Operating Manual: DMAN-00IM-0719 - Rev. B - 06/2020

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Operating Manual

RISH EM 1320/30/40

DMAN-00IM-0719_Rev. B - 06/2020

1
2
DIGITAL MULTIFUNCTION INSTRUMENT
Programmable Multi-function Energy Meter
Installation & Operating Instructions
Section Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.1.1 System Type
3.2.1.2 Potential Transformer Primary value
3.2.1.3 Potential Transformer Secondary value
3.2.1.4 Current Transformer Primary value
3.2.1.5 Current Transformer Secondary value
3.2.1.6 Demand Integration Time
3.2.1.7 Auto Scrolling
3.2.1.8 Low Current Noise Cutoff
3.2.1.9 No. of Poles Selection
3.2.1.10 Energy Output
3.2.1.11 Energy Digit Reset count
3.2.1.12 Energy Rate
3.2.2 Communication Parameter selection screen
3.2.2.1 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection
3.2.3 Reset Parameter selection screen
3.2.3.1 Resetting Parameter
3.2.4 Output Option selection screen (menu)
3.2.4.1 Configuration of Output
3.2.4.1.1 Relay Output Selection menu
3.2.4.1.1.1 Pulse Output
3.2.4.1.1.1.1 Assignment of Energy to Pulse
3.2.4.1.1.1.2 Pulse Duration Selection

3
3.2.4.1.1.1.3 Pulse Rate
3.2.4.1.1.2 Limit output
3.2.4.1.1.2.1 Assignment of Limit Output to Parameter
3.2.4.1.1.2.2 Limit Configuration
3.2.4.1.1.2.3 Trip point selection
3.2.4.1.1.2.4 Hysteresis selection
3.2.4.1.1.2.5 Energizing delay time
3.2.4.1.1.2.6 De-energizing delay time
3.2.5 User Assignable Features
3.2.5.1 Feature Selection Menu
3.2.5.1.1 Backlit
3.2.5.1.2 User Assignable Screens
3.2.6 Quit screen
4. Current Reversal screen
5. Phase Rotation Error screen
6. Phase Absent screen
7. Run - Hour
8. On - Hour
9. Number of Interruption
10. Relay Output
10.1 Pulse output
10.2 Limit Switch
11. Phasor Diagram
12. Installation
12.1 EMC Installation Requirements
12.2 Case Dimensions and Panel Cut-out
12.3 Wiring
12.4 Auxiliary Supply
12.5 Fusing
12.6 Earth / Ground Connections
13. Connection Diagrams
14. Optional Pluggable Module
15. Specification
16. Connection for Optional Pulse output / RS 485

4
TABLE 1: Measured Parameters System Wise:
Measured Parameters Units 3P 4W 3P 3W 1P 2W
System Voltage Volts   
System Current Amps   
Voltage VL1-N / 2-N / 3-N Volts   
Voltage VL1-L2 / L2-L3 / L3-L1 Volts   
Current L1 / L2 / L3 Volts   
Neutral Current Amps
  
Frequency Hz   
Active Power (System / Phase) kW  only system only system
Reactive Power (System / Phase) kVAr  only system only system
Apparent Power (System / Phase) kVA  only system only system
Power Factor (System / Phase)  only system only system
Phase Angle (System / Phase) Degree  only system only system
Active Import Energy (9 Digit resolution)* kWh   
Active Export Energy (9 Digit resolution)* kWh   
Capacitive Reactive Energy (9 Digit resolution)* kVArh   
Inductive Reactive Energy (9 Digit resolution)* kVArh   
Apparent Energy (9 Digit resolution)* kVAh   
Current Demand Amps   
kVA Demand kVA   
kW Import Demand kW   
kW Export Demand kW   
Max Current Demand Amps   
Max kVA Demand kVA   
Max kW Import Demand kW   
Max kW Export Demand kW   
Run Hour Hours   
On Hour Hours   
Number of Interruptions Counts   
Phase Rotation Error   
Phase Absent Indication   
Current Reversal Indication   
Voltage THD (System / Phase) %   only system
Current THD (System / Phase) %   only system
Min / Max System Voltage Volts   
Min / Max System Current Amps   
*Note: Units of these parameters will depend on “Energy Output”. (Refer section 3.2.1.10)

5
1. INTRODUCTION
The Multifunction Energy Meter is a panel mounted 96 x 96mm DIN Quadratic Digital Panel Meter,
which measures important electrical parameters in 3 ph 4 wire / 3 wire / 1ph Network and replaces
the multiple analog panel meters. It measures electrical parameters like AC voltage, Current, Frequency,
Power, Energy(Active / Reactive / Apparent), phase angle, power factor & many more. The
instrument integrates accurate measurement technology (All Voltages & current measurements
are True RMS upto 15th Harmonic) with LCD display with backlit.

It can be configured & Programmed at site for the following :


PT Primary, PT Secondary, CT Primary, CT Secondary 3 Phase 3W,
3 Phase 4W, 1 Phase 2W system.

The front panel has two push buttons using which the user can scroll
through different screens, reset the energy & configure the product.
The front panel also has Impulse red led, flashing at rate proportional
to measured power.

DOWN UP

2. MEASUREMENT READING SCREENS


In normal operation, the user is presented with one of the measurement
reading screens out of several screens. These screens may be scrolled
through one at a time in incremental order by pressing the “UP key” and in
decremental order by pressing “DOWN key”.

6
TABLE 2 : Measurement Screens (Model wise)
EM 1320 EM 1330 EM 1340
Screen
Parameters On On On On On On
No.
Display Modbus Display Modbus Display Modbus
1 Sys Power / Voltage / Current × √ √ √ √ √
2 L-N Voltage × √ √ √ √ √
3 L-L Voltage × √ √ √ √ √
4 Current × √ √ √ √ √
5 RPM / Frequency × √ √ √ √ √
6 Sys W / VA / Phase Angle × √ √ √ √ √
7 Sys VAr / PF × √ only PF √ √ √
8 Active Energy Import √ √ √ √ √ √
9 Active Energy Export √ √ √ √ √ √
10 Capacitive Reactive Energy × √ × √ √ √
11 Inductive Reactive Energy × √ × √ √ √
12 Apparent Energy √ √ √ √ √ √
14 Min Sys Voltage & Current × √ × √ √ √
15 Max Sys Voltage & Current × √ × √ √ √
16 R Phase W/ VA / Phase Angle × √ √ √ √ √
17 Y Phase W/ VA / Phase Angle × √ √ √ √ √
18 B Phase W/ VA / Phase Angle × √ √ √ √ √
19 R Phase VAr / PF × √ only PF √ √ √
20 Y Phase VAr / PF × √ only PF √ √ √
21 B Phase VAr / PF × √ only PF √ √ √
22 W IMP / VA / Current Demand × √ × √ √ √
23 Max W IMP / VA / Current Demand × √ × √ √ √
24 W EXP / VA / Current Demand × √ × √ √ √
25 Max W EXP / VA / Current Demand × √ × √ √ √
26 Per Phase Voltage THD × × × × √ √
27 Per Phase Current THD × × × × √ √
28 Sys Voltage / Current THD × × × × √ √

7
TABLE 2 : Continued...
EM 1320 EM 1330 EM 1340
Screen
Parameters On On On On On On
No.
Display Modbus Display Modbus Display Modbus
29 Run Hour × √ √ √ √ √
30 On Hour × √ √ √ √ √
35 No of Interruptions × √ √ √ √ √
37 I neutral × √ × √ √ √
38 Old Active Import Energy × √ × √ √ √
39 Old Active Export Energy × √ × √ √ √
41 Old Reactive Capacitive Energy × √ × √ √ √
42 Old Reactive Inductive Energy × √ × √ √ √
43 Old Apparent Energy × √ × √ √ √
45 Old Run Hour × √ × √ √ √
46 Old On Hour × √ × √ √ √
51 Old No of Interruptions × √ × √ √ √
53 Current Reversal √ × √ × √ ×
54 Phase Rotation Error √ × √ × √ ×
55 Phase Absent √ × √ × √ ×

