CVM CH-8

1.1.- Simple or compound voltages


- Simple voltages (between phase and neutral): U1, U2, U3 1.9.- Returning the energy counters to zero.
CVM CH-8 POWER ANALYZER - Compound voltages (phase and phase): U12, U23, U31
"CLr ENER no" or Yes (Clear energy counters) appears
1.2.- Voltage transformer primary. on the display.
On screen the words "SET VOLT PRI" appear followed by 6 1.10.- Setting THD or D
digits. These allow the voltage transformer primary to be set.
Two types of Harmonic Distortion can be set ("SET
(from 1 to 100,000)
HAR d"):
1.3.- Voltage transformer secondary. - D %: value harmonic distortion with respect to the
fundamental
On screen the words "SET VOLT SEC" appear followed
- Thd %: value harmonic distortion with reference to
by 3 digits. These allow the voltage transformer secondary
the effective value (RMS).
to be set. (from 1 to 999)

1.4.- Current transformer primary. 1.11.- Additional screen with transistor alarm
On the screen "SET CURR PRI" appears with 5 digits. This outputs
allows the current transformer primary to be set. (from 1 to
(“OUT VAR CODE”) With these outputs the CVM CH8
10,000)
relay may be set for:
1.5.- Setting the Power Demand Meter screens. A. Pulse every x kW.h or kvar.h (Energy). The
value of consumed energy may be set so that
The CVM CH-8 is an instrument that measures, a) PARAMETER TO CONTROL: ("SET Pd Code xx") it generates a pulse (lasting 0.1 secs.) kW.h /
calculates and displays the main electrical parameters in 1 pulse or kvar.h / 1 pulse. Maximum 5
three phase industrial systems (balanced or unbalanced). None 00 imp/sec.
Measurements are in true effective value, via three AC Three phase active power kW III 16
voltage inputs and three AC current inputs. (via In / 5 A B. ALARM conditions: the variable to be
Three phase apparent power kVA III 34
current transformers). The parameters measured are controlled is set for each output per transistor,
Three phase current AIII 36
shown in the variables list table. i.e. the maximum value, minimum value and
Current per phase A1-A2-A3 A-PH the "delay".
Value of power integrated during set period. Note: The list of variables appears in the table
This manual is a quick guide to the use and operation of
the CVM CH-8. For more information, the whole manual b) INTEGRATION PERIOD (from1 to 60 minutes): ("SET below.
may be downloaded from Circutor's web page: Pd Per xx") 2.- Second CVM CH-8 SET UP
www.circutor.es c) CLEAR MAXIMUM VALUE STORED IN MEMORY:
Before starting any maintenance, change ("CLr Pd no”) no or YES To access the menu where the equipment's
in connections, repair, etc, it must be communication may be changed:
disconnected from all power sources. 1.6.- Setting preferred page.
Press the " ", "max" and "min" key at the same time
When an operating fault or protection fault This option allows the fixed or rotating pages ("SET to supply voltage to CVM CH8 or RESET the
is suspected, the equipment must be taken out of def Page”): equipment.
service. The equipment is designed to be quickly a) Fixed page: selects the page, from all possible
replaced in the event of any breakdown.
Configurable parameters:
pages, that will appear first when applying voltage - n PER : Peripheral no. 001 to 255
to the CH8 (or on resetting). - Baud 1: (speed) 1200 - 2400 - 4800 - 9600 - 19200
1.- SETTING (SETUP menu) b) Rotating pages: automatically rotates the 10 - Parity: No, even, odd
pages (every 5 seconds it moves on to the - LEN: (length) 8 bits
(press the MAX and MIN keys at the same time once in following screen). - Stop bits: 1 or 2
the main program) Default configuration: 001 / 9,600 / 8 / N /1
 The key validates the information and moves on 1.7.- Setting energy display
to the next menu. On screen the words " SET def Page Ener " appear. Block or unblock SETUP
 The MAX key allows the different options in a menu These allow the way of display the energies: - If the LOC option is selected, it is only possible to
to be selected or increases a digit where a variable is kW.h, kvarL.h, kvarC.h, kva.h see the setting on entering SETUP and nothing
being entered. may be changed.
 The MIN key is used to move the cursor among the 1.8.- Setting disconnection time for the - If a previously set option is to be changed, then it is
digits. “backlight” necessary to enter a password. PASSWORD for
The different options are sequentially described below: ("SET disp off”): Setting the time after which the light the CVM CH-8: 1234
on the CVM CH8's display switches off (low consumption)
after a key is pressed. If 00 is set, the
backlight is permanently on.

