AHU-FF-05 Baddi
AHU-FF-05 Baddi
AHU-FF-05 Baddi
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient ( Out Side ) 110.00 78.80 28.00 114.00
J
ROOM SENSIBLE HEAT Room ( In side ) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 38.40 -22 53.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0 K
By Pass Factor (BF) = 0.06
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
A.
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 L
Min. Air Flow 263 20.00 GRADE - D Minimum Fresh Air = 13
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 GRADE-D 13
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM ) 0.00
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0 =
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 13
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 ERSH
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0 N Effective Room Sensible Heat Factor = Effective Room Sensible Heat / Effective Room Total Heat = 0.99
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 38.40 °F x 0.20 0
Partition 0.00 SqFt x 33.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
Ceiling 89.00 SqFt x 28.40 °F x 0.19 480 DEHUMIDIFIED AIR QUANTITY
C
Floor 89.00 SqFt x 28.40 °F x 0.13 329 Effective Room Sensible Heat = 154 CFM
Surface Area of
0.00 SqFt x 82.40 °F 2.60 0 Dehumidified Rise x 1.08
Equipment P
EQP. Hot Surface 50.00 °C 22.00 Room Inside°C
INFILTRATION AND BY PASSED AIR
D
Infiltration 0.00 CFM x 38.40 T.Diff x 1.08 0
Outside Air 13.14 CFM x 38.40 T.Diff x BF x 1.08 33
INTERNAL HEAT
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 89 SqFt x 2.00 W / SqFt x 3.41 607
E
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Monsoon
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient(Out Side) 86.00 80.10 82.00 163.00
J
ROOM SENSIBLE HEAT Room (InDoor) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 14.40 32 102.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0
K
By Pass Factor (BF) = 0.06
A.
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 Min. Air Flow 263 20.00 Minimum Fresh Air = 13
L
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 13
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM )
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 13
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 Supply CFM from Machine
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0
N
Effective Room Sensible Heat Factor =
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0 Effective Room Sensible Heat/Eff Room Total Heat = 0.97
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 14.40 °F x 0.20 0
Partition 0.00 SqFt x 9.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
C Ceiling 89.00 SqFt x 4.40 °F x 0.19 74 DEHUMIDIFIED AIR QUANTITY
Floor 89.00 SqFt x 4.40 °F x 0.11 43 Effective Room Sensible Heat = 106.27 CFM
Surface Area of Equipment 0.00 SqFt x 82.40 °F 2.60 0 P Dehumidified Rise x 1.08
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 14.40 T.Diff x 1.08 0
D
Outside Air 13.14 CFM x 14.40 T.Diff x BF x 1.08 12
Internal Heat
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 89.00 SqFt x 2.00 W / SqFt x 3.41 607
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0
E LAF Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Other Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0
Blower Indicated 0.41 HP
Blower Selected 0.33 HP x 245.85 Watts 3.41 838 Grand Total Heat = 0.24 TR
Sub Total 1,575 SENSIBLE HEAT CAPACITY
Factor 10% 158 Grand Sensible Heat
=
Effective Room Sensible Heat (ERSH) 1,733 1.00 12,000.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 102.00 Gr / Lb x 0.68 0 Notes:
F Outside Air 13.14 CFM x 102.00 Gr / Lb x BFx0.68 55 Check Figures
People 0.00 Nos. x 275.00 Btu / Hour Per Person 0 btu/hr Sq ft 32.72 1,972.73
Sub Total 55 CFM/Sq ft 0.84 939.52
Factor 10% 5 Sq ft / TR 366.73
Effective Room Latent Heat (ERLH) 60 2.00 CFM/TR 438
EFFECTIVE ROOM TOTAL HEAT 1,793 Occupancy 0.00
OUTSIDE AIR HEAT
G Sensible 13.14 CFM x 14.40 °F (TD) x CF x 1.08 192 3.00
Latent 13.14 CFM x 102.00 Gr / Lb x CF x 0.68 856 4.00
OUTSIDE AIR TOTAL HEAT 1,049
GRAND SUB-TOTAL HEAT 2,841
Factor 2.50% 71
GRAND TOTAL HEAT 2,912
H
TONS = GRAND TOTAL HEAT/12000 0.24
PROJECT 1016 - PINNACLE LIFE SCIENCES - BADDI PLANT FLOOR GF
LOCATION BADDI, HIMACHAL PRADESH SPACE REFERENCE Sec. Pkg. Change
CLIENT PINNACLE LIFE SCIENCES - BADDI PLANT I AREA (SQFT) 102
CONSULTANT Pharmaglance Consultancy LLP Falce Ceiling Height (Ft) 11.48
Volume (Cu.Ft) 1,171
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient ( Out Side ) 110.00 78.80 28.00 114.00
J
ROOM SENSIBLE HEAT Room ( In side ) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 38.40 -22 53.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0 K
By Pass Factor (BF) = 0.06
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
A.