√ Available on Display
× Not available on Display

8
Rish EM 1320/30/40 Setup Parameter Screen
codE (PassWord) Exit from setup Parameter to Main Display
SEL (Select)
A

SYS PArA Out PArA


Ser PArA rSEt USEr PArA quit
(System Parameter) (Reset Parameter) (Output Parameter) (User Assignable
(Sec 3.2.1) (Serial Comm.Parameter) (Exit Menu)
(Sec 3.2.2) (Sec 3.2.3) (Sec 3.2.4) Parameter) (Sec 3.2.6)
(Sec 3.2.5)
B
SYS
(System Type / Network) Addr none (No Parameter),
(Sec 3.2.1.1) (Modbus Address) ALL (All Parameters), A
(Sec 3.2.2.1) rEL1 out quit bcLt (Backlit On/Off)
d (Demand),
E (Energy), (Relay 1 Output) (Exit Menu) (Sec 3.2.5.1.1)
UP hi (Max values), (Sec 3.2.4.1.1) (Sec 3.2.4)
(PT Primary) Lo (Min values),
(Sec 3.2.1.2) br Hr(Run Hour & On Hour),
(Baud Rate) Intr (No. of Interrupts) rEL2 out Scrn(User assignable
(Sec 3.2.2.2) Select any one option (Relay 2 Output) Screen feature)
B
US using “Down” key. (Sec 3.2.4.1.1) (Sec 3.2.5.1.2)
(PT Secondary)
(Sec 3.2.1.3)
Pr
(Parity Bits)
AP (Sec 3.2.2.3) quit
(CT Primary) (Exit Menu)
(Sec 3.2.1.4) PUL Lt (Sec 3.2.5)
(Pulse Output) (Limit Output)
(Sec 3.2.4.1.1.1) (Sec 3.2.4.1.1.2)
AS
(CT Secondary)
(Sec 3.2.1.5) Para. Selection Para. Selection
(Acc. To Table)
(U-AC, g-AC, U-rE, (Sec 3.2.4.1.1.2.1)
dit g-rE, U-AP, g-AP)
(Demand Integ. Time) (Sec 3.2.4.1.1.1.1)
(Sec 3.2.1.6)
Limit Config
.
Selection
Auto dur (Hi-E,Hi-d,
(Auto Scrolling) (Pulse Duration) Lo-E,Lo-d)
(Sec 3.2.1.7) 60,100,200 (Sec 3.2.4.1.1.2.2)
(Sec 3.2.4.1.1.1.2)
: UP KEY
nC
(Noise Current Cut-off) trip (Trip Point)
(Sec 3.2.1.8) 10% to 100%
rAt (Sec 3.2.4.1.1.2.3)
(Pulse Divisor Rate)
: DOWN KEY
1, 10, 100, 1000
PoLE (Sec 3.2.4.1.1.1.3)
(No. of poles selection) HYS (Hysterisis)
(Sec 3.2.1.9) 0.5% to 50%
(Sec 3.2.4.1.1.2.4)

B
En.OP
(Energy Output) En-d
(Sec 3.2.1.10) (Energizing Delay time)
1s to 10s
(Sec 3.2.4.1.1.2.5)
Edrc
(Energy digit reset count)
(Sec 3.2.1.11)
dE-d
(De-energizing Delay time)
B 1s to 10s
Enrt (Sec 3.2.4.1.1.2.6)
(Energy rate)
(Sec 3.2.1.12)

9
3. PROGRAMMING
The following sections comprise step by step procedures for configuring the Multifunction
Meter according to individual user requirements.
To access the set-up screens press and hold “ UP” and “ DOWN” keys simultaneously
for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 3.1).
3.1. Password Protection
Password protection can be enabled to Press the “ ” key to advance to next digit.
prevent unauthorised access to set-up
screens, by default password protection
is not enabled. Enter Password, second
digit entered, prompt for
Password protection is enabled by selecting third digit. (* Denotes
a four digit number other than 0000, setting that decimal point will
a password of 0000 disables the password be flashing).
protection.
Use the “ ” key to scroll the value of the
Enter Password, prompt third digit from 0 through to 9, the value
for first digit. (*Denotes will wrap from 9 round to 0.
that decimal Point will
be flashing). Press the “ ” key to advance to next digit.
Press the “ ” key to scroll the value of
first digit from 0 through to 9, the value Enter Password, third
will wrap from 9 round to 0. digit entered, prompt
for fourth digit.
Press the “ ” key to advance to next digit. (*Denotes that decimal
In special case where the Password is “0000” point will be flashing).
pressing the “ ” key when prompted for Use the “ ” key to scroll the value of the
the first digit will advance to “Password fourth digit from 0 through to 9, the value
confirmed” screen. will wrap from 9 round to 0.
Enter Password, first
digit entered, prompt for Press the “ ” key to advance to
second digit.(*Denotes verification of the password.
that decimal Point will
be flashing). Enter Password, fourth
digit entered, awaiting
Use the “ ” key to scroll the value of the verification of the
second Digit from 0 through to 9, the value password.
will wrap from 9 round to 0.

10
Password confirmed. Pressing the “ ” key to advance the operation to the
next digit and sets the second digit, in this case to “1”
Pressing “ ” key will
advance to the “New / change New / Change Password,
Password” entry stage. second digit entered,
prompting for third digit.
Pressing the “ ” key will advance to the Menu (*decimal point indicates
selection screen. (See section 3.2). that this will be flashing).
Password Incorrect. Pressing the “ ” key will scroll the value of the
third digit from 0 through to 9, the value will wrap
The unit has not accepted from 9 round to 0.
the Password entered. Pressing the “ ” key to advance the operation to the
next digit and sets the third digit, in this case to “5”
Pressing the “ ” key will return to the Enter
Password stage. New/ Change Password,
third digit entered, prompting
Pressing the “ ” key exits the Password menu for fourth digit. (* denotes that
& returns operation to the measurement reading decimal point will be flashing).
mode. Pressing the “ ” key will scroll the value of the
New / Change Password fourth digit from 0 through to 9, the value will wrap
from 9 round to 0.
(* Decimal point indicates Pressing the “ ” key to advance the operation to the
that this will be flashing). “New Password Confirmed” & sets the fourth digit in
this case to “3”.
Pressing the “ ” key will scroll the value of the first New Password confirmed.
digit from 0 through to 9, the value will wrap from
9 round to 0. Pressing the “ ” key will
return to the “New/Change
Pressing the “ ” key to advance the operation Password”.
to the next digit and sets the first digit, in this case to “2”
Pressing the “ ” key will advances to the Menu
New/ Change Password, first selection screen. (see section 3.2).
digit entered, prompting for
second digit. (*Decimal point 3.2 Menu selection.
indicates that this will be
flashing). 3.2.1 System Parameter selection
screen
Pressing the “ ” key will scroll the value of the This screen is used to select
second digit from 0 through to 9, the value will the different system Parameter
wrap from 9 round to 0. like “system type”,“CT

