Winter Reheat Calculations Vimpo
Winter Reheat Calculations Vimpo
Winter Reheat Calculations Vimpo
Winter Cycle
A room has a 18.0 kW sensible heat loss in winter and a 4.5 kW latent heat
gain from the occupants.
Determine the supply air temperature and heater battery load using the
following information.
DATA:
4. No Preheater condition P
6. Find the mix point M by measuring the length of the line O-R and multiply
this by the mixing ratio.
If there is more recirculated air than outside air at the mix point, then
point M will be closer to point R than point O.
7. Find the room ratio
Neglect signs ie. the total heat for the room will be Sensible loss plus
Latent gain.
Plot this ratio on the protractor, top segment, on the psychrometric chart
and transfer this line onto the chart so that it passes through point R.
8. Find the supply air dry bulb temperature by calculation.
9. Plot the supply air condition S on the room ratio line.
This is on a horizontal line from point M to the right hand side of the
chart, and intersects with the RRL.
The supply air Temperature is found to be 32.5oC.
Hs = ma x Cp (ts - tr)
where:
Hs = Sensible heat loss (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature
o
( C)
ts = supply air temperature
(oC) ..............therefore:
ma = Hs / Cp ( ts - tr )
ma = 18 / 11.615
ma = 1.55 kg/s
where:
H reheater battery = Reheater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg)
hM = specific enthalpy at condition M (kJ/kg)