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 L
Min. Air Flow 195 10.00 GRADE - CNC Minimum Fresh Air = 20
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 CNC 20
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM ) 0.00
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0 =
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 20
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 ERSH
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0 N Effective Room Sensible Heat Factor = Effective Room Sensible Heat / Effective Room Total Heat = 1.00
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 38.40 °F x 0.20 0
Partition 518.74 SqFt x 33.40 °F x 0.20 3,465 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
Ceiling 102.00 SqFt x 28.40 °F x 0.19 550 DEHUMIDIFIED AIR QUANTITY
C
Floor 102.00 SqFt x 28.40 °F x 0.13 377 Effective Room Sensible Heat = 1,863 CFM
Surface Area of
21.52 SqFt x 82.40 °F 2.60 4,610 Dehumidified Rise x 1.08
Equipment P
EQP. Hot Surface 50.00 °C 22.00 Room Inside°C
INFILTRATION AND BY PASSED AIR
D
Infiltration 0.00 CFM x 38.40 T.Diff x 1.08 0
Outside Air 19.52 CFM x 38.40 T.Diff x BF x 1.08 49
INTERNAL HEAT
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 102 SqFt x 2.00 W / SqFt x 3.41 696
E
M / C Equipment Load 7,500.00 0.50 x 3,750.00 Watts x 3.41 12,788 TOTAL HEAT CAPACITY
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Monsoon
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient(Out Side) 86.00 80.10 82.00 163.00
J
ROOM SENSIBLE HEAT Room (InDoor) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 14.40 32 102.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0
K
By Pass Factor (BF) = 0.06
A.
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 Min. Air Flow 195 10.00 Minimum Fresh Air = 20
L
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 20
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM )
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 20
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 Supply CFM from Machine
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0
N
Effective Room Sensible Heat Factor =
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0 Effective Room Sensible Heat/Eff Room Total Heat = 0.99
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 14.40 °F x 0.20 0
Partition 0.00 SqFt x 9.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
C Ceiling 102.00 SqFt x 4.40 °F x 0.19 85 DEHUMIDIFIED AIR QUANTITY
Floor 102.00 SqFt x 4.40 °F x 0.11 49 Effective Room Sensible Heat = 400.04 CFM
Surface Area of Equipment 0.00 SqFt x 82.40 °F 2.60 0 P Dehumidified Rise x 1.08
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 14.40 T.Diff x 1.08 0
D
Outside Air 19.52 CFM x 14.40 T.Diff x BF x 1.08 18
Internal Heat
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 102.00 SqFt x 2.00 W / SqFt x 3.41 696
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0
E LAF Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Other Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0
Blower Indicated 0.41 HP
Blower Selected 2.00 HP x 1,490.00 Watts 3.41 5,081 Grand Total Heat = 0.70 TR
