Rapha Denplant India Pvt. Ltd.

,Pune
Job : DY AUTO
Location : Chennai
Space : Documents Room BY:- Shaikh Tauseef
Unit in Ft. : W Length Area F/C Height Volume 16 Hours
Size : 19.30 21.65 417.845 10 4178 4.00pm Date : 3/19/2018
Clean Room Class : NIL Out Side DB deg.F WB deg.F Drange %RH DP GR/LB
Filtration : 10 Micron Summer 103 82 18 41 75 132.4
Pressure Gradient : NIL Monsoon 83 80 88 79 151.4
Lighting Load : 0.9 Watts / Sq.ft. Room 76 63.5 50 56 68
Occupancy : 3 T : 27 18.5 Gr/Lb : 64.4
Equipment Load : 0.2 KW VENTILATION:
CFM / Person : 15 3 People 15 CFM/Per. 45
Correction Factor : 12 417.8 Sq.ft. 10 H.T x 1 70
Coil By Pass Factor. : 0.1 Row Deep Coil. : 4 Select : 70
Fresh Air Changes/Hr.: 1 Effective Room Sensible Heat Factor ( ERSHF ) :
Weight OF Wall: 60
Heatload for(summmer/monsoon) SUMMER
Room Air Changes/Hr.: 1 70 11512 Effective Room Sensible Heat
= 0.94
Glasses Area In Sun Gain / Temp. 'U'Factor Heat 12301 Effective Room Total Heat
Sq.ft. In Deg. F Btu / Hr. Apparatus Dew Point. :( A.D.P.) Indicated = 56
Glass W 163 0.30 0 Selected = 58
Glass E 163 0.30 0 Dehumidified Rise =
Glass N 23 0.70 0 (1-B.F.) x (RM.TEMP- A.D.P.)
Glass S 12 0.30 0 0.90 x 18 = 16.2
Glass NW 138 0.30 0
Glass SW 85 0.30 0 Dehumidified CFM = 11512 (E.R.S.H.)
Glass NE 12 0.30 0 1.08 x 16.20 (Deh. Rise)
Glass SE 0 0.30 0

Walls Eq.Temp. Dehum. CFM = 658


Diff. : Supply Air CFM = 658
Wall W 37 0.28 0
Wall E 216.50 29 0.28 1758 Coil By Pass CFM = 0
Wall N 26 0.28 0 CFM / Sq.ft. = 1.6
Wall S 40 0.28 0 Sq.ft. / TR = 289
Wall NW 31 0.16 0 ROOM LATENT GAIN :
Wall SW 44 0.16 0 Infiltration 64.4 gr/lb 0.68 100
Wall NE 24 0.16 0 People 3 NO. X 175 Gain/Person 525
Wall SE 30 0.16 0 Steam Lb/Hr. X 1080
Roof SUN 55 0.09 0 Vap.Trans. 0 0.01 64.4 gr/lb
Roof SHA 20 0.40 0 Permeation Load
All Glass 216.50 32 0.47 3256 ROOM LATENT HEAT SUBTOTAL: 625
Partition 17 0.41 0 Supply Duct Leackage Loss & Safty Factor : 6% 38
PartitionGl. 216.50 22 0.30 1429 Out.Air 69.64083 64.4 0.1 B.F. 0.68 126
Ceiling 22 0.40 0 EFFECTIVE ROOM LATENT HEAT : 789
Floor 22 0.38 0 EFFECTIVE ROOM TOTAL HEAT : 12301
People 3 No. X 270 Gain/Person. 810 Out Side Air Heat : T x (1 - B.F.) x Factor = BTU / Hr.
Eqp Load 200 Watts X 3.41 Gain/KW 682 Sensible 70 27 T 0.90 1.08 1828
Lights 384 Watts X 1 X 3.40 1307 Latent 70 64.4 gr/lb 0.90 0.68 2745
Appliance 3.40 0 GRAND TOTAL HEAT SUBTOTAL : 16873
Product Load Safety Factor : 0.03 506
ROOM SENSIBLE HEAT SUBTOTAL : 9242 Roof Sun 32 0 0
Supply Duct Heat Gain : 5% 0 0
Safety Factor : 5% 462 Roof SHA 8 0 0
Fan Heat Gain : 8% 728 Ceiling 22 0 0
Out.Air 70 27 0.17 B.F. 1.08 345 GRAND TOTAL HEAT : 17379
Infiltration 3 245.00 Gain/Person 735 LOAD TR : 1.4
EFFECTIVE ROOM SENSIBLE HEAT : 11512 LOAD HP : 1.8
DAILY RANGE

T 8 10 12 14 16 18 20 22
-30 -39 -40 -41 -42 -43 -44 -45 -46
-20 -29 -30 -31 -32 -33 -34 -35 -36
-10 -19 -20 -21 -22 -23 -24 -25 -26
0 -9 -10 -11 -12 -13 -14 -15 -16

