A1 A2 Gnd
4 -20 mA

74
5. One Pulse (One Limit) + RS 485 Output

N/O N/C COM B A Gnd


Relay 2 RS 485

6. One Pulse (One Limit) + Two Analog Output

Gnd A1 A2 Gnd N/O N/C COM


0 - 1mA Relay 2

7. RS 485 + Two Analog Output

Gnd A1 A2 Gnd B A Gnd


4 -20 mA RS 485

8. RS 485 Output + One Pulse (One Limit) + Two Analog Output

Gnd A1 A2 Gnd N/O N/C COM B A Gnd


0 - 1mA Relay 2 RS 485

75
9. Two Pulse (Two Limit) + RS 485 Output

N/O N/C COM N/O N/C COM B A Gnd


Relay 1 Relay 2 RS 485

The Information contained in these installation instructions is for use only by installers
trained to make electrical power installations and is intended to describe the correct method
of installation for this product.
It is the user's responsibility to determine the suitability of the installation method in the
user’s field conditions.

76

You might also like