Battery Energy Storage Components For The OEM Presentation
Battery Energy Storage Components For The OEM Presentation
Battery Energy Storage Components For The OEM Presentation
MAY 2021
DC Main Disconnect/Isolation
- Voltage: up to 1500VDC
- Isolation: Disconnect switch or breaker disconnect
- Duty: load break/no-load break
PCS/Inverter/Converter - Short-circuit: fault level or withstand rating required
=~ AC Side
- Voltage: up to 800VAC
- Protection device: MCCB/ACB/Fusible switches
- Duty: load break
- Short-circuit: fault level or withstand rating required
* Subject to high fault currents on battery type and withstand ACB: air circuit breaker
July 23, 2021 rating required (Flow: 2-5xIn, Lead-acid: >100xIn, Li-ion: 45-55xIn) Breaker disconnect: breaker working as a disconnect switch w/o protection
Slide 3 MCB: miniature circuit breaker | MCCB: molded case circuit breaker ** can be accomplished with motorized devices or contactors
—
Example
Typical Battery Energy Storage System Line Diagram
Low Voltage Component Overview Selection parameters
Battery side – DC*
- Voltage: up to 1500VDC
BMS
Battery
- Protection device*: semiconductor fuse or MCB/MCCB
Management - Duty: load break and short-circuit fault level/withstand
System rating
CMS Battery - Short-circuit: fault level or withstand rating required
monitoring
Insulation - Insulation monitoring, voltage and current - CMS
Monitor - Battery state monitoring
DC Main disconnect/isolation
PCS/Inverter/Converter - Voltage: up to 1500VDC
- Isolation: Disconnect switch or breaker disconnect
=~ - Duty: load break/no-load break
- Short-circuit: fault level or withstand rating required
AC Side
- Voltage: up to 800VAC
DC breaker, Main DC DC Power AC AC main AC Contactor
- Protection device: MCCB/ACB/Fusible switches
Contactor breaker, SPD supplies SPD breaker - Duty: load break
and/or switch Contactor monitoring - Short-circuit: fault level or withstand rating required
disconnector and/or switch relay
disconnector
- Automatic AC or DC disconnection (optional)**
* Subject to high fault currents on battery type and withstand ACB: air circuit breaker
July 23, 2021 rating required (Flow: 2-5xIn, Lead-acid: >100xIn, Li-ion: 45-55xIn) Breaker disconnect: breaker working as a disconnect switch w/o protection
Slide 4 MCB: miniature circuit breaker | MCCB: molded case circuit breaker ** can be accomplished with motorized devices or contactors
—
Application Overview
Energy Storage System – Inverter and Batteries
LV AC LV DC
• Transformer • Switchgear • Switchboard • MCCB
• Switchboard • MCCB • SPD
• Panelboard • MCB • Contactor
• MCCB • SPD • Disconnect Switch
• ACB • Contactor • Fuse Holder
• SPD • Disconnect Switch • Pilot Device
• Contactor • Fuse Holder • Insulation Monitor
• Disconnect Switch • Surge Protection Devices • Current Monitoring System
• Fuse Holder • Current Monitoring System
• RCD • Pilot Device
• Power Supply
• Current Monitoring System
• Pilot Device
• MCB
MV LV AC LV DC
• Switchgear • Switchgear • Switchboard • MCCB
• Switchboard • MCCB • SPD
• Panelboard • MCB • Contactor
• MCCB • SPD • Disconnect Switch
• ACB • Contactor • Fuse Holder
• SPD • Disconnect Switch • Pilot Device
• Contactor • Fuse Holder • Insulation Monitor
• Disconnect Switch • Surge Protection Devices • Current Monitoring System
• Fuse Holder • Current Monitoring System
• RCD • Pilot Device
• Power Supply
• Current Monitoring System
• Pilot Device
• MCB
Used in:
OTDC Disconnect Switch Tmax T PV Circuit Breaker Emax DC ACB Emax 2 MS/DC-E
• 100 to 1000A; Up to • 40 to 800A MCCB; 100 to • Frame sizes range from 800 • E4.2 frame size from 1600
1500VDC (UL) 1000A MCS; Up to 1000VDC to 5000A for a circuit to 3200A switch
• UL disconnect switches can (UL) breaker and 800 to 6300A disconnector
breaker 1 or 2 circuits at the • 40 to 200A MCCB; 200 to for a switch disconnector • Rated up to 1500VDC and
same time 1200A MCS; Up to 1500VDC • Rated up to 1000VDC (IEC) 100kA (UL)
• Modular construction, (UL) • Available with accessories • Available with accessories
handle mechanism location • 80 to 300A MCCB; up to that allow remote open or that allow remote open or
variable 800VAC (UL) remote closing remote closing
• Remote opening with shunt
trip or Open/Close with
motor-operator accessory
• 3 to 4 poles in series,
depending on
the frame size
OVR PV Surge Protection Device S804U-PVS5 GFDI CMS-660 Current Monitoring System
• From 600VDC for small installation to • The S804U-PVS5 is for GFDI (ground- • Rated both UL and IEC, up to 1500VDC,
1000VDC and 1500VDC for large scale fault detector interrupter) applications and sensors up to 160A (TRMS)
solar farms in photovoltaic systems. In case of a • Up to 32 flexible monitoring points,
• Rated both UL1449 ground fault, the breaker will trip, and placed where current and temperature
the PV generator will not be damaged. measurement is required
• Pluggable cartridge, remote signaling
possible, and status indicator • UL 489B tested for 1000 V DC; UL • Modbus RTU protocol guarantees easy
Recognized for 1500V DC integration into plant or inverter
• Indicator window for fast visual status
• Rated current 5A monitoring systems
• -25 °C to 60°C ambient • Integration of SPD and Switch
disconnector status via 2 digital inputs
Insulation Monitors
CM-IWx Insulation monitoring relays
• System voltage monitoring up to 1500
V DC and 1100 V AC
• System leakage capacitance monitoring
up to 3000 µF
• Versatile system monitoring for 2-wire,
3-wire, 4-wire, and battery systems
• Easy-to-configure interrupted wire
detection
• Easy-to-configure non-volatile fault
storage
Used in: