ShaftWall 0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

ShaftWall

ShaftWall
Shaft and duct encasement system

All our systems are covered by SpecSure® when using


genuine Gyproc and Isover products
Specialist partitions
C05

british-gypsum.com
ShaftWall
ShaftWall
ShaftWall provides a lightweight, fire resistant
60 120
structure to protect elements in confined spaces mins

wherever access is limited to one side only.

The system provides a protective structure which 38 52


RwdB
can be incorporated at an early stage of the
construction without the need for scaffolding.

The system can also be built horizontally to Refer to C01. S01. P08

Specialist partitions
provide a fire rated membrane.

Key benefits
— Horizontal membranes are built entirely from below
— A ShaftWall variant with non-combustible

C05
Glasroc F firecase board linings is available
— High level commonality with GypWall partition
components, particularly 70mm stud solutions
— Higher certainty of installed acoustic performance
due to laboratory tests incorporating deflection heads
— Can be used where access is limited to one side at
the head, e.g. M & E cages already installed in corridors

You may also be interested in...


For assistance in choosing the right solution for your project, try our System Selector; an online tool
that enables quick and easy filtering by performance criteria. It provides system specific downloads
including:
— BIM (Revit) objects — Specification Clauses —System and product data sheets

Refer to gyproc.ie

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P291
ShaftWall performance
ShaftWall

For details of when


to specify fire
Vertical elements resistance using EN
Refer to C02. S01. P18
Table 1a — Solutions to satisfy the requirements of BS EN 1364-1: 1999

1 2 3 4

Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud
framework with Gyproc CoreBoard framework with Gyproc CoreBoard framework with Gyproc CoreBoard framework with Gyproc CoreBoard
between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe
Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm
Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional).
Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see
table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres.
Specialist partitions

Detail Partition Lining boards Max. Stud Sound insulation RwdB3 Duty Approx. System
thickness to non-shaft side1 partition size rating5 weight reference
mm Board type Lining height2 mm kg/m²
No insulation Sealed structure plus
thickness mm
25mm Isover Acoustic
mm Roll 4

60 minutes fire resistance


C05

1 87 Gyproc FireLine 2 x 12.5 4400 60 40 44 Severe 39 A306002/012

1 97 Gyproc FireLine 2 x 12.5 4400 70 40 44 Severe 39 A306002/012

1 119 Gyproc FireLine 2 x 12.5 6000 92 45 47 Severe 40 A306005/014

2 173 Gyproc FireLine 2 x 12.5 6000 146 48 52 Severe 42 A306008/020

90 minutes fire resistance

1 92 Gyproc FireLine 2 x 15 4500 60 42 45 Severe 43 A306003/023

1 102 Gyproc FireLine 2 x 15 4500 70 42 45 Severe 43 A306003/023

1 124 Gyproc FireLine 2 x 15 6000 92 44 46 Severe 44 A306006/025

2 178 Gyproc FireLine 2 x 15 6000 146 48 50 Severe 46 A306009/028

120 minutes fire resistance

3 107 Gyproc FireLine 3 x 15 4500 60 43 45 Severe 55 A306030/035

3 117 Gyproc FireLine 3 x 15 4500 70 43 45 Severe 55 A306030/035

3 139 Gyproc FireLine 3 x 15 6000 92 45 46 Severe 56 A306031/036

4 193 Gyproc FireLine 3 x 15 6000 146 49 50 Severe 58 A306032/033

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

1
For improved durability and impact resistance, the outer layer of Gyproc FireLine can be replaced with a layer of 15mm Gyproc DuraLine.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The acoustic performance figures quoted include ShaftWall partitions with deflection heads.
4
Gyproc CoreBoard and first layer of lining board are bedded onto Gyproc Sealant, as required for pressurised air shafts, in addition to normal sealing.
5
Estimated rating from non-shaft side only.

The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled,
or skimmed according to Gyproc’s recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and
the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at the head. For the base Gypframe Folded Edge Standard
Floor & Ceiling Channel should be used for heights up to 4200mm, Gypframe Deep Flange Floor & Ceiling Channel should be used for heights between
4200mm and 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used for heights in excess of 8000mm.

C05. S02. P292 gyproc.ie


ShaftWall performance (continued)

ShaftWall
For details of when
to specify fire
Vertical elements resistance using BS
Refer to C02. S01. P18
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987

1 2 3 4

Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud
framework with Gyproc CoreBoard framework with Gyproc CoreBoard framework with Gyproc CoreBoard framework with Gyproc CoreBoard
between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe
Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm
Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional).
Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see
table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres.

Specialist partitions
Detail Partition Lining boards Max. Stud Sound insulation RwdB3 Duty Approx. System
thickness to non-shaft side1 partition size rating5 weight reference
mm Board type Lining height2 mm kg/m²
No insulation Sealed structure plus
thickness mm
25mm Isover Acoustic
mm Roll 4

(60)/30 minutes fire resistance (exposure to fire from shaft side)

C05
1 77 Gyproc FireLine 1 x 15 4200 60 39 42 Heavy 30 A306001/010

1 87 Gyproc FireLine 1 x 15 4200 70 39 42 Heavy 30 A306001/010

1 109 Gyproc FireLine 1 x 15 6000 92 40 43 Heavy 31 A306004/011

2 163 Gyproc FireLine 1 x 15 7700 146 43 46 Heavy 33 A306007/013

(90)/60 minutes fire resistance (exposure to fire from shaft side)

1 87 Gyproc FireLine 2 x 12.5 4400 60 40 44 Severe 39 A306002/012

1 97 Gyproc FireLine 2 x 12.5 4400 70 40 44 Severe 39 A306002/012

1 119 Gyproc FireLine 2 x 12.5 6400 92 45 47 Severe 40 A306005/014

2 173 Gyproc FireLine 2 x 12.5 7900 146 48 52 Severe 42 A306008/020

(120)/90 minutes fire resistance (exposure to fire from shaft side)

3 92 Gyproc FireLine 2 x 15 4500 60 42 45 Severe 43 A306003/023

3 102 Gyproc FireLine 2 x 15 4500 70 42 45 Severe 43 A306003/023

3 124 Gyproc FireLine 2 x 15 6700 92 44 46 Severe 44 A306006/025

4 178 Gyproc FireLine 2 x 15 7900 146 48 50 Severe 46 A306009/028

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to Gyproc.ie

1
For improved durability and impact resistance, the outer layer of Gyproc FireLine can be replaced with a layer of 15mm Gyproc DuraLine.
2
Based on limiting deflection of L/240 at 200 Pa.
3
The acoustic performance figures quoted include ShaftWall partitions with deflection heads.
4
Gyproc CoreBoard and first layer of lining board are bedded onto Gyproc Sealant, as required for pressurised air shafts, in addition to normal sealing.
5
Estimated rating from non-shaft side only.

The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled,
or skimmed according to Gyproc’s recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and
the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at the head. For the base Gypframe Folded Edge Standard
Floor & Ceiling Channel should be used for heights up to 4200mm, Gypframe Deep Flange Floor & Ceiling Channel should be used for heights between
4200mm and 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used for heights in excess of 8000mm.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P293
ShaftWall performance (continued)
ShaftWall

For details of when


to specify fire
Vertical elements — non-combustible board linings resistance using EN
Refer to C02. S01. P18
Table 2a — Solutions to satisfy the requirements of BS EN 1364-1: 1999

1 2 3 4

Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud
framework with 20mm Glasroc F firecase framework with 20mm Glasroc F firecase framework with 20mm Glasroc F firecase framework with 20mm Glasroc F firecase
between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe
Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm
Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional).
Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see
table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres.
Specialist partitions

Detail Partition Lining boards Max. Stud Sound insulation RwdB3 Duty Approx. System
thickness to non-shaft side1 partition size rating5 weight reference
mm Board type Lining height2 mm kg/m²
No insulation Sealed structure plus
thickness mm
25mm Isover Acoustic
mm Roll4

60 minutes fire resistance


C05

1 92 Glasroc F firecase 2 x 15 4500 60 41 44 Severe 46 G306003/023

1 102 Glasroc F firecase 2 x 15 4500 70 41 44 Severe 46 G306003/023

1 124 Glasroc F firecase 2 x 15 6000 92 43 45 Severe 47 G306006/025

2 178 Glasroc F firecase 2 x 15 6000 146 47 49 Severe 49 G306009/028

90 minutes fire resistance

1 92 Glasroc F firecase 2 x 15 4500 60 41 44 Severe 46 G306003/023

1 102 Glasroc F firecase 2 x 15 4500 70 41 44 Severe 46 G306003/023

1 124 Glasroc F firecase 2 x 15 6000 92 43 45 Severe 47 G306006/025

2 178 Glasroc F firecase 2 x 15 6000 146 47 49 Severe 49 G306009/028

120 minutes fire resistance

3 107 Glasroc F firecase 3 x 15 4500 60 42 44 Severe 59 G306030/035

3 117 Glasroc F firecase 3 x 15 4500 70 42 44 Severe 59 G306030/035

3 139 Glasroc F firecase 3 x 15 6000 92 44 45 Severe 60 G306031/036

4 193 Glasroc F firecase 3 x 15 6000 146 48 49 Severe 62 G306032/033

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

1
For a non-combustible solution on the shaft side use only the Glasroc F firecase. On the non-shaft side this can be replaced with a layer of 15mm Gyproc FireLine
or Gyproc DuraLine.
2
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
The acoustic performance figures quoted include ShaftWall partitions with deflection heads.
4
20mm Glasroc F firecase and first layer of lining board are bedded onto Gyproc Sealant, as required for pressurised air shafts, in addition to normal sealing.
5
Estimated rating from non-shaft side only.

The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled,
or skimmed according to Gyproc’s recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and
the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at the head. For the base Gypframe Folded Edge Standard
Floor & Ceiling Channel should be used for heights up to 4200mm, Gypframe Deep Flange Floor & Ceiling Channel should be used for heights between
4200mm and 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used for heights in excess of 8000mm.

C05. S02. P294 gyproc.ie


ShaftWall performance (continued)

ShaftWall
For details of when
to specify fire
Vertical elements — non-combustible board linings resistance using BS
Refer to C02. S01. P18
Table 2b — Solutions to satisfy requirements of BS 476: Part 22: 1987

1 2 3 4

Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud Gypframe 60, 70 or 92mm ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud
framework with 20mm Glasroc F firecase framework with 20mm Glasroc F firecase framework with 20mm Glasroc F firecase framework with 20mm Glasroc F firecase
between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe between studs, secured by Gypframe
Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm Retaining Channel. 25mm
Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional). Isover Acoustic Roll in cavity (optional).
Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see Lining boards to non-shaft side, see
table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres. table. Studs at 600mm centres.

Specialist partitions
Detail Partition Lining boards Max. Stud Sound insulation RwdB3 Duty Approx. System
thickness to non-shaft side1 partition size rating5 weight reference
mm Board type Lining height2 mm kg/m²
No insulation Sealed structure plus
thickness mm
25mm Isover Acoustic
mm Roll4

(60)/30 minutes fire resistance (exposure to fire from shaft side)

C05
1 77 Glasroc F firecase 1 x 15 4200 60 38 41 Heavy 32 G306001/010

1 87 Glasroc F firecase 1 x 15 4200 70 38 41 Heavy 32 G306001/010

1 109 Glasroc F firecase 1 x 15 6000 92 39 42 Heavy 33 G306004/011

2 163 Glasroc F firecase 1 x 15 7700 146 42 45 Heavy 35 G306007/013

(90)/60 minutes fire resistance (exposure to fire from shaft side)

1 92 Glasroc F firecase 2 x 15 4500 60 41 44 Severe 46 G306003/023

1 102 Glasroc F firecase 2 x 15 4500 70 41 44 Severe 46 G306003/023

1 124 Glasroc F firecase 2 x 15 6400 92 43 45 Severe 47 G306006/025

2 178 Glasroc F firecase 2 x 15 7900 146 47 49 Severe 49 G306009/028

(120)/90 minutes fire resistance (exposure to fire from shaft side)

3 92 Glasroc F firecase 2 x 15 4500 60 41 44 Severe 46 G306003/023

3 102 Glasroc F firecase 2 x 15 4500 70 41 44 Severe 46 G306003/023

3 124 Glasroc F firecase 2 x 15 6700 92 43 45 Severe 47 G306006/025

4 178 Glasroc F firecase 2 x 15 7900 146 47 49 Severe 49 G306009/028

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

1
For a non-combustible solution on the shaft side use only the Glasroc F firecase. On the non-shaft side this can be replaced with a layer of 15mm Gyproc FireLine
or Gyproc DuraLine.
2
Based on limiting deflection of L/240 at 200 Pa.
3
The acoustic performance figures quoted include ShaftWall partitions with deflection heads.
4
20mm Glasroc F firecase and first layer of lining board are bedded onto Gyproc Sealant, as required for pressurised air shafts, in addition to normal sealing.
5
Estimated rating from non-shaft side only.