Sub Total 5,929 SENSIBLE HEAT CAPACITY
Factor 10% 593 Grand Sensible Heat
=
Effective Room Sensible Heat (ERSH) 6,522 1.00 12,000.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 102.00 Gr / Lb x 0.68 0 Notes:
F Outside Air 19.52 CFM x 102.00 Gr / Lb x BFx0.68 81 Check Figures
People 0.00 Nos. x 275.00 Btu / Hour Per Person 0 btu/hr Sq ft 82.09 6,977.82
Sub Total 81 CFM/Sq ft 0.25 1,395.80
Factor 10% 8 Sq ft / TR 146.17
Effective Room Latent Heat (ERLH) 89 2.00 CFM/TR 573
EFFECTIVE ROOM TOTAL HEAT 6,612 Occupancy 0.00
OUTSIDE AIR HEAT
G Sensible 19.52 CFM x 14.40 °F (TD) x CF x 1.08 285 3.00
Latent 19.52 CFM x 102.00 Gr / Lb x CF x 0.68 1,272 4.00
OUTSIDE AIR TOTAL HEAT 1,558
GRAND SUB-TOTAL HEAT 8,169
Factor 2.50% 204
GRAND TOTAL HEAT 8,374
H
TONS = GRAND TOTAL HEAT/12000 0.70
PROJECT 1016 - PINNACLE LIFE SCIENCES - BADDI PLANT FLOOR GF
LOCATION BADDI, HIMACHAL PRADESH SPACE REFERENCE Secondary Packaging
CLIENT PINNACLE LIFE SCIENCES - BADDI PLANT I AREA (SQFT) 1,588
CONSULTANT Pharmaglance Consultancy LLP Falce Ceiling Height (Ft) 8.86
Volume (Cu.Ft) 14,063
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient ( Out Side ) 110.00 78.80 28.00 114.00
J
ROOM SENSIBLE HEAT Room ( In side ) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 38.40 -22 53.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0 K
By Pass Factor (BF) = 0.06
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
A.
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 L
Min. Air Flow 2,344 10.00 GRADE - CNC Minimum Fresh Air = 234
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 CNC 234
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM ) 0.00
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0 =
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 234
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 ERSH
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0 N Effective Room Sensible Heat Factor = Effective Room Sensible Heat / Effective Room Total Heat = 0.99
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 38.40 °F x 0.20 0
Partition 518.74 SqFt x 33.40 °F x 0.20 3,465 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
Ceiling 1,588.00 SqFt x 28.40 °F x 0.19 8,569 DEHUMIDIFIED AIR QUANTITY
C
Floor 1,588.00 SqFt x 28.40 °F x 0.13 5,863 Effective Room Sensible Heat = 3,494 CFM
Surface Area of
21.52 SqFt x 82.40 °F 2.60 4,610 Dehumidified Rise x 1.08
Equipment P
EQP. Hot Surface 50.00 °C 22.00 Room Inside°C
INFILTRATION AND BY PASSED AIR
D
Infiltration 0.00 CFM x 38.40 T.Diff x 1.08 0
Outside Air 234.39 CFM x 38.40 T.Diff x BF x 1.08 583
INTERNAL HEAT
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 1,588 SqFt x 2.00 W / SqFt x 3.41 10,830
E
M / C Equipment Load 7,500.00 0.50 x 3,750.00 Watts x 3.41 12,788 TOTAL HEAT CAPACITY
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Monsoon
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient(Out Side) 86.00 80.10 82.00 163.00
J
ROOM SENSIBLE HEAT Room (InDoor) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 14.40 32 102.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0
K
By Pass Factor (BF) = 0.06
A.