11
Ratio”,“PT Ratio”,Pressing the “ ” key allows the Pressing the “ ” key allows the user to select &
user to set Different system parameters. Configure the output option. (see section 3.2.4.1)
(see section 3.2.1.1 to 3.2.1.12) Pressing the “ ” key will advance to User
Pressing the “ ” key will advance to Communication Assignable Feature Selection screen.
selection screen (see section 3.2.2) (see section 3.2.5)
3.2.2 Communication 3.2.5 User Assignable Feature
Parameter selection screen Selection screen
This screen is used to select This screen will allow the
the different communication user to access different
parameters like “Address features like “Backlit”,“User
selection”,“RS485 Parity assignable screens”.
selection”, “RS485 baud rate”. Pressing the “ ” key will allow the user to select &
Pressing the “ ” key allows the user to set different configure the features.(see section 3.2.5.1)
Communication parameters.
(see section 3.2.2.1 to 3.2.2.3) Pressing the “ ” key will advance to Quit
screen. ( see section 3.2.6)
Pressing the “ ” key will advance to Reset 3.2.6 Quit screen
parameter Screen.(see section 3.2.3)
This screen will allow the
3.2.3 Reset Parameter user to Quit the Menu.
selection screen
Pressing the “ ” key will allow the user to Quit
This screen is used to Reset from menu & return to measurement screen.
the different parameters.
Pressing the “ ” key will advance to System
Pressing the “ ” key allows the user to Reset Parameter Selection screen ( see section 3.2.1)
different system parameters (see section 3.2.3.1)
3.2.1 System parameters Selection
Pressing the “ ” key will advance to Output 3.2.1.1 System Type
Option selection screen (see section 3.2.4).
This screen is used to set the
3.2.4 Output Option selection system type(only for 3 phase).
screen System type “3” for 3 phase
3 wire, “4” for 3 phase 4 wire
This screen will allow the system & “1” for single phase
user to select Output option system.
Like “Relay” Output. Pressing the “ ” key accepts the present value
and advances to the “Potential transformer primary
value Edit” menu. (see section 3.2.1.2)

12
Pressing the “ ” key will enter the system type edit Potential Transformer Primary Digit Edit
mode & scroll through the values available.
Pressing the “ ” key advances to the system Pressing the “ ” key
type confirmation menu. will scroll the value of the
most significant digit from 0
System Type Confirmation through to 9 unless the
This screen will only appear presently displayed Potential Transformer Primary
following the edit of system Value together with the Current Transformer Primary
type. Value, previously set, would result in a maximum
Pressing the “ ” key sets the displayed system power of greater than 3000 MVA (1000 MVA
value and will advance to “Potential Transformer per phase) in which case the digit range will be
Primary Value Edit” menu. (See section 3.2.1.2) restricted.

Pressing the “ ” key will return to the system type Pressing the “ ” key accepts the present value at
edit stage. the cursor position and advances the cursor to the
NOTE: Default value is set to ‘4’ i.e. 3P 4W. next less significant digit.
The PT Primary value can be set from 100 VL- L to
3.2.1.2 Potential Transformer 1200 kVL-L. The value will be forced to 100 VL-L
Primary Value if set less than 100.
The nominal full scale voltage which will be displayed Note: the flashing decimal point indicates the cursor
as the Line to Line voltages for all system types. position, a steady decimal point will be present to
The values displayed represent the voltage in identify the scaling of the number until the cursor
kilovolts (note “K” symbol). position coincides with the steady decimal point
Pressing the “ ” key accepts position. At this stage the decimal point will flash.
the present value and
advances to the “potential When the least significant digit has been set pressing
Transformer secondary Value the “ ” key will advance to the “Potential Transformer
Edit” menu. (See Section Primary Value Confirmation” screen showing display
3.2.1.3) of 0.120 kV i.e. 120 Volts indicating steady decimal
point and cursor flashing at the “hundreds of volts”
Pressing the “ ” key will enter the “Potential position.
Transformer Primary Value Edit” mode.
Initially the “multiplier must be selected, pressing the Note :
“ ” key will move the decimal point position to the 1. PT Values must be set as Line to Line
right until it reaches # # # #. after which it will return Voltage for Primary as Well as Secondary for all
to #. # # #.
system types (3P3W/3P4W/1P2W).
Pressing the “ ” key accepts the present multiplier 2. Default value is set as System Input Voltage.
(decimal point position) and advances to the
“potential Transformer primary Digit Edit” mode.

13
Potential Transformer Primary Value Confirmation
Pressing the “ ” key accepts the present value at
This screen will only appear the cursor position and advances the cursor to the
following an edit of the
Potential Transformer Primary next less significant digit.
Value.
Note : the flashing decimal point indicates the
If the scaling is not correct, pressing the “ ” key cursor position, a steady decimal point will be
will return to the “Potential Transformer Primary present to identify the scaling of the number
Value Edit” stage with the digits flashing indicating until the cursor position coincides with the
that the multiplier (decimal point position) should be steady decimal point position. At this stage the
selected. decimal point will flash
Pressing the “ ” key sets the displayed value and When the least significant digit has been set,
will advance to the Potential Transformer secondary pressing the “ ” key will advance to the “Potential
Value (See Section 3.2.1.3) Transformer secondary Value Confirmation” stage.

3.2.1.3 Potential Transformer Potential Transformer Secondary Value


Secondary Value Confirmation
The value must be set to the nominal full scale
secondary voltage which will be obtained from This screen will only appear
the Transformer when the potential transformer following an edit of the
(PT) primary is supplied with the voltage defined Potential Transformer
in 3.2.1.2 Potential Transformer Primary voltage. Secondary Value .
The ratio of full scale primary to full scale secondary If the scalling is not correct, pressing the “ ” key .
is defined as the transformer ratio. will return to the “Potential Transformer Secondary
The PT Secondary value can be set from 100VL-L Value Edit” menu.
to 500VL-L.
Pressing the “ ” key Pressing the “ ” key sets the displayed value and
accepts the present value will advance to the Current Transformer Primary
and advances to the “Current Value. (See Section 3.2.1.4)
Transformer Primary Value
edit” menu.(See Section
3.2.1.4)
Pressing the “ ” key will enter the “Potential
Transformer Secondary Value Edit” mode. “ ” key
will scroll the value of the most significant digit
from available range of PT secondary value. Please
refer the table below for different ranges.

14
3.2.1.4 Current Transformer Primary Value Current Transformer Primary Value Confirmation
This screen will only appear
The nominal Full Scale Current that will be displayed following an edit of the
as the Line currents. This screen enables the user to Current Transformer Primary
display the Line currents inclusive of any transformer Value.
ratios, the values displayed represent the Current in If the scaling is not correct, Pressing the “ ” key
Amps. will return to the “Current Transformer Primary Value
Pressing the “ ” key accepts the present value and Edit” stage with the most significant digit highlighted
advances to the Current Transformer secondary (associated decimal point flashing) and the bottom
Value (See Section 3.2.1.5) line of the display will be blanked.
Pressing the “ ” key will Pressing the “ ” key sets the displayed value and
enter the “Current Transformer will advance to the “Current Transformer Secondary
Primary Value Edit” mode. Value Edit” menu. (See Section 3.2.1.5)
This will scroll the value of the most significant digit NOTE: Default value is set to ‘5’ i.e. 5A.
from 0 through to 9, unless the presently displayed
Current Transformer Primary Value together with 3.2.1.5 Current Transformer Secondary Value
the Potential Transformer Primary Value results in a This screen is used to set the
maximum system power of greater than 3000 MVA secondary value for Current
(1000 MVA per phase) in which case the digit range Transformer. Secondary value
will be restricted, the value will wrap. “5” for 5A or “1” for 1A can be
Example: If primary value of PT is set as selected.
1200 kVL-L (max value) then primary value of Pressing “ ” key accepts the present value and
Current is restricted to 1002 A. advances to the Demand integration Time
Pressing the “ ” key will advance to the next less (See Section 3.2.1.6)
significant digit. (* Denotes that decimal point will .
be flashing). Pressing the “ ” key will enter the CT Secondary
value edit mode and scroll the value through the
The “Maximum Power” restriction of 3000 MVA values available.
refers to 120% of nominal current and 120% of
nominal voltage, i.e, 2083.3 MVA nominal power Pressing the “ ” key will advance to the CT
per phase. Secondary Value Confirmation screen.
When the least significant digit has been set, CT Secondary Value Confirmation
pressing the “ ” key will advance to the “Current This screen will only appears
Transformer Primary Value Confirmation” stage. following an edit of CT
secondary value. If secondary
The minimum value allowed is 1, the value will be value shown is not correct,
forced to 1 if the display contains zero when the pressing the “ ” key will return to CT secondary
“ ” key is pressed. edit stage.