The fire resistance and sound insulation performances are for imperforate partitions, but incorporating deflection heads, with all joints taped and filled,
or skimmed according to Gyproc’s recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and
the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at the head. For the base Gypframe Folded Edge Standard
Floor & Ceiling Channel should be used for heights up to 4200mm, Gypframe Deep Flange Floor & Ceiling Channel should be used for heights between
4200mm and 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used for heights in excess of 8000mm.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P295
ShaftWall performance (continued)
ShaftWall

Vertical elements
Table 3 — Limiting heights at various air pressure and allowable deflections

1 2 3 4 5 6 7

Gypframe 60 I 70 ‘I’ Gypframe 70 I 70 ‘I’ Gypframe 92 I 90 ‘I’ Gypframe 60 I 70 ‘I’ Gypframe 70 I 70 ‘I’ Gypframe 92 I 90 ‘I’ Gypframe 146 TI
Stud framework with Stud framework with Stud framework with Stud framework with Stud framework with Stud framework with 90 Tabbed ‘I’ Stud
one layer of 15mm one layer of 15mm one layer of 15mm two layers of 12.5mm two layers of 12.5mm two layers of 12.5mm framework with two
Gyproc FireLine1. Gyproc FireLine1. Gyproc FireLine1. Gyproc FireLine1. Gyproc FireLine1. Gyproc FireLine1. layers of 12.5mm
Gyproc FireLine1.
Specialist partitions

Detail System Allowable Limiting height (mm) at stated air pressure (Pa) System
deflection 200 240 300 360 400 480 500 600 650 reference

L/125 5000 4700 4400 4100 4000 3800 3700 3500 3400

1 ShaftWall L/240 4200 4000 3700 3500 3300 3200 3100 2900 2800 A306001/010

L/360 3700 3500 3300 3100 2900 2800 2700 2600 2500

L/125 5000 4700 4400 4100 4000 3800 3700 3500 3400
C05

Based on
2 ShaftWall L/240 4200 4000 3700 3500 3300 3200 3100 2900 2800
A306001/010
L/360 3700 3500 3300 3100 2900 2800 2700 2600 2500

L/125 7500 7100 6600 6200 6000 5700 5500 5200 5100

3 ShaftWall L/240 6000 5700 5300 5000 4800 4600 4400 4200 4100 A306004/011

L/360 5200 4900 4600 4300 4200 4000 3900 3600 3500

L/125 5200 4900 4600 4300 4200 4000 3800 3600 3500

4 ShaftWall L/240 4400 4100 3800 3600 3500 3300 3200 3000 2900 A306002/012

L/360 3800 3600 3300 3100 3000 2900 2800 2600 2500

L/125 5200 4900 4600 4300 4200 4000 3800 3600 3500
Based on
5 ShaftWall L/240 4400 4100 3800 3600 3500 3300 3200 3000 2900
A306002/012
L/360 3800 3600 3300 3100 3000 2900 2800 2600 2500

L/125 7900 7400 6900 6500 6300 5900 5800 5500 5300

6 ShaftWall L/240 6400 6000 5600 5200 5000 4800 4700 4400 4300 A306005/014

L/360 5600 5200 4900 4600 4400 4200 4100 3900 3800

L/125 9800 9200 8600 8100 7800 7300 7200 6800 6600

7 ShaftWall L/240 7900 7400 6900 6500 6200 6000 5800 5500 5300 A306008/020

L/360 6900 6500 6000 5600 5500 5200 5100 4800 4600

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

1
Gyproc FireLine can be replaced with Gyproc DuraLine or Glasroc F firecase.

C05. S02. P296 gyproc.ie


ShaftWall performance (continued)

ShaftWall
Vertical elements
Table 3 — Limiting heights at various air pressure and allowable deflections (continued)

8 9 10 11

Gypframe 60 I 70 ‘I’ Stud Gypframe 70 I 70 ‘I’ Stud Gypframe 92 I 90 ‘I’ Stud Gypframe 146 TI 90 Tabbed ‘I’ Stud
framework with two layers of framework with two layers of framework with two layers of framework with two layers of
15mm Gyproc FireLine1. 15mm Gyproc FireLine1. 15mm Gyproc FireLine1. 15mm Gyproc FireLine1.

Specialist partitions
Detail System Allowable Limiting height (mm) at stated air pressure (Pa) System
deflection 200 240 300 360 400 480 500 600 650 reference

L/125 5200 4900 4600 4300 4100 4000 3800 3600 3500

8 ShaftWall L/240 4500 4200 3900 3700 3500 3400 3300 3100 3000 A306003/023

L/360 3900 3700 3400 3200 3100 3000 2900 2700 2600

L/125 5200 4900 4600 4300 4100 4000 3800 3600 3500
Based on
9 ShaftWall L/240 4500 4200 3900 3700 3500 3400 3300 3100 3000

C05
A306003/023
L/360 3900 3700 3400 3200 3100 3000 2900 2700 2600

L/125 8400 7900 7300 6900 6600 6300 6200 5800 5600

10 ShaftWall L/240 6700 6300 5900 5500 5300 5100 5000 4700 4500 A306006/025

L/360 5600 5300 4900 4600 4500 4200 4100 3900 3800

L/125 9900 9300 8600 8100 7800 7400 7200 6800 6600

11 ShaftWall L/240 7900 7400 6900 6500 6300 6000 5800 5500 5300 A306009/028

L/360 6900 6500 6000 5700 5500 5200 5100 4800 4700

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

These tables give the limiting heights for ShaftWall systems when subjected to air pressures ranging from 200 Pa through to 650 Pa and at three allowable
deflection levels - L/125, L/240, L/360. Partition heights are normally quoted for air pressures of 200 Pa at an allowable deflection of L/240.

When the fire performance of ShaftWall is specified in terms of EN 1364-1: 1999, then the maximum height cannot exceed that given in the relevant table in
this book, irrespective of air pressure or allowable deflection.

1
Gyproc FireLine can be replaced with Gyproc DuraLine or Glasroc F firecase.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at the head. For the base Gypframe Folded Edge Standard
Floor & Ceiling Channel should be used for heights up to 4200mm, Gypframe Deep Flange Floor & Ceiling Channel should be used for heights between
4200mm and 8000mm, Gypframe Extra Deep Flange Floor & Ceiling Channel should be used for heights in excess of 8000mm.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P297
ShaftWall performance (continued)
ShaftWall

For details of when


to specify fire
Horizontal elements resistance using EN
Refer to C02. S01. P18
Table 4a – Solutions to satisfy the requirements of BS EN 1364-2: 1999

1 2 3

Gypframe 60, 70 or 92mm ‘I’ Stud or Gypframe Two Gypframe 146 TI 90 Tabbed ‘I’ Stud frames at Two Gypframe 146 TI 90 Tabbed ‘I’ Stud frames at
146 TI 90 Tabbed ‘I’ Stud frames at 600mm centres 600mm centres with Gyproc CoreBoard between 600mm centres with Gyproc CoreBoard between
Specialist partitions

with Gyproc CoreBoard between studs, secured by studs, secured by Gypframe Retaining Channel. 25mm studs, secured by Gypframe Retaining Channel. 25mm
Gypframe Retaining Channel. 25mm Isover Acoustic Isover Acoustic Roll in cavity (optional). On the lower Isover Acoustic Roll in cavity (optional). On the lower
Roll in cavity (optional). Gypframe MF5 Ceiling framework only, Gypframe MF5 Ceiling Sections fixed framework only, Gypframe MF5 Ceiling Sections fixed
Sections fixed to ceiling side at 450mm centres. Lining to ceiling side at 450mm centres. Lining boards to to ceiling side at 450mm centres. Lining boards to
boards to ceiling side, see table. ceiling side, see table. ceiling side, see table.