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 Min. Air Flow 2,344 10.00 Minimum Fresh Air = 234
L
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 234
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM )
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 234
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 Supply CFM from Machine
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0
N
Effective Room Sensible Heat Factor =
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0 Effective Room Sensible Heat/Eff Room Total Heat = 0.95
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 14.40 °F x 0.20 0
Partition 0.00 SqFt x 9.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
C Ceiling 1,588.00 SqFt x 4.40 °F x 0.19 1,328 DEHUMIDIFIED AIR QUANTITY
Floor 1,588.00 SqFt x 4.40 °F x 0.11 769 Effective Room Sensible Heat = 1,229.66 CFM
Surface Area of Equipment 0.00 SqFt x 82.40 °F 2.60 0 P Dehumidified Rise x 1.08
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 14.40 T.Diff x 1.08 0
D
Outside Air 234.39 CFM x 14.40 T.Diff x BF x 1.08 219
Internal Heat
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 1,588.00 SqFt x 2.00 W / SqFt x 3.41 10,830
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0
E LAF Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Other Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0
Blower Indicated 0.41 HP
Blower Selected 2.00 HP x 1,490.00 Watts 3.41 5,081 Grand Total Heat = 3.40 TR
Sub Total 18,226 SENSIBLE HEAT CAPACITY
Factor 10% 1,823 Grand Sensible Heat
=
Effective Room Sensible Heat (ERSH) 20,049 1.00 12,000.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 102.00 Gr / Lb x 0.68 0 Notes:
F Outside Air 234.39 CFM x 102.00 Gr / Lb x BFx0.68 975 Check Figures
People 0.00 Nos. x 275.00 Btu / Hour Per Person 0 btu/hr Sq ft 25.71 24,061.90
Sub Total 975 CFM/Sq ft 1.29 16,763.62
Factor 10% 98 Sq ft / TR 466.77
Effective Room Latent Heat (ERLH) 1,073 2.00 CFM/TR 361
EFFECTIVE ROOM TOTAL HEAT 21,122 Occupancy 0.00
OUTSIDE AIR HEAT
G Sensible 234.39 CFM x 14.40 °F (TD) x CF x 1.08 3,427 3.00
Latent 234.39 CFM x 102.00 Gr / Lb x CF x 0.68 15,282 4.00
OUTSIDE AIR TOTAL HEAT 18,708
GRAND SUB-TOTAL HEAT 39,830
Factor 2.50% 996
GRAND TOTAL HEAT 40,826
H
TONS = GRAND TOTAL HEAT/12000 3.40
PROJECT 1016 - PINNACLE LIFE SCIENCES - BADDI PLANT FLOOR GF
LOCATION BADDI, HIMACHAL PRADESH SPACE REFERENCE Change Parts
CLIENT PINNACLE LIFE SCIENCES - BADDI PLANT I AREA (SQFT) 192
CONSULTANT Pharmaglance Consultancy LLP Falce Ceiling Height (Ft) 8.86
Volume (Cu.Ft) 1,700
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient ( Out Side ) 110.00 78.80 28.00 114.00
J
ROOM SENSIBLE HEAT Room ( In side ) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 38.40 -22 53.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0 K
By Pass Factor (BF) = 0.06
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
A.
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 L
Min. Air Flow 283 10.00 GRADE - CNC Minimum Fresh Air = 28
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 CNC 28
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM ) 0.00
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0 =
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 28
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 ERSH
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0 N Effective Room Sensible Heat Factor = Effective Room Sensible Heat / Effective Room Total Heat = 1.00
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 38.40 °F x 0.20 0
Partition 518.74 SqFt x 33.40 °F x 0.20 3,465 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
Ceiling 192.00 SqFt x 28.40 °F x 0.19 1,036 DEHUMIDIFIED AIR QUANTITY
C
Floor 192.00 SqFt x 28.40 °F x 0.13 709 Effective Room Sensible Heat = 1,961 CFM
Surface Area of
21.52 SqFt x 82.40 °F 2.60 4,610 Dehumidified Rise x 1.08
Equipment P
EQP. Hot Surface 50.00 °C 22.00 Room Inside°C
INFILTRATION AND BY PASSED AIR
D
Infiltration 0.00 CFM x 38.40 T.Diff x 1.08 0
Outside Air 28.34 CFM x 38.40 T.Diff x BF x 1.08 71
INTERNAL HEAT
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 192 SqFt x 2.00 W / SqFt x 3.41 1,309
E
M / C Equipment Load 7,500.00 0.50 x 3,750.00 Watts x 3.41 12,788 TOTAL HEAT CAPACITY
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Monsoon
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient(Out Side) 86.00 80.10 82.00 163.00
J
ROOM SENSIBLE HEAT Room (InDoor) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 14.40 32 102.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0
K
By Pass Factor (BF) = 0.06
A.