15
Pressing “ ” key sets the displayed value and will 3.2.1.8 Low Current Noise Cutoff
advance to Demand Integration Time Edit menu.
(See Section 3.2.1.6) This screen allows the user to set Low noise
current cutoff in mA.
3.2.1.6 Demand Integration Time Low Current Cutoff Edit
Pressing “ ” key accepts
This screen is used to set the .
the present value and
period over which current and advance to No. of Poles
power readings are to be selection.
integrated. The Unit of (See section 3.2.1.9)
displayed values is Pressing the “ ” key will enter the “Low current
minutes. noise cutoff Edit” mode and scroll the “Value”
Pressing the “ ” key will scroll through the through 0 & 30 and wrapping back to 0.
following Options 8,15,20,30. Setting 30 will display measured
currents as 0 below 30 mA.
Pressing the “ ” key will advance to Demand
Integration confirmation screen. Low current noise cutoff Confirmation
Demand Integration Time value confirmation Pressing the “ ” key will
re-enter the “Low current
Pressing “ ” key sets the Noise cutoff Edit” mode.
displayed value and will
advance to Auto Scroll screen. Pressing “ ” key will set displayed value and
(See Section 3.2.1.7) advance to the No. of Poles selection.
NOTE: Default value is set to ‘8’ i.e. 8 min. (See section 3.2.1.9)
NOTE: Default value is set as ‘0’.
3.2.1.7 Auto Scrolling :
This screen allows user to 3.2.1.9 No. of Poles Selection
enable screen scrolling. This screen enables to set No. of poles of a Generator
of which RPM is to be measured and to which the
Pressing “ ” key accepts the present status and instrument is connected to monitor its parameters.
advance to the Low Current Noise Cutoff selection. Selection of No. of poles of the Generator
(See Section 3.2.1.8).
Pressing the “ ” key will Pressing “ ” key accepts the
enter the “Auto Screen present value and advance to
Scrolling Edit” and toggle the Energy Output menu.
status ‘Yes’ and ‘No’. (See section 3.2.1.10)
Pressing the “ ” key will select the status displayed Pressing the “ ” key will enter the “No. of Poles
and advance to the Low Current Noise Cutoff selection” mode and scroll the number from 2 to 40
selection. (See Section 3.2.1.8) in steps of 2. After 40 it scrolls the number back to 2.
NOTE: Default value is set to ‘NO’.

16
No. of poles Confirmation Pressing “ ” key sets the displayed value and
Pressing the “ ” key will will advance to the “Energy Digit Reset Count”
re-enter the “No. of Poles menu. (See section 3.2.1.11)
Selection” mode. Note : 1. Default value is set to ‘2’ i.e. Energy
Pressing “ ” key set the number on screen as will be in terms of kWh/kVArh/kVAh resp.
number of poles of generator & advance to “Energy 2. If (PT primary(VLL) * CT primary * Root3) >
Resolution” menu. (See section 3.2.1.10) 30000 kW, then Energy Output can be set only as
NOTE: Default value is set to ‘2’. kWh and MWh.
3. Old Energy is stored as per Energy Output only.
3.2.1.10. Energy Output
This screen enables user to set energy in terms of 3.2.1.11 Energy Digit Reset Count :
Wh / kWh / MKWh as per the requirement . Same is This screen enables user for setting maximum energy
applicable to all types of energy. count after which energy will roll over to zero depending
Pressing “ ” key accepts the presents value and on setting of Wh,KWh, & MWh.
advances to the “Energy Digit Reset Count”menu. Pressing the “ ” key accepts the present value and
(See section 3.2.1.11). will advance to the “Energy Rate”menu.
Pressing the “ ” key will (See Section 3.2.1.12)
enter the “Energy Output Pressing the “ ” key will enter
Edit” mode and scroll the Energy Digit Reset Count
through the values 1,2 & 3 edit mode. This will scroll the
wrapping back to 1. value of reset count from 7 to 9.
1 : Energy In Wh
Ex. If Energy Digit count is set to 9 then energy will reset
2 : Energy in KWh
after “999,999,999” & rollback to zero.
3: Energy in MWh.
Pressing the “ ” key advances to the Pressing “ ” key will advance to Energy Digit Reset Count
“Energy Output Confirmation” menu. confirmation screen.
Energy Output Confirmation Pressing the “ ” key will re-enter Energy Digit Reset Count
edit mode.
This screen will only appear
Pressing the “ ” key sets the displayed value and will
following an edit of the
advance to the “Energy Rate”menu.
Energy Output.
(See Section 3.2.1.12)
Pressing the “ ” key will
enter the “Energy Output Note: Default value is set to ‘8’ i.e. if energy count crosses
Edit” stage. 8 digits, then it will reset and rollback to zero.

17
3.2.1.12 Energy Rate : (* Denotes that decimal point will be flashing).
This screen allows user to enter energy update Press the “ ” key to scroll the value of the first digit
rate in min. After entering particular value in min. Press the “ ” key to advance to next digit.
the energy will be updated on modbus location from Similarly, Enter second and third digits of address.
After entering third digit, press “ ” key to advance
30145 to 30153 of 3X register and 44241 to 44249 to Address Confirmation screen.
of 4X register as per value that user has entered.
Pressing the “ ” key accepts the present Address confirmation Screen
value and will jump back to System This Screen confirms the
Parameter selection. (See Section 3.2.1) Address set by user.
Pressing the “ ” key will Press the “ ” key to advance
enter the Energy Rate edit to next Screen “Rs485 Baud
mode. This will scroll the Rate” (See Section 3.2.2.2)
count in minutes from
1 to 60. Pressing the “ ” key will re-enter the “Address
Edit” mode.
Ex. If Energy Rate is set to 2 then energy
will get stored after 2 minutes.
3.2.2.2 RS 485 Baud Rate :
Pressing “ ” key will advance to Energy Digit
Reset Count confirmation screen. This screen allows the user
Pressing the “ ” key will re-enter Energy Digit to set Baud Rate of RS 485
port. The values displayed
Reset Count edit mode. on screen are in kbaud.
Pressing the “ ” key sets the displayed value Pressing “ ” key accepts the
and will jump back to System Parameter present value and advance
selection. (See Section 3.2.1) to the Parity Selection
(See Section 3.2.2.3)
NOTE: Default value is set to ‘15’ i.e. 15 min.
Pressing the “ ” key will enter the “Baud Rate
3.2.2 Communication Parameter Selection : Edit” mode and scroll the value through 4.8, 9.6
19.2, 38.4 & back to 4.8.
3.2.2.1 Address Setting :
Pressing the “ ” key will select the value and
This screen applies to the RS 485 advances to the Parity Selection
output only. This screen allows (See Section 3.2.2.3).
the user to set RS 485 address NOTE: Default value is set to ‘9.6’.
for the meter.
The allowable range of addresses is 1 to 247. When
entering new address, it will prompt for first digit.