Detail Thickness Lining boards Max. Stud Sound insulation RwdB Approx. System
mm to non-shaft side span1 size weight reference
mm mm kg/m²
C05

Board type Lining No insulation Sealed structure plus


thickness 25mm Isover
mm Acoustic Roll

60 minutes fire resistance

1 120 Gyproc FireLine 2 x 15 2500 60 42 45 39 C106053

1 130 Gyproc FireLine 2 x 15 2800 70 42 45 39 C106053

1 152 Gyproc FireLine 2 x 15 3000 92 44 46 39 C106054

1 206 Gyproc FireLine 2 x 15 4400 146 48 50 39 C106055

90 minutes fire resistance

Gyproc FireLine upper frame 1 x 15


2 397 4400 146 48 50 77 C106057
Gyproc FireLine lower frame 2 x 15

120 minutes fire resistance

Gyproc FireLine upper frame 2 x 15


3 422 4000 146 48 50 88 C106056
Gyproc FireLine lower frame 2 x 15

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

1
Based on fire state field of application, or by a limiting deflection of L/400, whichever is greater.

The fire resistance and sound insulation performances are for imperforate ceilings incorporating boards, with all joints taped and filled,
or skimmed according to Gyproc’s recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and
the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc.

ShaftWall used horizontally should not be used for materials storage or access for personnel, or to provide support to services.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at perimeter.

C05. S02. P298 gyproc.ie


ShaftWall performance (continued)

ShaftWall
For details of when
to specify fire
Horizontal elements resistance using BS
Refer to C02. S01. P18
Table 4b – Solutions to satisfy requirements of BS 476: Part 22: 1987

1 2 3

Gypframe 60, 70 or 92mm ‘I’ Stud or Gypframe Two Gypframe 146 TI 90 Tabbed ‘I’ Stud frames at Two Gypframe 146 TI 90 Tabbed ‘I’ Stud frames at
146 TI 90 Tabbed ‘I’ Stud frames at 600mm centres 600mm centres with Gyproc CoreBoard between 600mm centres with Gyproc CoreBoard between

Specialist partitions
with Gyproc CoreBoard between studs, secured by studs, secured by Gypframe Retaining Channel. 25mm studs, secured by Gypframe Retaining Channel. 25mm
Gypframe Retaining Channel. 25mm Isover Acoustic Isover Acoustic Roll in cavity (optional). On the lower Isover Acoustic Roll in cavity (optional). On the lower
Roll in cavity (optional). Gypframe MF5 Ceiling framework only, Gypframe MF5 Ceiling Sections fixed framework only, Gypframe MF5 Ceiling Sections fixed
Sections fixed to ceiling side at 450mm centres. Lining to ceiling side at 450mm centres. Lining boards to to ceiling side at 450mm centres. Lining boards to
boards to ceiling side, see table. ceiling side, see table. ceiling side, see table.

Detail Thickness Lining boards Max. Stud Sound insulation RwdB Approx. System
mm to non-shaft side span1 size weight reference
mm mm kg/m²

C05
Board type Lining No insulation Sealed structure plus
thickness 25mm Isover
mm Acoustic Roll

60 minutes fire resistance

1 120 Gyproc FireLine 2 x 15 2500 60 42 45 39 C106053

1 130 Gyproc FireLine 2 x 15 2800 70 42 45 39 C106053

1 152 Gyproc FireLine 2 x 15 3700 92 44 46 39 C106054

1 206 Gyproc FireLine 2 x 15 5100 146 48 50 39 C106055

90 minutes fire resistance

Gyproc FireLine upper frame 1 x 15


2 397 5100 146 48 50 77 C106057
Gyproc FireLine lower frame 2 x 15

120 minutes fire resistance

Gyproc FireLine upper frame 2 x 15


3 422 5100 146 48 50 88 C106056
Gyproc FireLine lower frame 2 x 15

For further assistance in choosing the right solution for your project, try our System Selector; an online tool that enables quick and easy
filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to gyproc.ie

1
Based on a limiting deflection of L/400.

The fire resistance and sound insulation performances are for imperforate ceilings incorporating boards, with all joints taped and filled,
or skimmed according to Gyproc’s recommendations. The quoted performances are achieved only if Gyproc and Isover components are used throughout, and
the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with Gyproc.

ShaftWall used horizontally should not be used for materials storage or access for personnel, or to provide support to services.

Gypframe Extra Deep Flange Floor & Ceiling Channel or Gypframe ‘J’ Channel should be used at perimeter.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P299
ShaftWall design
ShaftWall

Building design Fixing the floor channel

ShaftWall comprises Gypframe 'I' Studs and Gypframe Starter The floor channel must have continuous support along its length
Channels within Gypframe Floor & Ceiling Channels. to maintain specified performance levels. If continuous support is
not provided by the structure, e.g. Z-sections running transverse to
The shaft-side boards are retained between the Gypframe Floor a steel beam, the designer should detail the installation of a rigid
& Ceiling Channels and adjacent studs using Gypframe Retaining non-combustible material between the Z-sections. Z-sections need
Channels; which enables construction from the side only. to be protected and remain in-situ in the event of a fire, taking into
account any loads they are supporting.
Planning – key factors
In situations where the floor channel is fixed to diagonal structural
The position of services should be pre-determined and their
steel, the studs should be accurately scribed to the rake of the
installation planned into the frame erection stage. Timber sole
channel to maintain the full bearing surface.
plates should be considered, if appropriate, where the floor is uneven.

Refer to C02. S01. P41 – Service installations. Fixing to metal decking

Where ShaftWall is to be located transverse to the profiles of the


Specialist partitions

decking, all slots or perforations above the head channel should


Important information be sealed using a proprietary fire barrier or fire spray. Fire-stopping
material can be applied prior to the head channel being positioned,
When exposed to fire from the corridor providing that any surplus is removed flush with the steel decking.
side in accordance with BS 476: Part
22, an insulation failure will occur. If Fixing to structural steel encasements
relaxation from Building Control is not
Where ShaftWall abuts a column or beam encasement, the framing
given and a full fire rating (insulation and
C05

will generally require fixing to the structural steelwork.


integrity) is required in both directions,
the following options are available:
Where ShaftWall abuts the web of the steelwork a Z-section can
— Use equivalent EN 1364-1 specification, be located to provide a fixing point level with the flanges of the
e.g. if 60 minutes BS 476: Part 22 steelwork. With FireCase encasements, where fire resistance up
performance is required, use a to 60 minutes and a Light or Medium Duty Rating to BS 5234 is
60 minutes EN 1364-1 specification required, it is possible to fix directly to the board cladding subject to
— Specify the next level of fire fire resistance and loading criteria.
performance from BS table, e.g. if Refer to C03. S02. P84 – FireCase construction details.
60 minutes BS 476: Part 22 performance
is required, use a 90 minute
BS 476: Part 22 specification1
Handy hint
Where the floor channel is not fully
It is important that a good standard of control is exercised on site
supported, e.g. at the edge of a floor slab,
to ensure that the adoption of drylining techniques at such an
Gypframe Extra Deep Flange Floor & Ceiling
early stage of construction is fully integrated into the site planning
Channel or Gypframe 'J' Channel must be
programme. If the building envelope is left unsealed while
used with a continuous 19mm
ShaftWall is under construction, Gyproc FireLine mr, Gyproc DuraLine
Gyproc CoreBoard fire stop inserted into
mr or Glasroc F firecase should be used for the lining. All penetrations
the base of the channel. The maximum
will need to be adequately fire-stopped.
allowable overhang is 25% of the floor
channel width.

Important information
Limiting heights at different air pressures
For ShaftWall systems utilising Gypframe
The maximum heights quoted in the performance tables for vertical
60 I 70 'I' Studs, Gypframe 62 JC 70 'J'
elements are based on a limiting deflection of L/240 at 200 Pa, or by
Channel with its asymmetrical legs is
the fire state field of application. In practice, deflection from L/125
needed at the head to facilitate the
to L/360 may be allowed and pressure conditions between 200 Pa
installation of the Gyproc CoreBoard. The
and 650 Pa may be encountered. These variations will affect the
shorter leg is installed facing the non-
maximum wall height. Refer to table 3.
shaft side. For ShaftWall systems that use
wider Gypframe 'I' studs, the appropriate
Gypframe Extra Deep Flange Floor and
Ceiling Channel should be used.

Where 120 mins is required to BS 476: Part 22, replace the inner layer of 15mm Gyproc FireLine (corridor side) with 19mm Gyproc CoreBoard, fixed horizontally.
1

C05. S02. P300 gyproc.ie


ShaftWall design (continued)

ShaftWall
Connection to the structure Deflection heads

Structural steelwork and its associated connections often result in Deflection heads, by definition, must be able to move and,
complex junctions around shafts. If ShaftWall is built on the same therefore, achieving an airtight seal is difficult. Inevitably, this will
line as the beamwork framing the shaft, problems may arise in have a detrimental effect on the acoustic performance of any wall
trying to seal the wall up to the steelwork. It is recommended that, that incorporates deflection at the head. In most cases, a suspended
wherever possible, the wall should be located to one side of the ceiling will assist in minimising loss of performance.
beams, and fixed from structural floor to structural soffit.
Refer to construction details 11-17 for standard head details.

Partition to structural steelwork junctions


Gyproc FireStrip must be applied as a continuous seal where
When designing the layout of rooms requiring separation by sound indicated to maintain fire performance. Also, board fixings must
insulating walls abutting structural steelwork, consideration should not be inserted above the uppermost line depicted by the red arrow
be given to the potential loss of sound insulation performance in each drawing. Designs incorporating Gypframe Retaining Clips
through the steelwork. are not suitable for live loads. Where greater deflection needs to
be accommodated, contact the Gyproc Technical Department for
Refer to C02. S01. P21 – Building acoustics.
further guidance.

Specialist partitions
Door openings
Deflection criteria
In the case of both normal access doors and lift doors, the door and
Partitions built to a maximum height based on L/125 at 200 Pa
frame assembly must have been shown by a fire resistance test
will exhibit greater deflection compared to partitions built to
to achieve the required standard of performance in this form of
a maximum height based on L/240 at 200 Pa. Partitions with
construction.
deflection characteristics outside the standard L/240 criteria
will exhibit more flex during installation and in general use,
Lift doors must be substantiated in conjunction with ShaftWall

C05
and therefore we recommend you verify the acceptability of the
complete with their framing members and transom panels. To
deflections with the relevant interested parties before specifying /
achieve a satisfactory level of compatibility, a suitable starter
installing partitions based on L/125 criteria.
channel should be mechanically fixed to the door frame at 300mm
centres.
Services
Refer to construction details 23-25 within this section.
Penetrations
Penetrations of fire-resistant constructions for services should be
Pressurised airshafts and service ducts
minimised, however if essential, careful consideration should be
The use of pressure conditions in various types of shaft / duct given to ensure that the integrity of the element is not impaired,
requires that the boards should be sealed into the framing and that the services themselves do not act as the mechanism of
members using Gyproc Sealant in addition to the normal sealing of fire spread.
the framing to adjoining structures. It is essential that these areas
Refer to C02. S01. P41 – Service installations.
are identified at a very early stage of the contract, and that other
trades are instructed to recognise the need for the application of
Independent support
sealant and its replacement if subsequently damaged or removed.
When designing for the installation of services such as fire dampers
In order that the integrity of the pressurised system can be
and associated ductwork through ShaftWall, consideration should
maintained, Gyproc Sealant should be specified for all
be given to the size and weight of the damper – this will determine
board-to-metal applications, and the sealing of Gyproc CoreBoard
whether it can be supported directly from the partition or needs to
(or Glasroc F firecase) to the framing.
be independently supported from the structure.
Refer to construction details 17-20 within this section.
Refer to C04. S01. P122 – Partitions introduction, construction
details 29-31.
Control joints

Control joints may need to be considered in conditions where Openings bridging studs
excessive movement is likely to occur, or to coincide with Openings should be constructed using channels for the trimming
constructional expansion joints. In order that the deflection criteria members. The web of the channel should be rebated to allow
can be maintained throughout the building, it is necessary to the flanges to oversail the stud. The flanges are secured with two
introduce horizontal movement joints in the lining where this fixings. Channels are cut and inserted to maintain the 25mm gap
would normally be required to extend through the height of the surround and fixed to the trimming channels.
building, e.g. stairwells.
Refer to construction detail 21 within this section.

The horizontal movement joint can be accommodated adjacent


to the floor slab.

Refer to construction detail 28 within this section.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P301
ShaftWall design (continued)
ShaftWall

Access for maintenance

Important information For access doors, openings should be framed to avoid impairing
the structural or fire-resistant properties of ShaftWall. To provide
The quoted sound insulation an opening ready to receive a door set, the jambs to storey height
performances of ShaftWall, detailed should be capped with Gypframe ‘J’ Channel incorporating a
in the preceeding performance tables, plasterboard packer. A pre-formed spandrel panel assembled
incorporate a deflection head as part between starter channels should be inserted between jambs
of the tested construction. Therefore, and engaged into the head channel, retaining the 15mm gap for
this effectively downgrades the sound deflection at the head.
insulation performance of the system. Refer to construction detail 23 within this section.
To minimise the loss, install Gypframe
GA4 Steel Angle at the head, which Support is provided by a Gypframe ‘J’ Channel transom. The door
will improve the performance by frame is secured to both Gypframe ‘I’ Stud and Gypframe ‘J’ Channel
approximately 2-3dB, refer to jambs and also to the transom member.
C02. S01. P21 – Building acoustics.
Refer to construction detail 25 within this section.
Specialist partitions

Further sound insulation improvement


can be achieved by substituting Gyproc
A range of Gyproc Profilex Access Panels providing fire integrity
DuraLine in lieu of Gyproc FireLine,
is available. Please contact the Gyproc Technical Department for
providing 1-2dB improvement. The
further information:
installation of a Gypframe RB1 Resilient
ROI: 1800 744480
Bar may further improve performance,
NI: 0845 3990159
contact the Gyproc Technical Department
Email: tech.ie@saint-gobain.com
for further information.
C05

Board finishing

Openings between studs Refer to C08. S01. P517 – Finishes.