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 Min. Air Flow 283 10.00 Minimum Fresh Air = 28
L
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 28
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM )
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 28
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 Supply CFM from Machine
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0
N
Effective Room Sensible Heat Factor =
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0 Effective Room Sensible Heat/Eff Room Total Heat = 0.98
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 14.40 °F x 0.20 0
Partition 0.00 SqFt x 9.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
C Ceiling 192.00 SqFt x 4.40 °F x 0.19 161 DEHUMIDIFIED AIR QUANTITY
Floor 192.00 SqFt x 4.40 °F x 0.11 93 Effective Room Sensible Heat = 450.02 CFM
Surface Area of Equipment 0.00 SqFt x 82.40 °F 2.60 0 P Dehumidified Rise x 1.08
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 14.40 T.Diff x 1.08 0
D
Outside Air 28.34 CFM x 14.40 T.Diff x BF x 1.08 26
Internal Heat
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 192.00 SqFt x 2.00 W / SqFt x 3.41 1,309
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0
E LAF Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Other Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0
Blower Indicated 0.41 HP
Blower Selected 2.00 HP x 1,490.00 Watts 3.41 5,081 Grand Total Heat = 0.83 TR
Sub Total 6,670 SENSIBLE HEAT CAPACITY
Factor 10% 667 Grand Sensible Heat
=
Effective Room Sensible Heat (ERSH) 7,337 1.00 12,000.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 102.00 Gr / Lb x 0.68 0 Notes:
F Outside Air 28.34 CFM x 102.00 Gr / Lb x BFx0.68 118 Check Figures
People 0.00 Nos. x 275.00 Btu / Hour Per Person 0 btu/hr Sq ft 51.94 7,945.32
Sub Total 118 CFM/Sq ft 0.43 2,026.84
Factor 10% 12 Sq ft / TR 231.04
Effective Room Latent Heat (ERLH) 130 2.00 CFM/TR 542
EFFECTIVE ROOM TOTAL HEAT 7,467 Occupancy 0.00
OUTSIDE AIR HEAT
G Sensible 28.34 CFM x 14.40 °F (TD) x CF x 1.08 414 3.00
Latent 28.34 CFM x 102.00 Gr / Lb x CF x 0.68 1,848 4.00
OUTSIDE AIR TOTAL HEAT 2,262
GRAND SUB-TOTAL HEAT 9,729
Factor 2.50% 243
GRAND TOTAL HEAT 9,972
H
TONS = GRAND TOTAL HEAT/12000 0.83
PROJECT 1016 - PINNACLE LIFE SCIENCES - BADDI PLANT FLOOR GF
LOCATION BADDI, HIMACHAL PRADESH SPACE REFERENCE Off-Line Coding
CLIENT PINNACLE LIFE SCIENCES - BADDI PLANT I AREA (SQFT) 173
CONSULTANT Pharmaglance Consultancy LLP Falce Ceiling Height (Ft) 8.86
Volume (Cu.Ft) 1,532
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient ( Out Side ) 110.00 78.80 28.00 114.00
J
ROOM SENSIBLE HEAT Room ( In side ) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 38.40 -22 53.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0 K
By Pass Factor (BF) = 0.06
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
A.