18
3.2.2.3 RS 485 Parity Selection: E : reset all energies
This screen allows the user to set Parity & number Hi : reset maximum values of voltage & current
of stop bits of RS 485 port. Lo : reset minimum values of voltage & current
hr : reset run hour & on hour
Pressing “ ” key accepts intr : reset no. of auxiliary supply interruption count
the present value and
advance to Communication Pressing the “ ” key will select the value.
Parameter selection screen. Pressing the “ ” key again will jump back to the
(see section 3.2.2) Communication Parameter selection menu
Pressing the “ ” key will enter the “Parity & Stop (see section 3.2.2).
bit Edit” mode & scroll the value through 3.2.4. Output Option Selection menu
odd : odd parity with one stop bit 3.2.4.1 Configuration of Output
no 1 : no parity with one stop bit This screen applies to the
no 2 : no parity with two stop bit Relay Output option Selection.
E : even parity with one stop bit
Pressing “ ” key will select
Pressing the “ ” key will set the Relay output selection
the value. menu (See section 3.2.4.1.1).
Pressing the “ ” key again will jump back to the Pressing the “ ” key will advance
Communication Parameter selection menu to the Relay 2 output option.
(see section 3.2.2).
NOTE: Default value is set as ‘no 1’. Pressing “ ” key will advance to
Assignment of Energy to Pulse Output
3.2.3 Reset Parameter Selection : Pressing the “ ” key will advance to the Quit screen.
3.2.3.1 Resetting Parameter This screen allows the user to quit the output option.
This screen allows the users to reset Energy, Pressing “ ” key will advance
Lo(Min), hi(Max), Demand, Run hour, On hour, to the Output Parameter selection.
No. of Interrupts.
After Reset, the current value of the parameters are Pressing the “ ” key will go back to Relay output
shown on their respective OLD screens. option. (See section 3.2.4.1).
Reset (None) 3.2.4.1.1 Relay 1 & 2 output Selection menu :
Pressing “ ” key advances 3.2.4.1.1.1 Pulse output :
to Reset Parameter selection This screen is used to
screen. (see section 3.2.3) assign Relay in Pulse output
mode.
Pressing the “ ” key will enter the “Reset option”
mode & scroll through the parameter given below- Pressing “ ” key will advance to the Pulse
ALL : reset all resettable parameters output configuration. (See section 3.2.4.1.1.1.1)
d : reset all demand parameters
Pressing “ ” key will show “Limit”output option.
(See section 3.2.4.1.1.2)
19
3.2.4.1.1.2 Limit output : Pulse Duration Edit
This screen is used to Pressing “ ” key accepts the
assign Relay in limit output present value and advance to
mode. Pulse Rate selection menu
( see section 3.2.4.1.1.1.3).
Pressing “ ” key will Assign
Limit output mode (See Pressing the “ ” key will enter the “Pulse Duration
section 3.2.4.1.1.2.1). Edit” mode and scroll the value through 60, 100, 200
Pressing the “ ” key will go back to the pulse option and wrapping back to 60.
Screen. (See section 3.2.4.1.1.1)
Pressing the “ ” key will select the value and
advances to “Pulse Duration Confirmation”.
3.2.4.1.1.1.1 Assignment of Energy to Pressing the “ ” key again will set displayed
pulse output : value and advance to Pulse Rate selection
This screen allows the user to assign pulse output menu. (See section 3.2.4.1.1.1.3)
to energy. NOTE: Default value is set to ‘100’.
Pressing “ ” key accepts
the present setting and advance 3.2.4.1.1.1.3 Pulse Rate
to “Pulse duration selection” This screen applies to the Relay Output option only.
(see section 3.2.4.1.1.1.2). The screen allows user to set the Energy Pulse Rate
Pressing the “ ” key will enter into edit mode divisor. Divisor values can be selected through
and scroll through the energy setting: 1,10,100,1000 as per EnOP set. Refer TABLE 4
for details.
A - E : Apparent Energy Pressing “ ” key accepts
I - E : Import Energy (Active) the present value and
E - E : Export Energy (Active) advances to the
C - rE : Capacitive Reactive Energy “Configuration of output”
L - rE : Inductive Reactive Energy (See section 3.2.4.1).
Pressing the “ ” key will set the value & advances Pressing the “ ” key will enter the “Pulse Rate
to the “Pulse Duration Selection”. Divisor Edit” mode & scroll the value through the
(see section 3.2.4.1.1.1.2) values 1,10,100, 1000 wrapping back to 1. Pressing
NOTE: Default value is set as ‘I-E’. the “ ” key advances to the “Pulse Rate Divisor
Confirmation” menu.
3.2.4.1.1.1.2 Pulse Duration Selection: Pressing the “ ” key will return to the
“Pulse rate Divisor Edit” stage.
This screen applies only to the Pulse output mode
of relay. Pressing “ ” key sets the displayed value and will
This screen allows the user to set Relay energization advance to the “Configuration of output”.
time in milliseconds. (See section 3.2.4.1)

20
3.2.4.1.1.2.1 Assignment of Limit output Pressing the “ ” key will enter the Limit
to parameter. Configuration edit mode and scroll through the
modes available.
This screen is for Limit output mode selection. It
allows the user to set Limit output corresponding Pressing the “ ” key advances to the Limit
measured value. Refer TABLE 3 “Parameter for Configuration type confirmation menu.
Limit output” for assignment.
Pressing the “ ” key sets the displayed value &
Pressing “ ” key accepts will advance to “Trip point selection” Screen.
the present value and (See section 3.2.4.1.1.2.3 )
advance to the Limit NOTE: Default value is set to ‘Hi-E’.
Configuration select screen.
(see section 3.2.4.1.1.2.2 ).
3.2.4.1.1.2.3 Trip point selection :
Pressing the “ ” key will enter the “Limit output This screen applies to the Trip point selection.
Edit” mode and scroll the values, as per TABLE 3, This screen allows the user to set Trip point for
“Parameter for Limit Output”. instruments.
Pressing the “ ” key will advance to the Limit The allowable range is 10%
output confirmation screen. to 120% for High Alarm 10%
to 100% for Low Alarm.
Pressing the “ ” key sets the displayed value & (refer TABLE 3).
will advance to the Limit Configuration select screen.
(see section 3.2.4.1.1.2.2 ) Enter value, prompt for first digit. (* Denotes that
digit will be flashing).
3.2.4.1.1.2.2 Limit Configuration select Press the “ ” key to scroll the values of the first
digit.
This screen is used to set the Limit Configuration.
Four different types of configuration can be selected: Press the “ ” key to advance to next digit.
H i - E (High Alarm & Similarly, enter second and third digits also.
Energized Relay)
H i - d (High Alarm & Press “ ” to confirm and advance to “Hysterisis
De-Energized Relay) Selection” screen. (See section 3.2.4.1.1.2.4)
Lo - E (Low Alarm & Pressing the “ ” key will return to Edit mode.
Energized Relay) NOTE: Default value is set to ‘100’.
Lo - d (Low Alarm &
De-Energized Relay) 3.2.4.1.1.2.4 Hysteresis selection :
(For details refer to section 10.2) This screen applies to the Hysteresis selection.
This screen allows the user
Pressing the “ ” key accepts the present value to set Hysteresis for relay
and advances to the “Trip Point selection” screen. output.
(see section 3.2.4.1.1.2.3) The allowable range is 0.5% to 50.0 % of Trip point.

21
Enter value, prompt for first digit. 3.2.4.1.1.2.6 De-Energizing Delay
(* Denotes that decimal point will be flashing). time
This screen allows the user to set De-Energizing
Press the “ ” key to scroll the value of the Delay time in seconds for Relay Limit Assigned
first digit Parameters.
Press the “ ” key to advance to next digit. Pressing “ ” key accepts the
present value and jumps back
Hysteresis for Frequency is calculated as % of trip to Configuration of Output.
point span from 45 to 66 Hz. Eg. If trip point is 50% (See section 3.2.4.1)
(55.5 Hz) and hysteresis is set to 10%, then relay will Pressing the “ ” key will enter the “De-Energizing
reset at 49.95 Hz [10% of 55.5 is 5.55 Hz. Delay” Edit mode and scroll the “Value” through 1 to10.
Hence, 55.5 - 5.55 = 49.95 Hz]
Note : In case of lo alarm if trip point is set at 100% Pressing “ ” key set displayed value & will advance
then maximum 20% Hysterisis can be set. to Configuration of output. (See section 3.2.4.1)
NOTE: Default value is set to ‘1’.
Similarly, enter second and third digits also.
3.2.5 User Assignable Features
Press “ ” to confirm and advance to “Energizing
Delay Time” screen. (See section 3.2.4.1.1.2.5) 3.2.5.1 Feature Selection Menu
Pressing the “ ” key will return to Edit mode. This menu allows the user
to scroll through different
NOTE: Default value is set to ‘50’. User Configurable features:
3.2.4.1.1.2.5 Energizing Delay time bcLt : backlit on/off
Scrn : user screen on/off
This screen allows the user
to set Energizing Delay time Pressing the “ ” key will scroll through the features
in seconds for Relay Limit backlit, user screen and quit.
Assigned Parameters.
Pressing “ ” key will select that particular option.
Pressing “ ” key accepts the (See section 3.2.5.1.1 or 3.2.5.1.2)
present value and. advance Selecting “Quit” option will return to “User Assignable
to De-energizing delay screen. Features” screen. (See section 3.2.5)
Pressing the “ ” key will enter the “Energizing Delay” 3.2.5.1.1 Backlit
Edit mode and scroll the “Value” through 1 to10.
This screen allows the user
Pressing “ ” key set displayed value & will advance to switch the backlit on or off.
to Assignment of De-energizing delay time.
(See section 3.2.4.1.1.2.6 )
NOTE: Default value is set to ‘1’. Pressing the “ ” key will toggle between options
“ON” and “OFF”.

