Product data sheet GV2P05

Characteristics TeSys GV2-Circuit breaker-thermal-magnetic -


0.63…1 A - screw clamp terminals

Product availability: Stock - Normally stocked in distribution facility

Main
Commercial Status Commercialised
Range of product TeSys GV2
Device short name GV2P
Product or component Circuit breaker
type
Circuit breaker Motor protection
application
Poles description 3P
Network type AC

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Utilisation category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Breaking capacity Icu = 100 kA at 690 V AC 50/60 Hz conforming to
IEC 60947-2
Icu = 100 kA at 500 V AC 50/60 Hz conforming to
IEC 60947-2
Icu = 100 kA at 440 V AC 50/60 Hz conforming to

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
IEC 60947-2

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Icu = 100 kA at 400/415 V AC 50/60 Hz conforming

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
to IEC 60947-2
Icu = 100 kA at 230/240 V AC 50/60 Hz conforming
to IEC 60947-2
[Ics] rated service 100 % at 400/415 V AC 50/60 Hz conforming to IEC
short-circuit breaking 60947-2
capacity 100 % at 440 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC
60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC
60947-2
Thermal protection 0.63...1 A
adjustment range
Trip unit technology Thermal-magnetic
Magnetic tripping 13 A
current

Complementary
Mounting mode By clips
By screws
Mounting support Plate
Rail
Mounting position Horizontal
Vertical
Motor power kW 0.55 kW at 690 V AC 50/60 Hz
0.25 kW at 400/415 V AC 50/60 Hz
Control type Rotary knob
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 1 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Power dissipation per pole 2.5 W

Feb 29, 2016


1
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 440 V
Operating rate 25 cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Connections - terminals Screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness : flexible
- with cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...6 mm²) - cable stiffness :
flexible - without cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (1...6 mm²) - cable stiffness : solid
Tightening torque 15.04 lbf.in (1.7 N.m) - on screw clamp terminals
Mechanical robustness Shocks 30 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations 5 Gn, 5...150 Hz conforming to IEC 60068-2-6
Suitability for isolation Yes conforming to IEC 60947-1
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Height 3.5 in (89 mm)
Width 1.77 in (45 mm)
Depth 3.82 in (97 mm)
Product weight 0.77 lb(US) (0.35 kg)

Environment
Standards EN 60204
IEC 60947-1
IEC 60947-2
IEC 60947-4-1
NF C 63-120
NF C 63-650
NF C 79-130
UL 508
VDE 0113
VDE 0660
CSA C22.2
Product certifications ATEX
BV
CCC
CSA
DNV
EZU
GL
GOST
RINA
TSE
UL
UL 508 type E
LROS
Protective treatment TH
IP degree of protection IP20 conforming to IEC 60529
IK degree of protection IK04
Ambient air temperature for operation -4...140 °F (-20...60 °C)
Ambient air temperature for storage -40...176 °F (-40...80 °C)
Fire resistance 1760 °F (960 °C) conforming to IEC 60695-2-1
Operating altitude 6561.68 ft (2000 m)

Ordering and shipping details


Category 22367 - MANUAL STR PROTECTOR - GV2
Discount Schedule I11
GTIN 00785901832874
Nbr. of units in pkg. 1
Package weight(Lbs) 0.63
Product availability Stock - Normally stocked in distribution facility
Returnability Y
Country of origin FR

2
Offer Sustainability
Sustainable offer status Green Premium product
RoHS
Compliant - since 0631 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Period 18 months

3