The opening is constructed using channels for the trimming
members. The web should be rebated and the flanges allowed to Tiling
oversail the studs. The stud is secured with two fixings. Channels Tiles can be applied to the surface of lightweight partition systems.
are cut and inserted with the webs folded to provide fixings. A
Refer to C08. S04. P531 – Tiling.
plasterboard packer is inserted adjacent to the stud.

Refer to construction detail 22 within this section.


Horizontal ShaftWall

Electrical services ShaftWall can be specified for horizontal applications as a


The installation of electrical services should be carried out in free-spanning membrane with no support from the soffit. The
accordance with BS 7671. The positions for light switches and other membrane can be constructed entirely from below and can achieve
electrical outlets should be pre-determined in order that provision spans up to 5100mm and fire resistance up to 120 minutes. A
can be made for support, and also for the fire integrity of the typical application is for fire escape corridors. Services should be
system. independently supported from the building structure.

Gypframe 99 FC 50 Fixing Channel should be cut to bridge adjoining Supporting partitions should be of at least the same fire resistance
studs, with the edges flattened to permit fixing. The fixing channel period as the horizontal ShaftWall.
should be backed with stone mineral wool. Gyproc FireLine (or
Glasroc F firecase) linings should be cut to allow a close fitting entry
of the switch box which can be secured to the fixing channel.

Refer to construction detail 7 within this section.


SpecSure®
All our systems are covered by SpecSure®
when using genuine Gyproc and Isover
products.

C05. S02. P302 gyproc.ie


ShaftWall construction details

ShaftWall
2
1 2

2 5

6
8

7
1
11

Specialist partitions
Base Junction with other elements

3 4
2

C05
4 2

8 4

10
1

Junction with other elements (framework showing


Gypframe Tabbed Starter Channel) Intermediate stud

5 6
3
9

2 2

4 4

Intermediate stud (framework showing Gypframe Tabbed 'I' Stud) Partition junction (on-stud)

1 Gyproc FireLine1 7 Gyproc Sealant


2 Gyproc CoreBoard2 8 Structure
3 Gypframe 'I' Stud 9 Gypframe Tabbed 'I' Stud
4 Gypframe Retaining Channel 10 Gypframe Tabbed Starter Channel
5 Gypframe Starter Channel 11 Bulk fill with Gyproc jointing materials (where gap exceeds 5mm)
6 Gypframe Folded Edge Standard Floor & Ceiling Channel

1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings.
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P303
ShaftWall construction details (continued)
ShaftWall

7 8

3
10
4
2
2

4 8

1 7
6
9
1
Specialist partitions

Horizontal Gyproc CoreBoard joints

5
10
C05

4
1
2

Socket box Internal corner

10

2
1
5

10
4

External corner

1 Gyproc FireLine1 6 Gyproc Sealant


2 Gyproc CoreBoard2 7 Gypframe GA3 Steel Angle
3 Gypframe 'I' Stud 8 Gyproc CoreBoard strip (cut on site)2
4 Gypframe Retaining Channel 9 Gypframe 99 FC 50 Fixing Channel
5 Gypframe Starter Channel 10 Stone mineral wool (100kg/m3 - by others)

1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings.
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings.

C05. S02. P304 gyproc.ie


ShaftWall construction details (continued)

ShaftWall
Head details incorporating 15mm downward deflection

11 12

7 7

8 8
15mm 15mm 9
15mm
15mm
5 6
10 15mm

20mm 10
20mm 15mm
3

3
2

Specialist partitions
1
4
4
1
2

C05
60mm framework (live loads)3 70mm framework (live loads)

13 14

7
7
8
15mm
8
9
15mm
15mm 9
6 15mm
15mm 6
15mm
20mm 10
20mm 2
3
10

2
4
4
1
1
11

92mm framework (live loads) 146mm framework (live loads)

1 Gyproc FireLine1 7 Gyproc Sealant


2 Gyproc CoreBoard2 8 Gyproc FireStrip
3 Gypframe 'I' Stud 9 Gyproc CoreBoard2
4 Gypframe Retaining Channel 10 Gyproc CoreBoard fire-stop2
5 Gypframe 'J' Channel 11 Gypframe Tabbed 'I' Stud
6 Gypframe Extra Deep Flange Floor & Ceiling Channel

1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings. 3
Vertical fire-stops are not recommended for non-combustible linings, use
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings. horizontal fire-stops similar to detail 12.

No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P305
ShaftWall construction details (continued)
ShaftWall

Head details with Retaining Clips

15 16
12 12
8 8
9 9

13 14
3 3

4 4
2 2

1 1
Specialist partitions

Head incorporating Gypframe G108 Retaining Clip (92mm) Head incorporating Gypframe G109 Retaining Clip (146mm)

Sealing pressurised air shafts and service ducts

17 8 18
10
3
7
C05

9 2
2 4

1
4

Head (sealed structure). Example shows 60mm stud3 Intermediate stud (sealed structure)

19 20 2

4
7
2 5

1
4
7

6 11

7 1
Base (sealed structure) Junction with other elements (sealed structure)

1 Gyproc FireLine1 8 Gyproc FireStrip


2 Gyproc CoreBoard2 9 Gyproc CoreBoard fire-stop (cut on site)2
3 Gypframe 'I' Stud 10 Gypframe 'J' Channel
4 Gypframe Retaining Channel 11 Structure
5 Gypframe Starter Channel 12 Gypframe Extra Deep Flange Floor & Ceiling Channel
6 Gypframe Folded Edge Standard Floor & Ceiling Channel 13 Gypframe G108 Retaining Clip
7 Gyproc Sealant 14 Gypframe G109 Retaining Clip
1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings.
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings.
3
Use alternative deflection head detail for systems with non-combustible linings.

C05. S02. P306 gyproc.ie


ShaftWall construction details (continued)

ShaftWall
21
Section W-W

W
6

X X

Specialist partitions
W

5
Section X-X
3
4

C05
1
2

Opening bridging studs. Example shows 60mm stud

22

Section Y-Y

7
Y

Z Z
3
2

Section Z-Z

1
7

Opening between studs. Example shows 60mm stud

1 Gyproc FireLine 5 Gypframe 'J' Channel


2 Gyproc CoreBoard 6 Gyproc CoreBoard fire-stops (cut on site)
3 Gypframe 'I' Studs 7 Access panel frame (by others)
4 Gypframe Retaining Channel

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P307
ShaftWall construction details (continued)
ShaftWall

23 24

6
7
3

2
2
4
8 4

1
1
5
5
Specialist partitions

Access door - spandrel panel Lift door (Gypframe Starter Channel mechanically fixed to frame)

25

2
6
C05

3
9
8

4
1

Access door jamb

1 Gyproc FireLine1 6 Gypframe 'J' Channel


2 Gyproc CoreBoard2 7 Gyproc Sealant
3 Gypframe 'I' Stud 8 Gyproc CoreBoard packer (cut on site)2
4 Gypframe Retaining Channel 9 Door frame
5 Gypframe Starter Channel

1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings.
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings.