22
Pressing the “ ” key will select that particular After entering User Screen 10 value, pressing the
option and jump back to “Feature Selection Menu”. “ ” key will jump back to “Feature Selection Menu”.
(See section 3.2.5.1) (See section 3.2.5.1)
Note: When backlit is switched ‘Off’, on pressing 4. Current Reversal screen
any key backlit will turn ‘On’ for 1 min.
Default value is set to ‘On’. This screen is useful to indicate if current in any
phase is reversed or not.
3.2.5.1.2 User Assignable Screens If current in any phase gets reversed, then
This feature is applicable only to EM 1340 model. corresponding phase will be indicated on this screen.
This screen allows the user to turn On or Off the
User Screen feature. Using this feature, the user This screen shows that
can select any FIVE / TEN measurement screens of currents in all three phase
his choice and scroll through only those selected are reversed.
screens.
This screen shows that currents
Pressing the “ ” key will in all three phase are correct.
toggle between options
“no”, “5” and “10”.
This screen shows that the
5: Five userscreens meter has no current input.
10: Ten userscreens
If “NO” option is selected by pressing “ ” key, then
it will jump back to “Feature Selection Menu”. 5. Phase Rotation Error screen
(See section 3.2.5.1) Meter shows phase rotation error if the phase
If “5” or “10” option is selected, then it will advance to sequence R-Y-B (L1-L2-L3) is not maintained or if
“User Screen 1” selection screen. any of the phase is absent.
NOTE: If User Screen feature is ON and System type This screen indicates that
is changed, then Active Energy screen (No. 8) is Phase Sequence is incorrect.
shown after exiting from setup.
User Screens Selection User must check this screen
in order to get correct readings
Pressing the “ ” key accepts when meter is connected.
the present value and advance
to “User Screen 2” selection. This screen indicates that
Pressing the “ ” key will enter the “User Screen” Phase Sequence is correct.
Edit mode and scroll through the screen numbers
as per TABLE 2 “Measurement Screens”. This screen indicates that all
Pressing “ ” key will set the displayed value & three phases (voltages) are
advance to “User Screen 2” selection. absent.
Similarly, enter the screen numbers for “User Screens Note: In 3P3W, this screen is applicable only
2 to 5 or 2 to 10” depending upon the selection. when load is balanced.

23
6. Phase Absent screen 8. On Hour
This screen is useful to indicate if voltage or current This Screen shows the total
in any phase is absent. Hence, user will know no. of hours the Auxiliary
which voltage or current is missing and take Supply is ON. Even if the
corrective action. Auxiliary supply is interrupted
count of On hour will be
This screen indicates that maintained in internal
all three phases (voltage memory & displayed in the
& current) are absent. format “hours. min”.
For example if Displayed count is 105000.10 it
This screen indicates that indicates 105000 hours and 10 minutes.
V2, I2 and I3 are absent. After 999999.59 On hours display will restart from
zero. To reset On hour manually see section
Resetting Parameter 3.2.3.1
This screen indicates that
all three phases are present
i.e. all inputs are present. 9. Number of Interruption :
This Screen Displays the
total no. of times the Axillary
7. Run Hour Supply was Interrupted. Even
if the Auxiliary supply is
This Screen shows the total interrupted count will be
no. of hours the load is maintained in internal memory.
connected. Even if the To reset No of Interruption
Auxiliary supply is interrupted, manually see section
count of Run hour will be Resetting Parameter 3.2.3.1
maintained in internal
memory & displayed in the
format “hours. min”.
For example if Displayed count is 105000.10 it
indicates 105000 hours & 10 minutes.
After 999999.59 run hours display will restart from
zero. To reset run hour manually see section
Resetting Parameter 3.2.3.1

24
TABLE 3 : Parameters for Limit output
Parameter 3P 3P 1P Trip Point 100%
Parameter Set Range
No. 4W 3W 2W Value
0 None   
1 Volts 1    10 - 120 % Vnom (L-N)
2 Volts 2    10 - 120 % Vnom (L-N)
3 Volts 3    10 - 120 % Vnom (L-N)
4 IL1    10 - 120 % Inom
5 IL2    10 - 120 % Inom
6 IL3    10 - 120 % Inom
7 W1    10 - 120 % Nom (3)
8 W2    10 - 120 % Nom
(3)

9 W3    10 - 120 % Nom (3)


10 VA1    10 - 120 % Nom (3)
11 VA2    10 - 120 % Nom (3)
12 VA3    10 - 120 % Nom
(3)

13 VAr1    10 - 120 % Nom (3)


14 VAr2    10 - 120 % Nom (3)
15 VAr3    10 - 120 % Nom (3)
16 PF1 #    10 - 90 % 90°
17 PF2 #    10 - 90 % 90°
#
18 PF3    10 - 90 % 90°
#
19 Pa1    10 - 90 % 360°
20 Pa2
#
   10 - 90 % 360°
#
21 Pa3    10 - 90 % 360°

25
Parameter 3P 3P 1P Trip Point 100%
Parameter Set Range
No. 4W 3W 2W Value
22 Volts Ave.    10 - 120 % Vnom
(2)

24 Current Ave.    10 - 120 % Inom


27 Watts sum    10 - 120 % Nom
(3)

29 VA sum    10 - 120 % Nom


(3)

31 VAr sum    10 - 120 % Nom


(3)

32 PF Ave. #    10 - 90 % 90°
34 PA Ave.#    10 - 90 % 360°
36 Freq.    10 - 90 % 66 Hz
(1)

(3)
43 Watt Demand Imp.    10 - 120 % Nom
(3)
44 Watt Max Demand Imp.    10 - 120 % Nom
45 Watt Demand Exp    10 - 120 % Nom (3)
46 Watt Demand Max Exp    10 - 120 % Nom (3)
51 VA Demand    10 - 120 % Nom
(3)

52 VA Max Demand.    10 - 120 % Nom


(3)

53 Current Demand.    10 - 120 % Inom


54 Current Max Demand.    10 - 120 % Inom
101 VL1-L2    10 - 120 % Vnom (L-L)
102 VL2-L3    10 - 120 % Vnom (L-L)
103 VL3-L1    10 - 120 % Vnom (L-L)
113 I Neutral    10 - 120 % Inom
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W.
(1) For Frequency 0% corresponds to 45 Hz and 100% corresponds to 66 Hz.
(2) For 3P 4W and 1Ph the nominal value is VL-N and that for 3P 3W is VL-L.
(3) Nominal Value for power is calculated from Nominal Voltage and current values.
(4) Nominal Value is to be considered with set CT/ PT Primary values.
(5) For single phase L1 Phase values are to be considered as System values.