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 L
Min. Air Flow 255 10.00 GRADE - CNC Minimum Fresh Air = 26
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 CNC 26
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM ) 0.00
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0 =
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 26
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 ERSH
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0 N Effective Room Sensible Heat Factor = Effective Room Sensible Heat / Effective Room Total Heat = 1.00
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 38.40 °F x 0.20 0
Partition 518.74 SqFt x 33.40 °F x 0.20 3,465 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
Ceiling 173.00 SqFt x 28.40 °F x 0.19 934 DEHUMIDIFIED AIR QUANTITY
C
Floor 173.00 SqFt x 28.40 °F x 0.13 639 Effective Room Sensible Heat = 1,940 CFM
Surface Area of
21.52 SqFt x 82.40 °F 2.60 4,610 Dehumidified Rise x 1.08
Equipment P
EQP. Hot Surface 50.00 °C 22.00 Room Inside°C
INFILTRATION AND BY PASSED AIR
D
Infiltration 0.00 CFM x 38.40 T.Diff x 1.08 0
Outside Air 25.53 CFM x 38.40 T.Diff x BF x 1.08 64
INTERNAL HEAT
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 173 SqFt x 2.00 W / SqFt x 3.41 1,180
E
M / C Equipment Load 7,500.00 0.50 x 3,750.00 Watts x 3.41 12,788 TOTAL HEAT CAPACITY
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Monsoon
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient(Out Side) 86.00 80.10 82.00 163.00
J
ROOM SENSIBLE HEAT Room (InDoor) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 14.40 32 102.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0
K
By Pass Factor (BF) = 0.06
A.
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 Min. Air Flow 255 10.00 Minimum Fresh Air = 26
L
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 26
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM )
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 26
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 Supply CFM from Machine
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0
N
Effective Room Sensible Heat Factor =
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0 Effective Room Sensible Heat/Eff Room Total Heat = 0.98
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 14.40 °F x 0.20 0
Partition 0.00 SqFt x 9.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
C Ceiling 173.00 SqFt x 4.40 °F x 0.19 145 DEHUMIDIFIED AIR QUANTITY
Floor 173.00 SqFt x 4.40 °F x 0.11 84 Effective Room Sensible Heat = 439.41 CFM
Surface Area of Equipment 0.00 SqFt x 82.40 °F 2.60 0 P Dehumidified Rise x 1.08
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 14.40 T.Diff x 1.08 0
D
Outside Air 25.53 CFM x 14.40 T.Diff x BF x 1.08 24
Internal Heat
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 173.00 SqFt x 2.00 W / SqFt x 3.41 1,180
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0
E LAF Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Other Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0
Blower Indicated 0.41 HP
Blower Selected 2.00 HP x 1,490.00 Watts 3.41 5,081 Grand Total Heat = 0.80 TR
Sub Total 6,513 SENSIBLE HEAT CAPACITY
Factor 10% 651 Grand Sensible Heat
=
Effective Room Sensible Heat (ERSH) 7,164 1.00 12,000.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 102.00 Gr / Lb x 0.68 0 Notes:
F Outside Air 25.53 CFM x 102.00 Gr / Lb x BFx0.68 106 Check Figures
People 0.00 Nos. x 275.00 Btu / Hour Per Person 0 btu/hr Sq ft 55.22 7,725.97
Sub Total 106 CFM/Sq ft 0.39 1,826.26
Factor 10% 11 Sq ft / TR 217.33
Effective Room Latent Heat (ERLH) 117 2.00 CFM/TR 552
EFFECTIVE ROOM TOTAL HEAT 7,281 Occupancy 0.00
OUTSIDE AIR HEAT
G Sensible 25.53 CFM x 14.40 °F (TD) x CF x 1.08 373 3.00
Latent 25.53 CFM x 102.00 Gr / Lb x CF x 0.68 1,665 4.00
OUTSIDE AIR TOTAL HEAT 2,038
GRAND SUB-TOTAL HEAT 9,319
Factor 2.50% 233
GRAND TOTAL HEAT 9,552
H
TONS = GRAND TOTAL HEAT/12000 0.80
PROJECT 1016 - PINNACLE LIFE SCIENCES - BADDI PLANT FLOOR GF
LOCATION BADDI, HIMACHAL PRADESH SPACE REFERENCE SPM / TPM & FG Hold
CLIENT PINNACLE LIFE SCIENCES - BADDI PLANT I AREA (SQFT) 533
CONSULTANT Pharmaglance Consultancy LLP Falce Ceiling Height (Ft) 8.86
Volume (Cu.Ft) 4,720
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Summer
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient ( Out Side ) 110.00 78.80 28.00 114.00
J
ROOM SENSIBLE HEAT Room ( In side ) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 38.40 -22 53.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0 K
By Pass Factor (BF) = 0.06
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
A.
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 L
Min. Air Flow 787 10.00 GRADE - CNC Minimum Fresh Air = 79
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 CNC 79
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM ) 0.00
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0 =
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 79
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 ERSH
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0 N Effective Room Sensible Heat Factor = Effective Room Sensible Heat / Effective Room Total Heat = 1.00
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 38.40 °F x 0.20 0
Partition 518.74 SqFt x 33.40 °F x 0.20 3,465 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
Ceiling 533.00 SqFt x 28.40 °F x 0.19 2,876 DEHUMIDIFIED AIR QUANTITY
C
Floor 533.00 SqFt x 28.40 °F x 0.13 1,968 Effective Room Sensible Heat = 2,336 CFM
Surface Area of
21.52 SqFt x 82.40 °F 2.60 4,610 Dehumidified Rise x 1.08
Equipment P
EQP. Hot Surface 50.00 °C 22.00 Room Inside°C
INFILTRATION AND BY PASSED AIR
D
Infiltration 0.00 CFM x 38.40 T.Diff x 1.08 0
Outside Air 78.67 CFM x 38.40 T.Diff x BF x 1.08 196
INTERNAL HEAT
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 533 SqFt x 2.00 W / SqFt x 3.41 3,635
E
M / C Equipment Load 7,500.00 0.50 x 3,750.00 Watts x 3.41 12,788 TOTAL HEAT CAPACITY
Item Area Sun Gain or Temp. Diff. Factor (U) Btu / Hour
Estimate for Monsoon
Design Conditions DB (°F) WB (°F) RH (%) w (Gr/Lb)
Q= U*A*ΔT Ambient(Out Side) 86.00 80.10 82.00 163.00
J
ROOM SENSIBLE HEAT Room (InDoor) 71.60 59.00 50.00 61.00
Solar Gain - Glass Area (Btu / h.sqft) U Difference Δ 14.40 32 102.00
Glass - N 0.00 Sq ft x 23.00 x 1.00 0 Altitude (Ft) 1,397
Glass - NE 0.00 Sq ft x 12.00 x 1.00 0 CHW IN & OUT (Deg. C) 7.00 12.00
Glass - E 0.00 Sq ft x 12.00 x 1.00 0
K
By Pass Factor (BF) = 0.06
A.
