Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

1) Fresh Air - ASHRAE

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

Unit

Area of Store Sqm 87.00


Sqft 936.12

Fresh Air Calculation


Rp
Number of people PPL/100sqm 15.00
People on site 13.05
Fresh Air per person lps/person 3.80
Total Rp lps 49.59

Area Fresh Air lps/sqm 0.60


Total Ra Lps 52.20

Total Fresh Air Requirement Lps 101.79


cfm 213.76
Total Extract Air Requirement Lps 86.52
cfm 181.70

Grill size Fresh Air


Velocity m/s 200.00
ft/m 295.00
Area Supply sqft 0.72
Sqm 0.07 2.7
Unit
Area of Store Sqm 200.00
Sqft 2,152.00

Fresh Air Calculation


Rp
Number of people PPL/100sqm 70.00
People on site 140.00
Fresh Air per person lps/person 3.80
Total Rp lps 532.00

Area Fresh Air lps/sqm 0.90


Total Ra Lps 180.00

Total Fresh Air Requirement Lps 712.00


cfm 1,495.20
Total Extract Air Requirement Lps 605.20
cfm 1,270.92

Grill size Fresh Air


Velocity m/s 200.00
ft/m 295.00
Area Supply sqft 5.07
Sqm 0.47
FOR GYM AREA
Unit
Area of Store Sqm 960.00
Sqft 10,329.60

Fresh Air Calculation


Rp
Number of people PPL/100sqm 7.00
People on site 67.20
Fresh Air per person lps/person 10.00
Total Rp lps 672.00

Area Fresh Air lps/sqm 0.90


Total Ra Lps 864.00

Total Fresh Air Requirement Lps 1,536.00 1561


cfm 3,225.60
Total Extract Air Requirement Lps 1,305.60 1327
cfm 2,741.76
FOR OFFICE AREA
Unit
Area of Store Sqm 60.00
Sqft 645.60

Fresh Air Calculation


Rp
Number of people PPL/100sqm 5.00
People on site 3.00
Fresh Air per person lps/person 2.50
Total Rp lps 7.50

Area Fresh Air lps/sqm 0.30


Total Ra Lps 18.00

25.00 Total Fresh Air Requirement Lps 25.50


### cfm 53.55
21.40 Total Extract Air Requirement Lps 21.68
cfm 45.52
60
Unit
Area of Store Sqm 27.00
Sqft 290.52

Fresh Air Calculation


Rp
Number of people PPL/100sqm 50.00
People on site 13.50
Fresh Air per person lps/person 2.50
Total Rp lps 33.75

Area Fresh Air lps/sqm 0.60


Total Ra Lps 16.20

Total Fresh Air Requirement Lps 49.95


cfm 104.90
Total Extract Air Requirement Lps 42.46
cfm 89.16

Grill size Fresh Air


Velocity m/s 200.00
ft/m 295.00
Area Supply sqft 0.36
Sqm 0.03 2.7