C05. S02. P308 gyproc.ie


ShaftWall construction details (continued)

ShaftWall
26
16
2
3

15

Specialist partitions
Retro-fit non-performance partition junction

Connection to the structure

27 28

C05
2
4
5

15
12

14 9

9
15
6
10
7
13
2 11
7
4
1

Fixing head channel to Z-section at underside of beams3 Control joint at floor slab junction where lining boards continue

1 Gyproc FireLine1 9 Gyproc FireStrip


2 Gyproc CoreBoard2 10 Gyproc Edge Bead - if no cover strip is used
3 Gypframe 'I' Stud 11 Cover strip (by others)
4 Gypframe Retaining Channel 12 Structure
5 Gypframe Floor & Ceiling Channel 13 Glasroc F firecase
6 Gypframe 'J' Channel 14 Z-section (by others)
7 Gyproc CoreBoard fire-stops2 15 Gyproc Sealant
8 Beam encasement 16 Suitable metal self-drive fixing (by others)

1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings. 3
Use alternative deflection head detail for systems with non-combustible
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings. linings.

No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P309
ShaftWall construction details (continued)
ShaftWall

29 30

9 2
10 1
15 12

11 4

15
8
10
Specialist partitions

7
11
5
13
6
14
2
4
3 7
1
C05

Column encasement and partition junction for partitions up to


Beam encasement and partition junction for partitions to satisfy 120 minutes fire resistance and BS 5234 Parts 1 & 2: 1992
BS 5234: Parts 1 & 2: 1992 Heavy and Severe Duty Rating Heavy and Severe Duty Rating

1 Gyproc FireLine1 10 Glasroc F firecase


2 Gyproc CoreBoard2 11 Structural steel
3 Gypframe 'I' Stud 12 Gypframe Starter Channel suitably fixed through Glasroc F firecase to
column at 600mm centres (in two lines staggered by 300mm for studs
4 Gypframe Retaining Channel
wider than 75mm)
5 Gypframe 'J' Channel suitably fixed through encasement to structure
13 Suitable size Z-section (by others) fixed between column flanges at
6 Gyproc CoreBoard fire-stops2 600mm centres
7 Gyproc Sealant 14 Gypframe Starter Channel suitably fixed through Glasroc F firecase
8 Gyproc FireStrip to Z-sections (in two lines staggered by 300mm for studs wider
than 75mm).
9 Gypframe GA1 Steel Angle
15 Isover insulation if required to minimise acoustic downgrade

1
Replace with 15mm Glasroc F firecase for systems with non-combustible linings.
2
Replace with 20mm Glasroc F firecase for systems with non-combustible linings.

No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing.

C05. S02. P310 gyproc.ie


ShaftWall construction details (continued)

ShaftWall
31

400mm

Specialist partitions
3
10mm

C05
160mm
200mm

56 / 66 / 88mm

Fixing zone
20mm
10mm

20mm
Overlap of studs
200mm

160mm

3
400mm

60 / 70 / 92mm

60 / 70 / 92mm 'I' Stud splicing detail

1 Gyproc CoreBoard 3 Gyproc Wafer Head Jack-Point Screw


2 Gypframe 'I' Stud 4 14mm dia. pre-drilled hole in Gypframe Retaining Channel to coincide
and clear screws connecting overlap of 'I' Studs

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P311
ShaftWall construction details (continued)
ShaftWall

32

50mm

2
1
Specialist partitions

4 4
C05

50mm

1000mm
50mm

3
50mm

1
50mm

3
50mm

146mm 'I' Stud splicing detail

1 Gyproc CoreBoard 3 Gyproc Wafer Head Jack-Point Screw


2 Gypframe 'I' Stud 4 Gypframe G105 Retaining Channel

C05. S02. P312 gyproc.ie


ShaftWall construction details (continued)

ShaftWall
Horizontal ShaftWall (ShaftWall used horizontally should not be used for material storage or access for personnel)

33 34

10 11 9 4 2 4 2

Specialist partitions
1 7 3 9 8 5 1 3 7

C05
Gyproc CoreBoard joint Perimeter detail 1

35

2 4

9 8 6 1 7 3

Perimeter detail 2

1 Gyproc FireLine 6 Gypframe Starter Channel


2 Gyproc CoreBoard 7 Gypframe MF5 Ceiling Section
3 Gypframe 'I' Stud 8 Gypframe MF6 Perimeter Channel
4 Gypframe Retaining Channel 9 Gyproc Sealant
5 Gypframe Extra Deep Flange Floor & Ceiling Channel 10 Gypframe GA3 Steel Angle
or Gypframe 'J' Channel
11 122mm wide strip of 19mm Gyproc CoreBoard

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P313
ShaftWall construction details (continued)
ShaftWall

Horizontal ShaftWall (ShaftWall used horizontally should not be used for material storage or access for personnel)

36

1 8 7 6 3 2 4 5
Specialist partitions
C05

Reflected ceiling

1 Gyproc FireLine 5 Gypframe Starter Channel


2 Gyproc CoreBoard 6 Gypframe MF5 Ceiling Section
3 Gypframe 'I' Stud 7 Gypframe MF6 Perimeter Channel
4 Gypframe Extra Deep Flange Floor & Ceiling Channel 8 Isover Acoustic Insulation
or Gypframe 'J' Channel

C05. S02. P314 gyproc.ie


ShaftWall system components

ShaftWall
Gypframe metal components

Gypframe ‘I’ Studs (60 I 70, 70 I 70, 92 I 90, Gypframe Retaining Channel (G102, G105, G110)
146 TI 90 Tabbed) Insert channel to provide support for the
Enhanced strength stud that allows for partition Gyproc CoreBoard located within the Gypframe ‘I’
height, without increasing partition width. Designed stud. G102 for 60 I 70 and 146 TI 90 'I' Studs.
G105 for 92 I 90 'I' Studs.
to receive fixing of board to one side (face fixed) and
G110 for 70 I 70 'I' Studs.
to accommodate Gyproc CoreBoard within its flange.

Gypframe Folded Edge Standard Floor & Ceiling Gypframe Retaining Clips (G108, G109)
Channels (62 FEC 50, 72 FEC 50, 94 FEC 50, 148 FEC 50) Used within Gypframe ‘I’ studs at deflection heads.
Standard floor channels for retaining the Gypframe G108 for 92 I 90 'I' Studs.
studs at floor junctions for heights not exceeding G109 for 146 TI 90 'I' Studs.
4200mm.