Glass - SE 0.00 Sq ft x 12.00 x 1.00 0 Contact Factor (CF = 1 - BF) = 0.94
Glass - S 0.00 Sq ft x 12.00 x 1.00 0 CFM Ventilation
Glass - SW 0.00 Sq ft x 85.00 x 1.00 0 CFM / Person 15.00 0.00 People = 0
Glass - W 0.00 Sq ft x 163.00 x 1.00 0 Min. Air Flow 787 10.00 Minimum Fresh Air = 79
L
Glass - NW 0.00 Sq ft x 138.00 x 1.00 0 Fresh Air ACPH 1
Skylight 0.00 Sq ft x 118.00 x 1.00 0 79
Solar & Transmission Gain - Walls & Roof
CFM EX-Filtration
Walls & Roof Area ΔT U
Wall - N 0.00 Sq ft x 23.00 °F x 0.35 0 Required Fresh Air ( CFM )
Wall - NE 0.00 Sq Ft x 12.00 °F x 0.35 0 Cutout Size ( MM ) Cutout ( CFM ) QTY. ( Nos. )
Wall - E 0.00 Sq Ft x 12.00 °F x 0.35 0 M 0.00
Wall - SE 0.00 Sq Ft x 12.00 °F x 0.35 0
B Wall - S 0.00 Sq Ft x 12.00 °F x 0.35 0 79
Wall - SW 0.00 Sq Ft x 85.00 °F x 0.35 0 Supply CFM from Machine
Wall - W 0.00 Sq Ft x 163.00 °F x 0.35 0
N
Effective Room Sensible Heat Factor =
Wall - NW 0.00 Sq Ft x 138.00 °F x 0.35 0 Effective Room Sensible Heat/Eff Room Total Heat = 0.97
Roof 0.00 Sq Ft x 118.00 °F x 0.14 0 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (°F) = 50.50
Except Walls & Roof Area ΔT U O Selected ADP (°F) = 55.54
All Glass 0.00 SqFt x 14.40 °F x 0.20 0
Partition 0.00 SqFt x 9.40 °F x 0.20 0 (Room DB - ADP) x CF Dehum. Temp Rise °F = 15.10
C Ceiling 533.00 SqFt x 4.40 °F x 0.19 446 DEHUMIDIFIED AIR QUANTITY
Floor 533.00 SqFt x 4.40 °F x 0.11 258 Effective Room Sensible Heat = 640.47 CFM
Surface Area of Equipment 0.00 SqFt x 82.40 °F 2.60 0 P Dehumidified Rise x 1.08
INFILTRATION AND BY PASSED AIR
Infiltration 0.00 CFM x 14.40 T.Diff x 1.08 0
D
Outside Air 78.67 CFM x 14.40 T.Diff x BF x 1.08 73
Internal Heat
People 0.00 Nos. x 350.00 Btu / Hour Per Person 0
Lighting 533.00 SqFt x 2.00 W / SqFt x 3.41 3,635
M / C Equipment Load 0.00 0.50 x 0.00 Watts x 3.41 0
E LAF Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0 TOTAL HEAT CAPACITY
Other Load (watts) 0.00 0.30 x 0.00 Watts x 3.41 0
Blower Indicated 0.41 HP
Blower Selected 2.00 HP x 1,490.00 Watts 3.41 5,081 Grand Total Heat = 1.46 TR
Sub Total 9,493 SENSIBLE HEAT CAPACITY
Factor 10% 949 Grand Sensible Heat
=
Effective Room Sensible Heat (ERSH) 10,442 1.00 12,000.00
ROOM LATENT HEAT
Infiltration 0.00 CFM x 102.00 Gr / Lb x 0.68 0 Notes:
F Outside Air 78.67 CFM x 102.00 Gr / Lb x BFx0.68 327 Check Figures
People 0.00 Nos. x 275.00 Btu / Hour Per Person 0 btu/hr Sq ft 32.85 11,882.11
Sub Total 327 CFM/Sq ft 0.83 5,626.58
Factor 10% 33 Sq ft / TR 365.30
Effective Room Latent Heat (ERLH) 360 2.00 CFM/TR 439
EFFECTIVE ROOM TOTAL HEAT 10,802 Occupancy 0.00
OUTSIDE AIR HEAT
G Sensible 78.67 CFM x 14.40 °F (TD) x CF x 1.08 1,150 3.00
Latent 78.67 CFM x 102.00 Gr / Lb x CF x 0.68 5,129 4.00
OUTSIDE AIR TOTAL HEAT 6,279
GRAND SUB-TOTAL HEAT 17,082
Factor 2.50% 427
GRAND TOTAL HEAT 17,509
H
TONS = GRAND TOTAL HEAT/12000 1.46