Wiring Requirements in Hazardous Locations
Wiring Requirements in Hazardous Locations
Wiring Requirements in Hazardous Locations
Hazardous Locations
By IAEI
April 3, 2017
02904
Division System
Since Class I, Division 1 locations are expected to include ignitable
concentrations of flammable gases, flammable liquid-produced vapors, or
combustible liquid-produced vapors under normal operating conditions, the
wiring requirements are more restrictive (see photo 1). Wiring methods
permitted in these spaces include threaded rigid metal conduit and threaded
steel intermediate metal conduit. Rigid Type PVC and Type RTRC conduits may
be permitted under certain conditions where placed underground and encased in
concrete. Type MI cable, and within specific industrial applications, listed Types
MC-HL and ITC-HL cable systems are permitted. With these wiring methods, it
is anticipated that ground faults and/or short circuits could take place within
them and they would be able to contain those faults. Since ignitable
concentrations are expected under normal conditions, it is also anticipated that
these faults could result in an explosion within the wiring method that must be
contained. In many cases, these types of wiring methods are connected to
explosionproof enclosures and, consequently, become an extension of that
enclosure (see figure 1).
Figure 1.
Explosionproof enclosures require proper connection of wiring methods and
conduit seals to maintain the integrity and functionality of the enclosure.
In addition to the more robust wiring methods described above, where the
wiring is intrinsically safe, any wiring method permitted for unclassified
locations and any wiring method or cabling system recognized in Chapters 7 or
8 of the NEC is permitted [NEC, 504.20]. All of these systems provide
acceptable protection of the electrical circuits and containment of possible faults
to prevent ignition of surrounding ignitible atmospheres.
This type of cable is permitted in cable tray, in direct sunlight, and/or in direct
burial or concrete encasement. The installation of MC-HL cable is limited by the
Code to industrial establishments with restricted public access and facilities
where the conditions of maintenance and supervision ensure that only qualified
persons service the installation.
Photo 4.
Instrumentation Tray Cable (Type ITC-HL)Courtesy of Southwire Company
Optical Fiber Cables
Optical fiber cables Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and
OFC are permitted to be installed in raceways in accordance with 501.10(A).
Photo 7. Marks on an intrinsically safe barrier referencing a particular control
drawing.
Identification
Other key requirements in Article 504 include rules for separation, identification,
and conduit sealing. Intrinsically safe circuits are required to be identified at
intervals not exceeding 7.5 m (25 ft) and must include the specific wording
“Intrinsic Safety Wiring” (see figure 5). This identification requirement applies to
raceways, cables, cable trays, and other wiring methods used for intrinsically
safe system wiring.
Figure 5.
Identification is required for intrinsically safe circuits.
Identification labels must be located to be readily visible and traceable for the
entire length of the wiring, except for any underground portions, which are re-
identified as they emerge from the earth. Likewise, separate sections of this
wiring created by walls, partitions, or other enclosures are required to be
identified. Where a color code is used for intrinsically safe circuit conductors or
wiring, such as raceways, boxes, and so forth, the color light blue is required
[NEC, 504.80(C)].
Spacing Requirements
The Code permits any wiring method that is acceptable for an unclassified
location to be used for intrinsically safe (IS) circuits. However, there are specific
spacing requirements between IS circuits and those not instrinsically safe. The
Code generally restricts IS circuits from being installed in the same raceway,
cable tray, or cable with conductors of any nonintrinsically safe circuit.
Conductors of intrinsically safe circuits are permitted where they are separated
from nonintrinsically safe circuit conductors by a space of not less than 50 mm
(2 in.) or by grounded metal partitions or insulating barriers. The concern here
is the possibility of compromising the intrinsic safety of the circuit through
inductive or capacitive coupling conditions related to close proximities of other
wiring. The identification rules covered above help installers and facilities
maintain initial spacing when additional wiring or systems are installed [see
504.30(A)(1) Exceptions and 504.30(A)(2)(1) through (4)].
Flexible Cord
Where flexible cord is installed as provided in 501.10(A) and 501.140, the cord
must be listed for extra-hard usage and include an equipment grounding
conductor A review of NECTable 400.4 will provide a description of the cords
that are considered extra-hard usage. Other limitations for use of those cords
are also included in that table. The cords must be continuous; they must be
supported or secured to prevent tension on the terminal connections; be
terminated with a cord connector or attachment plug listed for the location and
they must be sealed where they enter explosionproof enclosures or boxes to
maintain the explosionproof integrity of the enclosure. Extreme care must be
applied to select a fitting that matches the cord diameter to ensure that the
explosionproof integrity of the enclosure is not compromised. As mentioned
above, the provisions in 400.8 are applicable to cords installed in accordance
with 501.140. It is important to consider all of the activities that take place on a
normal basis that might subject flexible cords to physical damage and to
provide proper precautions to protect the cord or cable where it is used.