Specialist partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GA3 Steel Angle
(62 DC 60, 72 DC 60, 94 DC 60, 148 DC 60) Steel angle providing framing stability and
Floor and ceiling channels with deep flanges for board support. Used at horizontal joints of
retaining the Gypframe studs at floor and ceiling Gyproc CoreBoard.
junctions for partitions 4200mm to 8000mm high.
Also used around openings and in deflection heads
(maximum 30mm deflection). Also accommodates Gypframe 99 FC 50 Fixing Channel

C05
Gypframe Retaining Clips / Channels and where A versatile metal fixing channel used to support
applicable used around the perimeter in horizontal medium weight fixtures on walls.
applications.

Gypframe ‘J’ Channel (62 JC 70) Gypframe GFS1 Fixing Strap


Channels with uneven flanges for retaining the Used to support horizontal board joints.
Gypframe studs at ceiling junctions. Also used
around openings and in deflection heads.

Gypframe Extra Deep Flange Floor & Ceiling Gypframe GFT1 Fixing T
Channels (72 EDC 80, 94 EDC 70, 148 EDC 80) Used to support horizontal board joints.
Floor and ceiling channels with extra deep flanges
for retaining the Gypframe studs at floor and ceiling
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum Gypframe Service Support Plate
50mm deflection). Also accommodates Gypframe For installation of 18mm plywood within
Retaining Clips / Channels and where applicable used a partition cavity to support medium to
around the perimeter in horizontal applications. heavyweight fixtures.

Gypframe Starter Channels (60 SC 50 at 3600mm, Gypframe MF5 Ceiling Section


70 SC 70 at 36000mm or 4200mm, 92 SC 90 at Secondary section to support fixing of board.
5000mm or 6000mm)
Vertical stud used at abutments and openings to
receive fixing of board.

Gypframe Tabbed Starter Channel (146 TSC 90) Gypframe MF6 Perimeter Channel
Vertical stud used at abutments and openings to Perimeter section to support Gypframe MF5 Ceiling
receive fixing of board. Section and fixing of board.

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P315
ShaftWall system components (continued)
ShaftWall

Board products

Gyproc FireLine2 Gyproc DuraLine2


Gypsum plasterboard with fire resistant additives. Gypsum plasterboard with fire resistant additives
and a high density core for enhanced sound
insulation and impact resistance performance.

Gyproc CoreBoard Glasroc F firecase 1


Gypsum plasterboard with fire and moisture Non-combustible glass-reinforced gypsum board.
resistant additives. Retained within studs and to Also used to form deflection head.
form deflection head.

1
Glasroc F firecase boards used to replace Gyproc CoreBoard on the shaft side of the system must be cut to 598mm wide (+0mm / -3mm).
2
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
Specialist partitions

Fixing products

Gyproc Drywall Screws Gyproc Jack-Point Screws


Corrosion resistant self-tapping steel screws for Corrosion resistant self-tapping steel screws
fixing board-to-timber and board-to-metal framing for fixing board to metal framing 0.8mm thick and
C05

less than 0.8mm thick (‘I’ Studs less than 0.6mm greater (‘I’ Studs 0.6mm thick and greater).
thick).

Gyproc Collated Drywall Screws Gyproc Wafer Head Jack-Point Screws


Corrosion resistant self-tapping steel screws for Corrosion resistant self-tapping steel screws
fixing board-to-timber and board-to-metal framing for fixing metal to metal framing 0.8mm thick and
less than 0.8mm thick (‘I’ Studs less than 0.6mm greater ('I' Studs 0.6mm thick and greater).
thick).

Gyproc Wafer Head Drywall Screws


Corrosion resistant self-tapping steel screws
for fixing metal to metal framing less than
0.8mm thick ('I' Studs less than 0.6mm thick).

Plasterboard accessories

Gyproc Jointing Materials Gyproc edge and angle beads


Jointing compounds, ready mixes and adhesives for Protecting and enhancing board edges and corners.
reinforcement and finishing of board joints.

Gyproc FireStrip Gyproc Sealant


A soft extruded linear intumescent gap sealer Used to seal air paths for optimum sound
to maintain fire resistance located directly to insulation.
the underside of the soffit when forming a
deflection head.

Gyproc Corner Tape Gyproc Paper Joint Tape


A paper tape bonded to two corrosion resistant A paper tape designed for reinforcement of flat
steel strips. joints or internal angles.

Gyproc Drywall Primer Gyproc Drywall Sealer


Used to prepare for painting. Used to provide vapour control.
Tub contents 10 litre. Tub contents 10 litre.

C05. S02. P316 gyproc.ie


ShaftWall system components (continued)

ShaftWall
Finishing products

Gyproc Skimcoat Gyproc Carlite Finish


To provide a plaster skim finish on most common To provide a plaster skim finish on most common
backgrounds including undercoat plasters and backgrounds including undercoat plasters and
plasterboard. plasterboard.

Gyproc Carlite Ultra Finish Plaster accessories


Offers all the benefits of Gyproc Skimcoat and Designed for the reinforcement and finishing of
Gyproc Carlite Finish with a reduced set time of 90- board joints before plaster skimming.
120mins, making it ideal for smaller jobs.

Insulation products

Specialist partitions
Isover Acoustic Roll
Glass mineral wool for enhanced acoustic and
thermal performance.

C05

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P317
ShaftWall installation overview
ShaftWall

This is intended to be a basic description of how the system is built.


For detailed installation guidance refer to the Gyproc Installation Guide.

The appropriate Gypframe channels, are Gypframe Starter Channels are suitably Gypframe ‘I’ Studs or Gypframe Tabbed 'I'
suitably fixed to the floor and soffit of the fixed to vertical abutments. The perimeter Studs are friction fitted into the channels at
structure. Gyproc FireStrip is used on the of the partition is sealed with 600mm required centres. Gyproc CoreBoard
Specialist partitions

channel at the soffit. Gyproc Sealant. or 20mm Glasroc F firecase is fitted between
the studs on the shaft side, and held in
place with appropriate Gypframe Retaining
Channels. Door openings are formed to the
ShaftWall Access Door Details.
C05

Gyproc Sealant

Gypframe GA3
Steel Angle

Pressurised shafts and service ducts are Horizontal board joints are fire stopped Isover Acoustic Roll can be added to the
sealed using Gyproc Sealant. This is applied using Gypframe GA3 Angle and strips of partition cavity for increased acoustic
to all board-to-metal junctions. Gyproc CoreBoard from the non-shaft side. performance.

Gyproc plasterboard or Glasroc F firecase


are then fixed to the Gypframe framework
with Gyproc Drywall Screws or Gyproc Jack-
Point Screws.

Additional information
For full installation details, refer to the
Gyproc Installation Guide, available to
download from gyproc.ie

C05. S02. P318 gyproc.ie


ShaftWall
Specialist partitions
C05

ROI: 1800 744480 NI: 0845 3990159 tech.ie@saint-gobain.com C05. S02. P319