26
10. Relay output (Optional) : 2. For Energy Output in KWhr
Pulse rate
The Meter is provided with relay for pulse output Divisor System Power*
Pulse
as well as for limit switch. 1 1 per kWhr Up to 3600 kW
10.1 Pulse Output : 1 per MWhr Above 3600 kW
Pulse Output is the potential free, very fast acting 3. For Energy Output in MWhr
relay contact which can be used to drive an external Pulse rate
Divisor Pulse
mechanical counter for energy measurement. The 1 1 per MWhr
Pulse Output can be configured to any of the following
parameter through setup parameter screen: Above options are also applicable for Apparent and
1) Active Energy (Import) Reactive Energy.
2) Active Energy (Export) *Note:
3) Capacitive Reactive Energy 1) System power = 3 x CT(Primary) x PT (Primary)
L-N for 3 Phase 4 Wire
4) Inductive Reactive Energy 2) System power = Root3 x CT(Primary) x PT
5) Apparent Energy (Primary)L-L for 3 Phase 3 Wire
3) System power = CT(Primary) x PT(Primary)L-N
TABLE 4 : Energy Pulse Rate Divisor for 1 Phase 2 Wire
1.For Energy Output in Whr
Pulse rate
10.2 Limit Switch :
Divisor Pulse System Power*
Limit switch can be used to monitor the measured
1 1 per Whr Up to 3600 W parameter ( Ref. TABLE 3 )in relation with to a set
1 per kWhr Up to 3600 kW limit. The limit switch can be configured in one of the
1 per MWhr Above 3600 kW four mode given below:-
up to 30000 kW 1) Hi alarm & Energized Relay
10 1 per 10Whr Up to 3600 W 2) Hi alarm & De-Energized Relay
1 per 10kWhr Up to 3600 kW 3) Lo alarm & Energized Relay
1 per 10MWhr Above 3600 kW 4) Lo alarm & De-Energized Relay
up to 30000 kW
100 1 per 100Whr Up to 3600 W With User selectable Trip point, Hysteresis,
1 per 100kWhr Up to 3600 kW Energizing Delay & De-Energizing delay.
1 per 100MWhr Above 3600 kW Hi Alarm:
up to 30000 kW
1000 1 per 1000Whr Up to 3600 W If Hi-Alarm Energized or Hi Alarm De-Energized option
1 per 1000kWhr Up to 3600 kW is selected then relay will get energized or
1 per 1000MWhr Above 3600 kW De-energized,if selected parameter is greater than or
up to 30000 kW equal to trip point.
Pulse Duration 60 ms,100 ms or 200 ms
Lo Alarm:
If Lo-Alarm Energized or Lo Alarm De-Energized option
is selected then relay will get energized or De-energized,
if selected parameter is less than or equal to trip point.

27
# Note: For Lo-Alarm configuration, set the values Trip point:
of trip point & hysteresis such that % trip point + Trip point can be set in the range as specified in
% hysteresis should be less than 100%. TABLE 3 of nominal value for Hi-Alarm & 10% to
100 % of nominal value for Lo-Alarm.
Example for Phase angle:
If trip point is set 70% then maximum
applicable hysteresis is 42.8%. i.e Trip point 70% Hysteresis:
(252°) + Hysteresis 42.8% (107.8°) = 359.8° Hysteresis can be set in the range of 0.5% to 50 %
If total value is greater than the 100% i.e. 360° of set trip point .
then relay will not release. If Hi-alarm Energized or Hi-alarm De-energized is
selected then relay will get De-energized or
Example for PF: Energized respectively, if set parameter value is
For Hi-Alarm Energized, if trip point is 70% & less than Hysteresis
hysterisis is 30%, then trip value = 0.7x90°=63°. Similarly if Lo-alarm Energized or Lo-alarm
Tripping PF = cos(63)=0.4539 & De-Energized.
hysterisis=0.3x0.4539=0.136.
0° (+1)
Note : In case of lo alarm if trip point is set greater
than 80% then the maximum hysteresis can be set
Relay Energise such that the total Trip point+ Hysteresis(% of trip
0.4539
0.4539(Trip point) point value) will not exceed 120% of range.
0.136 0.136(Hysterisis point)
For example :If trip point is set at 90%, then
270° (0.00) 90° (0.00) maximum 33.3% hysteresis should be set such that,
Relay De-energise [90 + 29.99 (33.3% of 90)] = 120

Energizing Delay:
The energizing delay can be set in the range from
180° (-1)
1 to 10 sec.
Hence, the relay will energize above 0.4539 and
de-energize below 0.136. De-Energizing Delay:
Note: This function will work irrespective of The De-energizing delay can be set in the range
+/- sign. It depends only on value. from 1 to 10 sec.

28
Sign of Sign of Sign of Inductive /
Connections Quadrant Active Reactive Power Capacitive
Power ( P ) Power ( Q ) Factor ( PF )
Import 1 +P +Q + L
Import 4 +P -Q + C
Export 2 -P +Q - C
Export 3 -P -Q - L
Inductive means Current lags Voltage
Capacitive means Current leads Voltage Caution
When Multifunction Meter displays Active 1. In the interest of safety and functionality this
power ( P )with “ + ” ( positive sign ),the product must be installed by a qualified engineer,
connection is “ Import ” . abiding by any local regulations.
2. Voltages dangerous to human life are present at
When Multifunction Meter displays Active some of the terminal connections of this unit.
power ( P )with “ - ” ( negative sign ), the Ensure that all supplies are de-energised before
connection is “ Export ” attempting any connection or disconnection.
3. These products do not have internal fuses
12. Installation therefore external fuses must be used to ensure
safety under fault conditions.

Mounting of the Meter is featured


with easy “Clip- in” mounting. Push the meter
in panel slot (size 92 x92 mm), it will click
fit into panel with the four integral retention
clips on two sides of meter. If required,
additional support is provided with swivel
Easy Clip - in
screws as shown in figure.
mounting The front of the enclosure conforms to IP50.
Additional protection to the panel may be
obtained by the use of an Optional panel
gasket. The terminals at the rear of the
product should be protected from liquids.
Swivel screw The Meter should be mounted in a
reasonably stable ambient temperature
and where the operating temperature is within
the range 0 to 500C. Vibration should be
Panel Thickness : 1 - 3mm for self clicking, kept to a minimum and the product should
1 - 6mm for swivel screws not be mounted where it will be subjected
to excessive direct sunlight.

29
Examples of different configurations
Parameter No. 4 (Current1)
Trip Point = 50%
Hysteresis = 50% of trip point
Energising Delay: 2S
De-energising Delay: 2S
1) Hi alarm & Energised relay 2) Hi alarm & De-energised relay
Relay Energise Relay De-energise
Input Relay De-energise Input Relay Energise

50% Trip point 50% Trip point

25% Hysterisis point 25% Hysterisis point

Time Time

2s 2s 2s 2s

3) Lo alarm & Energised relay 4) Lo alarm & De-energised relay


Relay De-energise Relay Energise
Input Relay Energise Relay De-energise
Input

75% Hysterisis point 75% Hysterisis point

50% Trip point 50% Trip point

Time Time

2s 2s 2s 2s

Capacitive Inductive
11. Phasor Diagram :

Inductive Capacitive

30
12.1 EMC Installation Requirements 12.2 Case Dimension & Panel Cut
This product has been designed to meet the
Out
96 mm 27 mm
certification of the EU directives when
installed to a good code of practice for EMC
in industrial environments,e.g.
1. Screened output and low signal input Front Display Area

96mm
leads or have provision for fitting RF
suppression components,such as ferrite
absorbers, line filters etc., in the event
that RF fields cause problems. 6 mm
35 mm

Note:It is good practice to install sensitive


electronic instruments that are With optional MODBUS / Limit switch.
performing critical functions, in EMC 92mm+0.8
enclosures that protect against
electrical interference which could
cause a disturbance in function.