5 -4 -5 -6 -7 -8 -9 -10 -11
10 1 0 -1 -2 -3 -4 -5 -6
15 6 5 4 3 2 1 0 -1
20 11 10 9 8 7 6 5 4

25 16 15 14 13 12 11 10 9
30 21 20 19 18 17 16 15 14
35 26 25 24 23 22 21 20 19

40 31 30 29 28 27 26 25 24

TYPICAL BYPASS FACTORS

DEPTH OF COILS WITH OUT SPRAYS


(ROWS) VELOCITY( LPM)
300 400 500 600 700
2 0.225 0.274 0.314 0.346 0.373
3 0.107 0.143 0.176 0.204 0.228

4 0.052 0.076 0.099 0.12 0.14


5 0.025 0.04 0.056 0.071 0.086

6 0.012 0.022 0.032 0.042 0.052


8 0.05 0.03
RANGE

24 26 28 30 32 34 36 38 40
-47 -48 -49 -50 -51 -52 -53 -54 -55

-37 -38 -39 -40 -41 -42 -43 -44 -45

-27 -28 -29 -30 -31 -32 -33 -34 -35

-17 -18 -19 -20 -21 -22 -23 -24 -25

-12 -13 -14 -15 -16 -17 -18 -19 -20

-7 -8 -9 -10 -11 -12 -13 -14 -15

-2 -3 -4 -5 -6 -7 -8 -9 -10

3 2 1 0 -1 -2 -3 -4 -5

8 7 6 5 4 3 2 1 0

13 12 11 10 9 8 7 6 5

18 17 16 15 14 13 12 11 10

23 22 21 20 19 18 17 16 15
N.E=NORTH EAST E=EAST S.E=SOUTH EAST
FOR WALL SURFACES
FOR 4 PM SUN TIME
EXPOSURE WEIGHT OF WALL(lb/sq ft)
20 60 100 140
N.E 14 12 10 14

E 14 12 18 18

S.E 16 18 18 16

S 20 23 18 13

S.W 40 32 14 8

W 40 25 12 10

N.W 24 12 6 6

N 14 10 4 2

FOR ROOF SUN ANS ROOF SHADED

CONDITION WEIGHT OF WALL(lb/sq ft)


10 20 40 60

EXPOSED 43 41 38 35
TO SUN

COVERED WITH 18 16 14
WATER

SPRAYED 16 14 12

SHADED 14 12 8
SOLAR HEAT GAIN THRU ORDINARY GLASS
FOR 20 DEGREE
SUN TIME IS TAKEN AS 4 PM

TIME OF YEAR EXPOSURE 4:00 PM

N 23
23 JULY & MAY 21 N.E 12
E 12

S.E 12
S 12
S.W 85

W 163
N.W 138
HORIZONTAL 118
S.E=SOUTH EAST S.W= SOUTH WEST

BACK TO HEAT LOAD

OF SHADED

80

32
FOR EXPOSED WALL

1/2" CEMENT
PLASTER
CEMENT
MORTAR

INSIDE
OUT SIDE AIR FILM
AIR FILM

BACK TO HEAT LOAD 1/2" CEMENT


PLASTER

CONSTRUCTION: RESISTANCE
• OUTDOOR AIR SURFACE FILM (7.5 mph WIND) 0.25
• BRICK FACING, 9 INCH 1.8
• 0.5” CEMENT MORTAR 0.1
• SAND CEMENT PLASTER 1 in (0.5” ON BOTH SIDES) 0.2
• INSIDE AIR SURFACE (STILL AIR)(VER/HORZ) 0.68
TOTAL RESISTANCE 3.03
U FACTOR 0.3300330033

MATERIAL

STILL AIR POSITION


HORIZONTAL
SLOPING 45
VERTICAL
SLOPING 45
HORIZONTAL

• BRICK FACING 4 INCH


0.8

U Factor For Floor / Ceiling

FLOOR TILE AIR FILM INSIDE


1/2" PLASTER

4" CONCRETE SLAB


HEAT
FLOW UP
1/2" PLASTER
AIR FILM
CONSTRUCTION: RESISTANCE
• INDOOR AIR SURFACE FILM (STILL AIR) 0.61
• PLASTER 0.5” 0.1
• CONCRETE 4’’ 0.8
• PLASTER 0.5” 0.1
FLOOR TILE 1/8" 0.05
• INSIDE AIR SURFACE (STILL AIR (HOR/UP) 0.61
TOTAL RESISTANCE 2.27
U Factor For Floor / Ceiling 0.4405286344

U Factor For UN-insulated Roof

OUT SIDE AIR FILM


1/2" PLASTER
HEAT
FLOW
DOWN 4" CONCRETE SLAB

1/2" PLASTER
IN SIDE AIR FILM
CONSTRUCTION: RESISTANCE
• OUTDOOR AIR SURFACE(71/2MPH WIND) 0.25
• PLASTER 0.5” 0.1
• CONCRETE 4 in 0.8
• INSIDE AIR SURFACE (STILL AIR) 0.92
• PLASTER 0.5” 0.1
TOTAL RESISTANCE 2.17
U Factor For UN-insulated Roof 0.46

U Factor For insulated Roof


OUTSIDE AIR FILM
1/2" PLASTER
HEAT 2" INSULATION
FLOW
1/2" PLASTER
DOWN

4" CONCRETE SLAB

1/2" PLASTER
INSIDE AIR FILM

CONSTRUCTION: RESISTANCE
• OUTDOOR AIR SURFACE FILM (7.5 mph WIND) 0.25
• PLASTER 0.5” 0.1
• INSULATION 2 in 5.26
• CONCRETE 4 in 0.8
• PLASTER 0.5” 0.1
• INSIDE AIR SURFACE (STILL AIR) 0.92
TOTAL RESISTANCE 7.43
U Factor For insulated Roof 0.134589502

U Factor For Ordinary Glass


FOR INSIDE VENETIAN BLIND 45 DEG HORZ OR BLIND
LIGHT COLOUR MEDIUM COLOUR
0.56 0.65
HEAT FLOW RESISTANCE
UP 0.61
UP 0.62
HORIZONTAL 0.68
DOWN 0.76
DOWN 0.92

6 INCH 8 INCH 9 INCH


1.2 1.6 1.8

TER

ETE SLAB

TER
PER INCH 0.2

STER

ETE SLAB

STER

ROOF INSULATION
THICKNESS(INCH) WT(LB/SQFT) RESISTANCE(1/C)
0.50 0.7 1.39
1 1.3 2.78
1.5 1.9 4.17
2 2.6 5.26
2.5 3.2 6.67
3 3.9 8.33

DARK COLOUR
0.75
FOR CALCULATING CFM

APPLICATION CFM PER PERSON

DEPARTMENT AVERAGE 20
DEPARTMENT DELUXE 30
BANKING SPACE 10
BARBER SHOPS 15
BEAUTY PARLOURS 10

BROKERS BOARD ROOM 50


COCKTAIL BARS 30
CORRIDORS
DEPARTMENT STORES 7.5
DIRECTORS ROOMS 50

DRUG STORES 10
FACTORIES 10
FIRE AND TEN CENT STORES 7.5
FUNERAL PARLOURS 10
GARAGE

HOSPITAL OPERATING ROOMS


HOSPITAL PRIVATE ROOMS 30
HOSPITAL WARDS 20

HOTEL ROOMS 30
KITCHEN RESTAURANT
KITCHEN RESIDENCE
LABORATORIES 20

MEETING ROOMS
OFFICE GENERAL 15
OFFICE PVT (NO SMOKING) 25
OFFICE GENERAL (SMOKING) 30

RESTAURANT 15
SHOP RETAIL 10
THEATER (NO SMOIKING) 7.5
THEATER ( SMOIKING) 15

FOR KNOWING THE SENSIBLE/LATENT HEAT GAIN

DEGREE OF ACTIVITY TYPICAL APPLICATION

SEATED AT REST THEATER


SEATED,VERY LIGHT WORK HIGH SCHOOL

OFFICE WORKER OFFICES,HOTELS,APTS,COLLEGE

STANDING,WALKING SLOWLY DEPT,RETAIL,OR VARIETY STORE

WALKING,SEATED DRUG STORE

STANDING,WALKING SLOWLY BANK

SEDENTARY WORK RESTAURANT

LIGHT BENCH WORK FACTORY,LIGHT WORK

MODERATE DANCING DANCE HALL

WALKING,3MPH FACTORY,FAIRLY HEAVY WORK

HEAVY WORK BOWLING ALLEY FACTORY


FOR OCCUPANCY
SQ Ft
CLASSIFICATION PER
PERSON

APARTMENTS AND HOTEL GUEST


ROOMS 60

BANKS 35

DEPARTMENT STORES/MALLS 25

OFFICFE BUILDINGS 49

OFFICES SMALL SUITES 55

RESTAURANTS 22

THEATERS AND AUDITORIUMS 5

82F 80F 78F 75F


SENS LAT SENS LAT SENS LAT

175 195 155 210 140 230 120


SENS-180 LATENT-220 195 205 215 185 240 160

SENS-180 LATENT-270 200 250 215 235 245 205

SENS-180 LATENT-270 200 250 215 235 245 205

SENS-180 LATENT-320 200 300 220 280 255 245

SENS-180 LATENT-320 200 300 220 280 255 245

SENS-190 LATENT-360 220 330 240 310 280 270

SENS-190 LATENT-560 220 530 245 505 295 455

SENS-220 LATENT-630 245 605 275 575 325 525

SENS-270 LATENT-730 300 700 330 670 380 620

SENS-450 LATENT-1000 465 985 485 965 525 925


70F
SENS LAT

260 90
275 125

285 165

285 165

290 210

290 210

320 230

365 385

400 450

460 540

605 845