Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Air Conditioning System: Pan Humidifier Load Calculation Building Room1

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 1

AIR CONDITIONING SYSTEM

PAN HUMIDIFIER LOAD CALCULATION

BUILDING
S.No. DESCRIPTION UNIT
ROOM1

1 Design Room Condition

- Temperature [°C] 24

- Relative Humidity [%} 50


Anticipated condition for Pan
2
humidifier sizing
- Temperature [°C] 24

- Relative Humidity [%} 45


Absolute humidity of air at design
3 [Kg/m3] 0.0109
room condition
Absolute humidity of air at
4 [Kg/m3] 0.0098
anticipated condition
Moisture to be added to increase
5 the humidity to maintain the [Kg/m3] 0.0011
design condition.
[CFM] 30600
6 Air Flow rate in supply air header
[m3/hr] 51989.73

7 Humidification load [kg/hr] 57.19

8 Heater capacity calculated [KW] 4.36

9 Pan Humidifier capacity selected [KW] 6

You might also like