92mm+0.8
2. Avoid routing leads alongside cables and Panel Cutout
products that are, or could be, a source of
interference.
3. To protect the product against permanent
damage, surge transients must be limited
to 2kV pk. It is good EMC practice to 12.3 Wiring
suppress differential surges to 2kV at the Input connections are made directly to
source. The unit has been designed to screw-type terminals with indirect wire
automatically recover in the event of a high pressure. Numbering is clearly marked on
level of transients. In extreme the connector. Choice of cable should
circumstances it may be necessary to meet local regulations. Terminal for both
temporarily disconnect the auxiliary supply Current and Voltage inputs will accept upto
for a period of greater than 5 seconds to 4mm2 (12AWG) solid or 2.5 mm2 stranded
restore correct operation. The Current cable.
inputs of these products are designed for Note : It is recommended to use wire
connection in to systems via Current with lug for connection with meter.
Transformers only, where one side is
grounded. 12.4 Auxiliary Supply
Meter should ideally be powered from a
4. ESD precautions must be taken at all dedicated supply, however powered from
times when handling this product. the signal source, provided the source
remains within it may be the limits of the
Chosen auxiliary voltage range.

31
12.5 Fusing SINGLE PHASE 2-WIRE
DIGITAL METERING SYSTEM (WITH EXTERNAL AUX.)
It is recommended that all voltage lines are
fitted with 1 Amp HRC fuse. 2 11 1 3 13 14

12.6 Earth/Ground Connections


For safety reasons, CT secondary
connections should be grounded in
accordance with local regulations. L N
AUX
13. Connection Diagrams SUPPLY
P1 S1
3-PHASE 3-WIRE UNBALANCED LOAD L L
O
DIGITAL METERING SYSTEM (WITH EXTERNAL AUX.) A
2 5 8 3 7 9 N D

14. Optional Pluggable Module


L N
AUX
SUPPLY
P1 S1
L1 L
L2 O
P1 S1 A
L3 D
N

3-PHASE 4-WIRE UNBALANCED LOAD


DIGITAL METERING SYSTEM (WITH EXTERNAL AUX.)
2 5 8 11 1 3 4 6 7 9 13 14

L N
AUX
SUPPLY
P1 S1
L1 L
P1 S1
L2 O
P1 S1
L3 A
D
N

32
15. Specification : Overload withstand
System Voltage input 2 x Rated Value
3 Phase 3 Wire / 4 Wire or Single (1s application
Phase programmable at site repeated 10 times
at 10s intervals)
Inputs
Current input 20 x Imax for 0.5sec
Nominal Input 100 VL-L to 500 VL-L
Voltage 57.7 VL-N to 290 VL-N Auxiliary Supply
Higher 60V to 300V AC/DC
System PT Primary 100VL-L to 1200 kVL-L, Auxiliary Supply (+/- 5% approx.)
Values programmable at site Nominal Value 230V AC/DC
System PT 100 VL-L to 500 VL-L 50/60 Hz for AC Aux
Secondary Values OR
programmable at site
Lower 20V to 60V DC /
Max continuous 120% of Nominal Value Auxiliary Supply 20V to 40V AC
input voltage Nominal Value 48V DC /
Nominal input <0.3 VA approx. 24 V AC 50/60 Hz
voltage burden per Phase
Frequency Range 45 to 65 Hz
Nominal Input 1A / 5A AC RMS VA Burden
Current With Addon card < 6 VA approx.
max continuous 120% of Nominal value Without Addon card < 4 VA approx.
input current
Nominal input <0.3 VA approx. Operating Measuring Ranges
current burden per phase Voltage with 50 ... 120 % of
SystemCT primary Std. Values 1 to external Aux. Nominal Value
values 9999A (1 or 5 Amp Current 1A - 20mA to 1.2A
secondary) 5A - 100mA to 6A
System Secondary 1A / 5A, Starting Current 1A - 2mA
Values programmable at site (As per IEC 5A - 10mA
Overload Indication “-OL-” 62053-21)
>121% of Nominal value Frequency 50 Hz / 60 Hz
(for voltage and current) Power Factor 0.5 Lag ... 1 ... 0.8 Lead
Total Harmonic 0...50%
Distortion

33
Controls
Reference conditions for Accuracy User Interface 2 push buttons
0 0
Reference 23 C + 2 C Standards
temperature EMC Immunity IEC 61000-4-3
(as per IEC 62053-21) 10V/m - Level 3
Industrial Low Level
Accuracy
Voltage + 0.5 % of EMC Emmision IEC 61326-1
Nominal Value Safety IEC 61010-1-2010,
Current + 0.5 % of permanently connected use
Nominal Value IP for water & dust IEC 60529
Frequency + 0.2 % of mid Pollution degree 2
frequency
Installation III
Active power + 0.5 % of Category
Nominal Value at
cos ø = 1 Isolation
Reactive power + 1.0 % of Protective Class 2
Nominal Value at
sin ø = 1 High Voltage Test
Input+Aux vs 4 kV RMS, 50Hz, 1 min
Apparent Power + 0.5 % of Surface
Nominal Value
Input vs Remaining 2 kV RMS, 50Hz, 1 min
Power Factor / + 3° Circuit
Phase Angle
class 1 as per Environmental conditions
Active energy
IEC 62053-21 Operating temperature -10 to +55 0C
Reactive energy class 2 as per Storage temperature -20 to +65 0C
IEC 62053-23 Relative humidity 0 .. 90 % RH (Non
Apparent energy class 1 condensing)
THD (Voltage +2% Warm up time 3 minute (minimum)
/ Current) Shock Half Sine wave,
Note: Variation due to influence quantity (As per Peak acceleration
is 100% of class index for all other IEC 60068-2-27) 30gn (300 m/s^2),
parameters except energy. duration 18 ms
Display Vibration 10..150..10 Hz,
0.15mm amplitude
LCD Display with backlit
Update rate Approx. 1 sec. Number of Sweep 10 per axis
cycles
34
Enclosure
Enclosure front IP 50 100 1 per 100Wh (up to
Enclosure front 3600W),
with seal (optional) IP 65 1 per 100kWh (up to
Enclosure back 3600 kW),
IP 20
1 per 100MWh (above
Dimensions 3600 kW up to
Bezel Size 96mm x 96mm DIN 30000 kW)
43718
Panel cut out 92+0.8mm X 92+0.8mm 1000 1 per 1000Wh (up to
Overall Depth 3600W),
55 mm
1 per 1000kWh (up to
Panel thickness 1 - 3mm for self clicking
3600kW),
1 - 6mm for swivel 1 per 1000MWh (above
screws 3600 kW up to
Weight 320 grams Approx. 30000 kW)
Pulse output Option
Relay 1NO Pulse Duration 60ms , 100ms or
200ms
Switching Voltage 240 VAC , 5 A.
Note :
& Current 1. Refer TABLE 4 for details.
Default Pulse rate 1 per Wh (up to 2. Above conditions are also applicable
Divisor 3600W), for Reactive & Apparent Energy.
1 per kWh (up to
3600kW), ModBus ( RS 485 ) Option :
1 per MWh (above Protocol ModBus ( RS 485 )
3600 kW up to Baud Rate 38400, 19200, 9600
30000 kW) or 4800 (Programmable)
Pulse rate Programmable on site
Divisors Parity Odd or Even, with
10 1 per 10Wh (up to 1 stop bit, Or None
3600W), with 1 or 2 stop bits
1 per 10kWh (up to Impulse Output :
3600kW), Impulse Constant as per PT Secondary
1 per 10MWh (above 100 to 125 VLL: 16000 impulse/kWh
3600 kW up to 126 to 250 VLL: 8000 impulse/kWh
30000 kW) 251 to 500 VLL: 4000 impulse/kWh

35
16. Connection for Optional Pulse 2. RS 485 Output
Output / RS 485
(rear view of Multifunction Meter):
1. One Pulse Output (Limit Output)
B A Gnd
RS 485

NO COM
4. Two Pulse/limit Output
Relay 1

NO COM NO COM
3. One Pulse (Limit) + RS 485 Output Relay 1 Relay 2

5. Two Pulse/limit + RS 485 Output


B A Gnd NO COM
RS 485 Relay 1

B A Gnd NO COM NO COM


RS 485 Relay 1 Relay 2

36