 List of variables and alarm codes for the CVM CH-8 Parameter Symbol Code Parameter Symbol Code
 If no variable is required enter No. par.= 00. Simple voltages V1 or V2 or V3 90 Power factors PF1 or PF2 or PF3 94
Currents I1 or I2 or I3 91 Compound V12 or V23 or V31 95
Parameter Symbol L1 Code L2 Code L3 Code voltages
Simple Voltage V 01 06 11 Active powers KW1 or KW2 or 92 % THD V THDV1 or V2 or V3 96
KW3
Current A 02 07 12
Reactive powers kvar1 or 2 or 3 93 % THD I THDI1 or I2 or I3 97
Active power kW 03 08 13
Reactive power kvar 04 09 14
*(inductive / capacitive)
Power factor PF 05 10 15
 FOUR QUADRANTS OF THE CVM CH-8
% THD V THD V 25 26 27
% THD A THD A 28 29 30

Parameter Symbol Code Parameter Symbol Code


Three phase active power kW III 16 Neutral Current IN 37
3 pha. inductive power kvarL III 17 Max demand (L1) Md (Pd) 35*
3 pha capacitve power kvarC III 18 Max demand (L2) Md (Pd) 42*
cos ϕ three phase cos ϕ 19 Max demand (L3) Md (Pd) 43*
3 pha. power factor PF III 20 Active energy kW.h 31
Frequency (L1) Hz 21 Induct reactive energy. Kvar.h L 32
V comp. L1- L2 V 12 22 Capacit reactive energy Kvar.h C 33
V comp. L2 - L3 V 23 23 App. three pha. energy. Kva.h III 44
V comp. L3 - L1 V 31 24 Active energy generated kW.h III - 45
Apparent power kVA III 34 Inductive enr. generated KvarhLIII - 46
Maximum demand Md (Pd) 35 Capacit. ener. generated KvarhCIII - 47
Three phase current AIII 36 Apparent ener. generated KvahIII - 48
*Variables valid only if the maximum demand of current per phase has been set.

There are also some variables that refer to the three phases at the same time. If
one of these variables is chosen, the alarm will activate when any of the three
phases match the set conditions.

M069A01-03-15A
CVM CH-8

3.- CVM CH-8 COMMUNICATIONS


One or more CVM CH-8's can be connected to a computer or PLC. As well as the RS-232 / RS-485
CONVERTER
usual operation of each piece of equipment, data may also be centralised at one
single point by using this system (Power Studio System). The CVM CH-8 has an
RS-485 series communications output. If more than one unit is connected to one
RS-485 series line, it is necessary to assign a number or address to each (from 01
to 255) so that the central computer sends data to those addresses.

To change the setting for the communications see section 2.

The RS-485 connection is made with woven mesh shielded communications


cables, with a minimum of three wires and with a maximum distance between PC
and the last analyzer of 1,200 metres. The CVM CH-8 uses an RS-485 CVM CH-8
communications line which can be connected to a maximum of 32 analyzers in
parallel (multi-point Bus) for each series port on the computer used.

The CVM CH-8 system analyzer communicates using the MODBUS RTU ©
protocol (Question/ Answer).

4.- TECHNICAL FEATURES


Power supply: a.c. .Model : Measurement circuit:
- Single phase: 230 V a.c. - Nominal voltage phase-neutral : 300 V AC.
- Voltage tolerance: -15 % / +10 % between phases : 520 V AC.
- Frequency: 50 - 60 Hz - Frequency : 45 ~ 65 Hz
- Max. consumption (with communications): 4,2 VA - Nominal current : In / 5 A
- Max. consumption (without communications): 4 VA
- Permanent overload : 1.1 In
- Operating temperature: -10º ~ 50 º C
- Humidity (without condensation): 5% ~ 95% - Current circuit consumption : 0.75 W
- Altitude: 2000 m
Mechanical features: Transistor output features
- Casing material: Self extinguishing V0 plastic - Type: Opto-isolated transistor: (open collector). NPN
- Protection: - Maximum operating voltage: 24 V DC.
Equipment assembly (front ) : IP 51 - Maximum operating current: 50 mA
Non assembled equipment (sides and rear cover) : IP 31 - Maximum frequency: 5 pulses / second
- Sizes (mm) : 96 x 96 x 63 - Energy Output: (default) 100 pulses / kW.h
- Weight: 0.400 kg - Length of pulse: 100 ms
Accuracy class: Safety:
- Voltage: 0.5 % of scale range ± 2 digits Category III - 300 V AC. / 520 AC. EN-61010 Class II double
- Current : 0.5 % of scale range ± 2 digits insulation against electric shock
- Powers: 1 % of scale range ± 2 digits
Measurement conditions : Standards :
Current transformer not included and direct voltage: IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1,
Temperature : + 5 ºC + 45 ºC EN 61000-6-3, EN 61000-6-1, EN-61010-1
Power factor : 0.5 to 1
Scale range measurement margin: 10 .. 100 %

5.- CONNECTION

4 wire / 3 wire (low voltage) 3 wire (2 voltage and 3 current transformers) 3 wire (2 voltage and 2 current transformers)

Power Supply V a.c. Power Supply V a.c. Power Supply V a.c.

6.- TECHNICAL SERVICE


In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR S.A.
CIRCUTOR S.A. - After sales service
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
tel - (+34) 93 745 29 00 & fax - (+34) 93 745 29 14
E-mail : sat@circutor.es
www.circutor.com

M069A01-03-15A